WebGraph-AnalogIO-57661-US-MIB

File: WebGraph-AnalogIO-57661-US-MIB.mib (114289 bytes)

Imported modules

RFC-1212 RFC-1215 RFC1213-MIB
RFC1155-SMI

Imported symbols

OBJECT-TYPE TRAP-TYPE DisplayString
PhysAddress enterprises TimeTicks
IpAddress NetworkAddress

Defined Types

WtWebGraphAnalog57661SensorEntry  
SEQUENCE    
  wtWebGraphAnalog57661SensorNo INTEGER

WtWebGraphAnalog57661ValuesEntry  
SEQUENCE    
  wtWebGraphAnalog57661Values OCTET STRING

WtWebGraphAnalog57661BinaryValuesEntry  
SEQUENCE    
  wtWebGraphAnalog57661BinaryValues INTEGER

WtWebGraphAnalog57661BinaryIfEntry  
SEQUENCE    
  wtWebGraphAnalog57661BinaryModeNo INTEGER

WtWebGraphAnalog57661BinaryEntry  
SEQUENCE    
  wtWebGraphAnalog57661BinaryOperationMode OCTET STRING
  wtWebGraphAnalog57661BinaryTcpServerLocalPort INTEGER
  wtWebGraphAnalog57661BinaryTcpServerInputTrigger OCTET STRING
  wtWebGraphAnalog57661BinaryTcpServerApplicationMode OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientLocalPort INTEGER
  wtWebGraphAnalog57661BinaryTcpClientServerPort INTEGER
  wtWebGraphAnalog57661BinaryTcpClientServerIpAddr OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientServerPassword OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientInactivity INTEGER
  wtWebGraphAnalog57661BinaryTcpClientInputTrigger OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientInterval INTEGER
  wtWebGraphAnalog57661BinaryTcpClientApplicationMode OCTET STRING
  wtWebGraphAnalog57661BinaryUdpPeerLocalPort INTEGER
  wtWebGraphAnalog57661BinaryUdpPeerRemotePort INTEGER
  wtWebGraphAnalog57661BinaryUdpPeerRemoteIpAddr OCTET STRING
  wtWebGraphAnalog57661BinaryUdpPeerInputTrigger OCTET STRING
  wtWebGraphAnalog57661BinaryUdpPeerInterval INTEGER
  wtWebGraphAnalog57661BinaryUdpPeerApplicationMode OCTET STRING
  wtWebGraphAnalog57661BinaryConnectedPort INTEGER
  wtWebGraphAnalog57661BinaryConnectedIpAddr IpAddress
  wtWebGraphAnalog57661BinaryTcpServerClientHttpPort INTEGER
  wtWebGraphAnalog57661BinaryTcpClientServerHttpPort INTEGER
  wtWebGraphAnalog57661BinaryTcpServerHysteresis1 OCTET STRING
  wtWebGraphAnalog57661BinaryTcpServerHysteresis2 OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientHysteresis1 OCTET STRING
  wtWebGraphAnalog57661BinaryTcpClientHysteresis2 OCTET STRING
  wtWebGraphAnalog57661BinaryUdpPeerHysteresis1 OCTET STRING
  wtWebGraphAnalog57661BinaryUdpPeerHysteresis2 OCTET STRING

WtWebGraphAnalog57661SensorColorEntry  
SEQUENCE    
  wtWebGraphAnalog57661SensorColor OCTET STRING

WtWebGraphAnalog57661AlarmIfEntry  
SEQUENCE    
  wtWebGraphAnalog57661AlarmNo INTEGER

WtWebGraphAnalog57661AlarmEntry  
SEQUENCE    
  wtWebGraphAnalog57661AlarmTrigger OCTET STRING
  wtWebGraphAnalog57661AlarmMin1 OCTET STRING
  wtWebGraphAnalog57661AlarmMax1 OCTET STRING
  wtWebGraphAnalog57661AlarmHysteresis1 OCTET STRING
  wtWebGraphAnalog57661AlarmDelay OCTET STRING
  wtWebGraphAnalog57661AlarmInterval OCTET STRING
  wtWebGraphAnalog57661AlarmEnable OCTET STRING
  wtWebGraphAnalog57661AlarmEMailAddr OCTET STRING
  wtWebGraphAnalog57661AlarmMailSubject OCTET STRING
  wtWebGraphAnalog57661AlarmMailText OCTET STRING
  wtWebGraphAnalog57661AlarmManagerIP OCTET STRING
  wtWebGraphAnalog57661AlarmTrapText OCTET STRING
  wtWebGraphAnalog57661AlarmMailOptions OCTET STRING
  wtWebGraphAnalog57661AlarmTcpIpAddr OCTET STRING
  wtWebGraphAnalog57661AlarmTcpPort INTEGER
  wtWebGraphAnalog57661AlarmTcpText OCTET STRING
  wtWebGraphAnalog57661AlarmClearMailSubject OCTET STRING
  wtWebGraphAnalog57661AlarmClearMailText OCTET STRING
  wtWebGraphAnalog57661AlarmClearTrapText OCTET STRING
  wtWebGraphAnalog57661AlarmClearTcpText OCTET STRING
  wtWebGraphAnalog57661AlarmMin2 OCTET STRING
  wtWebGraphAnalog57661AlarmMax2 OCTET STRING
  wtWebGraphAnalog57661AlarmHysteresis2 OCTET STRING
  wtWebGraphAnalog57661AlarmSyslogIpAddr OCTET STRING
  wtWebGraphAnalog57661AlarmSyslogPort INTEGER
  wtWebGraphAnalog57661AlarmSyslogText OCTET STRING
  wtWebGraphAnalog57661AlarmSyslogClearText OCTET STRING
  wtWebGraphAnalog57661AlarmFtpDataPort OCTET STRING
  wtWebGraphAnalog57661AlarmFtpFileName OCTET STRING
  wtWebGraphAnalog57661AlarmFtpText OCTET STRING
  wtWebGraphAnalog57661AlarmFtpClearText OCTET STRING
  wtWebGraphAnalog57661AlarmFtpOption OCTET STRING
  wtWebGraphAnalog57661AlarmTimerCron OCTET STRING

