HUAWEI-POWER-MIB

File: HUAWEI-POWER-MIB.mib (110077 bytes)

Imported modules

HUAWEI-ENVIRONMENT-MIB HUAWEI-MIB SNMPv2-SMI
SNMPv2-TC HUAWEI-DEVICE-MIB

Imported symbols

hwEnvEmuIndex hwEnvEmuType hwDigChannelIndex
huaweiUtility Integer32 OBJECT-TYPE
MODULE-IDENTITY NOTIFICATION-TYPE DisplayString
RowStatus TruthValue DateAndTime
TEXTUAL-CONVENTION hwFrameIndex

Defined Types

MeasuresRange  
Basic unit of measure: 1.pressure:indicated by mV, 1V = 1000 mV 2.current:indicated by mA, 1A = 1000 mA 3.temperature: indicated by 1% degree centigrade
TEXTUAL-CONVENTION    
  Integer32  

HwPowerSysInfoEntry  
SEQUENCE    
  hwPowerIndex Integer32
  hwPowerType INTEGER
  hwPowerName DisplayString
  hwPowerState INTEGER
  hwPowerRowStatus RowStatus
  hwPowerControlMode INTEGER
  hwPowerRemoteFrameID Integer32
  hwPowerProtect INTEGER
  hwPowerVersion DisplayString
  hwPowerSupplyState INTEGER

HwACInputEntry  
SEQUENCE    
  hwACLoopIndex Integer32
  hwACPowerState INTEGER
  hwACVoltA MeasuresRange
  hwACCurrentA MeasuresRange
  hwACVoltB MeasuresRange
  hwACCurrentB MeasuresRange
  hwACVoltC MeasuresRange
  hwACCurrentC MeasuresRange
  hwACVoltageHigh MeasuresRange
  hwACVoltageLow MeasuresRange
  hwACRowStatus RowStatus
  hwACVoltageAState INTEGER
  hwACVoltageBState INTEGER
  hwACVoltageCState INTEGER

HwDCOutEntry  
SEQUENCE    
  hwDCVoltageOut MeasuresRange
  hwDCCurrentOut MeasuresRange
  hwDCVoltageOutHigh MeasuresRange
  hwDCVoltageOutLow MeasuresRange
  hwDCVoltageOutState INTEGER
  hwDCCurrentOutHigh MeasuresRange
  hwDCCurrentOutLow MeasuresRange
  hwDCCurrentOutState INTEGER
  hwDCOutRowStatus RowStatus
  hwDCOutLoadCurrent MeasuresRange
  hwDCOutLoadTmpHigh MeasuresRange
  hwDCOutRunState BITS
  hwDCCommunicationState INTEGER

HwLoadinfoEntry  
SEQUENCE    
  hwLoadIndex Integer32
  hwLoadInfoAdminState INTEGER
  hwLoadInfoOperStatus INTEGER
  hwLoadCurrent MeasuresRange
  hwLoadVoltage MeasuresRange
  hwLoadVoltageHigh MeasuresRange
  hwLoadLoadName DisplayString
  hwLoadInfoRowStatus RowStatus
  hwLoadFuseState INTEGER
  hwLoadHoreIndex Integer32

HwRectifierEntry  
SEQUENCE    
  hwRectifierIndex Integer32
  hwRectifierAdminState INTEGER
  hwRectifierOperState INTEGER
  hwRectifierVoltage MeasuresRange
  hwRectifierCurrent MeasuresRange
  hwRectifierRowStatus RowStatus
  hwRectifierCurrentLimit TruthValue
  hwRectifierRunState BITS
  hwRectifierChargeState INTEGER

HwBatteryGroupEntry  
SEQUENCE    
  hwBatteryGroupCapacity Integer32
  hwBatteryGroupCapcaityRemain Integer32
  hwBatteryGroups Integer32
  hwBatteryGroupVoltageLow MeasuresRange
  hwBatteryGroupChargeLimit MeasuresRange
  hwBatteryGroupRowStatus RowStatus
  hwBatteryGroupOperStatus INTEGER
  hwBatteryGroupVoltageHigh MeasuresRange
  hwBatteryGroupTwiceOffVoltage MeasuresRange
  hwBatteryGroupProtectVoltage MeasuresRange
  hwBatteryGroupTmpOffHigh MeasuresRange
  hwBatteryInstallTime DisplayString
  hwBatteryGroupBomCode OCTET STRING

HwChargeEntry  
SEQUENCE    
  hwChargeAdminStatus INTEGER
  hwChargeOperStatus INTEGER
  hwAverageChargeVoltage MeasuresRange
  hwFloatChargeVoltage MeasuresRange
  hwChargeControlRowStatus RowStatus
  hwAverageChargeTime Integer32
  hwBatteryTmpRedeemingQuotiety Integer32

HwBatteryEntry  
SEQUENCE    
  hwBatteryIndex Integer32
  hwBatteryCapacity Integer32
  hwBatteryLoopState INTEGER
  hwBatteryVoltage MeasuresRange
  hwBatteryState INTEGER
  hwBatteryCurrent MeasuresRange
  hwBatteryTemperature Integer32
  hwBatteryRowStatus RowStatus
  hwBatteryCurrentHigh MeasuresRange
  hwBatteryFuseState INTEGER
  hwBatteryContactState INTEGER
  hwBatteryRemainCapacity Integer32
  hwBatteryProtectState INTEGER
  hwBatteryVoltageState INTEGER
  hwBatteryHardwareState INTEGER

