DGPUPS-MIB
File:
DGPUPS-MIB.mib (51345 bytes)
Imported modules
Imported symbols
Defined Types
MconfigTrapsReceiversEntry |
|
SEQUENCE |
|
|
|
|
trapsIndex |
INTEGER |
|
|
trapsReceiverAddr |
IpAddress |
|
|
receiverCommunityString |
DisplayString |
|
|
severityLevel |
INTEGER |
|
|
receiverAccept |
INTEGER |
|
UpsBaseConfigDeviceEntry |
|
SEQUENCE |
|
|
|
|
indexOfDevice |
INTEGER |
|
|
nameOfDevice |
DisplayString |
|
|
vaRatingOfDevice |
INTEGER |
|
|
deviceAccept |
INTEGER |
|
Defined Values
dgp |
1.3.6.1.4.1.17420 |
OBJECT IDENTIFIER |
|
|
|
products |
1.3.6.1.4.1.17420.1 |
OBJECT IDENTIFIER |
|
|
|
ppcmgmt |
1.3.6.1.4.1.17420.2 |
OBJECT IDENTIFIER |
|
|
|
hardware |
1.3.6.1.4.1.17420.1.1 |
OBJECT IDENTIFIER |
|
|
|
mconfig |
1.3.6.1.4.1.17420.2.1 |
OBJECT IDENTIFIER |
|
|
|
protocol |
1.3.6.1.4.1.17420.1.1.1 |
select protocol |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ups01(0), ups02(1), rpm(2), cps(3), ats(4) |
|
ups |
1.3.6.1.4.1.17420.1.1.2 |
OBJECT IDENTIFIER |
|
|
|
upsIdentp |
1.3.6.1.4.1.17420.1.1.2.1 |
OBJECT IDENTIFIER |
|
|
|
upsBatteryp |
1.3.6.1.4.1.17420.1.1.2.2 |
OBJECT IDENTIFIER |
|
|
|
upsOutputp |
1.3.6.1.4.1.17420.1.1.2.4 |
OBJECT IDENTIFIER |
|
|
|
upsConfigp |
1.3.6.1.4.1.17420.1.1.2.5 |
OBJECT IDENTIFIER |
|
|
|
upsControlp |
1.3.6.1.4.1.17420.1.1.2.6 |
OBJECT IDENTIFIER |
|
|
|
upsTestp |
1.3.6.1.4.1.17420.1.1.2.7 |
OBJECT IDENTIFIER |
|
|
|
upsBaseTest |
1.3.6.1.4.1.17420.1.1.2.7.1 |
OBJECT IDENTIFIER |
|
|
|
mconfigTrapsReceiversNum |
1.3.6.1.4.1.17420.2.1.1 |
The number of managers to send traps to. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
mconfigTrapsReceiversEntry |
1.3.6.1.4.1.17420.2.1.2.1 |
The managers to send traps to. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
MconfigTrapsReceiversEntry |
|
|
trapsIndex |
1.3.6.1.4.1.17420.2.1.2.1.1 |
The index to a trap receiver entry. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
trapsReceiverAddr |
1.3.6.1.4.1.17420.2.1.2.1.2 |
The IP address of the manager to send a trap to. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
severityLevel |
1.3.6.1.4.1.17420.2.1.2.1.4 |
The severity threshold of traps to send to the manager.