WtWebGraphAnalog57661SensorColor2Entry  
SEQUENCE    
  wtWebGraphAnalog57661GraphicsSensorColor OCTET STRING
  wtWebGraphAnalog57661GraphicsSelectScale OCTET STRING

WtWebGraphAnalog57661ReportIfEntry  
SEQUENCE    
  wtWebGraphAnalog57661ReportNo INTEGER

WtWebGraphAnalog57661ReportEntry  
SEQUENCE    
  wtWebGraphAnalog57661ReportEnable OCTET STRING
  wtWebGraphAnalog57661ReportTimerCron OCTET STRING
  wtWebGraphAnalog57661ReportMethodeEnable OCTET STRING
  wtWebGraphAnalog57661ReportEMailAddr OCTET STRING
  wtWebGraphAnalog57661ReportMailSubject OCTET STRING
  wtWebGraphAnalog57661ReportMailText OCTET STRING
  wtWebGraphAnalog57661ReportManagerIP OCTET STRING
  wtWebGraphAnalog57661ReportTrapText OCTET STRING
  wtWebGraphAnalog57661ReportMailOptions OCTET STRING
  wtWebGraphAnalog57661ReportTcpIpAddr OCTET STRING
  wtWebGraphAnalog57661ReportTcpPort INTEGER
  wtWebGraphAnalog57661ReportTcpText OCTET STRING
  wtWebGraphAnalog57661ReportClearMailSubject OCTET STRING
  wtWebGraphAnalog57661ReportClearMailText OCTET STRING
  wtWebGraphAnalog57661ReportClearTrapText OCTET STRING
  wtWebGraphAnalog57661ReportClearTcpText OCTET STRING
  wtWebGraphAnalog57661ReportSyslogIpAddr OCTET STRING
  wtWebGraphAnalog57661ReportSyslogPort INTEGER
  wtWebGraphAnalog57661ReportSyslogText OCTET STRING
  wtWebGraphAnalog57661ReportSyslogClearText OCTET STRING
  wtWebGraphAnalog57661ReportFtpDataPort OCTET STRING
  wtWebGraphAnalog57661ReportFtpFileName OCTET STRING
  wtWebGraphAnalog57661ReportFtpText OCTET STRING
  wtWebGraphAnalog57661ReportFtpClearText OCTET STRING
  wtWebGraphAnalog57661ReportFtpOption OCTET STRING

WtWebGraphAnalog57661PortEntry  
SEQUENCE    
  wtWebGraphAnalog57661PortName OCTET STRING
  wtWebGraphAnalog57661PortText OCTET STRING
  wtWebGraphAnalog57661PortOffset1 OCTET STRING
  wtWebGraphAnalog57661SetPoint1 OCTET STRING
  wtWebGraphAnalog57661PortOffset2 OCTET STRING
  wtWebGraphAnalog57661SetPoint2 OCTET STRING
  wtWebGraphAnalog57661PortComment OCTET STRING
  wtWebGraphAnalog57661PortSensorSelect OCTET STRING
  wtWebGraphAnalog57661PortUnit OCTET STRING
  wtWebGraphAnalog57661PortScale0 OCTET STRING
  wtWebGraphAnalog57661PortScale100 OCTET STRING
  wtWebGraphAnalog57661PortOutputMode OCTET STRING
  wtWebGraphAnalog57661PortInputMode OCTET STRING

Defined Values

wut 1.3.6.1.4.1.5040
OBJECT IDENTIFIER    

wtComServer 1.3.6.1.4.1.5040.1
OBJECT IDENTIFIER    

wtWebio 1.3.6.1.4.1.5040.1.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661 1.3.6.1.4.1.5040.1.2.28
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Inventory 1.3.6.1.4.1.5040.1.2.28.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661SessCntrl 1.3.6.1.4.1.5040.1.2.28.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Config 1.3.6.1.4.1.5040.1.2.28.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Diag 1.3.6.1.4.1.5040.1.2.28.4
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Device 1.3.6.1.4.1.5040.1.2.28.3.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Ports 1.3.6.1.4.1.5040.1.2.28.3.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Manufact 1.3.6.1.4.1.5040.1.2.28.3.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Text 1.3.6.1.4.1.5040.1.2.28.3.1.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661TimeDate 1.3.6.1.4.1.5040.1.2.28.3.1.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Basic 1.3.6.1.4.1.5040.1.2.28.3.1.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Datalogger 1.3.6.1.4.1.5040.1.2.28.3.1.4
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Alarm 1.3.6.1.4.1.5040.1.2.28.3.1.5
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Graphics 1.3.6.1.4.1.5040.1.2.28.3.1.6
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Report 1.3.6.1.4.1.5040.1.2.28.3.1.7
OBJECT IDENTIFIER    

wtWebGraphAnalog57661TimeZone 1.3.6.1.4.1.5040.1.2.28.3.1.2.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661TimeServer 1.3.6.1.4.1.5040.1.2.28.3.1.2.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661DeviceClock 1.3.6.1.4.1.5040.1.2.28.3.1.2.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Network 1.3.6.1.4.1.5040.1.2.28.3.1.3.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661HTTP 1.3.6.1.4.1.5040.1.2.28.3.1.3.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Mail 1.3.6.1.4.1.5040.1.2.28.3.1.3.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661SNMP 1.3.6.1.4.1.5040.1.2.28.3.1.3.4
OBJECT IDENTIFIER    