HwBatteryTestEntry  
SEQUENCE    
  hwBatteryTestAdminStatus INTEGER
  hwBatteryTestAutoDischargePeriod Integer32
  hwBatteryTestResult INTEGER
  hwBatteryTestStartTime DateAndTime
  hwBatteryTestDuration Integer32
  hwBatteryTestTerminateVoltage Integer32
  hwBatteryTestTotalDischargeAH Integer32
  hwBatteryTestOperStatus INTEGER
  hwBatteryTestPhase INTEGER
  hwBatteryTestStartHour Integer32
  hwBatteryTestAlarmThreshold Integer32

HwBatteryLogTestEntry  
SEQUENCE    
  hwBatteryLogTestIndex Integer32
  hwBatteryLogTestStartTime DateAndTime
  hwBatteryLogTestDischargeDuration Integer32
  hwBatteryLogTestTerminateVoltage Integer32
  hwBatteryLogTestBatteryStatus INTEGER
  hwBatteryLogTestTotalDischargeAH Integer32
  hwBatteryLogTestFinish INTEGER
  hwBatteryLogTestEfficiency Integer32
  hwBatteryLogTestBatteryTemperature Integer32
  hwBatteryLogTestBatteryCurrent Integer32

HwRemoteProvidePowerInfoEntry  
SEQUENCE    
  hwPowerCentralState INTEGER
  hwPowerCentralDCInPutState INTEGER
  hwPowerCentralDCOutputState INTEGER
  hwPowerCentralDCOutputMode INTEGER
  hwPowerRemoteCommState INTEGER
  hwPowerRemoteDCInputState INTEGER
  hwPowerRemoteLineCurState INTEGER
  hwPowerRemotePowerState INTEGER
  hwPowerRemoteLineState BITS
  hwPowerCentralLoadState INTEGER

HwACInfomationEntry  
SEQUENCE    
  hwACInfoCommState INTEGER
  hwACInfoThunderState INTEGER
  hwACInfoCurrentLoop Integer32
  hwACInfoMCBTrigger INTEGER
  hwACInfoFrequency Integer32
  hwACInfoRowStatus RowStatus

Defined Values

hwPower 1.3.6.1.4.1.2011.6.2
This MIB is used for defining Power Monitor management MIB objects.
MODULE-IDENTITY    

hwPowerMonObjects 1.3.6.1.4.1.2011.6.2.1
OBJECT IDENTIFIER    

hwPowerSysInfoTable 1.3.6.1.4.1.2011.6.2.1.1
Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwPowerSysInfoEntry

hwPowerSysInfoEntry 1.3.6.1.4.1.2011.6.2.1.1.1
Power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwPowerSysInfoEntry  

hwPowerIndex 1.3.6.1.4.1.2011.6.2.1.1.1.1
Index of the power supply monitored by the monitoring unit
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwPowerType 1.3.6.1.4.1.2011.6.2.1.1.1.2
Type of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.power48100(3) - Type of the Power emu device is power48100 4.power4850(4) - Type of the Power emu device is power4850 5.power48240(5) - Type of the Power emu device is power48240 6.power48120(6) - Type of the Power emu device is power48120 7.power48300(7) - Type of the Power emu device is power48300 8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase 9.universalPower(9) - Type of the Power emu device is universalPower 10.power4845(10) - Type of the Power emu device is power4845 11.rpower(11) - Type of the Power emu device is rpower 12.power4805(15) - Type of the Power emu device is power4805 13.power4820(16) - Type of the Power emu device is power4820 14.onps(17) - Type of the Power emu device is onps 15.power4875l(18) - Type of the Power emu device is power4875l 16.psma(100) - Type of the Power emu device is psma 17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt 18.mcs1800(102) - Type of the Power emu device is mcs1800 19.mcs1800A(103) - Type of the Power emu device is mcs1800A 20.mcs3000(104) - Type of the Power emu device is mcs3000 21.sm40sm60(105) - Type of the Power emu device is sm40sm60 22.scu(106) - Type of the Power emu device is scu 23.eltek(107) - Type of the Power emu device is eltek 24.dk04(108) - Type of the Power emu device is dk04 25.dk04C(109) - Type of the Power emu device is dk04C 26.dpc(110) - Type of the Power emu device is dpc 27.power4830(120) - Type of the Power emu device is power4830 28.h831pmua(121) - Type of the Power emu device is h831pmua 29.power3000(122) - Type of the Power emu device is power3000 30.liFeBattery(123) - Type of the Power emu device is LiFeBattery 31.etp4830(125), - Type of SMU Power emu device is etp4830 32.etp4890(126), - Type of SMU Power emu device is etp4890 33.other(255) - other Power Type
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER power4875(1), power4810(2), power48100(3), power4850(4), power48240(5), power48120(6), power48300(7), power48240SinglePhase(8), universalPower(9), power4845(10), rpower(11), power4805(15), power4820(16), onps(17), power4875l(18), psma(100), perm-al175nt(101), mcs1800(102), mcs1800A(103), mcs3000(104), sm40sm60(105), scu(106), eltek(107), dk04(108), dk04C(109), dpc(110), power4830(120), h831pmua(121), power3000(122), liFeBattery(123), etp4830(125), etp4890(126), other(255)  

hwPowerName 1.3.6.1.4.1.2011.6.2.1.1.1.3
Power name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwPowerState 1.3.6.1.4.1.2011.6.2.1.1.1.4
Power board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - indicates the faulty state 3.protecting(3)- indicates that the backup power supply works in the protection state 4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply 5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), fault(2), protecting(3), switched(4), invalid(-1)  

hwPowerRowStatus 1.3.6.1.4.1.2011.6.2.1.1.1.5
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwPowerControlMode 1.3.6.1.4.1.2011.6.2.1.1.1.6
Control mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER manualControl(1), autoControl(2), invalid(-1)  