traps are labeled in severity as informational(1), warning(2),
severe(3). Only traps of equal or greater severity than
this value are sent to the manager. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
information(1), warning(2), severe(3) |
|
receiverAccept |
1.3.6.1.4.1.17420.2.1.2.1.5 |
An entry will become active if yes, and will
be deleted if no. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
yes(1), no(2) |
|
upsBaseIdentModel |
1.3.6.1.4.1.17420.1.1.2.1.1.1 |
The UPS model name (e.g. 'Intelligent 8000E 900VA'). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
upsBaseIdentUpsName |
1.3.6.1.4.1.17420.1.1.2.1.1.2 |
An 8 byte ID string identifying the UPS. This object
can be set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
upsSmartIdentUpsSerialNumber |
1.3.6.1.4.1.17420.1.1.2.1.2.3 |
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
upsBaseBatteryStatus |
1.3.6.1.4.1.17420.1.1.2.2.1.1 |
The status of the UPS batteries. A batteryLow(3)
value indicates the UPS will be unable to sustain the
current load, and its services will be lost if power is
not restored. The amount of run time in reserve at the
time of low battery can be configured by the
upsSmartConfigLowBatteryRunTime. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3) |
|
upsBaseBatteryTimeOnBattery |
1.3.6.1.4.1.17420.1.1.2.2.1.2 |
The elapsed time in seconds since the UPS has switched
to battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBaseBatteryLastReplaceDate |
1.3.6.1.4.1.17420.1.1.2.2.1.3 |
The date when the UPS system's batteries were last replaced
in mm/dd/yy format. For UPS models, this value is originally
set in the factory. When the UPS batteries are replaced,
this value should be reset by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
upsSmartBatteryCapacity |
1.3.6.1.4.1.17420.1.1.2.2.2.1 |
The remaining battery capacity expressed in
percent of full capacity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartBatteryVoltage |
1.3.6.1.4.1.17420.1.1.2.2.2.2 |
The current battery voltage expressed in 1/10 VDC. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartBatteryTemperature |
1.3.6.1.4.1.17420.1.1.2.2.2.3 |
The current internal UPS temperature expressed in tenths of
a Celsius degree. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartBatteryRunTimeRemaining |
1.3.6.1.4.1.17420.1.1.2.2.2.4 |
The UPS battery run time remaining before battery
exhaustion, in seconds. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartBatteryReplaceIndicator |
1.3.6.1.4.1.17420.1.1.2.2.2.5 |
Indicates whether the UPS batteries need replacing. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noBatteryNeedsReplacing(1), batteryNeedsReplacing(2) |
|
upsSmartBatteryFullChargeVoltage |
1.3.6.1.4.1.17420.1.1.2.2.2.6 |
The fully charged battery voltage of the battery system
used in the UPS, expressed in tenths of a volt. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartBatteryCurrent |
1.3.6.1.4.1.17420.1.1.2.2.2.7 |
The current battery current expressed in percent of
maximum current. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBaseOutputStatus |
1.3.6.1.4.1.17420.1.1.2.4.1.1 |
The current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), onLine(2), onBattery(3), onBoost(4), sleeping(5), onBypass(6), rebooting(7), standBy(8), onBuck(9) |
|
upsBaseOutputPhase |
1.3.6.1.4.1.17420.1.1.2.4.1.2 |
The current output phase. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartOutputVoltage |
1.3.6.1.4.1.17420.1.1.2.4.2.1 |
The output voltage of the UPS system in 1/10 VAC. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartOutputFrequency |
1.3.6.1.4.1.17420.1.1.2.4.2.2 |
The current output frequency of the UPS system in 1/10 Hz. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartOutputLoad |
1.3.6.1.4.1.17420.1.1.2.4.2.3 |
The current UPS load expressed in percent
of rated capacity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBaseConfigNumDevices |
1.3.6.1.4.1.17420.1.1.2.5.1.1 |
The number of devices that are plugged into the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBaseConfigDeviceTable |
1.3.6.1.4.1.17420.1.1.2.5.1.2 |
A list of devices that are plugged into the UPS. The
number of entries is given by the value of
upsBaseConfigNumDevices. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsBaseConfigDeviceEntry |
|
upsBaseConfigDeviceEntry |
1.3.6.1.4.1.17420.1.1.2.5.1.2.1 |
The devices plugged in to the UPS. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsBaseConfigDeviceEntry |
|
|
indexOfDevice |
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.1 |
The index of the device that is plugged into the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
nameOfDevice |
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.2 |
The name/description of the device plugged into the UPS. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
vaRatingOfDevice |
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.3 |
The volt-amp rating of the device plugged into the UPS. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
deviceAccept |
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.4 |
An entry is added if yes, the entry is deleted if no. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
yes(1), no(2) |
|
upsSmartConfigRatedOutputVoltage |
1.3.6.1.4.1.17420.1.1.2.5.2.1 |
The nominal output voltage from the UPS in 1/10 VAC.
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
and 2400.
NOTE: Only units that are 2200, 2250, 2300 and 2400 can
be changed. Allowable values are 2200, 2250, 2300 and
2400.
For these adjustable units, if a value other than
a supported value is provided in a set request, the
UPS interprets it as the next lower acceptable value.