wtWebGraphAnalog57661UDP 1.3.6.1.4.1.5040.1.2.28.3.1.3.5
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Syslog 1.3.6.1.4.1.5040.1.2.28.3.1.3.6
OBJECT IDENTIFIER    

wtWebGraphAnalog57661FTP 1.3.6.1.4.1.5040.1.2.28.3.1.3.7
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Language 1.3.6.1.4.1.5040.1.2.28.3.1.3.8
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Binary 1.3.6.1.4.1.5040.1.2.28.3.1.3.9
OBJECT IDENTIFIER    

wtWebGraphAnalog57661GraphicsBase 1.3.6.1.4.1.5040.1.2.28.3.1.6.1
OBJECT IDENTIFIER    

wtWebGraphAnalog57661GraphicsSelect 1.3.6.1.4.1.5040.1.2.28.3.1.6.2
OBJECT IDENTIFIER    

wtWebGraphAnalog57661GraphicsScale 1.3.6.1.4.1.5040.1.2.28.3.1.6.3
OBJECT IDENTIFIER    

wtWebGraphAnalog57661Sensors 1.3.6.1.4.1.5040.1.2.28.1.1
Number of sensors
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2  

wtWebGraphAnalog57661SensorTable 1.3.6.1.4.1.5040.1.2.28.1.2
List of sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661SensorEntry

wtWebGraphAnalog57661SensorEntry 1.3.6.1.4.1.5040.1.2.28.1.2.1
List of sensor numbers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661SensorEntry  

wtWebGraphAnalog57661SensorNo 1.3.6.1.4.1.5040.1.2.28.1.2.1.1
Sensor number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2  

wtWebGraphAnalog57661ValuesTable 1.3.6.1.4.1.5040.1.2.28.1.3
List of measurement values corresponding to the channel numbers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661ValuesEntry

wtWebGraphAnalog57661ValuesEntry 1.3.6.1.4.1.5040.1.2.28.1.3.1
Measurement values of the sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661ValuesEntry  

wtWebGraphAnalog57661Values 1.3.6.1.4.1.5040.1.2.28.1.3.1.1
Measurement value of the sensor, ASCII. This value will be translated according to the ports settings for the read and write operations.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(5)  

wtWebGraphAnalog57661BinaryValuesTable 1.3.6.1.4.1.5040.1.2.28.1.4
List of binary measurement values corresponding to the channel numbers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661BinaryValuesEntry

wtWebGraphAnalog57661BinaryValuesEntry 1.3.6.1.4.1.5040.1.2.28.1.4.1
Binary measurement values of the sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661BinaryValuesEntry  

wtWebGraphAnalog57661BinaryValues 1.3.6.1.4.1.5040.1.2.28.1.4.1.1
Binary measurement value of the sensor in 1/1000, signed number, 0x7FFFFFFF indicates an invalid value. This value will be translated according to the ports settings for the read and write operations.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661SessCntrlPassword 1.3.6.1.4.1.5040.1.2.28.2.1
Entering this password opens a session which is ended by writing a 1 to wtWebGraphAnalog57661SessCntrlLogout. When read this variable provides a string of length zero.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SessCntrlConfigMode 1.3.6.1.4.1.5040.1.2.28.2.2
When the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661SessCntrl-NoSession(0), wtWebGraphAnalog57661SessCntrl-Session(1)  

wtWebGraphAnalog57661SessCntrlLogout 1.3.6.1.4.1.5040.1.2.28.2.3
If the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661SessCntrlAdminPassword 1.3.6.1.4.1.5040.1.2.28.2.4
This password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SessCntrlConfigPassword 1.3.6.1.4.1.5040.1.2.28.2.5
This password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DeviceName 1.3.6.1.4.1.5040.1.2.28.3.1.1.1
Name of the Webio, which is user definable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DeviceText 1.3.6.1.4.1.5040.1.2.28.3.1.1.2
Description of the Webio, which is user definable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DeviceLocation 1.3.6.1.4.1.5040.1.2.28.3.1.1.3
Description of the location of the Webio, which is user definable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DeviceContact 1.3.6.1.4.1.5040.1.2.28.3.1.1.4
Contact address of the system operator of the Webio, which is user definable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661TzOffsetHrs 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.1
Offset hours for the time zone (winter time) with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661TzOffsetMin 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.2
Offset minutes for the time zone (winter time) with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661TzEnable 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.3
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezone
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661StTzOffsetHrs 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.4
Offset hours of the time zone (summer time) with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661StTzOffsetMin 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.5
Offset minutes of the time zone (summer time) with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661StTzEnable 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.6
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertime
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661StTzStartMonth 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.7
Month in which the change is made from winter time to summer time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StartMonth-January(1), wtWebGraphAnalog57661StartMonth-February(2), wtWebGraphAnalog57661StartMonth-March(3), wtWebGraphAnalog57661StartMonth-April(4), wtWebGraphAnalog57661StartMonth-May(5), wtWebGraphAnalog57661StartMonth-June(6), wtWebGraphAnalog57661StartMonth-July(7), wtWebGraphAnalog57661StartMonth-August(8), wtWebGraphAnalog57661StartMonth-September(9), wtWebGraphAnalog57661StartMonth-October(10), wtWebGraphAnalog57661StartMonth-November(11), wtWebGraphAnalog57661StartMonth-December(12)  

wtWebGraphAnalog57661StTzStartMode 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.8
Mode of the day of the week for which the change is made from winter time to summer time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StartMode-first(1), wtWebGraphAnalog57661StartMode-second(2), wtWebGraphAnalog57661StartMode-third(3), wtWebGraphAnalog57661StartMode-fourth(4), wtWebGraphAnalog57661StartMode-last(5)  