hwPowerRemoteFrameID 1.3.6.1.4.1.2011.6.2.1.1.1.7
Apply for remote power system. It is the frame ID that the remote unit exists in
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

hwPowerProtect 1.3.6.1.4.1.2011.6.2.1.1.1.8
Apply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER protect(1), undoProtect(2)  

hwPowerVersion 1.3.6.1.4.1.2011.6.2.1.1.1.9
Version of power
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwPowerSupplyState 1.3.6.1.4.1.2011.6.2.1.1.1.10
Power supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ac(1), battery(2)  

hwACInputTable 1.3.6.1.4.1.2011.6.2.1.2
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwACInputEntry

hwACInputEntry 1.3.6.1.4.1.2011.6.2.1.2.1
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwACInputEntry  

hwACLoopIndex 1.3.6.1.4.1.2011.6.2.1.2.1.1
Input loop index. There are two channels of AC current input, which are the backup for each other.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwACPowerState 1.3.6.1.4.1.2011.6.2.1.2.1.2
Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is overvoltage 4.belowVoltage(4) - indicates that the power supply is undervoltage 5.backup(5) - indicates that the power supply is not supported currently 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), offline(2), exceedVoltage(3), belowVoltage(4), backup(5), invalid(-1)  

hwACVoltA 1.3.6.1.4.1.2011.6.2.1.2.1.3
AC Inuput voltage A. Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACCurrentA 1.3.6.1.4.1.2011.6.2.1.2.1.4
AC input Current A. Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACVoltB 1.3.6.1.4.1.2011.6.2.1.2.1.5
AC input voltage B. Unit: mv
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACCurrentB 1.3.6.1.4.1.2011.6.2.1.2.1.6
AC input current B. Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACVoltC 1.3.6.1.4.1.2011.6.2.1.2.1.7
AC input voltage C. Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACCurrentC 1.3.6.1.4.1.2011.6.2.1.2.1.8
AC input current C. Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwACVoltageHigh 1.3.6.1.4.1.2011.6.2.1.2.1.9
AC input over-voltage alarm threshold. Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwACVoltageLow 1.3.6.1.4.1.2011.6.2.1.2.1.10
AC input under-voltage alarm threshold. Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwACRowStatus 1.3.6.1.4.1.2011.6.2.1.2.1.11
Only the add operation, delete operation, and status query operation are supported.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwACVoltageAState 1.3.6.1.4.1.2011.6.2.1.2.1.12
Phase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)  

hwACVoltageBState 1.3.6.1.4.1.2011.6.2.1.2.1.13
Phase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)  

hwACVoltageCState 1.3.6.1.4.1.2011.6.2.1.2.1.14
Phase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)  

hwDCOutTable 1.3.6.1.4.1.2011.6.2.1.3
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwDCOutEntry

hwDCOutEntry 1.3.6.1.4.1.2011.6.2.1.3.1
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwDCOutEntry  

hwDCVoltageOut 1.3.6.1.4.1.2011.6.2.1.3.1.1
DC voltage output. Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwDCCurrentOut 1.3.6.1.4.1.2011.6.2.1.3.1.2
DC current output. Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwDCVoltageOutHigh 1.3.6.1.4.1.2011.6.2.1.3.1.3
Output DC exceed-voltage alarm point. Default: 58000 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwDCVoltageOutLow 1.3.6.1.4.1.2011.6.2.1.3.1.4
Output DC below-voltage alarm point . Default value is 45V. Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwDCVoltageOutState 1.3.6.1.4.1.2011.6.2.1.3.1.5
DC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage 4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: deprecated Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), exceedVoltage(2), belowVoltage(3), invalid(-1)  

hwDCCurrentOutHigh 1.3.6.1.4.1.2011.6.2.1.3.1.6
Output DC exceed-current alarm point . Unit: mA
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwDCCurrentOutLow 1.3.6.1.4.1.2011.6.2.1.3.1.7
Output below-current alarm point . Unit: mA
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwDCCurrentOutState 1.3.6.1.4.1.2011.6.2.1.3.1.8
DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: deprecated Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), exceedVoltage(2), belowVoltage(3), invalid(-1)  

hwDCOutRowStatus 1.3.6.1.4.1.2011.6.2.1.3.1.9
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwDCOutLoadCurrent 1.3.6.1.4.1.2011.6.2.1.3.1.10
Total load current of DC output . Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwDCOutLoadTmpHigh 1.3.6.1.4.1.2011.6.2.1.3.1.11
The off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwDCOutRunState 1.3.6.1.4.1.2011.6.2.1.3.1.12
DC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates output over-voltage 4.batteryVoltageLack(3) - indicates battery lack-voltage 5.loadOff(4) - indicates load off twice 6.batteryOff(5) - indictes battery protection (off once) 7.communicationFailure(6) - indicates that the communication fails 8.dcOutManual(7) - indicates DC by manual
Status: current Access: read-only
OBJECT-TYPE    
  BITS battery1ChargeCurOver(0), battery2ChargeCurOver(1), batteryVoltageOver(2), batteryVoltageLack(3), loadOff(4), batteryOff(5), communicationFailure(6), dcOutManual(7)  

hwDCCommunicationState 1.3.6.1.4.1.2011.6.2.1.3.1.13
DC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), fault(1)  

hwLoadinfoTable 1.3.6.1.4.1.2011.6.2.1.4
Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwLoadinfoEntry

hwLoadinfoEntry 1.3.6.1.4.1.2011.6.2.1.4.1
Load information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwLoadinfoEntry  

hwLoadIndex 1.3.6.1.4.1.2011.6.2.1.4.1.1
Loop index: usually each DC output loop corresponds to a load.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwLoadInfoAdminState 1.3.6.1.4.1.2011.6.2.1.4.1.2
Load operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwLoadInfoOperStatus 1.3.6.1.4.1.2011.6.2.1.4.1.3
Status of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state of power supply is stopping power supply 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), abnormal(2), stop(3), invalid(-1)  

