HUAWEI-ENVIRONMENT-MIB

File: HUAWEI-ENVIRONMENT-MIB.mib (80265 bytes)

Imported modules

HUAWEI-MIB SNMPv2-SMI SNMPv2-TC
HUAWEI-DEVICE-MIB

Imported symbols

huaweiUtility Integer32 OBJECT-TYPE
MODULE-IDENTITY NOTIFICATION-TYPE DisplayString
RowStatus hwFrameIndex

Defined Types

HwEnvironmentInfoEntry  
SEQUENCE    
  hwEnvEmuIndex Integer32
  hwEnvEmuType INTEGER
  hwEnvBoardName DisplayString
  hwEnvCommState INTEGER
  hwEnvRowStatus RowStatus
  hwEnvVersion DisplayString
  hwEnvFrameId Integer32
  hwEnvAdminStatus INTEGER
  hwEnvSlaveNodeId Integer32
  hwEnvComType INTEGER
  hwEnvCLEICode OCTET STRING
  hwEnvEmuPower Integer32
  hwEnvEmuTypeName DisplayString

HwAnaChannelEntry  
SEQUENCE    
  hwAnaChannelIndex Integer32
  hwAnaName DisplayString
  hwAnaType INTEGER
  hwAnaMeasureType DisplayString
  hwAnaWorkHigh Integer32
  hwAnaWorkLow Integer32
  hwAnaAlmHigh Integer32
  hwAnaAlmLow Integer32
  hwAnaCurrentValue Integer32
  hwAnaAlarmState INTEGER
  hwAnaRowStatus RowStatus
  hwAnaAlarmID INTEGER

HwDigChannelEntry  
SEQUENCE    
  hwDigChannelIndex Integer32
  hwDigChannelName DisplayString
  hwAlmCondition INTEGER
  hwDigChannelState INTEGER
  hwDigRowStatus RowStatus
  hwDigAlarmID INTEGER

HwControlOutEntry  
SEQUENCE    
  hwControlOutIndex Integer32
  hwControlOutName DisplayString
  hwControlOutAdminStatus INTEGER
  hwControlOutRowStatus RowStatus

HwFanEntry  
SEQUENCE    
  hwFanName DisplayString
  hwFanControlMode INTEGER
  hwFanControlState BITS
  hwESCFanTempAutoOn Integer32
  hwESCFanTempAutoOff Integer32
  hwFanRowStatus RowStatus
  hwCurrentTemp Integer32
  hwFanSpeedMode INTEGER
  hwFanSpeed Integer32
  hwFanTypeDescription DisplayString

HwTcuEntry  
SEQUENCE    
  hwTcuHeatExchangerType DisplayString
  hwTcuExternalFanRev Integer32
  hwTcuInternalFanRev Integer32
  hwTcuStartHeatTemp Integer32
  hwTcuStopHeatTemp Integer32

Defined Values

hwEnvironment 1.3.6.1.4.1.2011.6.1
The MIB module defines MIB objects which include Environment Monitor Unit, Analog Environment data, Digital Environment data, Out data and Fan data Monitor management MIB interfaces.
MODULE-IDENTITY    

hwEnvironmentMon 1.3.6.1.4.1.2011.6.1.1
OBJECT IDENTIFIER    

hwEnvironmentInfoTable 1.3.6.1.4.1.2011.6.1.1.1
Information table of Environment Monitor Unit. The Environment Monitor Unit is some kind of Environment monitoring device and is used to monitor many kinds of Environment data. The maximum number of Environment Monitor Units in one device node is 64. The index of this table is hwEnvEmuIndex. hwEnvEmuIndex is the index of one Environment Monitor Unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwEnvironmentInfoEntry

hwEnvironmentInfoEntry 1.3.6.1.4.1.2011.6.1.1.1.1
Information table of Environment Monitor Unit. The Environment Monitor Unit is some kind of Environment monitoring device and is used to monitor many kinds of Environment data. The maximum number of Environment Monitor Units in one device node is 64. The index of this entry is hwEnvEmuIndex. hwEnvEmuIndex is the index of one Environment Monitor Unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwEnvironmentInfoEntry  

hwEnvEmuIndex 1.3.6.1.4.1.2011.6.1.1.1.1.1
hwEnvEmuIndex is the index of the Environment monitoring unit, used as the index of hwEnvironmentInfoTable. Range: 0 - 2048
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..2048  