wtWebGraphAnalog57661StTzStartWday 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.9
Day of the week on which the change is made from winter time to summer time
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StartWday-Sunday(1), wtWebGraphAnalog57661StartWday-Monday(2), wtWebGraphAnalog57661StartWday-Tuesday(3), wtWebGraphAnalog57661StartWday-Thursday(4), wtWebGraphAnalog57661StartWday-Wednesday(5), wtWebGraphAnalog57661StartWday-Friday(6), wtWebGraphAnalog57661StartWday-Saturday(7)  

wtWebGraphAnalog57661StTzStartHrs 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.10
Hour in which the time zone is changed from winter to summer time with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661StTzStartMin 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.11
Minute in which the time zone is changed from winter to summer time with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661StTzStopMonth 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.12
Month in which the change is made from summer time to winter time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StopMonth-January(1), wtWebGraphAnalog57661StopMonth-February(2), wtWebGraphAnalog57661StopMonth-March(3), wtWebGraphAnalog57661StopMonth-April(4), wtWebGraphAnalog57661StopMonth-May(5), wtWebGraphAnalog57661StopMonth-June(6), wtWebGraphAnalog57661StopMonth-July(7), wtWebGraphAnalog57661StopMonth-August(8), wtWebGraphAnalog57661StopMonth-September(9), wtWebGraphAnalog57661StopMonth-October(10), wtWebGraphAnalog57661StopMonth-November(11), wtWebGraphAnalog57661StopMonth-December(12)  

wtWebGraphAnalog57661StTzStopMode 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.13
Mode of the week day on which the change is made from summer time to winter time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StopMode-first(1), wtWebGraphAnalog57661StopMode-second(2), wtWebGraphAnalog57661StopMode-third(3), wtWebGraphAnalog57661StopMode-fourth(4), wtWebGraphAnalog57661StopMode-last(5)  

wtWebGraphAnalog57661StTzStopWday 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.14
Day of the week on which the change is made from summer time to winter time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661StopWday-Sunday(1), wtWebGraphAnalog57661StopWday-Monday(2), wtWebGraphAnalog57661StopWday-Tuesday(3), wtWebGraphAnalog57661StopWday-Thursday(4), wtWebGraphAnalog57661StopWday-Wednesday(5), wtWebGraphAnalog57661StopWday-Friday(6), wtWebGraphAnalog57661StopWday-Saturday(7)  

wtWebGraphAnalog57661StTzStopHrs 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.15
Hour at which the time zone is changed from summer to winter time with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661StTzStopMin 1.3.6.1.4.1.5040.1.2.28.3.1.2.1.16
Minute at which the time zone is changed from summer to winter time with respect to UTC.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661TimeServer1 1.3.6.1.4.1.5040.1.2.28.3.1.2.2.1
IP address or name of the 1st time server in ASCII
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661TimeServer2 1.3.6.1.4.1.5040.1.2.28.3.1.2.2.2
IP address or name of the 2nd time server in ASCII
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661TsEnable 1.3.6.1.4.1.5040.1.2.28.3.1.2.2.3
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Server
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661TsSyncTime 1.3.6.1.4.1.5040.1.2.28.3.1.2.2.4
Daily synchronisation time with the time server (hour: 0-23).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661ClockHrs 1.3.6.1.4.1.5040.1.2.28.3.1.2.3.1
Clock hours taking into account the time zone settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..23  

wtWebGraphAnalog57661ClockMin 1.3.6.1.4.1.5040.1.2.28.3.1.2.3.2
Clock minutes taking into account the time zone settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..59  

wtWebGraphAnalog57661ClockDay 1.3.6.1.4.1.5040.1.2.28.3.1.2.3.3
Date: Day of the month, taking into account the time zone settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..31  

wtWebGraphAnalog57661ClockMonth 1.3.6.1.4.1.5040.1.2.28.3.1.2.3.4
Date: Month, taking into account the time zone settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661ClockMonth-January(1), wtWebGraphAnalog57661ClockMonth-February(2), wtWebGraphAnalog57661ClockMonth-March(3), wtWebGraphAnalog57661ClockMonth-April(4), wtWebGraphAnalog57661ClockMonth-May(5), wtWebGraphAnalog57661ClockMonth-June(6), wtWebGraphAnalog57661ClockMonth-July(7), wtWebGraphAnalog57661ClockMonth-August(8), wtWebGraphAnalog57661ClockMonth-September(9), wtWebGraphAnalog57661ClockMonth-October(10), wtWebGraphAnalog57661ClockMonth-November(11), wtWebGraphAnalog57661ClockMonth-December(12)  

wtWebGraphAnalog57661ClockYear 1.3.6.1.4.1.5040.1.2.28.3.1.2.3.5
Date: Year, taking into account the time zone settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

wtWebGraphAnalog57661IpAddress 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.1
IP address of the Webio
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

wtWebGraphAnalog57661SubnetMask 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.2
Subnet mask of the Webio
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

wtWebGraphAnalog57661Gateway 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.3
Gateway of the Webio
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