hwLoadCurrent 1.3.6.1.4.1.2011.6.2.1.4.1.4
Present current . Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwLoadVoltage 1.3.6.1.4.1.2011.6.2.1.4.1.5
Present voltage . Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwLoadVoltageHigh 1.3.6.1.4.1.2011.6.2.1.4.1.6
Off voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Default: 43500 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwLoadLoadName 1.3.6.1.4.1.2011.6.2.1.4.1.7
Load name: usually each DC output loop corresponds to a load.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwLoadInfoRowStatus 1.3.6.1.4.1.2011.6.2.1.4.1.8
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwLoadFuseState 1.3.6.1.4.1.2011.6.2.1.4.1.9
Load fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwLoadHoreIndex 1.3.6.1.4.1.2011.6.2.1.4.1.10
load hore index
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

hwRectifierTable 1.3.6.1.4.1.2011.6.2.1.5
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwRectifierEntry

hwRectifierEntry 1.3.6.1.4.1.2011.6.2.1.5.1
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwRectifierEntry  

hwRectifierIndex 1.3.6.1.4.1.2011.6.2.1.5.1.1
Rectifier Module index. There are multiple rectifier modules to a power source.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwRectifierAdminState 1.3.6.1.4.1.2011.6.2.1.5.1.2
Switch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwRectifierOperState 1.3.6.1.4.1.2011.6.2.1.5.1.3
Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2. fault(2) - indicates that the Rectifier operation state is fault 3. protect(3) - indicates that the Rectifier operation state is protect 4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure 5. on(5) - indicates that the Rectifier operation state is on 6. off(6) - indicates that the Rectifier operation state is off 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), fault(2), protect(3), communicationFailure(4), on(5), off(6), invalid(-1)  

hwRectifierVoltage 1.3.6.1.4.1.2011.6.2.1.5.1.4
Output voltage . Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwRectifierCurrent 1.3.6.1.4.1.2011.6.2.1.5.1.5
Output current . Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwRectifierRowStatus 1.3.6.1.4.1.2011.6.2.1.5.1.6
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwRectifierCurrentLimit 1.3.6.1.4.1.2011.6.2.1.5.1.7
current limit switch
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

hwRectifierRunState 1.3.6.1.4.1.2011.6.2.1.5.1.8
Running state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the module has output 4. isLimit(3) - indicates the current limit switch
Status: current Access: read-only
OBJECT-TYPE    
  BITS rectifierOn(0), averageCharge(1), output(2), isLimit(3)  

hwRectifierChargeState 1.3.6.1.4.1.2011.6.2.1.5.1.9
Charging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that the Charge state of Rectifier is test
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER float(0), average(1), test(2)  

hwBatteryGroup 1.3.6.1.4.1.2011.6.2.1.6
OBJECT IDENTIFIER    

hwBatteryGroupTable 1.3.6.1.4.1.2011.6.2.1.6.1
Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwBatteryGroupEntry

hwBatteryGroupEntry 1.3.6.1.4.1.2011.6.2.1.6.1.1
Basic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwBatteryGroupEntry  

hwBatteryGroupCapacity 1.3.6.1.4.1.2011.6.2.1.6.1.1.1
Total capacity of the present battery group. Unit: Ah
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryGroupCapcaityRemain 1.3.6.1.4.1.2011.6.2.1.6.1.1.2
Total remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..100  

hwBatteryGroups 1.3.6.1.4.1.2011.6.2.1.6.1.1.3
Number of battery group
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

hwBatteryGroupVoltageLow 1.3.6.1.4.1.2011.6.2.1.6.1.1.4
When the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryGroupChargeLimit 1.3.6.1.4.1.2011.6.2.1.6.1.1.5
Charge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryGroupRowStatus 1.3.6.1.4.1.2011.6.2.1.6.1.1.6
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwBatteryGroupOperStatus 1.3.6.1.4.1.2011.6.2.1.6.1.1.7
The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is abnormal, the battery group usually supplies power in an emergency. Options: 1.on(1) - indicates that the state of the battery power supply is on 2.off(2) - indicates that the state of the battery power supply is off 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwBatteryGroupVoltageHigh 1.3.6.1.4.1.2011.6.2.1.6.1.1.8
When the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryGroupTwiceOffVoltage 1.3.6.1.4.1.2011.6.2.1.6.1.1.9
The twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryGroupProtectVoltage 1.3.6.1.4.1.2011.6.2.1.6.1.1.10
The first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryGroupTmpOffHigh 1.3.6.1.4.1.2011.6.2.1.6.1.1.11
The high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryInstallTime 1.3.6.1.4.1.2011.6.2.1.6.1.1.12
The installing date of battery group.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwBatteryGroupBomCode 1.3.6.1.4.1.2011.6.2.1.6.1.1.13
The BAR code of battery.
Status: current Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(0..32)  

hwChargeTable 1.3.6.1.4.1.2011.6.2.1.6.2
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwChargeEntry

hwChargeEntry 1.3.6.1.4.1.2011.6.2.1.6.2.1
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwChargeEntry  

hwChargeAdminStatus 1.3.6.1.4.1.2011.6.2.1.6.2.1.1
Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicates that the charge management mode is auto-control charge 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER average(1), float(2), auto(3), invalid(-1)  

hwChargeOperStatus 1.3.6.1.4.1.2011.6.2.1.6.2.1.2
Charge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that the charge operation state is full 4. noCharge(4) - indicates that there is no charge in operation 5. discharge(5) - indicates that there is discharge in operation 6. sleep(6) - indicates that the charge operation state is sleep 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER average(1), float(2), full(3), noCharge(4), discharge(5), sleep(6), invalid(-1)  