If the provided value is lower than the lowest acceptable
value, the lowest acceptable value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigHighTransferVolt |
1.3.6.1.4.1.17420.1.1.2.5.2.2 |
The maximum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowed value depend on the UPS used:
120 Volt units allow settings of 1290, 1320, 1350, 1380.
100 Volt units allow settings of 1080, 1100, 1120, 1140.
230 Volt units allow settings of 2530, 2640, 2710, 2800.
208 Volt units allow settings of 2240, 2290, 2340, 2390.
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigLowTransferVolt |
1.3.6.1.4.1.17420.1.1.2.5.2.3 |
The minimum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
120 Volt units allow settings of 970, 1000, 1030, 1060.
100 Volt units allow settings of 810, 830, 850, 870.
230 Volt units allow settings of 1880, 1960, 2040, 2080.
208 Volt units allow settings of 1680, 1720, 1770, 1820.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigAlarm |
1.3.6.1.4.1.17420.1.1.2.5.2.4 |
A flag indicating how the UPS should handle audible line fail
alarms. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
timed(1), atLowBattery(2), never(3) |
|
upsSmartConfigAlarmTimer |
1.3.6.1.4.1.17420.1.1.2.5.2.5 |
The time in seconds after initial line failure at which the
UPS begins emitting audible alarms (beeping). This timer is
observerd only if the value of extControlAlarm is timed(2).
Allowed values are 0 or 30 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigMinReturnCapacity |
1.3.6.1.4.1.17420.1.1.2.5.2.6 |
The minimum battery capacity as a percent of full capacity
required before the UPS will return from a low battery
shutdown condition. In other words, the UPS will not
re-energize the output until the battery capacity is equal
to this value. Allowed values are 0, 10, 25, or 90 percent.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigSensitivity |
1.3.6.1.4.1.17420.1.1.2.5.2.7 |
The sensitivity of the UPS to utility line abnormalities
or noises. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
auto(1), low(2), medium(3), high(4) |
|
upsSmartConfigLowBatteryRunTime |
1.3.6.1.4.1.17420.1.1.2.5.2.8 |
The desired run time in seconds once the low battery
condition is reached. Allowed values are 120, 300, 420,
or 600 seconds. During this time the UPS will produce a
constant warning tone which can not be disabled.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigReturnDelay |
1.3.6.1.4.1.17420.1.1.2.5.2.9 |
The delay in seconds after utility line power returns
before the UPS will turn on. This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sleep' mode. Allowed values are 0, 60,
180 and 300 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigShutoffDelay |
1.3.6.1.4.1.17420.1.1.2.5.2.10 |
The delay in seconds the UPS remains on after being told
to turn off. Allowed values are 12, 18, 24, 30, 36, 42,
48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
600 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as next higher acceptable
value. If the provided value is higher than the highest
acceptable value, the highest acceptable value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigUpsSleepTime |
1.3.6.1.4.1.17420.1.1.2.5.2.11 |
The time in minutes for the UPS to go to 'sleep' when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable
value, the highest acceptable value is used. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsSmartConfigSetEEPROMDefaults |
1.3.6.1.4.1.17420.1.1.2.5.2.12 |
WRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0 |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noSetEEPROMDefaults(1), setEEPROMDefaults(2) |
|
upsBaseControlConserveBattery |
1.3.6.1.4.1.17420.1.1.2.6.1.1 |
Setting this variable to turnUpsOffToConserveBattery(2)
causes a UPS on battery to be put into 'sleep' mode immediately.
The (10) means suspending time(10 minutes) before turn off UPS.
UPS will turn back on when utility power is restored.
Attempting to turn off a UPS that is not on battery will
result in a badValue error.
Setting this value to noTurnOffUps(1) has no
effect.
The value noTurnOffUps(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noTurnOffUps(1), turnUpsOffToConserveBattery(2), turnUpsOffToConserveBatteryDelay(3) |
|
upsSmartControlUpsOff |
1.3.6.1.4.1.17420.1.1.2.6.2.1 |
Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state. The on/off switch on the UPS
must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noTurnUpsOff(1), turnUpsOff(2) |
|
upsSmartControlRebootUps |
1.3.6.1.4.1.17420.1.1.2.6.2.2 |
Setting this variable to rebootUps(2) causes the
UPS to shut off and turn back on.
Setting this value to noRebootUps(1) has no effect.
The value noRebootUps(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noRebootUps(1), rebootUps(2) |
|
upsSmartControlUpsSleep |
1.3.6.1.4.1.17420.1.1.2.6.2.3 |
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsSmartConfigUpsSleepTime.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noPutUpsToSleep(1), putUpsToSleep(2) |
|
upsSmartControlSimulatePowerFail |
1.3.6.1.4.1.17420.1.1.2.6.2.4 |
Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The value noSimulatePowerFailure(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noSimulatePowerFailure(1), simulatePowerFailure(2) |
|
upsSmartControlFlashAndBeep |
1.3.6.1.4.1.17420.1.1.2.6.2.5 |
UPS to identify itself by lighting all indicators
and beeping.
Setting this variable to FlashAndBeep(2) causes
the UPS lights all panel indicators and beeps.
Setting this value to noFlashAndBeep(1) has no
effect.
The value noFlashAndBeep(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noFlashAndBeep(1), flashAndBeep(2) |
|
upsSmartControlTurnOnUpsLoad |
1.3.6.1.4.1.17420.1.1.2.6.2.6 |
Setting this variable to upsSmartControlTurnOnUpsLoad(2)
causes the UPS switch back to utility power if utility
power is present.
Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
has no effect.
The value noUpsSmartControlTurnOnUpsLoad(1) will always
be returned when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noUpsSmartControlTurnOnUpsLoad(1), upsSmartControlTurnOnUpsLoad(2) |
|
upsSmartTestDiagnosticSchedule |
1.3.6.1.4.1.17420.1.1.2.7.2.1 |
The UPS system's automatic battery test schedule. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), biweekly(2), weekly(3), never(4) |
|
upsSmartTestDiagnostics |
1.3.6.1.4.1.17420.1.1.2.7.2.2 |
Setting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The value noTestDiagnostics(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noTestDiagnostics(1), testDiagnostics(2) |
|
upsSmartTestDiagnosticsResults |
1.3.6.1.4.1.17420.1.1.2.7.2.3 |
The results of the last UPS diagnostics test performed. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(1), failed(2), invalidTest(3), testInProgress(4) |
|
upsSmartTestIndicators |
1.3.6.1.4.1.17420.1.1.2.7.2.5 |
Setting this variable to testIndicators(2) causes
the UPS to perform a front panel indicator (lights) test.
Setting this value to noTestIndicators(1) has no effect.
The value noTestIndicators(1) will always be returned
when the variable is read. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noTestIndicators(1), testIndicators(2) |
|
upsSmartTestRuntimeCalibration |
1.3.6.1.4.1.17420.1.1.2.7.2.6 |
Setting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100 percent.
The test runs until capacity is less than 25 percent.
Setting this variable to cancelCurrentCalibration(3)
after setting performCalibration(2) will cancel the
current discharge.
Setting this variable to noPerformCalibration(1)
will have no effect.
The value noPerformCalibration(1) will always be returned
when the variable is read.
The result of the calibration will be saved in
upsSmartTestCalibrationResult. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noPerformCalibration(1), performCalibration(2), cancelCurrentCalibration(3) |
|
upsSmartTestCalibrationResults |
1.3.6.1.4.1.17420.1.1.2.7.2.7 |
The results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidTest(2) indicates last calibration did
not take place since the battery capacity was below
100 percent.
Value calibrationInProgress(3) means a calibration
is occurring now. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(1), invalidTest(2), calibrationInProgress(3) |
|
upsThreePhaseBatteryTimeRemain |
1.3.6.1.4.1.17420.1.1.2.8.1.3 |
Battery Time Remain (unit is Minute) |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsThreePhaseBatteryCurrent |
1.3.6.1.4.1.17420.1.1.2.8.1.4 |
Battery Electric Current |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsThreePhaseUPSStatusACStatus |
1.3.6.1.4.1.17420.1.1.2.8.6.3 |
AC Status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(10), abnormal(11) |
|
upsThreePhaseUPSStaticSwitchMode |
1.3.6.1.4.1.17420.1.1.2.8.6.4 |
Switch Mode |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
invermode(12), bypassmode(13) |
|
upsEnvTemperature |
1.3.6.1.4.1.17420.1.1.2.9.1.1 |
The ambient environment temperature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEnvHumidity |
1.3.6.1.4.1.17420.1.1.2.9.1.2 |
The environment humidity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEnvOverTemperature |
1.3.6.1.4.1.17420.1.1.2.9.2.1 |
Alarm dupsAlarmOverTemperature on when the environment
temperature over the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEnvOverHumidity |
1.3.6.1.4.1.17420.1.1.2.9.2.3 |
Alarm dupsAlarmOverHumidity on when the environment
humidity over the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEnvSecurity1 |
1.3.6.1.4.1.17420.1.1.2.9.1.5 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity2 |
1.3.6.1.4.1.17420.1.1.2.9.1.6 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity3 |
1.3.6.1.4.1.17420.1.1.2.9.1.7 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity4 |
1.3.6.1.4.1.17420.1.1.2.9.1.8 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity5 |
1.3.6.1.4.1.17420.1.1.2.9.1.9 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity6 |
1.3.6.1.4.1.17420.1.1.2.9.1.10 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSecurity7 |
1.3.6.1.4.1.17420.1.1.2.9.1.11 |
Security status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvWater |
1.3.6.1.4.1.17420.1.1.2.9.1.3 |
Water status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvSmoke |
1.3.6.1.4.1.17420.1.1.2.9.1.4 |
Smoke status |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), abnormal(2) |
|
upsEnvUnderTemperature |
1.3.6.1.4.1.17420.1.1.2.9.2.2 |
Alarm dupsAlarmUnderTemperature on when the environment
temperature below the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEnvUnderHumidity |
1.3.6.1.4.1.17420.1.1.2.9.2.4 |
Alarm dupsAlarmUnderHumidity on when the environment
humidity below the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
communicationLost |
1 |
SEVERE: Communication to the UPS has been lost. Steps
to reestablish communication are in progress. |
TRAP-TYPE |
|
|
|
upsOverLoad |
2 |
SEVERE: The UPS has sensed a load greater than 100 percent
of its rated capacity. |
TRAP-TYPE |
|
|
|
upsDischarged |
4 |
SEVERE: The UPS just started a runtime calibration
discharge. The UPS batteries are being discharged. |
TRAP-TYPE |
|
|
|
upsOnBattery |
5 |
WARNING: The UPS has switched to battery backup power. |
TRAP-TYPE |
|
|
|
boostOn |
6 |
WARNING: The UPS has enabled Boost. |
TRAP-TYPE |
|
|
|
lowBattery |
7 |
SEVERE: The UPS batteries are low and will soon be exhausted.
If utility power is not restored the UPS will put itself
to 'sleep' and immediately cut power to the load. |
TRAP-TYPE |
|
|
|
powerRestored |
9 |
INFORMATION: Utility power has been restored. |
TRAP-TYPE |
|
|
|
upsTurnedOff |
12 |
WARNING: The UPS has been turned 'off' by the
management station. |
TRAP-TYPE |
|
|
|
upsSleeping |
13 |
WARNING: The UPS is entering 'sleep' mode. Power
to the load will be cut off. |
TRAP-TYPE |
|
|
|
upsWokeUp |
14 |
INFORMATION: The UPS woke up from 'sleep' mode. Power
to the load has been restored. |
TRAP-TYPE |
|
|
|
upsRebootStarted |
15 |
WARNING: The UPS has started its reboot sequence. After
the specified delay the UPS will perform a reboot. |
TRAP-TYPE |
|
|
|
envOverTemperature |
16 |
WARNING: The environment temperature exceed the normal value. |
TRAP-TYPE |
|
|
|
envOverHumidity |
18 |
WARNING: The environment humidity exceed the normal value. |
TRAP-TYPE |
|
|
|
upsTemp |
27 |
WARNING: UPS Temperature Overrun |
TRAP-TYPE |
|
|
|
envUnderHumidity |
31 |
WARNING: The environment humidity below the normal value. |
TRAP-TYPE |
|
|
|
upsBypass |
32 |
WARNING: The UPS is entering 'bypass' mode. |
TRAP-TYPE |
|
|
|
upsTest |
51 |
WARNING: UPS Test |
TRAP-TYPE |
|
|
|