wtWebGraphAnalog57661DnsServer1 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.4
IP address of the 1st DNS server in ASCII
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DnsServer2 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.5
IP address of the 2nd DNS server in ASCII
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AddConfig 1.3.6.1.4.1.5040.1.2.28.3.1.3.1.6
Additional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: DHCP disable Bit 0: BOOTP disable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661Startup 1.3.6.1.4.1.5040.1.2.28.3.1.3.2.1
Binary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: Index.htm Bit 2: Home.htm Bit 3: User.htm Only one page may be selected at a time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GetHeaderEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.2.2
If these bits are set, every answer of a short form GET question will be lead by the IP-address and name of the device and/or a HTTP header: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-6: unused Bit 1 : GET HTTP enable Bit 0 : GET Header enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661HttpPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.2.3
Definition of the standard HTML port (Default: 80).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661MailAdName 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.1
Device name for mail administration.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MailReply 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.2
Reply address for the mail server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MailServer 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.3
Name or IP address of the mail server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebioAn1MailEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.4
Set this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MailAuthentication 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.5
Selection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authentication
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661MailAuthUser 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.6
Name of the user to be authenticated.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MailAuthPassword 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.7
Authentication password.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MailPop3Server 1.3.6.1.4.1.5040.1.2.28.3.1.3.3.8
Name or Ip-address of the POP3 Servers.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SnmpCommunityStringRead 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.1
Community string read only
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SnmpCommunityStringReadWrite 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.2
Community string read / write
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SystemTrapManagerIP 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.3
Name or IP address of the TCP server which accepts the system trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SystemTrapEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.4
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661SnmpEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.5
Set bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SnmpCommunityStringTrap 1.3.6.1.4.1.5040.1.2.28.3.1.3.4.6
Community string send within traps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661UdpPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.5.1
Udp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661UdpEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.5.2
Set this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SyslogServerIP 1.3.6.1.4.1.5040.1.2.28.3.1.3.6.1
Name or IP address of the Syslog server, which accepts the Syslog messgaes.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SyslogServerPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.6.2
Portnumber of the Syslog servers, default 514.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661SyslogSystemMessagesEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.6.3
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661SyslogEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.6.4
Set bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPServerIP 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.1
Name or IP address of the FTP server, which accepts the FTP messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPServerControlPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.2
Portnumber of the control port of the FTP server, default 21.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661FTPUserName 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.3
FTP Loggin: user name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPPassword 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.4
FTP Loggin: user password.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPAccount 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.5
FTP Loggin: name of account.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPOption 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.6
Bit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661FTPEnable 1.3.6.1.4.1.5040.1.2.28.3.1.3.7.7
Set Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661LanguageSelect 1.3.6.1.4.1.5040.1.2.28.3.1.3.8.1
Language selection: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 2-7: unused Bit 1 : English Bit 0 : German
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryModeCount 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.1
Number of independent binary channels.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2  

wtWebGraphAnalog57661BinaryIfTable 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.2
Table of indices.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661BinaryIfEntry

wtWebGraphAnalog57661BinaryIfEntry 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.2.1
Indices of the binary channels.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661BinaryIfEntry  

wtWebGraphAnalog57661BinaryModeNo 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.2.1.1
Number of the binary channel.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2  

wtWebGraphAnalog57661BinaryTable 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3
Table of properties of the binary mode.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661BinaryEntry

wtWebGraphAnalog57661BinaryEntry 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1
Binary properties.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661BinaryEntry  

wtWebGraphAnalog57661BinaryOperationMode 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.1
Selection of the operation mode: The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client Bit 0 : TCP Server
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryTcpServerLocalPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.2
Local TCP port for data exchange in this server mode. This port number must be unique within the device. Reserved port number must not be used (refere to the manual).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryTcpServerInputTrigger 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.3
Every change on the inputs causes their state to be transmitted to the remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input states. If a bit is set (1), a change of state on the corresponding input triggers a transmission. If the bit is not set (0), no transmission takes place. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 0-1: Analog inputs 0-1
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryTcpServerApplicationMode 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.4
Selection of the application mode: The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box Slave Bit 1 : Compatible 50xxx Bit 0 : Default
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryTcpClientLocalPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.5
Local TCP port for data exchange in this client mode. This port number must be unique within the device. Reserved port number must not be used (refere to the manual).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryTcpClientServerPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.6
Port number of the server. A complete set of port number, IP address and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryTcpClientServerIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.7
Ip address of the server. A complete set of port number, IP address and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryTcpClientServerPassword 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.8
Building a connection may be protected by the administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryTcpClientInactivity 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.9
Connection timeout in 100ms. If no data are exchanged within the specified time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661BinaryTcpClientInputTrigger 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.10
Every change on the inputs causes their state to be transmitted to the remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input states. If a bit is set (1), a change of state on the corresponding input triggers a transmission. If the bit is not set (0), no transmission takes place. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 0-1: Analog inputs 0-1
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryTcpClientInterval 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.11
Configurable interval with a 100ms base, in which the Webio device sends data to the configured application. A interval of zero stopps the periodical sending.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

wtWebGraphAnalog57661BinaryTcpClientApplicationMode 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.12
Selection of the application mode: The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compatible 50xxx Bit 0 : Default
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryUdpPeerLocalPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.13
Local UDP port for data exchange in this peer to peer mode. This port number must be unique within the device. Reserved port number must not be used (refere to the manual).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryUdpPeerRemotePort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.14
Port number of the remote device. A complete set of port number, IP address and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryUdpPeerRemoteIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.15
Ip address of the remote device. A complete set of port number, IP address and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryUdpPeerInputTrigger 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.16
Every change on the inputs causes their state to be transmitted to the remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input states. If a bit is set (1), a change of state on the corresponding input triggers a transmission. If the bit is not set (0), no transmission takes place. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 0-1: Analog inputs 0-1
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryUdpPeerInterval 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.17
Configurable interval with a 100ms base, in which the Webio device sends data to the configured remote device. A interval of zero stopps the periodical sending.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

wtWebGraphAnalog57661BinaryUdpPeerApplicationMode 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.18
Selection of the application mode: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compatible 50xxx Bit 0 : Default
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661BinaryConnectedPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.19
Port number of the remote device, after connection has been established. In case of no connection or missing port informations a zero will be read.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryConnectedIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.20
IP address of the remote device, after connection has been established. In case of no connection or missing port informations 0.0.0.0 will be read.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