hwAverageChargeVoltage 1.3.6.1.4.1.2011.6.2.1.6.2.1.3
Voltage value of average charge, in unit of mV. Default: 56500 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwFloatChargeVoltage 1.3.6.1.4.1.2011.6.2.1.6.2.1.4
Voltage value of float charge . Default: 53500 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwChargeControlRowStatus 1.3.6.1.4.1.2011.6.2.1.6.2.1.5
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwAverageChargeTime 1.3.6.1.4.1.2011.6.2.1.6.2.1.6
Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTmpRedeemingQuotiety 1.3.6.1.4.1.2011.6.2.1.6.2.1.7
Temperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree centigrade of the battery temperature. The unit is mV. Specific value is determined by the redeem feature curve of floating charge for the battery group used. Default value is 100mV
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTable 1.3.6.1.4.1.2011.6.2.1.6.3
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwBatteryEntry

hwBatteryEntry 1.3.6.1.4.1.2011.6.2.1.6.3.1
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwBatteryEntry  

hwBatteryIndex 1.3.6.1.4.1.2011.6.2.1.6.3.1.1
Battery group loop index
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwBatteryCapacity 1.3.6.1.4.1.2011.6.2.1.6.3.1.2
The permitted max battery capacity of the battery group loop charge. Unit: Ah
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryLoopState 1.3.6.1.4.1.2011.6.2.1.6.3.1.3
The battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwBatteryVoltage 1.3.6.1.4.1.2011.6.2.1.6.3.1.4
The loop voltage of the battery group. Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwBatteryState 1.3.6.1.4.1.2011.6.2.1.6.3.1.5
The present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop is discharge 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER charge(1), discharge(2), invalid(-1)  

hwBatteryCurrent 1.3.6.1.4.1.2011.6.2.1.6.3.1.6
Present current . Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  MeasuresRange  

hwBatteryTemperature 1.3.6.1.4.1.2011.6.2.1.6.3.1.7
The loop temperature of the battery group. Unit: degree
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryRowStatus 1.3.6.1.4.1.2011.6.2.1.6.3.1.8
RowStatus standard operation
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwBatteryCurrentHigh 1.3.6.1.4.1.2011.6.2.1.6.3.1.9
The over-current alarm point of the battery group. Unit: mA
Status: current Access: read-write
OBJECT-TYPE    
  MeasuresRange  

hwBatteryFuseState 1.3.6.1.4.1.2011.6.2.1.6.3.1.10
Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwBatteryContactState 1.3.6.1.4.1.2011.6.2.1.6.3.1.11
The state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), invalid(-1)  

hwBatteryRemainCapacity 1.3.6.1.4.1.2011.6.2.1.6.3.1.12
Remain capacity of the battery
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryProtectState 1.3.6.1.4.1.2011.6.2.1.6.3.1.13
Protection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature 3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), overtemperature(2), overCurrent(3)  

hwBatteryVoltageState 1.3.6.1.4.1.2011.6.2.1.6.3.1.14
Voltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), exceedVoltage(2), belowVoltage(3)  

hwBatteryHardwareState 1.3.6.1.4.1.2011.6.2.1.6.3.1.15
Hardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), fault(2)  

hwBatteryTestTable 1.3.6.1.4.1.2011.6.2.1.6.4
Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwBatteryTestEntry

hwBatteryTestEntry 1.3.6.1.4.1.2011.6.2.1.6.4.1
Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwBatteryTestEntry  

hwBatteryTestAdminStatus 1.3.6.1.4.1.2011.6.2.1.6.4.1.1
Battery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that the Battery enables auto test function 4. disableAutoTest(4) - indicates that the Battery disables auto test function 5. timeautoTest(5) - indicates that the Battery enable timing auto test function 6. offautoTest(6) - indicates that the Battery enable off auto test function 7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER start(1), terminate(2), enableAutoTest(3), disableAutoTest(4), timeautoTest(5), offautoTest(6), timeoffautoTest(7)  

hwBatteryTestAutoDischargePeriod 1.3.6.1.4.1.2011.6.2.1.6.4.1.2
Auto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTestResult 1.3.6.1.4.1.2011.6.2.1.6.4.1.3
Test result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms 4. hostTerminated(4) - indicates that the Battery test is stopped by the host 5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time 6. normal(6) - indicates that the Battery test is not started 7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover
Status: obsolete Access: read-only
OBJECT-TYPE    
  INTEGER testing(1), complete(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), normal(6), supplyRecoverAutotestTerminated(7)  

hwBatteryTestStartTime 1.3.6.1.4.1.2011.6.2.1.6.4.1.4
Time of starting test
Status: obsolete Access: read-only
OBJECT-TYPE    
  DateAndTime  

hwBatteryTestDuration 1.3.6.1.4.1.2011.6.2.1.6.4.1.5
Battery discharge test duration . Effective range is 1-100 hours. Default :value is 10 hours Unit: hour
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTestTerminateVoltage 1.3.6.1.4.1.2011.6.2.1.6.4.1.6
Battery discharge test end voltage. Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTestTotalDischargeAH 1.3.6.1.4.1.2011.6.2.1.6.4.1.7
Total discharge AH. Unit: mAH
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryTestOperStatus 1.3.6.1.4.1.2011.6.2.1.6.4.1.8
Battery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled 4. offautoTestPermit(4) - indicates that off auto discharge test is enabled 5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER autoTestPermit(1), autoTestForbid(2), timeautoTestPermit(3), offautoTestPermit(4), timeoffautoTestPermit(5)  

