ICT-MODULAR-POWER-SYSTEM-MIB
File:
ICT-MODULAR-POWER-SYSTEM-MIB.mib (8361 bytes)
Imported modules
Imported symbols
Defined Types
ModuleEntry |
|
SEQUENCE |
|
|
|
|
moduleNumber |
INTEGER |
|
|
moduleStatus |
INTEGER |
|
|
moduleType |
INTEGER |
|
|
moduleVoltage |
DisplayString |
|
|
moduleCurrentA |
DisplayString |
|
|
moduleCurrentB |
DisplayString |
|
|
moduleCurrentC |
DisplayString |
|
|
moduleCurrentD |
DisplayString |
|
|
moduleControlA |
INTEGER |
|
|
moduleControlB |
INTEGER |
|
|
moduleControlC |
INTEGER |
|
|
moduleControlD |
INTEGER |
|
AlarmEntry |
|
SEQUENCE |
|
|
|
|
alarmNumber |
INTEGER |
|
|
alarmName |
DisplayString |
|
|
alarmStatus |
INTEGER |
|
Defined Values
ictPower |
1.3.6.1.4.1.39145 |
OBJECT IDENTIFIER |
|
|
|
deviceHardware |
1.3.6.1.4.1.39145.13.3 |
Hardware Version |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..127 |
|
outputEnable |
1.3.6.1.4.1.39145.13.9 |
Output Enable Status (a value of '1' indicates Output is Enabled, and a value of '2' indicates Output is Disabled. Output cannot be disabled during an AC Failure) |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
moduleTable |
1.3.6.1.4.1.39145.13.10 |
Module Table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
ModuleEntry |
|
moduleEntry |
1.3.6.1.4.1.39145.13.10.1 |
Tok_String |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
ModuleEntry |
|
|
moduleNumber |
1.3.6.1.4.1.39145.13.10.1.1 |
Module Number |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..8 |
|
moduleStatus |
1.3.6.1.4.1.39145.13.10.1.2 |
Module Status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
notInstalled(1), ok(2), alarm(3) |
|
moduleType |
1.3.6.1.4.1.39145.13.10.1.3 |
Module Type ('1' indicates Module is NOT INSTALLED,'2' indicates POWER Module,'3' indicates BATTERY Module, and '4' indicates DISTRIBUTION Module) |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
notInstalled(1), power(2), battery(3), distribution(4) |
|
moduleControlA |
1.3.6.1.4.1.39145.13.10.1.9 |
Channel 1 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
moduleControlB |
1.3.6.1.4.1.39145.13.10.1.10 |
Channel 2 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
moduleControlC |
1.3.6.1.4.1.39145.13.10.1.11 |
Channel 3 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
moduleControlD |
1.3.6.1.4.1.39145.13.10.1.12 |
Channel 4 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
alarmTable |
1.3.6.1.4.1.39145.13.11 |
Alarm Input Table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
AlarmEntry |
|
alarmEntry |
1.3.6.1.4.1.39145.13.11.1 |
Tok_String |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
AlarmEntry |
|
|
alarmNumber |
1.3.6.1.4.1.39145.13.11.1.1 |
Alarm Input Number |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..4 |
|
alarmName |
1.3.6.1.4.1.39145.13.11.1.2 |
Alarm Input Name |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
alarmStatus |
1.3.6.1.4.1.39145.13.11.1.3 |
Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition) |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), ready(2), alarm(3) |
|
moduleAlarmTrap |
101 |
Trap generated when a Module Alarm is triggered |
TRAP-TYPE |
|
|
|
acFailAlarmTrap |
103 |
Trap generated when the AC Failure Alarm is triggered |
TRAP-TYPE |
|
|
|
sysCurrentLimitTrap |
104 |
Trap generated when the System Current Limit Alarm is triggered |
TRAP-TYPE |
|
|
|
acFailAlarmClear |
113 |
Trap generated when the AC Failure Alarm is cleared |
TRAP-TYPE |
|
|
|
batteryTestStart |
121 |
Trap generated when a Battery Discharge Test is started |
TRAP-TYPE |
|
|
|
batteryTestComplete |
122 |
Trap generated when a Battery Discharge Test completes successfully |
TRAP-TYPE |
|
|
|
batteryTestFail |
123 |
Trap generated when a Battery Discharge Test fails |
TRAP-TYPE |
|
|
|