wtWebGraphAnalog57661BinaryTcpServerClientHttpPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.21
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs status informations will be send to this port. Not used at mode Compatible 50xxx.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryTcpClientServerHttpPort 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.22
HTTP port number of the remote device at TCP Client Mode. In the operating mode Box2Box connection status informations will be exchanged through this port.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661BinaryTcpServerHysteresis1 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.23
A change greater than this value initiate a transmission of the corresponding input value. The input 1 must be selected at wtWebGraphAnalog57661BinaryTcpServerInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryTcpServerHysteresis2 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.24
A change greater than this value initiate a transmission of the corresponding input value. The input 2 must be selected at wtWebGraphAnalog57661BinaryTcpServerInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryTcpClientHysteresis1 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.25
A change greater than this value initiate a transmission of the corresponding input value. The input 1 must be selected at wtWebGraphAnalog57661BinaryTcpClientInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryTcpClientHysteresis2 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.26
A change greater than this value initiate a transmission of the corresponding input value. The input 2 must be selected at wtWebGraphAnalog57661BinaryTcpClientInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryUdpPeerHysteresis1 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.27
A change greater than this value initiate a transmission of the corresponding input value. The input 1 must be selected at wtWebGraphAnalog57661BinaryUdpPeerInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661BinaryUdpPeerHysteresis2 1.3.6.1.4.1.5040.1.2.28.3.1.3.9.3.1.28
A change greater than this value initiate a transmission of the corresponding input value. The input 2 must be selected at wtWebGraphAnalog57661BinaryUdpPeerInputTrigger. With a hysteresis of zero any change will be transmitted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661LoggerTimebase 1.3.6.1.4.1.5040.1.2.28.3.1.4.1
Time base of the data logger
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661Datalogger-15Sec(1), wtWebGraphAnalog57661Datalogger-30Sec(2), wtWebGraphAnalog57661Datalogger-1Min(3), wtWebGraphAnalog57661Datalogger-5Min(4), wtWebGraphAnalog57661Datalogger-15Min(5), wtWebGraphAnalog57661Datalogger-60Min(6)  

wtWebGraphAnalog57661LoggerSensorSel 1.3.6.1.4.1.5040.1.2.28.3.1.4.2
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661DisplaySensorSel 1.3.6.1.4.1.5040.1.2.28.3.1.4.3
Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661SensorColorTable 1.3.6.1.4.1.5040.1.2.28.3.1.4.4
List of sensor colors for the praphical presentation.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661SensorColorEntry

wtWebGraphAnalog57661SensorColorEntry 1.3.6.1.4.1.5040.1.2.28.3.1.4.4.1
Index numbers of the sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661SensorColorEntry  

wtWebGraphAnalog57661SensorColor 1.3.6.1.4.1.5040.1.2.28.3.1.4.4.1.1
Color of the sensors at the praphical presention.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(3)  

wtWebGraphAnalog57661AutoScaleEnable 1.3.6.1.4.1.5040.1.2.28.3.1.4.5
If bit 0 is set, vertical auto scale is enabled: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Auto Scale enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661VerticalUpperLimit 1.3.6.1.4.1.5040.1.2.28.3.1.4.6
This value defines the maximum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661VerticalLowerLimit 1.3.6.1.4.1.5040.1.2.28.3.1.4.7
This value defines the minimum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661HorizontalZoom 1.3.6.1.4.1.5040.1.2.28.3.1.4.8
Defines the default zoom stage, if no auto scaling is selected.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER wtWebGraphAnalog57661Zoom-25min(1), wtWebGraphAnalog57661Zoom-75min(2), wtWebGraphAnalog57661Zoom-5hrs(3), wtWebGraphAnalog57661Zoom-30hrs(4), wtWebGraphAnalog57661Zoom-5days(5), wtWebGraphAnalog57661Zoom-25days(6)  

wtWebGraphAnalog57661AlarmCount 1.3.6.1.4.1.5040.1.2.28.3.1.5.1
Number of independent alarms.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

wtWebGraphAnalog57661AlarmIfTable 1.3.6.1.4.1.5040.1.2.28.3.1.5.2
List of alarm indices.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661AlarmIfEntry

wtWebGraphAnalog57661AlarmIfEntry 1.3.6.1.4.1.5040.1.2.28.3.1.5.2.1
Numbers of the alarms.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661AlarmIfEntry  

wtWebGraphAnalog57661AlarmNo 1.3.6.1.4.1.5040.1.2.28.3.1.5.2.1.1
Alarm number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

wtWebGraphAnalog57661AlarmTable 1.3.6.1.4.1.5040.1.2.28.3.1.5.3
List of settings depending on the alarm number.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661AlarmEntry

wtWebGraphAnalog57661AlarmEntry 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1
Alarm parameters of the individual alarms.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661AlarmEntry  