hwBatteryTestPhase 1.3.6.1.4.1.2011.6.2.1.6.4.1.9
Battery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the power equipment recording test result 4. finish(4) - indicates that the discharge is complete 5.waitingfordischarge(5) - indicates that preparation is ready for discharge command
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER charge(1), discharge(2), record(3), finish(4), waitingfordischarge(5)  

hwBatteryTestStartHour 1.3.6.1.4.1.2011.6.2.1.6.4.1.10
Discharge start time. Effective range is 0 23 Default: 0 Unit: hour
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryTestAlarmThreshold 1.3.6.1.4.1.2011.6.2.1.6.4.1.11
The battery discharge test alarm threshold in ratio of the range:1~79.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestTable 1.3.6.1.4.1.2011.6.2.1.6.5
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwBatteryLogTestEntry

hwBatteryLogTestEntry 1.3.6.1.4.1.2011.6.2.1.6.5.1
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwBatteryLogTestEntry  

hwBatteryLogTestIndex 1.3.6.1.4.1.2011.6.2.1.6.5.1.1
Battery discharge test result index
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwBatteryLogTestStartTime 1.3.6.1.4.1.2011.6.2.1.6.5.1.2
Battery discharge test start time
Status: current Access: read-only
OBJECT-TYPE    
  DateAndTime  

hwBatteryLogTestDischargeDuration 1.3.6.1.4.1.2011.6.2.1.6.5.1.3
Duration of discharge. Unit: minute
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestTerminateVoltage 1.3.6.1.4.1.2011.6.2.1.6.5.1.4
End voltage of battery discharge test . Unit: mV
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestBatteryStatus 1.3.6.1.4.1.2011.6.2.1.6.5.1.5
Battery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER expectant(1), unexpected(2), unknown(3)  

hwBatteryLogTestTotalDischargeAH 1.3.6.1.4.1.2011.6.2.1.6.5.1.6
Discharge cumulate AH. Unit: mAH
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestFinish 1.3.6.1.4.1.2011.6.2.1.6.5.1.7
Battery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is stopped by alarms 4. hostTerminated(4) - indicates that the test is stopped by the host 5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours 6. notTest(6) - indicates that the test is not started
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER testing(1), completed(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), notTest(6)  

hwBatteryLogTestEfficiency 1.3.6.1.4.1.2011.6.2.1.6.5.1.8
The information of battery test efficiency.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestBatteryTemperature 1.3.6.1.4.1.2011.6.2.1.6.5.1.9
Battery discharge test end Temperature. Unit: 0.01 Degree
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwBatteryLogTestBatteryCurrent 1.3.6.1.4.1.2011.6.2.1.6.5.1.10
Battery discharge test average Current. Unit: mA
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwRemoteProvidePowerInfoTable 1.3.6.1.4.1.2011.6.2.1.7
Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwRemoteProvidePowerInfoEntry

hwRemoteProvidePowerInfoEntry 1.3.6.1.4.1.2011.6.2.1.7.1
Remote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwRemoteProvidePowerInfoEntry  

hwPowerCentralState 1.3.6.1.4.1.2011.6.2.1.7.1.1
State of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), temOver(2)  

hwPowerCentralDCInPutState 1.3.6.1.4.1.2011.6.2.1.7.1.2
State of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), lack(2), over(3)  

hwPowerCentralDCOutputState 1.3.6.1.4.1.2011.6.2.1.7.1.3
State of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) - indicates the over-loading 5. shortCircuit(5) - indicates the short circuit 6. noLoad(6) - indicates no load
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), volLack(2), volOver(3), loadOver(4), shortCircuit(5), noLoad(6)  

hwPowerCentralDCOutputMode 1.3.6.1.4.1.2011.6.2.1.7.1.4
Mode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER highVolMode(1), lowVolMode(2)  

hwPowerRemoteCommState 1.3.6.1.4.1.2011.6.2.1.7.1.5
Remote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), revfault(2), sendfault(3)  

hwPowerRemoteDCInputState 1.3.6.1.4.1.2011.6.2.1.7.1.6
State of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), lack(2)  

hwPowerRemoteLineCurState 1.3.6.1.4.1.2011.6.2.1.7.1.7
state of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - indicates the cur Over
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), cablejoining(2), curLeakage(3), curOver(4)  

hwPowerRemotePowerState 1.3.6.1.4.1.2011.6.2.1.7.1.8
state of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), fault(2)  

hwPowerRemoteLineState 1.3.6.1.4.1.2011.6.2.1.7.1.9
State of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 state 4. u4state(3) - indicates the power remote line state is u4 state 5. a1state(4) - indicates the power remote line state is a1 state 6. a2state(5) - indicates the power remote line state is a2 state 7. a3state(6) - indicates the power remote line state is a3 state 8. a4state(7) - indicates the power remote line state is a4 state
Status: current Access: read-write
OBJECT-TYPE    
  BITS u1state(0), u2state(1), u3state(2), u4state(3), a1state(4), a2state(5), a3state(6), a4state(7)  

hwPowerCentralLoadState 1.3.6.1.4.1.2011.6.2.1.7.1.10
state of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), overload(2), nonload(3)  