hwEnvEmuType 1.3.6.1.4.1.2011.6.1.1.1.1.2
Type of the physical monitoring devices associated with the environment monitoring unit. Options: 1.h302ESC(1) -Type of the physical monitoring devices is H302ESC 2.h303ESC(2) -Type of the physical monitoring devices is H303ESC 3.h4875(3) -Type of the physical monitoring devices is 4875 power monitoring frame 4.h301ESC(4) -Type of the physical monitoring devices is H301ESC 5.switch(5) -Distribute monitoring frame 6.fanEscFrame(6) -ESC monitoring fan frame 7.fanFrame(7) -monitoring fan frame 8.h4845(8) -4845 power monitoring 9.fanFCBFrame(9) -FCB monitoring fan frame 10.fanFDMUFrame(10) -FDMU monitoring fan frame 11.h304ESC(11) -provides the management function of battery 12.pwma(12) -Type of the physical monitoring devices is pwma 13.h561esc(13) -H561ESC 14.h801esc(14) -H801Esc 15.h612pwbp(15) -H612pwbp 16.pse158(16) -pse158 17.h4805(19) -h4805 18.pdu(20) -pdu 19.acrmu(21) -ac_rmu 20.acfan(22) -ac_fan 21.dcfan(23) -dc_fan 22.rmun1509(24) -rmun1509 23.onps150(25) -onps150 24.h801pmix(26) -h801pmix 25.h4875L(27) -h4875L 26.miniESC(28) -miniESC 27.h831VESC(29) -H831VESC 28.h601VESC(30) -H601VESC 29.h4830L(31) -h4830L 30.h801citx(32) -h801citx 31.h801citd(33) -h801citd 32.h831ccuh(34) -h831ccuh 33.h831pmu(35) -h831pmu 34.pwr3000(36) -a type of power named power 3000, supports 12 rectifier modules 35.tcu(37) -tcu 36.liFeBattery(38) -liFeBattery 37.transemu(39) -a type of emu for transport environment information to managment center 38.smu(40) -site monitoring unit 39.vpea(41) -vector monitoring unit 40.other(255) -other
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER h302ESC(1), h303ESC(2), h4875(3), h301ESC(4), switch(5), fanEscFrame(6), fanFrame(7), h4845(8), fanFCBFrame(9), fanFDMUFrame(10), h304ESC(11), pwma(12), h561esc(13), h801esc(14), h612pwbp(15), pse158(16), h4805(19), pdu(20), acrmu(21), acfan(22), dcfan(23), rmun1509(24), onps150(25), h801pmix(26), h4875L(27), miniESC(28), h831VESC(29), h601VESC(30), h4830L(31), h801citx(32), h801citd(33), h831ccuh(34), h831pmu(35), pwr3000(36), tcu(37), liFeBattery(38), transemu(39), smu(40), vpea(41), other(255)  

hwEnvBoardName 1.3.6.1.4.1.2011.6.1.1.1.1.3
Name of the environment monitoring unit.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwEnvCommState 1.3.6.1.4.1.2011.6.1.1.1.1.4
Status of the communication between the environment monitoring unit and the device. The environmental condition can be tested only when the communication is normal. Options: 1.normal(1) - indicates that communication state is normal 2.shutdown(2) - indicates that communication state is shutdown 3.fault(3) - indicates that communication state is fault 4.abnormal(4) - indicates that communication state is abnormal 5.config(5) - indicates that communication state is config
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), shutdown(2), fault(3), abnormal(4), config(5)  

hwEnvRowStatus 1.3.6.1.4.1.2011.6.1.1.1.1.5
RowStatus standard operation. The creation and deletion operations are supported currently.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwEnvVersion 1.3.6.1.4.1.2011.6.1.1.1.1.6
Version information of the environment monitoring unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwEnvFrameId 1.3.6.1.4.1.2011.6.1.1.1.1.7
ID of the shelf housing the environment monitoring unit.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwEnvAdminStatus 1.3.6.1.4.1.2011.6.1.1.1.1.8
The management status of the monitoring unit. Options: 1.noOperation(1) -no any operation 2.reset(2) -reset the monitoring board 3.manage(3) -manage the monitoring unit 4.unmanage(4) -undo manage the monitoring unit 5.clearsmokealarm(5) -clear the smoke alarm for miniEsc
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2), manage(3), unmanage(4), clearsmokealarm(5)  

hwEnvSlaveNodeId 1.3.6.1.4.1.2011.6.1.1.1.1.9
ID of the slave object that the environment monitoring unit belongs to. The environment monitoring unit uses the slave object ID to communicate with the upstream equipment.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwEnvComType 1.3.6.1.4.1.2011.6.1.1.1.1.10
The serial communication protocol type between the monitoring unit and the upstream equipment. The protocol types used are as follows: Options: 1.unknown(1) -The protocol types is unknown 2.serialRS485(2) -The protocol types is serialRS485 3.serialRS232(3) -The protocol types is serialRS232 4.serialRS422(4) -The protocol types is serialRS422
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unknown(1), serialRS485(2), serialRS232(3), serialRS422(4)  

hwEnvCLEICode 1.3.6.1.4.1.2011.6.1.1.1.1.11
Environment CLEI Code.
Status: current Access: read-only
OBJECT-TYPE    
  OCTET STRING Size(0..640)  