wtWebGraphAnalog57661AlarmTrigger 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.1
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661AlarmMin1 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.2
Minimum sensor 1 with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMax1 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.3
Maximum sensor 1 with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmHysteresis1 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.4
Reading changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmDelay 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.5
Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes).
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmInterval 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.6
Send interval for alarm messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmEnable 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.7
Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog enable Bit 4: FTP Client enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661AlarmEMailAddr 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.8
E-Mail address for sending the alarm mail to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMailSubject 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.9
Subject line for alarm mail.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMailText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.10
Alarm mail text: provides the current temperature; n = 1..2. provides the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmManagerIP 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.11
Name or IP address of the SNMP Manager which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmTrapText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.12
This text is sent in the trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMailOptions 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.13
Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Logger.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661AlarmTcpIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.14
Name or IP address of the TCP server which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmTcpPort 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.15
Port number of the TCP server which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661AlarmTcpText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.16
This text is sent in the TCP trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmClearMailSubject 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.17
Subject line for alarm clear mail.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmClearMailText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.18
Alarm clear mail text: provides the current temperature; n = 1..2. provides the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmClearTrapText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.19
This text is sent in the trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmClearTcpText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.20
This text is sent in the TCP trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMin2 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.21
Minimum sensor 2 with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmMax2 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.22
Maximum sensor 2 with maximum 2 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmHysteresis2 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.23
Hysterese rel. sensor 2 with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmSyslogIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.24
IP address of the syslog server to which the Webio device should send syslog messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmSyslogPort 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.25
Port number of the syslog server to which the Webio device should send syslog messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661AlarmSyslogText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.26
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmSyslogClearText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.27
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body of a alarm clear message.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmFtpDataPort 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.28
Local data port: 1..65535 or AUTO: the next free port will be assigned.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmFtpFileName 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.29
Name of the file including path informations.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmFtpText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.30
Message text to store on the FTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmFtpClearText 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.31
Alarm clear message to store on the FTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661AlarmFtpOption 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.32
Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661AlarmTimerCron 1.3.6.1.4.1.5040.1.2.28.3.1.5.3.1.33
This entry defines a time window for alarm 1-8 and a activation time for the report. A time window is definied by start and stop time stamp, seperated by a space or tab. The activation time of the report is defined by a single start time stamp. Each time stamp contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger an action, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas (i.e.: 2,14,22) - a partition within the allowed range (i.e.: 1-5) - step size within a partition of the allowed range (i.e.: 0-59/2 every second minute).
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsBaseEnable 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.1
Defines the viewing options of the graphic: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Auto scroll enable Bit 1 : Show table Bit 2 : Show graph Bit 3 : Show control buttons Bit 4 : Show config menu Bit 5-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsBaseWidth 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.2
Defines the width of the graphic in pixels.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsBaseHeight 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.3
Defines the height of the graphic in pixels.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsBaseFrameColor 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.4
Frame color definition in RGB.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(3)  

wtWebGraphAnalog57661GraphicsBaseBackgroundColor 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.5
Background color definition in RGB.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(3)  

wtWebGraphAnalog57661GraphicsBasePollingrate 1.3.6.1.4.1.5040.1.2.28.3.1.6.1.6
Defines the pollingrate in seconds, which defines the refreshing intervall of the graphic.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsSelectDisplaySensorSel 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.1
Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661GraphicsSelectDisplayShowExtrem 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.2
Binary coded sensor selection: only selected sensors will be shown with minima and maxima: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661SensorColor2Table 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.3
List of sensor colors for the praphical presentation.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661SensorColor2Entry

wtWebGraphAnalog57661SensorColor2Entry 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.3.1
Numbers of the sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661SensorColor2Entry  

wtWebGraphAnalog57661GraphicsSensorColor 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.3.1.1
Color of the sensors at the praphical presention.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(3)  

wtWebGraphAnalog57661GraphicsSelectScale 1.3.6.1.4.1.5040.1.2.28.3.1.6.2.3.1.2
Assignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsScaleAutoScaleEnable 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.1
Select the Auto Scale Mode: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto scale enable Bit 1 : Scale 2 Auto scale enable Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsScaleAutoFitEnable 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.2
Select the Auto Fit Mode:: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto fit enable Bit 1 : Scale 2 Auto fit enable Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsScale1Min 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.3
Scale 1: Minimum.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsScale2Min 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.4
Scale 2: Minimum.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsScale1Max 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.7
Scale 1: Maximum.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsScale2Max 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.8
Scale 2: Maximum.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661GraphicsScale1Unit 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.11
Scale 1: Unit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661GraphicsScale2Unit 1.3.6.1.4.1.5040.1.2.28.3.1.6.3.12
Scale 2: Unit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportCount 1.3.6.1.4.1.5040.1.2.28.3.1.7.1
Number of independent Reports.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

wtWebGraphAnalog57661ReportIfTable 1.3.6.1.4.1.5040.1.2.28.3.1.7.2
List of Report indices.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661ReportIfEntry

wtWebGraphAnalog57661ReportIfEntry 1.3.6.1.4.1.5040.1.2.28.3.1.7.2.1
Numbers of the Reports.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661ReportIfEntry  

wtWebGraphAnalog57661ReportNo 1.3.6.1.4.1.5040.1.2.28.3.1.7.2.1.1
Report number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661ReportTable 1.3.6.1.4.1.5040.1.2.28.3.1.7.3
List of settings depending on the Report number.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661ReportEntry

wtWebGraphAnalog57661ReportEntry 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1
Report parameters of the individual Reports.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661ReportEntry  

wtWebGraphAnalog57661ReportEnable 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.1
Binar kodierte Triggerbedingungen: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Report enable Bit 1-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661ReportTimerCron 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.2
This entry defines a time window for alarm 1-8 and a activation time for the report. A time window is definied by start and stop time stamp, seperated by a space or tab. The activation time of the report is defined by a single start time stamp. Each time stamp contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger an action, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas (i.e.: 2,14,22) - a partition within the allowed range (i.e.: 1-5) - step size within a partition of the allowed range (i.e.: 0-59/2 every second minute).
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportMethodeEnable 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.3
Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog enable Bit 4: FTP Client enable
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661ReportEMailAddr 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.8
E-Mail address for sending the alarm mail to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportMailSubject 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.9
Subject line for alarm mail.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportMailText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.10
Report mail text: provides the current temperature; n = 1..2. provides the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportManagerIP 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.11
Name or IP address of the SNMP Manager which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportTrapText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.12
This text is sent in the trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportMailOptions 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.13
Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Logger.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661ReportTcpIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.14
Name or IP address of the TCP server which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportTcpPort 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.15
Port number of the TCP server which accepts the trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661ReportTcpText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.16
This text is sent in the TCP trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportClearMailSubject 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.17
Subject line for alarm clear mail.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportClearMailText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.18
Report clear mail text: provides the current temperature; n = 1..2. provides the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportClearTrapText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.19
This text is sent in the trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportClearTcpText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.20
This text is sent in the TCP trap body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportSyslogIpAddr 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.24
IP address of the syslog server to which the Webio device should send syslog messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportSyslogPort 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.25
Port number of the syslog server to which the Webio device should send syslog messages.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