hwPowerMibTrap 1.3.6.1.4.1.2011.6.2.2
OBJECT IDENTIFIER    

hwPowerTrapOid 1.3.6.1.4.1.2011.6.2.2.1
OBJECT IDENTIFIER    

hwPowerTrapsDefine 1.3.6.1.4.1.2011.6.2.2.2
OBJECT IDENTIFIER    

hwPowerTraps 1.3.6.1.4.1.2011.6.2.2.2.0
OBJECT IDENTIFIER    

powerConnFaultAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.1
This trap message is reported when the communication between the power module and the monitoring board is fault.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerConnFaultAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.2
This trap message is reported when the communication between the power module and the monitoring board resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.3
This trap message is reported when there is a exception of AC input voltage.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.4
This trap message is reported when the state of AC input voltage resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageHighAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.5
This trap message is reported when the input voltage is too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageHighAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.6
This trap message is reported when the input voltage resumes to the normal range from a high value.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageLowAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.7
This trap message is reported when the input voltage is too low.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputVoltageLowAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.8
This trap message is reported when the input voltage resumes to the normal range from a low value.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputVoltageHighAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.9
This trap message is reported when the output voltage is too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputVoltageHighAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.10
This trap message is reported when the output voltage resumes to the normal range from a high value.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputCurrentHighAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.11
This trap message is reported when the output current is too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputCurrentHighAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.12
This trap message is reported when the output current resumes to the normal range from a high value.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputVoltageLowAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.13
This trap message is reported when the output voltage is too low.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputVoltageLowAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.14
This trap message is reported when the output voltage resumes to the normal range from a low value.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputCurrentLowAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.15
This trap message is reported when the output current is too low.
Status: current Access: read-write
NOTIFICATION-TYPE    

dcOutputCurrentLowAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.16
This trap message is reported when the output current resumes to the normal range from a low value.
Status: current Access: read-write
NOTIFICATION-TYPE    

overLoadPowerAbnormalAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.17
This trap message is reported when the state of load power is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

overLoadPowerAbnormalAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.18
This trap message is reported when the state of load power recovers to normal.
Status: current Access: read-write
NOTIFICATION-TYPE    

overBattPowerOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.19
This trap message is reported when the battery is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

overBattPowerOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.20
This trap message is reported when the battery is powered on.
Status: current Access: read-write
NOTIFICATION-TYPE    

overLoadPowerOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.21
This trap message is reported when the loadpower is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

overLoadPowerOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.22
This trap message is reported when the loadpower is powered on.
Status: current Access: read-write
NOTIFICATION-TYPE    

acMainsSupplyAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.23
This trap message is reported when the AC mains supply is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

acMainsSupplyAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.24
This trap message is reported when the AC mains supply recovers to normal.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryLoopAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.25
This trap message is reported when the loop of battery group disconnects.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryLoopAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.26
This trap message is reported when the loop of battery group connects.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryFuseAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.27
This trap message is reported when the fuse of battery group disconnects.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryFuseAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.28
This trap message is reported when the fuse of battery group connects.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryContachAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.29
This trap message is reported when the contactor of battery group disconnects.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryContachAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.30
This trap message is reported when the contactor of battery group connects.
Status: current Access: read-write
NOTIFICATION-TYPE    

userModuleOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.31
This trap message is reported when the user module is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

userModuleOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.32
This trap message is reported when the user module is powered on.
Status: current Access: read-write
NOTIFICATION-TYPE    

transferModuleOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.33
This trap message is reported when the transfer module is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

transferModuleOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.34
This trap message is reported when the transfer module is powered on.
Status: current Access: read-write
NOTIFICATION-TYPE    

userModuleSwitchAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.35
This trap message is reported when the user module is switched off.
Status: current Access: read-write
NOTIFICATION-TYPE    

transferModuleSwitchAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.37
This trap message is reported when the transfer module is switched off.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadFuseAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.39
This trap message is reported when the load fuse is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadFuseAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.40
This trap message is reported when the load fuse resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

chargeCtrlStateAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.41
This trap message is reported when the control state of average or floating charge converts.
Status: current Access: read-write
NOTIFICATION-TYPE    

chargeModeAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.42
This trap message is reported when the charge state converts.
Status: current Access: read-write
NOTIFICATION-TYPE    

acCommFailAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.43
This trap message is reported when the AC panel communication fails.
Status: current Access: read-write
NOTIFICATION-TYPE    

acCommFailAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.44
This trap message is reported when the AC panel communication resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryChargeOverAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.45
This trap message is reported when the Over-current of battery group happens.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryChargeOverAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.46
OThis trap message is reported when the Over-current of battery group resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryVoltageLackAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.47
This trap message is reported when the voltage of battery group lacks.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryVoltageLackAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.48
This trap message is reported when the voltage of battery group recovers from lack.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadTwiceOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.49
This trap message is reported when the load is powered off twice.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadTwiceOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.50
This trap message is reported when the load recovers from powering off twice.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadOnceOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.51
This trap message is reported when the load is powered off once.
Status: current Access: read-write
NOTIFICATION-TYPE    

loadOnceOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.52
This trap message is reported when the load recovers from powering off once.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputPowerOffAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.53
This trap message is reported when the AC input is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputPowerOffAlarmResume 1.3.6.1.4.1.2011.6.2.2.2.0.54
This trap message is reported when the AC input power is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

acInputLoopSwtichAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.55
This trap message is reported when the AC input loop switches to another one.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryDischargeTestStartAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.56
This trap message is reported when the battery discharge test starts.
Status: current Access: read-write
NOTIFICATION-TYPE    

batteryDischargeTestStopAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.57
This trap message is reported when the battery discharge test stops.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerProtectAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.58
This trap message is reported when the power protection function is enbaled.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerUndoProtectAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.59
This trap message is reported when the power protection function is disabled.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerCentralOutputModeSwtichAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.60
This trap message is reported when the central output mode swtiches to another one.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerCentralTempretaureAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.61
This trap message is reported when the central tempretaure is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerCentralInputAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.62
This trap message is reported when the central input voltage is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerCentralOutputAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.63
This trap message is reported when the central output voltage is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerRemoteCommFaultAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.64
This trap message is reported when the communiction between the remote and central fails.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerRemoteVoltageAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.65
This trap message is reported when the remote voltage is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerLineAlarm 1.3.6.1.4.1.2011.6.2.2.2.0.66
This trap message is reported when the power line is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerRemotePowerAlarm1 1.3.6.1.4.1.2011.6.2.2.2.0.67
This trap message is reported when the remote power is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerRemotePowerAlarm2 1.3.6.1.4.1.2011.6.2.2.2.0.68
This trap message is reported when the Line UA is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

powerRemotePowerAlarm3 1.3.6.1.4.1.2011.6.2.2.2.0.69
This trap message is reported when the Central load is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwACInfomationTable 1.3.6.1.4.1.2011.6.2.1.8
AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwACInfomationEntry

hwACInfomationEntry 1.3.6.1.4.1.2011.6.2.1.8.1
AC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwACInfomationEntry  

hwACInfoCommState 1.3.6.1.4.1.2011.6.2.1.8.1.1
communication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), fault(1)  

hwACInfoThunderState 1.3.6.1.4.1.2011.6.2.1.8.1.2
Thunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), fault(1)  

hwACInfoCurrentLoop 1.3.6.1.4.1.2011.6.2.1.8.1.3
Current AC input working loop. The leaf is not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwACInfoMCBTrigger 1.3.6.1.4.1.2011.6.2.1.8.1.4
AC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. break-down(1)- indicates the AC input MCB trigger state is break-down
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), break-down(1)  

hwACInfoFrequency 1.3.6.1.4.1.2011.6.2.1.8.1.5
The infomation of AC input frequency. This leaf is not supported. Unit: HZ
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwACInfoRowStatus 1.3.6.1.4.1.2011.6.2.1.8.1.6
RowStatus standard operation The leaf is not supported.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

powerConformance 1.3.6.1.4.1.2011.6.2.3
OBJECT IDENTIFIER    

powerCompliances 1.3.6.1.4.1.2011.6.2.3.1
OBJECT IDENTIFIER    

powerGroups 1.3.6.1.4.1.2011.6.2.3.2
OBJECT IDENTIFIER    

hwEnvironPowerTraps 1.3.6.1.4.1.2011.6.2.4
OBJECT IDENTIFIER    

hwEnvironPowerCommonTraps 1.3.6.1.4.1.2011.6.2.4.1
OBJECT IDENTIFIER    

hwEnvironPowerAlarmTraps 1.3.6.1.4.1.2011.6.2.4.2
OBJECT IDENTIFIER    

hwEnvironPowerAlarmTrapsPrefix 1.3.6.1.4.1.2011.6.2.4.2.0
OBJECT IDENTIFIER    

hwEmmPowerBattaryTestStartTrap 1.3.6.1.4.1.2011.6.2.4.2.0.1
The agent generates this trap when the power device battary discharge test starts.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBattaryTestStopTrap 1.3.6.1.4.1.2011.6.2.4.2.0.2
The agent generates this trap when the power device battary discharge test ends.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerAcvolFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.3
The agent generates this trap when the power device AC input voltage is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerAcvolRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.4
The agent generates this trap when the power device AC input voltage recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerDcvolFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.5
The agent generates this trap when the power device DC output voltage is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerDcvolRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.6
The agent generates this trap when the power device DC output voltage recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBattloopFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.7
The agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBattloopRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.8
The agent generates this trap when the power device battery loop recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerLoadfuseFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.9
The agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerLoadfuseRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.10
The agent generates this trap when the fuse of the power device recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerRectifierFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.11
The agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerRectifierRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.12
The agent generates this trap when the rectifier module of the power device recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigMainsupplyFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.13
The agent generates this trap when the main supply digital is faulty.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigMainsupplyRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.14
The agent generates this trap when the main supply digital recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBatteryOffTrap 1.3.6.1.4.1.2011.6.2.4.2.0.15
The agent generates this trap when the power of battary is off.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmBatt1TempFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.16
The agent generates this trap when the battery group 1 temperature sensor fault occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmBatt1TempRestoreTrap 1.3.6.1.4.1.2011.6.2.4.2.0.17
The agent generates this trap when the battery group 1 temperature sensor fault recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEnviHumFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.18
The agent generates this trap when the environment humidity sensor fault occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEnviHumRestoreTrap 1.3.6.1.4.1.2011.6.2.4.2.0.19
The agent generates this trap when the environment humidity sensor fault recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEnvi1TempFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.20
The agent generates this trap when the environment 1 temperature sensor fault occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEnvi1TempRestoreTrap 1.3.6.1.4.1.2011.6.2.4.2.0.21
The agent generates this trap when the environment 1 temperature sensor fault recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmBattTemFaultTrap 1.3.6.1.4.1.2011.6.2.4.2.0.22
The agent generates this trap when the battery temperature out of normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmBattTemRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.23
The agent generates this trap when the battery temperature recovers to normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBatteryOffRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.24
The agent generates this trap when the power of battary recovers to on state.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBatteryUnDetectTrap 1.3.6.1.4.1.2011.6.2.4.2.0.25
The agent generates this trap when the one or more batteries are not detected.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmPowerBatteryDetectRecoverTrap 1.3.6.1.4.1.2011.6.2.4.2.0.26
The agent generates this trap when the batteries recover.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwPowerModuleMismatchTrap 1.3.6.1.4.1.2011.6.2.4.2.0.27
The agent generates this trap when the the power supply system detects mismatched power module .
Status: current Access: read-write
NOTIFICATION-TYPE    

hwPowerModuleRestoreTrap 1.3.6.1.4.1.2011.6.2.4.2.0.28
The agent generates this trap when the power module recovers.
Status: current Access: read-write
NOTIFICATION-TYPE