hwEnvEmuPower 1.3.6.1.4.1.2011.6.1.1.1.1.12
Power of the environment monitoring equipment associated with the environment monitoring unit. Unit: Watt.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwEnvEmuTypeName 1.3.6.1.4.1.2011.6.1.1.1.1.13
Name of the environment type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwAnaChannelTable 1.3.6.1.4.1.2011.6.1.1.2
Information table of the analog parameters monitored. The indexes of this table are hwEnvEmuIndex or hwAnaChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwAnaChannelIndex is the index of the analog parameter that is monitored by a monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwAnaChannelEntry

hwAnaChannelEntry 1.3.6.1.4.1.2011.6.1.1.2.1
Information table of the analog parameters monitored. The indexes of this entry are hwEnvEmuIndex or hwAnaChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwAnaChannelIndex is the index of the analog parameter that is monitored by a monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwAnaChannelEntry  

hwAnaChannelIndex 1.3.6.1.4.1.2011.6.1.1.2.1.1
Index of the analog parameter that is monitored by the monitoring unit. Range: 0 - 255
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwAnaName 1.3.6.1.4.1.2011.6.1.1.2.1.2
Name of the analog parameter that is monitored by a monitoring unit.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwAnaType 1.3.6.1.4.1.2011.6.1.1.2.1.3
This object indicates the type of the sensor that is used to test the Analog parameter. Options: 1.invalid(-1) -there is no valid sensor 2.voltage(1) -voltage sensor currently 3.current(2) -current sensor currently
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER invalid(-1), voltage(1), current(2)  

hwAnaMeasureType 1.3.6.1.4.1.2011.6.1.1.2.1.4
This object indicates the unit of the analog parameter that is tested.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwAnaWorkHigh 1.3.6.1.4.1.2011.6.1.1.2.1.5
High limit of the analog normal work
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwAnaWorkLow 1.3.6.1.4.1.2011.6.1.1.2.1.6
Low limit of the analog normal work
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwAnaAlmHigh 1.3.6.1.4.1.2011.6.1.1.2.1.7
High limit of the analog alarm. The alarm is produced when the measurement value is higher than this value
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwAnaAlmLow 1.3.6.1.4.1.2011.6.1.1.2.1.8
The low limit of the analog alarm. The alarm is produced when the measurement value is lower than this value.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwAnaCurrentValue 1.3.6.1.4.1.2011.6.1.1.2.1.9
The actual measurement value of the present analog. Unit: milli
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwAnaAlarmState 1.3.6.1.4.1.2011.6.1.1.2.1.10
The status of the present monitored. Options: 1.normal(1) -indicates that the measurement value is lower than the set high limit of the alarm, and higher than the low limit 2.overWorkHigh(2) -indicates that the measurement value is higher than the high limit of the alarm 3.belowWorkLow(3) -indicates that the measurement value is lower than the low limit of the alarm 4.abnormal(4) -indicates that the measurement value is outside the scope of limit of the alarm 5.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), overWorkHigh(2), belowWorkLow(3), abnormal(4), invalid(-1)  

hwAnaRowStatus 1.3.6.1.4.1.2011.6.1.1.2.1.11
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwAnaAlarmID 1.3.6.1.4.1.2011.6.1.1.2.1.12
Analog alarm definition. Options: 1.temperature(1) -temperature alarm 2.humidity(2) -humidity alarm 3.voltage(3) -voltage alarm 4.current(4) -current alarm 5.userDefinedAlarm0(100) -analog user-defined alarm 0 6.userDefinedAlarm1(101) -analog user-defined alarm 1 7.userDefinedAlarm2(102) -analog user-defined alarm 2 8.userDefinedAlarm3(103) -analog user-defined alarm 3 9.userDefinedAlarm4(104) -analog user-defined alarm 4 10.userDefinedAlarm5(105) -analog user-defined alarm 5 11.userDefinedAlarm6(106) -analog user-defined alarm 6 12.userDefinedAlarm7(107) -analog user-defined alarm 7 13.userDefinedAlarm8(108) -analog user-defined alarm 8 14.userDefinedAlarm9(109) -analog user-defined alarm 9 15.userDefinedAlarm10(110) -analog user-defined alarm 10 16.userDefinedAlarm11(111) -analog user-defined alarm 11 17.userDefinedAlarm12(112) -analog user-defined alarm 12 18.userDefinedAlarm13(113) -analog user-defined alarm 13 19.userDefinedAlarm14(114) -analog user-defined alarm 14 20.userDefinedAlarm15(115) -analog user-defined alarm 15 21.default(65535) -default analog alarm
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER temperature(1), humidity(2), voltage(3), current(4), userDefinedAlarm0(100), userDefinedAlarm1(101), userDefinedAlarm2(102), userDefinedAlarm3(103), userDefinedAlarm4(104), userDefinedAlarm5(105), userDefinedAlarm6(106), userDefinedAlarm7(107), userDefinedAlarm8(108), userDefinedAlarm9(109), userDefinedAlarm10(110), userDefinedAlarm11(111), userDefinedAlarm12(112), userDefinedAlarm13(113), userDefinedAlarm14(114), userDefinedAlarm15(115), default(65535)  

hwDigChannelTable 1.3.6.1.4.1.2011.6.1.1.3
Information table of the digital parameters monitored. The indexes of this table are hwEnvEmuIndex and hwDigChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwDigChannelIndex is the index of the digital parameter that is monitored by a monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwDigChannelEntry

hwDigChannelEntry 1.3.6.1.4.1.2011.6.1.1.3.1
Information table of the digital parameters monitored. The indexes of this entry are hwEnvEmuIndex and hwDigChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwDigChannelIndex is the index of the digital parameter that is monitored by a monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwDigChannelEntry  

hwDigChannelIndex 1.3.6.1.4.1.2011.6.1.1.3.1.1
Index of the digital parameter that is monitored by a monitoring unit. Range: 0 - 255
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwDigChannelName 1.3.6.1.4.1.2011.6.1.1.3.1.2
Name of the digital parameter that is monitored by a monitoring unit.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwAlmCondition 1.3.6.1.4.1.2011.6.1.1.3.1.3
Alarm conditions. Options: 1.lowLevelAlarm(1) -refers to the alarm produced when the digital sensor detects the low level 2.highLevelAlarm(2) -refers to the alarm produced when the digital sensor detects the high level 3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER lowLevelAlarm(1), highLevelAlarm(2), invalid(-1)  

hwDigChannelState 1.3.6.1.4.1.2011.6.1.1.3.1.4
The status of the present monitored digital sensor Options: 1.normal(1) -indicates that the digital sensor works normally 2.alarm(2) -indicates that the digital sensor produces the alarm signal 3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), alarm(2), invalid(-1)  

hwDigRowStatus 1.3.6.1.4.1.2011.6.1.1.3.1.5
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwDigAlarmID 1.3.6.1.4.1.2011.6.1.1.3.1.6
Digital alarm definition. Options: 1.acvoltage(1) -ac voltage alarm 2.acswitch(2) -ac switch alarm 3.batteryvoltage(3) -battery voltage alarm 4.batteryfuse(4) -battery fuse alarm 5.loadfuse(5) -load fuse alarm 6.rectifier(6) -rectifier alarm 7.dcpower(7) -dc power alarm 8.cupboarddoor(8) -cupboard alarm 9.roomdoor(9) -room door alarm 10.window(10) -window alarm 11.thief(11) -thief alarm 12.wiring(12) -wiring alarm 13.fan(13) -fan alarm 14.fire(14) -fire alarm 15.fog(15) -fog alarm 16.water(16) -water alarm 17.diesel(17) -diesel alarm 18.smell(18) -smell alarm 19.aircondition(19) -air-condition alarm 20.arrester(20) -arrester alarm 21.dcvoltage(21) -dc voltage 22.outputswitch(22) -output swith 23.userDefinedAlarm0(100) -digital user-defined alarm 0 24.userDefinedAlarm1(101) -digital user-defined alarm 1 25.userDefinedAlarm2(102) -digital user-defined alarm 2 26.userDefinedAlarm3(103) -digital user-defined alarm 3 27.userDefinedAlarm4(104) -digital user-defined alarm 4 28.userDefinedAlarm5(105) -digital user-defined alarm 5 29.userDefinedAlarm6(106) -digital user-defined alarm 6 30.userDefinedAlarm7(107) -digital user-defined alarm 7 31.userDefinedAlarm8(108) -digital user-defined alarm 8 32.userDefinedAlarm9(109) -digital user-defined alarm 9 33.userDefinedAlarm10(110) -digital user-defined alarm 10 34.userDefinedAlarm11(111) -digital user-defined alarm 11 35.userDefinedAlarm12(112) -digital user-defined alarm 12 36.userDefinedAlarm13(113) -digital user-defined alarm 13 37.userDefinedAlarm14(114) -digital user-defined alarm 14 38.userDefinedAlarm15(115) -digital user-defined alarm 15 39.userDefinedAlarm16(116) -digital user-defined alarm 16 40.userDefinedAlarm17(117) -digital user-defined alarm 17 41.userDefinedAlarm18(118) -digital user-defined alarm 18 42.userDefinedAlarm19(119) -digital user-defined alarm 19 43.userDefinedAlarm20(120) -digital user-defined alarm 20 44.userDefinedAlarm21(121) -digital user-defined alarm 21 45.userDefinedAlarm22(122) -digital user-defined alarm 22 46.userDefinedAlarm23(123) -digital user-defined alarm 23 47.userDefinedAlarm24(124) -digital user-defined alarm 24 48.userDefinedAlarm25(125) -digital user-defined alarm 25 49.userDefinedAlarm26(126) -digital user-defined alarm 26 50.userDefinedAlarm27(127) -digital user-defined alarm 27 51.userDefinedAlarm28(128) -digital user-defined alarm 28 52.userDefinedAlarm29(129) -digital user-defined alarm 29 53.userDefinedAlarm30(130) -digital user-defined alarm 30 54.userDefinedAlarm31(131) -digital user-defined alarm 31 55.default(65535) -digital alarm
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER acvoltage(1), acswitch(2), batteryvoltage(3), batteryfuse(4), loadfuse(5), rectifier(6), dcpower(7), cupboarddoor(8), roomdoor(9), window(10), thief(11), wiring(12), fan(13), fire(14), fog(15), water(16), diesel(17), smell(18), aircondition(19), arrester(20), dcvoltage(21), outputswitch(22), userDefinedAlarm0(100), userDefinedAlarm1(101), userDefinedAlarm2(102), userDefinedAlarm3(103), userDefinedAlarm4(104), userDefinedAlarm5(105), userDefinedAlarm6(106), userDefinedAlarm7(107), userDefinedAlarm8(108), userDefinedAlarm9(109), userDefinedAlarm10(110), userDefinedAlarm11(111), userDefinedAlarm12(112), userDefinedAlarm13(113), userDefinedAlarm14(114), userDefinedAlarm15(115), userDefinedAlarm16(116), userDefinedAlarm17(117), userDefinedAlarm18(118), userDefinedAlarm19(119), userDefinedAlarm20(120), userDefinedAlarm21(121), userDefinedAlarm22(122), userDefinedAlarm23(123), userDefinedAlarm24(124), userDefinedAlarm25(125), userDefinedAlarm26(126), userDefinedAlarm27(127), userDefinedAlarm28(128), userDefinedAlarm29(129), userDefinedAlarm30(130), userDefinedAlarm31(131), default(65535)  

hwControlOutTable 1.3.6.1.4.1.2011.6.1.1.4
Monitored digital out table. This table indicates information about whether digital parameter is monitored. The indexes of this table are hwEnvEmuIndex and hwControlOutIndex. hwEnvEmuIndex is the index of the monitoring unit, and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwControlOutEntry

hwControlOutEntry 1.3.6.1.4.1.2011.6.1.1.4.1
Monitored digital out table. This table indicates information about whether digital parameter is monitored. The indexes of this entry are hwEnvEmuIndex and hwControlOutIndex. hwEnvEmuIndex is the index of the monitoring unit, and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwControlOutEntry  

hwControlOutIndex 1.3.6.1.4.1.2011.6.1.1.4.1.1
Index of the digital out table monitored in the monitoring unit Range: 0 - 255
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

hwControlOutName 1.3.6.1.4.1.2011.6.1.1.4.1.2
Name of the monitored digital out table
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwControlOutAdminStatus 1.3.6.1.4.1.2011.6.1.1.4.1.3
Control Out administration: executes the on/off operation. Options: 1. on(1) - trun on 2. off(2) - trun off
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

hwControlOutRowStatus 1.3.6.1.4.1.2011.6.1.1.4.1.4
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwFanTable 1.3.6.1.4.1.2011.6.1.1.5
Information table of fan monitoring. The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwFanEntry

hwFanEntry 1.3.6.1.4.1.2011.6.1.1.5.1
Information table of fan monitoring. The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwFanEntry  

hwFanName 1.3.6.1.4.1.2011.6.1.1.5.1.1
Fan name
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hwFanControlMode 1.3.6.1.4.1.2011.6.1.1.5.1.2
The fan control modes of the fan frame. Options: 1.manual(1) -indicates that the fan is always on, and the fan speed can be manually adjusted 2.emuAuto(2) -indicates that the fan is in the automatic mode, and can be automatically controlled depending on the temperature of the fan 3.fixed(3) -indicates that the fan is in the fixed mode, and adjusting its speed is not allowed 4.mainboardAuto(4) -indicates that the fan is in the automatic mode, and can be automatically controlled depending on the temperature of the boards in the frame
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER manual(1), emuAuto(2), fixed(3), mainboardAuto(4)  

hwFanControlState 1.3.6.1.4.1.2011.6.1.1.5.1.3
For ESC fan, all should be checked to turn on the fan, while all should not be checked to turn off the fan. Options: 1.fan1(0) -indicates that the first fan needs to be opened 2.fan2(1) -indicates that the second fan needs to be opened 3.fan3(2) -indicates that the third fan needs to be opened 4.fan4(3) -indicates that the fourth fan needs to be opened 5.fan5(4) -indicates that the fifth fan needs to be opened 6.fan6(5) -indicates that the sixth fan needs to be opened
Status: current Access: read-write
OBJECT-TYPE    
  BITS fan1(0), fan2(1), fan3(2), fan4(3), fan5(4), fan6(5)  

hwESCFanTempAutoOn 1.3.6.1.4.1.2011.6.1.1.5.1.4
The fan temperature set, in unit of centigrade. The MIB object only functions for the fan monitoring board of ESC and is not applicable to the type of fan monitoring board. Only when the fan control mode of the fan frame is hwFanControl =auto (3), the temperature control mode will take effect. When detecting the environment temperature higher than the set value, the fan will be on (or increase its rotation).
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwESCFanTempAutoOff 1.3.6.1.4.1.2011.6.1.1.5.1.5
The fan temperature set, in unit of centigrade. The MIB object only functions for the fan monitoring board of ESC and is not applicable to the type of fan monitoring board. Only when the fan control mode of the fan frame is hwFanControl =auto (3), the temperature control mode will take effect. When detecting the environment temperature is lower than the set value, the fan will be turned off (decrease its rotation).
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwFanRowStatus 1.3.6.1.4.1.2011.6.1.1.5.1.6
RowStatus standard operation.
Status: current Access: read-write
OBJECT-TYPE    
  RowStatus  

hwCurrentTemp 1.3.6.1.4.1.2011.6.1.1.5.1.7
The present temperature value, in unit of cent-centigrade
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwFanSpeedMode 1.3.6.1.4.1.2011.6.1.1.5.1.8
The adjusting rotation mode of the fan. Options: 1.continue(1) -continuous control 2.discontinue(2) -discrete control 3.percent(3) -duty ratio control 4.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER continue(1), discontinue(2), percent(3), invalid(-1)  

hwFanSpeed 1.3.6.1.4.1.2011.6.1.1.5.1.9
When hwFanSpeedMode is the continue mode, 0 indicates the present wind speed +1, while 1 indicates the present wind speed -1. When hwFanSpeedMode is discontinuous, 0 indicates fixed high speed, while 1 indicates fixed low speed. When hwFanSpeedMode is percent, the value delivered by the main control is the percent value, ranging from 35 to 100, used to initialize the rotation of fan for various device main controls. invalid(-1) indicates that the fan tray does not work normally. For example, the fan tray is disconnected from the control board, or some of the fans in the fan tray are blocked.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwFanTypeDescription 1.3.6.1.4.1.2011.6.1.1.5.1.10
Fan Type Description. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwTcuTable 1.3.6.1.4.1.2011.6.1.1.6
Information table of temperature control unit. The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HwTcuEntry

hwTcuEntry 1.3.6.1.4.1.2011.6.1.1.6.1
Information table of temperature control unit. The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  HwTcuEntry  

hwTcuHeatExchangerType 1.3.6.1.4.1.2011.6.1.1.6.1.1
Heat Exchanger Type Description.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

hwTcuExternalFanRev 1.3.6.1.4.1.2011.6.1.1.6.1.2
The rev of Heat Exchanger outer fan, in unit of RMP (rotate per minite)
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwTcuInternalFanRev 1.3.6.1.4.1.2011.6.1.1.6.1.3
The rev of Heat Exchanger inner fan, in unit of RMP (rotate per minite)
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

hwTcuStartHeatTemp 1.3.6.1.4.1.2011.6.1.1.6.1.4
The temperature of Heat Exchanger starts to heat up, in unit of Celsius
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

hwTcuStopHeatTemp 1.3.6.1.4.1.2011.6.1.1.6.1.5
The temperature of Heat Exchanger stops heating, in unit of Celsius
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

snmpTrapsDef 1.3.6.1.4.1.2011.6.1.2
OBJECT IDENTIFIER    

emmsnmpTraps 1.3.6.1.4.1.2011.6.1.2.0
OBJECT IDENTIFIER    

envCommAlarm 1.3.6.1.4.1.2011.6.1.2.0.1
The communication alarm of environment monitoring board, reporting the environment monitoring unit ID. This trap message is reported when the communication between the emu and control board is fault.
Status: current Access: read-write
NOTIFICATION-TYPE    

envCommAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.2
The communication alarm recovery of the environment monitoring, reporting the environment monitoring unit ID. This trap message is reported when the communication between the emu and control board resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaFaultAlarm 1.3.6.1.4.1.2011.6.1.2.0.3
The alarm recovery of the analog exception, reporting the environment monitoring unit ID. This trap message is reported when there is an analog exception in emu.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaFaultAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.4
The alarm recovery of the analog exception, reporting the environment monitoring unit ID. This trap message is reported when the analog exception recovery in emu.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaTooHighAlarm 1.3.6.1.4.1.2011.6.1.2.0.5
The alarm of too high an analog, reporting the environment monitoring unit ID and the channel ID of the analog sensor. This trap message is reported when an analog value is too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaTooHighAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.6
The alarm of too high analog resume, reporting the environment monitoring unit ID. This trap message is reported when an analog value returns to normal range from the high value.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaTooLowAlarm 1.3.6.1.4.1.2011.6.1.2.0.7
The alarm of too low an analog, reporting the environment monitoring unit ID and the channel ID of the analog sensor. This trap message is reported when an analog value is too low.
Status: current Access: read-write
NOTIFICATION-TYPE    

anaTooLowAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.8
The alarm of too low an analog, reporting the environment monitoring unit ID. This trap message is reported when an analog value returns to normal range from the low value.
Status: current Access: read-write
NOTIFICATION-TYPE    

controlAlarm 1.3.6.1.4.1.2011.6.1.2.0.9
The control alarm, reporting the environment monitoring unit ID. This trap message is reported when emu control operation fails.
Status: current Access: read-write
NOTIFICATION-TYPE    

controlAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.10
The control alarm, reporting the environment monitoring unit ID. This trap message is reported when emu control operation resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

digtalMeasureAlarm 1.3.6.1.4.1.2011.6.1.2.0.11
The digital measure alarm, reporting the environment monitoring unit ID and the channel ID of the digital sensor. This trap message is reported when emu measure operation fails.
Status: current Access: read-write
NOTIFICATION-TYPE    

digtaleasureAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.12
The digital measure alarm recovery, reporting the environment monitoring unit ID and the channel ID of the digital sensor. This trap message is reported when emu measure operation resumes.
Status: current Access: read-write
NOTIFICATION-TYPE    

fanExistsAlarm 1.3.6.1.4.1.2011.6.1.2.0.13
Fan nonexistance alarm. This trap message is reported when there is no fan device connected to control board.
Status: current Access: read-write
NOTIFICATION-TYPE    

fanExistsAlarmResume 1.3.6.1.4.1.2011.6.1.2.0.14
Fan nonexistance alarm recovery. This trap message is reported when there is a fan device connected to control board.
Status: current Access: read-write
NOTIFICATION-TYPE    

fanRunStateAlarm 1.3.6.1.4.1.2011.6.1.2.0.15
Fan running status alarm. This trap message is reported when the fan run state gets abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

envConformance 1.3.6.1.4.1.2011.6.1.3
OBJECT IDENTIFIER    

envCompliances 1.3.6.1.4.1.2011.6.1.3.1
OBJECT IDENTIFIER    

envGroups 1.3.6.1.4.1.2011.6.1.3.2
OBJECT IDENTIFIER    

hwEnvironTraps 1.3.6.1.4.1.2011.6.1.4
OBJECT IDENTIFIER    

hwEnvironCommonTraps 1.3.6.1.4.1.2011.6.1.4.1
OBJECT IDENTIFIER    

hwEnvironCommonTrapsPrefix 1.3.6.1.4.1.2011.6.1.4.1.0
OBJECT IDENTIFIER    

hwEmmEmuAutofindTrap 1.3.6.1.4.1.2011.6.1.4.1.0.1
The agent generates this trap when a new EMU autofind.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEnvironAlarmTraps 1.3.6.1.4.1.2011.6.1.4.2
OBJECT IDENTIFIER    

hwEnvironEmuAlarmTraps 1.3.6.1.4.1.2011.6.1.4.2.1
OBJECT IDENTIFIER    

hwEnvironEmuAlarmTrapsPrefix 1.3.6.1.4.1.2011.6.1.4.2.1.0
OBJECT IDENTIFIER    

hwEmmEmufailTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.1
The agent generates this trap when the communication of the EMU with the host is abnormal.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEmuRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.2
The agent generates this trap when the communication of the EMU with the host recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEmuHardwareFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.3
The agent generates this trap when the a Hardware exception occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEmuHardwareRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.4
The agent generates this trap when the a Hardware exception Recover
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEmuAutofindFailTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.5
The agent generates this trap when the emu autofind fail.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmEmuFanStateTrap 1.3.6.1.4.1.2011.6.1.4.2.1.0.6
The agent generates this trap when the fan is not configured or fails.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEnvironAnaAlarmTraps 1.3.6.1.4.1.2011.6.1.4.2.2
OBJECT IDENTIFIER    

hwEnvironAnaAlarmTrapsPrefix 1.3.6.1.4.1.2011.6.1.4.2.2.0
OBJECT IDENTIFIER    

hwEmmAnaUnnamedFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.1
The agent generates this trap when an unnamed analog alarm occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaUnnamedRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.2
The agent generates this trap when an unnamed analog alarm recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaTempFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.3
The agent generates this trap when the analog temperature alarm occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaTempRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.4
The agent generates this trap when the analog temperature alarm recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaHumyFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.5
The agent generates this trap when the analog humidity alarm occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaHumyRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.6
The agent generates this trap when the analog humidity alarm recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaVoltFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.7
The agent generates this trap when the analog voltage alarm occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaVoltRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.8
The agent generates this trap when the analog voltage alarm recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaCurrentFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.9
The agent generates this trap when the analog current alarm occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmAnaCurrentRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.2.0.10
The agent generates this trap when the analog current alarm recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEnvironDigAlarmTraps 1.3.6.1.4.1.2011.6.1.4.2.3
OBJECT IDENTIFIER    

hwEnvironDigAlarmTrapsPrefix 1.3.6.1.4.1.2011.6.1.4.2.3.0
OBJECT IDENTIFIER    

hwEmmDigFanBlockFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.1
The agent generates this trap when the fan is blocked.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFanBlockRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.2
The agent generates this trap when the fan is recovered from block.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFanTempHighFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.3
The agent generates this trap when the temperature of fan is too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFanTempHighRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.4
The agent generates this trap when the temperature of fan recover from too high.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigUnnamedFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.5
The agent generates this trap when a unnamed digital fault occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigUnnamedRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.6
The agent generates this trap when a unnamed digital recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigOutputswitchFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.7
The agent generates this trap when Output switch digital fault occurs.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigOutputswitchRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.8
The agent generates this trap when Output switch digital recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAcvolFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.11
The agent generates this trap when The AC voltage is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAcvolRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.12
The agent generates this trap when The AC voltage recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAcswitchFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.13
The agent generates this trap when The AC switch is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAcswitchRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.14
The agent generates this trap when The AC switch recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigBattvolFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.15
The agent generates this trap when The batt vol is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigBattvolRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.16
The agent generates this trap when The batt vol recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigBattfuseFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.17
The agent generates this trap when The battery fuse is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigBattfuseRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.18
The agent generates this trap when The battery fuse recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigLoadfuseFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.19
The agent generates this trap when The load fuse is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigLoadfuseRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.20
The agent generates this trap when The load fuse recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigRectifierFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.21
The agent generates this trap when The Rectifier is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigRectifierRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.22
The agent generates this trap when The Rectifier recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDcpowerFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.23
The agent generates this trap when The dc-power is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDcpowerRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.24
The agent generates this trap when The dc-power recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigRoomdoorFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.25
The agent generates this trap when The Roomdoor is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigRoomdoorRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.26
The agent generates this trap when The Roomdoor recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigTheftFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.27
The agent generates this trap when The Roomdoor is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigTheftRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.28
The agent generates this trap when The Roomdoor recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigWiringFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.29
The agent generates this trap when The WIRING is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigWiringRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.30
The agent generates this trap when The WIRING recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFanFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.31
The agent generates this trap when The FAN is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFanRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.32
The agent generates this trap when The FAN recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFireFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.33
The agent generates this trap when The Fire is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFireRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.34
The agent generates this trap when The Fire recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFogFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.35
The agent generates this trap when The Fog is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigFogRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.36
The agent generates this trap when The Fog recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigWaterFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.37
The agent generates this trap when The Water is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigWaterRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.38
The agent generates this trap when The Water recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDieselFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.39
The agent generates this trap when The Diesel is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDieselRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.40
The agent generates this trap when The Diesel recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigSmellFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.41
The agent generates this trap when The Smell is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigSmellRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.42
The agent generates this trap when The Smell recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAirconditionFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.43
The agent generates this trap when The Air condition is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigAirconditionRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.44
The agent generates this trap when The Air condition recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigArrsterFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.45
The agent generates this trap when The arrester is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigArrsterRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.46
The agent generates this trap when The arrester recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDcvolFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.47
The agent generates this trap when The DC VOL is out of the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigDcvolRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.48
The agent generates this trap when The DC VOL recovers to the normal range.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmFanCriticalBlockFaultTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.49
The agent generates this trap when more than two fans are blocked.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmFanCriticalBlockRecoverTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.50
The agent generates this trap when the critical multi-fan blocking recovers.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigitalSwitchOpenTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.51
The agent generates this trap when the 48V input switch is closed.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmDigitalSwitchCloseTrap 1.3.6.1.4.1.2011.6.1.4.2.3.0.52
The agent generates this trap when the 48V input switch is opened.
Status: current Access: read-write
NOTIFICATION-TYPE    

hwEmmTrapVbOids 1.3.6.1.4.1.2011.6.1.5
OBJECT IDENTIFIER    

hwFanStatus 1.3.6.1.4.1.2011.6.1.5.1
The status of the fan. Options: 1.notconfig(1) -The status of the fan is notconfig 2.failure(2) -The status of the fan is fail
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER notconfig(1), failure(2)  

hwFailureCause 1.3.6.1.4.1.2011.6.1.5.2
The reason of the auto-finding failure: Options: 1.fullemu(1) -No enough EMU IDs are available 2.shelfnotsupport(2) -The EMU does not support the auto discovery function 3.emunotsupportautofind(3) -The shelf does not support the EMU of this type
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER fullemu(1), shelfnotsupport(2), emunotsupportautofind(3)  

hwEnvAutofindNodeId 1.3.6.1.4.1.2011.6.1.5.3
The NodeId of the auto-found EMU.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

hwEnvAutofindEmuType 1.3.6.1.4.1.2011.6.1.5.4
The type of the auto-found EMU.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  OCTET STRING  

hwEnvAutofindBoardName 1.3.6.1.4.1.2011.6.1.5.5
The board name of the auto-found EMU.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  OCTET STRING