wtWebGraphAnalog57661ReportSyslogText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.26
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportSyslogClearText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.27
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body of a alarm clear message.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportFtpDataPort 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.28
Local data port: 1..65535 or AUTO: the next free port will be assigned.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportFtpFileName 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.29
Name of the file including path informations.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportFtpText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.30
Message text to store on the FTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportFtpClearText 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.31
Report clear message to store on the FTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661ReportFtpOption 1.3.6.1.4.1.5040.1.2.28.3.1.7.3.1.32
Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661PortTable 1.3.6.1.4.1.5040.1.2.28.3.2.1
List of settings depending on the sensor number.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WtWebGraphAnalog57661PortEntry

wtWebGraphAnalog57661PortEntry 1.3.6.1.4.1.5040.1.2.28.3.2.1.1
Sensor parameters for the individual sensors.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  WtWebGraphAnalog57661PortEntry  

wtWebGraphAnalog57661PortName 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.1
Name of the sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortText 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.2
Description of the sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortOffset1 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.3
Offset calibration: Offset in degrees with maximum 3 decimal places at set point 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SetPoint1 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.4
Offset calibration: Reference set point 1 in degrees with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortOffset2 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.5
Offset calibration: Offset in degrees with maximum 3 decimal places at set point 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661SetPoint2 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.6
Offset calibration: Reference set point 2 in degrees with maximum 3 decimal places.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortComment 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.7
Offset calibration: informations of date, name of operator, reference devices.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortSensorSelect 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.8
Binary coded options for sensor 1: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : 0-20mA (default) Bit 1 : 4-20mA Bit 2 : Disconnect Bit 3-7: unused
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661PortUnit 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.9
User scale: displayed unit.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortScale0 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.10
User scale: displayed value in 1/1000 at 0% full scale range. Range: -999999.999 to 999999.999
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortScale100 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.11
User scale: displayed value in 1/1000 at 100% full scale range. Range: -999999.999 to 999999.999
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661PortOutputMode 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.12
This binary coded output mode defines the individual operation mode for any output. More than one mode must not be selected. If an output mode is selected, Bit 2 in wtWebGraphAnalog57661PortInputMode will be set automatically. The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 6-7: unused Bit 5 : Output OFF Bit 4 : Binary 2 Bit 3 : Binary 1 Bit 2 : SNMP Bit 1 : UDP ASCII Bit 0 : HTTP
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661PortInputMode 1.3.6.1.4.1.5040.1.2.28.3.2.1.1.13
This binary coded input mode defines the individual operation mode for any input. More than one mode must not be selected. If an input mode is selected, Bit 5 in wtWebGraphAnalog57661PortOutputMode will be set automatically. The OCTETS are interpreted bit-by-bit,Bit 0 corresponds to the LSB. OCTET 1: ungenutzt OCTET 2: ungenutzt OCTET 3: ungenutzt OCTET 4: Bit 3-7: unused Bit 2 : I-Output Bit 1 : I-Input, active Bit 0 : I-Input, passive
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(4)  

wtWebGraphAnalog57661MfName 1.3.6.1.4.1.5040.1.2.28.3.3.1
Manufacturer company name
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MfAddr 1.3.6.1.4.1.5040.1.2.28.3.3.2
Manufacturer address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MfHotline 1.3.6.1.4.1.5040.1.2.28.3.3.3
Manufacturer hotline.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MfInternet 1.3.6.1.4.1.5040.1.2.28.3.3.4
Manufacturer Internet address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MfDeviceTyp 1.3.6.1.4.1.5040.1.2.28.3.3.5
Manufacturer device name (model number).
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661MfOrderNo 1.3.6.1.4.1.5040.1.2.28.3.3.6
Manufacturer part number.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DiagErrorCount 1.3.6.1.4.1.5040.1.2.28.4.1
Number of entries in the error memory.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661DiagBinaryError 1.3.6.1.4.1.5040.1.2.28.4.2
Error causes coded bit-by-bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DiagErrorIndex 1.3.6.1.4.1.5040.1.2.28.4.3
The value of this variable is used as an index to read an error massege from wtWebGraphAnalog57661DiagErrorMessage. Errors are numbered from 1 to wtWebGraphAnalog57661DiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphAnalog57661DiagErrorMessage.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661DiagErrorMessage 1.3.6.1.4.1.5040.1.2.28.4.4
Using wtWebGraphAnalog57661DiagErrorIndex as an index, the appropriate message is available.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

wtWebGraphAnalog57661DiagErrorClear 1.3.6.1.4.1.5040.1.2.28.4.5
Writing 1 into this variable clears all diagnosis messages.
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER  

wtWebGraphAnalog57661Alert1 31
This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert2 32
This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert3 33
This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert4 34
This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert5 35
This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert6 36
This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert7 37
This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert8 38
This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert9 91
This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert10 92
This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert11 93
This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert12 94
This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert13 95
This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert14 96
This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert15 97
This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661Alert16 98
This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661AlertReport 39
This SNMP trap is generated when the report was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE    

wtWebGraphAnalog57661AlertDiag 110
This SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE