TOSHIBAUPS-MIB

File: TOSHIBAUPS-MIB.mib (175215 bytes)

Imported modules

SNMPv2-TC RFC1155-SMI RFC-1212
RFC-1215

Imported symbols

DisplayString TimeStamp TimeInterval
TestAndIncr AutonomousType enterprises
Gauge32 IpAddress OBJECT-TYPE
TRAP-TYPE

Defined Types

PositiveInteger  
INTEGER 0..2147483647    

NonNegativeInteger  
INTEGER 0..2147483647    

UpsInputEntry  
SEQUENCE    
  upsInputIndex PositiveInteger
  upsInputFrequency INTEGER
  upsInputVoltage INTEGER
  upsInputCurrent INTEGER

UpsInputRatedEntry  
SEQUENCE    
  upsInputSlotIndex PositiveInteger
  upsInputRatedFrequency INTEGER
  upsInputRatedVoltage INTEGER
  upsInputRatedCurrent INTEGER

UpsOutputEntry  
SEQUENCE    
  upsOutputIndex PositiveInteger
  upsOutputFrequency INTEGER
  upsOutputVoltage INTEGER
  upsOutputCurrent INTEGER
  upsOutputActivePower INTEGER
  upsOutputApparentPower INTEGER

UpsOutputRatedEntry  
SEQUENCE    
  upsOutputSlotIndex PositiveInteger
  upsOutputRatedFrequency INTEGER
  upsOutputRatedVoltage INTEGER
  upsOutputRatedCurrent INTEGER
  upsOutputRatedActivePower INTEGER
  upsOutputRatedApparentPower INTEGER

UpsBypassEntry  
SEQUENCE    
  upsBypassIndex PositiveInteger
  upsBypassFrequency INTEGER
  upsBypassVoltage INTEGER
  upsBypassCurrent INTEGER

UpsBatteryExtEntry  
SEQUENCE    
  upsBatteryExtIndex PositiveInteger
  upsBatteryExtInSeries INTEGER
  upsBatteryExtInParallel INTEGER
  upsBatteryExtRatedAmpereHour INTEGER
  upsBatteryExtCRate INTEGER
  upsBatteryExtInstallDate DisplayString

UpsAlarmEntry  
SEQUENCE    
  upsAlarmId PositiveInteger
  upsAlarmDescr AutonomousType
  upsAlarmTime TimeStamp

UpsConnectedClientsEntry  
SEQUENCE    
  upsConnectedClientsIndex PositiveInteger
  upsConnectedClientsIPAddress IpAddress
  upsConnectedClientsName DisplayString
  upsConnectedClientsTimeAtConnection DisplayString
  upsConnectedClientsShutdownDelay DisplayString
  upsConnectedClientsConnectionTimeout INTEGER
  upsConnectedClientsShutdownTest INTEGER

UpsEmailClientsEntry  
SEQUENCE    
  upsEmailClientsIndex PositiveInteger
  upsEmailClientsEmailAddress DisplayString
  upsEmailClientsDescription DisplayString
  upsEmailClientsDailyStatusReportType INTEGER
  upsEmailClientsEventStatusReportType INTEGER
  upsEmailClientsInfoLevel INTEGER

UpsSNMPTrapsReceiversEntry  
SEQUENCE    
  upsSNMPTrapsReceiversIndex PositiveInteger
  upsSNMPTrapsReceiversIPAddress IpAddress
  upsSNMPTrapReceiversCommunityString DisplayString
  upsSNMPTrapReceiversTrapType INTEGER
  upsSNMPTrapReceiversInfoReceivingSeverityLevel INTEGER
  upsSNMPTrapReceiversDescription DisplayString

UpsSNMPCommunitiesEntry  
SEQUENCE    
  upsSNMPCommunitiesIndex PositiveInteger
  upsSNMPCommunitiesIPAddress IpAddress
  upsSNMPCommunitiesAccessString DisplayString
  upsSNMPCommunitiesAccessMode INTEGER

Defined Values

toshiba 1.3.6.1.4.1.186
OBJECT IDENTIFIER    

equ 1.3.6.1.4.1.186.1
OBJECT IDENTIFIER    

equUPS 1.3.6.1.4.1.186.1.19
OBJECT IDENTIFIER    

ticUPS 1.3.6.1.4.1.186.1.19.2
OBJECT IDENTIFIER    

rmti3 1.3.6.1.4.1.186.1.19.2.3
OBJECT IDENTIFIER    

upsIdent 1.3.6.1.4.1.186.1.19.2.3.1
OBJECT IDENTIFIER    

upsInput 1.3.6.1.4.1.186.1.19.2.3.2
OBJECT IDENTIFIER    

upsOutput 1.3.6.1.4.1.186.1.19.2.3.3
OBJECT IDENTIFIER    

upsBypass 1.3.6.1.4.1.186.1.19.2.3.4
OBJECT IDENTIFIER    

upsDCBus 1.3.6.1.4.1.186.1.19.2.3.5
OBJECT IDENTIFIER    

upsBattery 1.3.6.1.4.1.186.1.19.2.3.6
OBJECT IDENTIFIER    

upsStsCtlCfg 1.3.6.1.4.1.186.1.19.2.3.7
OBJECT IDENTIFIER    

upsHistory 1.3.6.1.4.1.186.1.19.2.3.8
OBJECT IDENTIFIER    

upsDisplay 1.3.6.1.4.1.186.1.19.2.3.9
OBJECT IDENTIFIER    

upsAlarm 1.3.6.1.4.1.186.1.19.2.3.10
OBJECT IDENTIFIER    

upsPassword 1.3.6.1.4.1.186.1.19.2.3.11
OBJECT IDENTIFIER    

upsAgent 1.3.6.1.4.1.186.1.19.2.3.12
OBJECT IDENTIFIER    

upsConnectedClients 1.3.6.1.4.1.186.1.19.2.3.13
OBJECT IDENTIFIER    

upsEmail 1.3.6.1.4.1.186.1.19.2.3.14
OBJECT IDENTIFIER    

upsSNMP 1.3.6.1.4.1.186.1.19.2.3.15
OBJECT IDENTIFIER    

upsEMD 1.3.6.1.4.1.186.1.19.2.3.16
OBJECT IDENTIFIER    

upsTrap 1.3.6.1.4.1.186.1.19.2.3.21
OBJECT IDENTIFIER    

upsIdentManufacturer 1.3.6.1.4.1.186.1.19.2.3.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentTypeform 1.3.6.1.4.1.186.1.19.2.3.1.2
The UPS Typeform.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentSerialNumber 1.3.6.1.4.1.186.1.19.2.3.1.3
The UPS Serial Number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentMainFirmwareVersion 1.3.6.1.4.1.186.1.19.2.3.1.4
The UPS firmware version of the main controller.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentMainBootSectorVersion 1.3.6.1.4.1.186.1.19.2.3.1.5
The UPS boot sector version of the main controller.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentMainBootLoaderVersion 1.3.6.1.4.1.186.1.19.2.3.1.6
The UPS Boot Loader version of the main controller.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentJobNumber 1.3.6.1.4.1.186.1.19.2.3.1.7
The UPS Job Number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentTestPerson 1.3.6.1.4.1.186.1.19.2.3.1.8
The test person.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsIdentTestDate 1.3.6.1.4.1.186.1.19.2.3.1.9
The test date displayed as YYYYMMDD format.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsIdentHardwareBuildDate 1.3.6.1.4.1.186.1.19.2.3.1.10
The date that the UPS was built in YYYYMMDD format.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsIdentEEPROMVersion 1.3.6.1.4.1.186.1.19.2.3.1.11
The UPS Main controller's EEPROM version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentSysName 1.3.6.1.4.1.186.1.19.2.3.1.12
A string identifying the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentAttachedDevices 1.3.6.1.4.1.186.1.19.2.3.1.13
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsIdentInstallationDate 1.3.6.1.4.1.186.1.19.2.3.1.14
The UPS installation date in YYYYMMDD format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8)  

upsInputPowerSupplyConfiguration 1.3.6.1.4.1.186.1.19.2.3.2.1
This parameter summarizes the measured and collected data describing the input power supply.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER undefined(1), volt200Hz60(2), volt200Hz50(3), volt208Hz60(4), volt208Hz50(5), volt230Hz60(6), volt230Hz50(7), volt240Hz60(8), volt240Hz50(9), volt220Hz60(10), volt220Hz50(11), volt120Hz60(12), volt120Hz50(13), reserved0(14), reserved1(15), reserved2(16)  

upsInputNumLines 1.3.6.1.4.1.186.1.19.2.3.2.2
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER one(1), two(2)  

upsInputTable 1.3.6.1.4.1.186.1.19.2.3.2.3
A list of input table entries. The number of entries is given by the value of upsInputNumLine.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputEntry

upsInputEntry 1.3.6.1.4.1.186.1.19.2.3.2.3.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputEntry  

upsInputIndex 1.3.6.1.4.1.186.1.19.2.3.2.3.1.1
The input line identifier
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsInputFrequency 1.3.6.1.4.1.186.1.19.2.3.2.3.1.2
The present input frequency to the UPS system in 1/10 of Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputVoltage 1.3.6.1.4.1.186.1.19.2.3.2.3.1.3
The input utility line voltage in RMS volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputCurrent 1.3.6.1.4.1.186.1.19.2.3.2.3.1.4
The magnitude of the present input Current in 1/10 RMS Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputActivePower 1.3.6.1.4.1.186.1.19.2.3.2.4
The UPS active power in Watt. -1 if value is invalid.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputApparentPower 1.3.6.1.4.1.186.1.19.2.3.2.5
The input apparent power in Volt-Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputPowerFactor 1.3.6.1.4.1.186.1.19.2.3.2.6
Ratio of actual power to apparent power. -1 if value is invalid.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputRatedTable 1.3.6.1.4.1.186.1.19.2.3.2.7
A list of input table entries. The number of entries is given by the value of upsInputNumLine.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputRatedEntry

upsInputRatedEntry 1.3.6.1.4.1.186.1.19.2.3.2.7.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputRatedEntry  

upsInputSlotIndex 1.3.6.1.4.1.186.1.19.2.3.2.7.1.1
The input line identifier
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsInputRatedFrequency 1.3.6.1.4.1.186.1.19.2.3.2.7.1.2
The present rated input frequency of the UPS system in 1/10 of Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputRatedVoltage 1.3.6.1.4.1.186.1.19.2.3.2.7.1.3
The magnitude of the rated input voltage in RMS volts. This is set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsInputRatedCurrent 1.3.6.1.4.1.186.1.19.2.3.2.7.1.4
The magnitude of the rated input current in 1/10 RMS Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputOverVoltage 1.3.6.1.4.1.186.1.19.2.3.2.8
This is the maximum limit of the input voltage before the UPS enters the over voltage state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputOverVoltageRecoverylevel 1.3.6.1.4.1.186.1.19.2.3.2.9
The over voltage recovery level. It is the limit at which the UPS returns from over voltage state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputVoltagePercent 1.3.6.1.4.1.186.1.19.2.3.2.10
The input voltage displayed as a percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputCurrentPercent 1.3.6.1.4.1.186.1.19.2.3.2.11
The input current displayed as a percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputUnderVoltageDetectlevel 1.3.6.1.4.1.186.1.19.2.3.2.12
The input under voltage detection level in RMS volt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputUnderVoltageRecoverylevel 1.3.6.1.4.1.186.1.19.2.3.2.13
The input under voltage recovery level in RMS volt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputRatedActivePower 1.3.6.1.4.1.186.1.19.2.3.2.14
The rated input active power in Watt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputFreqWithErr 1.3.6.1.4.1.186.1.19.2.3.2.15
The input frequency configuration in 1/10 Hz when detection error occurred. This is set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER hz50(1), hz60(2)  

upsOutputPowerSupplyConfiguration 1.3.6.1.4.1.186.1.19.2.3.3.1
This parameter summarizes the measured and collected data describing the output power supply.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER undefined(1), volt200Hz60(2), volt200Hz50(3), volt208Hz60(4), volt208Hz50(5), volt230Hz60(6), volt230Hz50(7), volt240Hz60(8), volt240Hz50(9), volt220Hz60(10), volt220Hz50(11), volt120Hz60(12), volt120Hz50(13), reserved0(14), reserved1(15), reserved2(16)  

upsOutputNumLines 1.3.6.1.4.1.186.1.19.2.3.3.2
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER one(1), two(2)  

upsOutputTable 1.3.6.1.4.1.186.1.19.2.3.3.3
A list of Output table entries. The number of entries is given by the value of upsOutputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputEntry

upsOutputEntry 1.3.6.1.4.1.186.1.19.2.3.3.3.1
An entry containing information applicable to a particular Output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputEntry  

upsOutputIndex 1.3.6.1.4.1.186.1.19.2.3.3.3.1.1
The Output line identifier.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsOutputFrequency 1.3.6.1.4.1.186.1.19.2.3.3.3.1.2
The present output frequency of the UPS system in 1/10 of Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputVoltage 1.3.6.1.4.1.186.1.19.2.3.3.3.1.3
The Output voltage in RMS volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputCurrent 1.3.6.1.4.1.186.1.19.2.3.3.3.1.4
The magnitude of the present output current in 1/10 RMS Amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputActivePower 1.3.6.1.4.1.186.1.19.2.3.3.3.1.5
The present output active power in Watt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputApparentPower 1.3.6.1.4.1.186.1.19.2.3.3.3.1.6
The output apparent power in Volt-Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputLoadPercentage 1.3.6.1.4.1.186.1.19.2.3.3.4
The present UPS ouput load percentage which is current percent or active power whichever greater.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputRatedTable 1.3.6.1.4.1.186.1.19.2.3.3.5
A list of Output table entries. The number of entries is given by the value of upsOutputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputRatedEntry

upsOutputRatedEntry 1.3.6.1.4.1.186.1.19.2.3.3.5.1
An entry containing information applicable to a particular Output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputRatedEntry  

upsOutputSlotIndex 1.3.6.1.4.1.186.1.19.2.3.3.5.1.1
The Output line identifier.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsOutputRatedFrequency 1.3.6.1.4.1.186.1.19.2.3.3.5.1.2
The present output rated frequency of the UPS system in 1/10 of Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputRatedVoltage 1.3.6.1.4.1.186.1.19.2.3.3.5.1.3
The rated output voltage in RMS volts. This is set by the administrator
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsOutputRatedCurrent 1.3.6.1.4.1.186.1.19.2.3.3.5.1.4
The output rated current in 1/10 RMS Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputRatedActivePower 1.3.6.1.4.1.186.1.19.2.3.3.5.1.5
The output rated active power in Watt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputRatedApparentPower 1.3.6.1.4.1.186.1.19.2.3.3.5.1.6
The output rated apparent power in Volt-Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputUndervoltagelevel 1.3.6.1.4.1.186.1.19.2.3.3.6
This parameter displays the minimum allowable voltage before it falls into under voltage range.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputOverVoltagelevel 1.3.6.1.4.1.186.1.19.2.3.3.7
This is the maximum limit of the output voltage before the UPS enters the over voltage state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputFrequencySynchRange 1.3.6.1.4.1.186.1.19.2.3.3.8
The allowable range for synchronizing output frequency in 1/10 of Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputVoltageAdjust 1.3.6.1.4.1.186.1.19.2.3.3.9
This parameter allows UPS to be configured to have adjustable voltages. This is set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsOutputRatedPowerFactor 1.3.6.1.4.1.186.1.19.2.3.3.10
The rated output power factor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassPowerSupplyConfiguration 1.3.6.1.4.1.186.1.19.2.3.4.1
This parameter summarizes the measured and collected data describing the power supply into the bypass circuit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER undefined(1), volt200Hz60(2), volt200Hz50(3), volt208Hz60(4), volt208Hz50(5), volt230Hz60(6), volt230Hz50(7), volt240Hz60(8), volt240Hz50(9), volt220Hz60(10), volt220Hz50(11), volt120Hz60(12), volt120Hz50(13), reserved0(14), reserved1(15), reserved2(16)  

upsBypassNumLine 1.3.6.1.4.1.186.1.19.2.3.4.2
The number of bypass lines utilized in this device. This variable indicates the number of rows in the bypass table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER one(1), two(2)  

upsBypassTable 1.3.6.1.4.1.186.1.19.2.3.4.3
A list of Bypass table entries. The number of entries is given by the value of upsBypassNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBypassEntry

upsBypassEntry 1.3.6.1.4.1.186.1.19.2.3.4.3.1
An entry containing information applicable to a particular line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBypassEntry  

upsBypassIndex 1.3.6.1.4.1.186.1.19.2.3.4.3.1.1
The Bypass line identifier.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsBypassFrequency 1.3.6.1.4.1.186.1.19.2.3.4.3.1.2
The present Bypass frequency of the UPS system in 1/10 of Hz of each phase.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassVoltage 1.3.6.1.4.1.186.1.19.2.3.4.3.1.3
The Bypass utility line voltage in RMS volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassCurrent 1.3.6.1.4.1.186.1.19.2.3.4.3.1.4
The magnitude of the present bypass Current in 1/10 RMS Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassApparentPower 1.3.6.1.4.1.186.1.19.2.3.4.4
The Bypass Apparent power in Volt-Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassUnderVoltageDetectionlevel 1.3.6.1.4.1.186.1.19.2.3.4.5
This parameter displays the minimum allowable voltage before it falls into bypass undervoltage range.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassUnderVoltageRecoverylevel 1.3.6.1.4.1.186.1.19.2.3.4.6
This parameter displays the allowable voltage that it can recover from.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassOverVoltageDetectionlevel 1.3.6.1.4.1.186.1.19.2.3.4.7
This parameter displays the maximum allowable voltage before it falls into over voltage range.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassOverVoltageRecoverylevel 1.3.6.1.4.1.186.1.19.2.3.4.8
This parameter displays the allowable voltage that it can recover from.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDCBusTotalVoltage 1.3.6.1.4.1.186.1.19.2.3.5.1
The DC Bus voltage in DC volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDCBusPositiveVoltage 1.3.6.1.4.1.186.1.19.2.3.5.2
The DC Bus positive voltage in DC volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDCBusNegativeVoltage 1.3.6.1.4.1.186.1.19.2.3.5.3
The DC Bus negative voltage in DC volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDCBusRatedVoltage 1.3.6.1.4.1.186.1.19.2.3.5.4
The DC Bus rated voltage in DC volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryStatus 1.3.6.1.4.1.186.1.19.2.3.6.1
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6)  

upsSecondsOnBattery 1.3.6.1.4.1.186.1.19.2.3.6.2
If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatteryVoltage 1.3.6.1.4.1.186.1.19.2.3.6.3
The magnitude of the present battery voltage in DC Volt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryDischargeCurrent 1.3.6.1.4.1.186.1.19.2.3.6.4
The present battery discharge current in 1/10 DC Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryChargeStatus 1.3.6.1.4.1.186.1.19.2.3.6.5
The UPS charger status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER normal-charging(1), preventative-charging(2), stop-charging(3)  

upsBatteryNumberofDischarge 1.3.6.1.4.1.186.1.19.2.3.6.6
This will increment when ups goes into backup mode which is longer than 10 seconds.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatteryCalculatedShutdownVoltage 1.3.6.1.4.1.186.1.19.2.3.6.7
The battery's shutdown voltage in DC Volt.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryLifeRemaining 1.3.6.1.4.1.186.1.19.2.3.6.8
The number of hours of UPS operation in the present environment until the batteries must be replaced.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatteryRatedAmpereHour 1.3.6.1.4.1.186.1.19.2.3.6.9
The battery capacity in Amp-Hour.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryInSeries 1.3.6.1.4.1.186.1.19.2.3.6.10
The number of batteries in each string connected in series.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryInParallel 1.3.6.1.4.1.186.1.19.2.3.6.11
The number of batteries connected in parallel.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryInstallationDate 1.3.6.1.4.1.186.1.19.2.3.6.12
The battery installation date in YYYYMMDD format.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsBatteryVoltageShutdownLevel 1.3.6.1.4.1.186.1.19.2.3.6.13
The UPS battery voltage shutdown level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryExtTable 1.3.6.1.4.1.186.1.19.2.3.6.14
A list of Battery table entries.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBatteryExtEntry

upsBatteryExtEntry 1.3.6.1.4.1.186.1.19.2.3.6.14.1
An entry containing information applicable to a particular Battery.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBatteryExtEntry  

upsBatteryExtIndex 1.3.6.1.4.1.186.1.19.2.3.6.14.1.1
The Battery line identifier
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsBatteryExtInSeries 1.3.6.1.4.1.186.1.19.2.3.6.14.1.2
Specifies the number of batteries in the external cabinet that are connected in series.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryExtInParallel 1.3.6.1.4.1.186.1.19.2.3.6.14.1.3
Specifies the number of batteries in the external cabinet that are connected in parallel.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryExtRatedAmpereHour 1.3.6.1.4.1.186.1.19.2.3.6.14.1.4
The external battery's capacity in Amp-Hour.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryExtCRate 1.3.6.1.4.1.186.1.19.2.3.6.14.1.5
The external battery's C rate.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryExtInstallDate 1.3.6.1.4.1.186.1.19.2.3.6.14.1.6
The battery installation date in YYYYMMDD format.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsBatteryLowBattLevel 1.3.6.1.4.1.186.1.19.2.3.6.15
The low battery level of the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryChargerOverVoltageDelay 1.3.6.1.4.1.186.1.19.2.3.6.16
The UPS's charger over voltage detection delay in seconds.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryCalcLBLevel 1.3.6.1.4.1.186.1.19.2.3.6.17
The calculated low battery level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryCapacity 1.3.6.1.4.1.186.1.19.2.3.6.18
The UPS battery capacity in percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryRuntime 1.3.6.1.4.1.186.1.19.2.3.6.19
The UPS battery runtime in minutes. It will return -1 or N/A if not available.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgSystemTemperature 1.3.6.1.4.1.186.1.19.2.3.7.1
The UPS system temperature in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgBatteryTemperature 1.3.6.1.4.1.186.1.19.2.3.7.2
The UPS Battery temperature in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgPresentMode 1.3.6.1.4.1.186.1.19.2.3.7.3
The present mode of the UPS system.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER shutdown0(1), shutdown1(2), shutdown2(3), online(4), backup(5), battery-test(6), bypass6(7), bypass7(8), bypass8(9), startup(10)  

upsStsCtlCfgModeRequest 1.3.6.1.4.1.186.1.19.2.3.7.4
The mode of the UPS system requested by the user.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), shutdown(2), bypass(3), online(4), battery-test(5)  

upsStsCtlCfgModeTransitionTimer 1.3.6.1.4.1.186.1.19.2.3.7.5
The timer upon whose expiration a mode transition will be attempted by the system.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgEPOContactState 1.3.6.1.4.1.186.1.19.2.3.7.6
The EPO contact state of the UPS system.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(1), closed(2)  

upsStsCtlCfgRunStopSwitchState 1.3.6.1.4.1.186.1.19.2.3.7.7
The Run/Stop switch state of the UPS system.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER stop(1), run(2)  

upsStsCtlCfgServicePortCommStatus 1.3.6.1.4.1.186.1.19.2.3.7.8
The service port communication status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), normal-OK(2), off(3), error(4)  

upsStsCtlCfgInternalCommStatus 1.3.6.1.4.1.186.1.19.2.3.7.9
The internal communication status of the UPS system such as display panel.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), normal-OK(2), off(3), error(4)  

upsStsCtlCfgSecurityLevel 1.3.6.1.4.1.186.1.19.2.3.7.10
The current security level of the UPS system
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsStsCtlCfgPresentDate 1.3.6.1.4.1.186.1.19.2.3.7.11
The present date of the UPS. This is configurable by Administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgPresentTime 1.3.6.1.4.1.186.1.19.2.3.7.12
The present time of the UPS. This is configurable by Administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgPresentTimeStamp 1.3.6.1.4.1.186.1.19.2.3.7.13
Present system timestamp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgEnableRMTIToControlMode 1.3.6.1.4.1.186.1.19.2.3.7.14
Allow to enable or disable SNMP to control the UPS Shutdown and Online Mode.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgEnableStartupDelay 1.3.6.1.4.1.186.1.19.2.3.7.15
This delay timer, when enabled, will begin counting down at UPS startup immediately following a UPS shutdown by any means other than battery exhaustion. UPS output of any kind will be prohibited.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgStartUpDelayMode 1.3.6.1.4.1.186.1.19.2.3.7.16
UPS mode into which the UPS will transition at the expiration of the Start-Up delay timer.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER bypass(1), online(2)  

upsStsCtlCfgStartUpDelay 1.3.6.1.4.1.186.1.19.2.3.7.17
When the timer is counting down, its changing value is reflected, otherwise its starting value is reported.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgRemoteShutDownContactState 1.3.6.1.4.1.186.1.19.2.3.7.18
The state of the Remote Contacts Shutdown Control.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(1), closed(2)  

upsStsCtlCfgRemoteShutdownContactMode 1.3.6.1.4.1.186.1.19.2.3.7.19
The mode of the Remote Contacts Shutdown control.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER bypass(1), shutdown-while-contact-closed(2)  

upsStsCtlCfgEnableDryContactLANShutdown 1.3.6.1.4.1.186.1.19.2.3.7.20
When enable, UPS will accept LAN signal request for UPS shutdown but only in accordance with restrictions of the following timer.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgDryContactLANShutdownTimer 1.3.6.1.4.1.186.1.19.2.3.7.21
Timer begins upon input power recovery and during its lifetime, allows the LAN input signal to affect a UPS Shutdown control.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgDryContactOnBattDelay 1.3.6.1.4.1.186.1.19.2.3.7.22
Time delay between actual event occurrence and dry contact closure to signal external devices of the event.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgDryContactLowBattDelay 1.3.6.1.4.1.186.1.19.2.3.7.23
Delay timer between actual event occurrence and dry contact closure to signal external devices of the event.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsStsCtlCfgEnableStartupBattTest 1.3.6.1.4.1.186.1.19.2.3.7.24
Forces a battery test when UPS starts.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgEnableBatteryTest 1.3.6.1.4.1.186.1.19.2.3.7.25
Allow to enable or disable battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgBatteryTestConditionStatus 1.3.6.1.4.1.186.1.19.2.3.7.26
This notifies the user of the availability of the battery test feature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER battery-test-prohibited(1), battery-test-ok(2)  

upsStsCtlCfgMaxBatteryTestFreq 1.3.6.1.4.1.186.1.19.2.3.7.27
This specified how often the battery test should occur. This is set by the administrator
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER daily(1), weekly(2), monthly(3)  

upsStsCtlCfgEnableRestartAfterBattShutdown 1.3.6.1.4.1.186.1.19.2.3.7.28
Mode set for UPS input power detection immediately after a shutdown while on batteries. This is set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgRestartDelay 1.3.6.1.4.1.186.1.19.2.3.7.29
Countdown begins only when UPS input power is restored immediately following a UPS Shutdown while on batteries.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgEnableAutoTransferMode 1.3.6.1.4.1.186.1.19.2.3.7.30
This feature allows the administrators to enable or to disable the auto transfer feature of the UPS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsStsCtlCfgAutoRetransferDelay 1.3.6.1.4.1.186.1.19.2.3.7.31
Time period to wait after fault occurrence before attempting transfer back Online
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsStsCtlCfgServicePortCommSetting 1.3.6.1.4.1.186.1.19.2.3.7.32
The UPS baud rate settings.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER bd9600(1), bd19200(2), bd38400(3), bd57600(4)  

upsStsCtlCfgInvertRemoteShutdownLogic 1.3.6.1.4.1.186.1.19.2.3.7.33
Remote Shutdown logic.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER not-inverted(1), inverted(2)  

upsStsCtlCfgRestartMode 1.3.6.1.4.1.186.1.19.2.3.7.34
Restart Mode.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER bypass(1), online(2)  

upsHistorySysOperationTime 1.3.6.1.4.1.186.1.19.2.3.8.1
The amount of time the UPS has been on.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryInverterOperationTime 1.3.6.1.4.1.186.1.19.2.3.8.2
The amount of time the UPS has been in On-Line Mode.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryBackupOperationTime 1.3.6.1.4.1.186.1.19.2.3.8.3
The amount of time the UPS has been in BackUp Mode.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryLifetimeRemaining 1.3.6.1.4.1.186.1.19.2.3.8.4
The remaining lifetime of the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryHighestSystemTemp 1.3.6.1.4.1.186.1.19.2.3.8.5
The highest system temperature of the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsHistoryHighestBatteryTemp 1.3.6.1.4.1.186.1.19.2.3.8.6
The highest battery temperature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsHistoryTotalNumInputUnderVolt 1.3.6.1.4.1.186.1.19.2.3.8.7
Total number of times the UPS has entered under voltage state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumOverload 1.3.6.1.4.1.186.1.19.2.3.8.8
Total number of times the UPS has been overloaded.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumTest 1.3.6.1.4.1.186.1.19.2.3.8.9
Total number of tests that has been conducted on the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumBackup 1.3.6.1.4.1.186.1.19.2.3.8.10
Total number of times the UPS has been in Back-Up mode.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumFaults 1.3.6.1.4.1.186.1.19.2.3.8.11
Total number of faults that has occurred on the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumOperationModeChange 1.3.6.1.4.1.186.1.19.2.3.8.12
The number of mode changes that has occurred.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumWarnings 1.3.6.1.4.1.186.1.19.2.3.8.13
The number of warnings that has occurred on the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumSystemSettingsChanged 1.3.6.1.4.1.186.1.19.2.3.8.14
The number of times the System settings have been changed.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsHistoryTotalNumResets 1.3.6.1.4.1.186.1.19.2.3.8.15
The number of times the UPS has reset.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsDisplayFirmwareVersion 1.3.6.1.4.1.186.1.19.2.3.9.1
The firmware version of the display.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsDisplayBootSectorVersion 1.3.6.1.4.1.186.1.19.2.3.9.2
The boot sector version of the display.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsDisplayBootLoaderVersion 1.3.6.1.4.1.186.1.19.2.3.9.3
The boot loader version of the display.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsDisplaySleepTimer 1.3.6.1.4.1.186.1.19.2.3.9.4
The sleep timer for the display.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsDisplayBuzzerMode 1.3.6.1.4.1.186.1.19.2.3.9.5
Configures buzzer mode.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

upsDisplayBuzzerStatus 1.3.6.1.4.1.186.1.19.2.3.9.6
Shows the current state of the buzzer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), idle(2), sound(3), silenced(4)  

upsDisplayRMTIInstallDate 1.3.6.1.4.1.186.1.19.2.3.9.7
The RMTI installation date.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(8)  

upsDisplayRMTIInstallStatus 1.3.6.1.4.1.186.1.19.2.3.9.8
Shows the installation status of the RMTI.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER uninstalled(1), installed(2)  

upsDisplayRMTIBaudRate 1.3.6.1.4.1.186.1.19.2.3.9.9
Configures the baud rate.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER bd9600(1), bd19200(2), bd38400(3), bd57600(4)  



upsAlarmsPresent 1.3.6.1.4.1.186.1.19.2.3.10.1
The present number of active alarm conditions.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge32  

upsAlarmTable 1.3.6.1.4.1.186.1.19.2.3.10.2
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAlarmEntry

upsAlarmEntry 1.3.6.1.4.1.186.1.19.2.3.10.2.1
An entry containing information applicable to a particular alarm.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAlarmEntry  

upsAlarmId 1.3.6.1.4.1.186.1.19.2.3.10.2.1.1
An unique identifier for an alarm condition. This value must remain constant.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsAlarmDescr 1.3.6.1.4.1.186.1.19.2.3.10.2.1.2
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
Status: mandatory Access: read-only
OBJECT-TYPE    
  AutonomousType  

upsAlarmTime 1.3.6.1.4.1.186.1.19.2.3.10.2.1.3
The value of upsConfigSystemTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

upsWellKnownAlarms 1.3.6.1.4.1.186.1.19.2.3.10.3
OBJECT IDENTIFIER    

upsAlarmFault 1.3.6.1.4.1.186.1.19.2.3.10.3.1
Fault: One or more fault reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOpenFuse 1.3.6.1.4.1.186.1.19.2.3.10.3.2
Fault: An open fuse reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmCurrentLimitFault 1.3.6.1.4.1.186.1.19.2.3.10.3.3
Fault: A current limit reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCBusOverCurrent 1.3.6.1.4.1.186.1.19.2.3.10.3.4
Fault: A DC bus overcurrent reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCOverVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.5
Fault: A DC bus overvoltage repoprted.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCBusImbalance 1.3.6.1.4.1.186.1.19.2.3.10.3.6
Fault: A DC bus imbalance reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputUnderVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.7
Fault: An inverter output undervoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOverVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.8
Fault: An inverter output overvoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmHeatSinkOverheat 1.3.6.1.4.1.186.1.19.2.3.10.3.9
Fault: Heat sink or device overheat reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassOverload 1.3.6.1.4.1.186.1.19.2.3.10.3.10
Fault: A bypass overload reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmChargerOverVoltageFault 1.3.6.1.4.1.186.1.19.2.3.10.3.11
Fault: Charger overvoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOverCurrent 1.3.6.1.4.1.186.1.19.2.3.10.3.12
Fault: A output overcurrent reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCUnderVoltAtBoostUp 1.3.6.1.4.1.186.1.19.2.3.10.3.13
Fault: A DC bus undervoltage reported during DC bus boost-up.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCUnderVoltAtCharge 1.3.6.1.4.1.186.1.19.2.3.10.3.14
Fault: A DC bus undervoltage during DC bus charging reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassOverheat 1.3.6.1.4.1.186.1.19.2.3.10.3.15
Fault: A bypass Overheat reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmResettableInverterOverload 1.3.6.1.4.1.186.1.19.2.3.10.3.16
Fault: An inverter overload reported. It is resetable.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUnresettableInverterOverload 1.3.6.1.4.1.186.1.19.2.3.10.3.17
Fault: An inverter overload reported. It is not resetable.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputOverVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.18
Warning: An input overvoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputUnderVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.19
Warning: An input undervoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputFrequencyError 1.3.6.1.4.1.186.1.19.2.3.10.3.20
Warning: An input frequency error reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassOverVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.21
Warning: A bypass overvoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassUnderVoltage 1.3.6.1.4.1.186.1.19.2.3.10.3.22
Warning: A bypass undervoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassFrequencyError 1.3.6.1.4.1.186.1.19.2.3.10.3.23
Warning: An bypass frequency error reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDCBusUnderVoltAtBattTest 1.3.6.1.4.1.186.1.19.2.3.10.3.24
Warning: A DC bus undervoltage reported during battery test
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryLow 1.3.6.1.4.1.186.1.19.2.3.10.3.25
Warning: A Low battery reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryAtShutdownlevel 1.3.6.1.4.1.186.1.19.2.3.10.3.26
Warning: A Battery shutdown voltage level reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmReplaceBattery 1.3.6.1.4.1.186.1.19.2.3.10.3.27
Warning: Batteries are in need of replacement.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmChargerOverVoltageWarning 1.3.6.1.4.1.186.1.19.2.3.10.3.28
Warning: Charger overvoltage reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryTestFailed 1.3.6.1.4.1.186.1.19.2.3.10.3.29
Warning: A battery test failed event reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryDepleted 1.3.6.1.4.1.186.1.19.2.3.10.3.30
Warning: A battery depleted event reported. It will not be able to support critical loads.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryOverheat 1.3.6.1.4.1.186.1.19.2.3.10.3.31
Warning: A Battery overheat reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmSystemOverheat 1.3.6.1.4.1.186.1.19.2.3.10.3.32
Warning: A system overheat reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOverloadWarning 1.3.6.1.4.1.186.1.19.2.3.10.3.33
Warning: An inverter output overload reported. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmCurrentLimitWarning 1.3.6.1.4.1.186.1.19.2.3.10.3.34
Warning: A current limit reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAsyncOperation 1.3.6.1.4.1.186.1.19.2.3.10.3.35
Warning: An Asynchronous operation reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmServiceUPS 1.3.6.1.4.1.186.1.19.2.3.10.3.36
Warning: UPS is in need of service. Please contact authorized Toshiba service center for assistance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryNearExpiration 1.3.6.1.4.1.186.1.19.2.3.10.3.37
Warning: Batteries are nearing the end of their expected lifetime.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryExpired 1.3.6.1.4.1.186.1.19.2.3.10.3.38
Warning: Batteries have reached their expected lifetime.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDisplayCableError 1.3.6.1.4.1.186.1.19.2.3.10.3.39
Warning: A display cable error reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmRemotEyeCommError 1.3.6.1.4.1.186.1.19.2.3.10.3.40
Warning: A Communication error between the main control and the RemotEye reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmRemotEyeUplinkCommError 1.3.6.1.4.1.186.1.19.2.3.10.3.41
Warning: A communication error between the RemotEye III and the network reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmServicePortCommError 1.3.6.1.4.1.186.1.19.2.3.10.3.42
Warning: A communication error between the main controller and the service communication port reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDispCommError 1.3.6.1.4.1.186.1.19.2.3.10.3.43
Warning: A communication error between the main controller and display controller reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmSystemTestFailed 1.3.6.1.4.1.186.1.19.2.3.10.3.44
Warning: A system test failed event reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassOn 1.3.6.1.4.1.186.1.19.2.3.10.3.45
Warning: The UPS is in Stop (Bypass) mode
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPowerFailure 1.3.6.1.4.1.186.1.19.2.3.10.3.46
Info: A power failure reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShutdownPending 1.3.6.1.4.1.186.1.19.2.3.10.3.47
Info: An output shutdown in progress reported. Output will turn off after delay.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOffAsRequested 1.3.6.1.4.1.186.1.19.2.3.10.3.48
Info: An output shutdown mode requested.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOff 1.3.6.1.4.1.186.1.19.2.3.10.3.49
Info: An output off reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryTestInProgress 1.3.6.1.4.1.186.1.19.2.3.10.3.50
Info: A battery test in progress reported.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryOn 1.3.6.1.4.1.186.1.19.2.3.10.3.51
Info: The UPS is on Battery mode; it is supplying output power from its batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDSensor1AlarmTriggered 1.3.6.1.4.1.186.1.19.2.3.10.3.52
Info: EMD sensor 1 alarm is triggered.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDSensor2AlarmTriggered 1.3.6.1.4.1.186.1.19.2.3.10.3.53
Info: EMD sensor 2 alarm is triggered.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDHumidityAtLowCriticalPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.54
Info: EMD humidity is at low critical point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDHumidityAtHighCriticalPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.55
Info: EMD humidity is at high critical point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDHumidityAtLowWarningPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.56
Info: EMD humidity is at low warning point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDHumidityAtHighWarningPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.57
Info: EMD humidity is at high warning point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDTemperatureAtLowCriticalPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.58
Info: EMD Temperature is at low critical point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDTemperatureAtHighCriticalPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.59
Info: EMD Temperature is at high critical point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDTemperatureAtLowWarningPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.60
Info: EMD Temperature is at low warning point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEMDTemperatureAtHighWarningPoint 1.3.6.1.4.1.186.1.19.2.3.10.3.61
Info: EMD Temperature is at high warning point.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmLogInError 1.3.6.1.4.1.186.1.19.2.3.10.3.62
Info: Username/Password information is incorrect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsPwdAdminCurrentAccessLevel 1.3.6.1.4.1.186.1.19.2.3.11.1
The administrator access level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsPwdAdminCurrentLogin 1.3.6.1.4.1.186.1.19.2.3.11.2
The administrator access login name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsPwdAdminNewLoginAccess 1.3.6.1.4.1.186.1.19.2.3.11.3
The administrator access login name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsPwdAdminCurrentPswd 1.3.6.1.4.1.186.1.19.2.3.11.4
The current password.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsPwdAdminNewPswd 1.3.6.1.4.1.186.1.19.2.3.11.5
The current password.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..7)  

upsAgentSoftwareVersion 1.3.6.1.4.1.186.1.19.2.3.12.1
The RemotEye III version number
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsAgentHardwareAddress 1.3.6.1.4.1.186.1.19.2.3.12.2
The hardware/MAC address that NMS can identify the managed device
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(20)  

upsAgentIPAddress 1.3.6.1.4.1.186.1.19.2.3.12.3
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentGatewayAddress 1.3.6.1.4.1.186.1.19.2.3.12.4
The default gateway that allow device managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentSubnetMask 1.3.6.1.4.1.186.1.19.2.3.12.5
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentDate 1.3.6.1.4.1.186.1.19.2.3.12.6
The date in agent, format is MM/DD/YYYY.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10)  

upsAgentTime 1.3.6.1.4.1.186.1.19.2.3.12.7
The time in agent, format is HH:MM:SS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8)  

upsAgentGeneralRecordLogFrequency 1.3.6.1.4.1.186.1.19.2.3.12.8
The interval frequency of the general record log. The value is in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 5..28800  

upsAgentPollingRate 1.3.6.1.4.1.186.1.19.2.3.12.9
The frequency that proxy agent polls the connected UPS in RemotEye III protocols.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..999  

upsAgentDHCPControl 1.3.6.1.4.1.186.1.19.2.3.12.10
Enable or disable DHCP/BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentTelnetControl 1.3.6.1.4.1.186.1.19.2.3.12.11
Enable or disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentTFTPControl 1.3.6.1.4.1.186.1.19.2.3.12.12
Enable or disable network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentResetToDefault 1.3.6.1.4.1.186.1.19.2.3.12.13
Reset all parameters of REMOTEYE III to default value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentRestart 1.3.6.1.4.1.186.1.19.2.3.12.14
Restart REMOTEYE III
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentSystemName 1.3.6.1.4.1.186.1.19.2.3.12.15
The Agent System name
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsAgentSystemContact 1.3.6.1.4.1.186.1.19.2.3.12.16
Contact Information
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsAgentSystemLocation 1.3.6.1.4.1.186.1.19.2.3.12.17
Agent Location
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsAgentDefaultLanguage 1.3.6.1.4.1.186.1.19.2.3.12.18
Current Default Language
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), english(2)  

upsAgentClearGeneralHistory 1.3.6.1.4.1.186.1.19.2.3.12.19
Clear general history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearTestHistory 1.3.6.1.4.1.186.1.19.2.3.12.20
Clear test history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearBackupHistory 1.3.6.1.4.1.186.1.19.2.3.12.21
Clear Backup history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearFaultHistory 1.3.6.1.4.1.186.1.19.2.3.12.22
Clear Fault history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearOperationModeHistory 1.3.6.1.4.1.186.1.19.2.3.12.23
Clear operation mode history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearWarningHistory 1.3.6.1.4.1.186.1.19.2.3.12.24
Clear warning history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearSystemsettingsChangeHistory 1.3.6.1.4.1.186.1.19.2.3.12.25
Clear System settings change history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAgentClearRMTIEventHistory 1.3.6.1.4.1.186.1.19.2.3.12.26
Clear RemotEye Event History log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsConnectedClientsNum 1.3.6.1.4.1.186.1.19.2.3.13.1
The count of clients which have registered for UPS Shutdown control.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsConnectedClientsTable 1.3.6.1.4.1.186.1.19.2.3.13.2
The devices powered by UPS and registered to RemotEye III
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsConnectedClientsEntry

upsConnectedClientsEntry 1.3.6.1.4.1.186.1.19.2.3.13.2.1
The devices protected by RemotEye III
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsConnectedClientsEntry  

upsConnectedClientsIndex 1.3.6.1.4.1.186.1.19.2.3.13.2.1.1
The index of the device that is plugged into the UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsConnectedClientsIPAddress 1.3.6.1.4.1.186.1.19.2.3.13.2.1.2
The ip address of the device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

upsConnectedClientsName 1.3.6.1.4.1.186.1.19.2.3.13.2.1.3
The name/description of the device plugged into the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsConnectedClientsTimeAtConnection 1.3.6.1.4.1.186.1.19.2.3.13.2.1.4
The time that the device registered to REMOTEYE III
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsConnectedClientsShutdownDelay 1.3.6.1.4.1.186.1.19.2.3.13.2.1.5
The shutdown delay set on REMOTEYE III
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsConnectedClientsConnectionTimeout 1.3.6.1.4.1.186.1.19.2.3.13.2.1.6
The device timeout counter. Unit: 10 seconds
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConnectedClientsShutdownTest 1.3.6.1.4.1.186.1.19.2.3.13.2.1.7
The client will shutdown test after receive shutdown request from REMOTEYE III.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEmailMailServer 1.3.6.1.4.1.186.1.19.2.3.14.1
The Email mail server for REMOTEYE III.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEmailUserAccount 1.3.6.1.4.1.186.1.19.2.3.14.2
The Email mail server login name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsEmailUserPassword 1.3.6.1.4.1.186.1.19.2.3.14.3
The Email mail server password.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsEmailDomainName 1.3.6.1.4.1.186.1.19.2.3.14.4
The Email mail server domain name
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEmailDNSServer 1.3.6.1.4.1.186.1.19.2.3.14.5
The Email DNS server name
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEmailStatusReportSendTime 1.3.6.1.4.1.186.1.19.2.3.14.6
The Email Status Report Send Time
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(6)  

upsEmailClientsTable 1.3.6.1.4.1.186.1.19.2.3.14.7
The email addresses that RemotEye III will send logs and status reports to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsEmailClientsEntry

upsEmailClientsEntry 1.3.6.1.4.1.186.1.19.2.3.14.7.1
The email addresses that RemotEye III will send logs and status reports to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsEmailClientsEntry  

upsEmailClientsIndex 1.3.6.1.4.1.186.1.19.2.3.14.7.1.1
The index of the email clients.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsEmailClientsEmailAddress 1.3.6.1.4.1.186.1.19.2.3.14.7.1.2
The email address of the clients.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..128)  

upsEmailClientsDescription 1.3.6.1.4.1.186.1.19.2.3.14.7.1.3
The name/description of the clients.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEmailClientsDailyStatusReportType 1.3.6.1.4.1.186.1.19.2.3.14.7.1.4
The type of daily information that clients would like to receive.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER general-test(1), test-records(2), backup-Records(3), fault-Records(4), operation-Mode-Records(5), warning-Records(6), system-Setting-Change-Record(7), remotEye-III-Events-Log(8)  

upsEmailClientsEventStatusReportType 1.3.6.1.4.1.186.1.19.2.3.14.7.1.5
The type of event information that clients would like to receive when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER general-test(1), test-records(2), backup-Records(3), fault-Records(4), operation-Mode-Records(5), warning-Records(6), system-Setting-Change-Record(7), remotEye-III-Events-Log(8)  

upsEmailClientsInfoLevel 1.3.6.1.4.1.186.1.19.2.3.14.7.1.6
The type of information that clients would like to receive.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER fault(1), warning(2), informational(3)  

upsSNMPVersion 1.3.6.1.4.1.186.1.19.2.3.15.1
The SNMP version
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER disable(1), snmpv1(2), snmpv3(3)  

upsSNMPTrapsReceiversTable 1.3.6.1.4.1.186.1.19.2.3.15.2
A list of managers to send traps to. The number of entries is given by the value of upsSNMPNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsSNMPTrapsReceiversEntry

upsSNMPTrapsReceiversEntry 1.3.6.1.4.1.186.1.19.2.3.15.2.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsSNMPTrapsReceiversEntry  

upsSNMPTrapsReceiversIndex 1.3.6.1.4.1.186.1.19.2.3.15.2.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsSNMPTrapsReceiversIPAddress 1.3.6.1.4.1.186.1.19.2.3.15.2.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsSNMPTrapReceiversCommunityString 1.3.6.1.4.1.186.1.19.2.3.15.2.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

upsSNMPTrapReceiversTrapType 1.3.6.1.4.1.186.1.19.2.3.15.2.1.4
The trap group that NMS desired.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), toshiba-trap(2), jema-trap(3), rfc1628-trap(4)  

upsSNMPTrapReceiversInfoReceivingSeverityLevel 1.3.6.1.4.1.186.1.19.2.3.15.2.1.5
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), fault(3)  

upsSNMPTrapReceiversDescription 1.3.6.1.4.1.186.1.19.2.3.15.2.1.6
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsSNMPCommunitiesTable 1.3.6.1.4.1.186.1.19.2.3.15.3
A list of managers which can access REMOTEYE III with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsSNMPCommunitiesEntry

upsSNMPCommunitiesEntry 1.3.6.1.4.1.186.1.19.2.3.15.3.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsSNMPCommunitiesEntry  

upsSNMPCommunitiesIndex 1.3.6.1.4.1.186.1.19.2.3.15.3.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsSNMPCommunitiesIPAddress 1.3.6.1.4.1.186.1.19.2.3.15.3.1.2
The IP address of the manager to access REMOTEYE III
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsSNMPCommunitiesAccessString 1.3.6.1.4.1.186.1.19.2.3.15.3.1.3
The community name to use in the manager when access REMOTEYE III
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

upsSNMPCommunitiesAccessMode 1.3.6.1.4.1.186.1.19.2.3.15.3.1.4
Access type, only read/Write access type can change parameter of REMOTEYE III
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), read-write(2), notAccess(3)  

upsEMDType 1.3.6.1.4.1.186.1.19.2.3.16.1
The name assign to specific EMD.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsEMDTemperature 1.3.6.1.4.1.186.1.19.2.3.16.2
The EMD temperature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureLowWarningSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.3
The EMD temperature low warning set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureLowCriticalSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.4
The EMD temperature low critical set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureHighWarningSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.5
The EMD temperature high warning set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureHighCriticalSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.6
The EMD temperature high critical set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureHysteresis 1.3.6.1.4.1.186.1.19.2.3.16.7
The EMD temperature hysteresis.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDTemperatureCalibrationOffset 1.3.6.1.4.1.186.1.19.2.3.16.8
The EMD temperature calibration offset.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidity 1.3.6.1.4.1.186.1.19.2.3.16.9
The EMD Humidity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityLowWarningSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.10
The EMD Humidity low warning set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityLowCriticalSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.11
The EMD Humidity low critical set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityHighWarningSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.12
The EMD Humidity high warning set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityHighCriticalSetPoint 1.3.6.1.4.1.186.1.19.2.3.16.13
The EMD Humidity high critical set point.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityHysteresis 1.3.6.1.4.1.186.1.19.2.3.16.14
The EMD Humidity hysteresis.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDHumidityCalibrationOffset 1.3.6.1.4.1.186.1.19.2.3.16.15
The EMD Humidity calibration offset.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDR1Status 1.3.6.1.4.1.186.1.19.2.3.16.16
The EMD dry contact 1 status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), active(3), inactive(4)  

upsEMDAlarmR1Enable 1.3.6.1.4.1.186.1.19.2.3.16.17
The EMD contact R1 alarm enable setting.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), normalClose(2), normalOpen(3), highActive(4), lowActive(5)  

upsEMDAlarmR1Hysteresis 1.3.6.1.4.1.186.1.19.2.3.16.18
The EMD Contact R1 alarm hysteresis.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEMDR2Status 1.3.6.1.4.1.186.1.19.2.3.16.19
The EMD dry contact 2 status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), active(3), inactive(4)  

upsEMDAlarmR2Enable 1.3.6.1.4.1.186.1.19.2.3.16.20
The EMD contact R2 alarm enable setting.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), normalClose(2), normalOpen(3), highActive(4), lowActive(5)  

upsEMDAlarmR2Hysteresis 1.3.6.1.4.1.186.1.19.2.3.16.21
The EMD Contact R2 alarm hysteresis.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsTrapFault 1
Fault: One or more fault reported.
TRAP-TYPE    

upsTrapFaultClear 2
Fault Clear: One or more fault reported.
TRAP-TYPE    

upsTrapOpenFuse 3
Fault: An open fuse reported.
TRAP-TYPE    

upsTrapOpenFuseClear 4
Fault Clear: An open fuse reported.
TRAP-TYPE    

upsTrapCurrentLimitFault 5
Fault: A current limit fault reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapCurrentLimitFaultClear 6
Fault Clear: A current limit fault reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusOverCurrent 7
Fault: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusOverCurrentClear 8
Fault Clear: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusOverVoltage 9
Fault: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusOverVoltageClear 10
Fault Clear: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusImbalance 11
Fault: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapDCBusImbalanceClear 12
Fault Clear: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapOutputUnderVoltage 13
Fault: An output undervoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapOutputUnderVoltageClear 14
Fault Clear: An output undervoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapOutputOverVoltage 15
Fault: An output overvoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapOutputOverVoltageClear 16
Fault Clear: An output overvoltage reported. Contact your Toshiba authorized service center for examination.
TRAP-TYPE    

upsTrapHeatSinkOverheat 17
Fault: A Heat sink or device overheat reported.
TRAP-TYPE    

upsTrapHeatSinkOverheatClear 18
Fault Clear: A Heat sink or device overheat reported.
TRAP-TYPE    

upsTrapBypassOverload 19
Fault: A bypass overload reported.
TRAP-TYPE    

upsTrapBypassOverloadClear 20
Fault Clear: A bypass overload reported.
TRAP-TYPE    

upsTrapChargerOvervoltageFault 21
Warning: Charger overvoltage reported.
TRAP-TYPE    

upsTrapChargerOvervoltageFaultClear 22
Warning Clear: Charger overvoltage reported.
TRAP-TYPE    

upsTrapOutputOvercurrent 23
Warning: An output overcurrent reported.
TRAP-TYPE    

upsTrapOutputOvercurrentClear 24
Warning Clear: An output overcurrent reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtBoostUp 25
Fault: A DC bus undervoltage during boost-up reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtBoostUpClear 26
Fault Clear: A DC bus undervoltage during boost-up reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtCharge 27
Fault: A DC bus undervoltage during charging reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtChargeClear 28
Fault Clear: A DC bus undervoltage during charging reported.
TRAP-TYPE    

upsTrapBypassOverheat 29
Fault: A Bypass overheat reported.
TRAP-TYPE    

upsTrapBypassOverheatClear 30
Fault Clear: A Bypass overheat reported.
TRAP-TYPE    

upsTrapResettableInverterOverload 31
Fault: An inverter overload reported. It is resettable.
TRAP-TYPE    

upsTrapResettableInverterOverloadClear 32
Fault Clear: An inverter overload reported. It is resettable.
TRAP-TYPE    

upsTrapUnResettableInverterOverload 33
Fault: An inverter overload reported. It is not resettable.
TRAP-TYPE    

upsTrapUnResettableInverterOverloadClear 34
Fault Clear: An inverter overload reported. It is not resettable.
TRAP-TYPE    

upsTrapInputOverVoltage 35
Warning: An input overvoltage reported.
TRAP-TYPE    

upsTrapInputOverVoltageClear 36
Warning Clear: An input overvoltage reported.
TRAP-TYPE    

upsTrapInputUnderVoltage 37
Warning: An input undervoltage reported.
TRAP-TYPE    

upsTrapInputUnderVoltageClear 38
Warning Clear: An input undervoltage reported.
TRAP-TYPE    

upsTrapInputFrequencyError 39
Warning: An input frequency error reported.
TRAP-TYPE    

upsTrapInputFrequencyErrorClear 40
Warning Clear: An input frequency error reported.
TRAP-TYPE    

upsTrapBypassOverVoltage 41
Warning: A bypass overvoltage reported.
TRAP-TYPE    

upsTrapBypassOverVoltageClear 42
Warning Clear: A bypass overvoltage reported.
TRAP-TYPE    

upsTrapBypassUnderVoltage 43
Warning: A bypass undervoltage reported.
TRAP-TYPE    

upsTrapBypassUnderVoltageClear 44
Warning Clear: A bypass undervoltage reported.
TRAP-TYPE    

upsTrapBypassFrequencyError 45
Warning: A bypass frequency error reported.
TRAP-TYPE    

upsTrapBypassFrequencyErrorClear 46
Warning Clear: A bypass frequency error reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtTest 47
Warning: A DC bus undervoltage during battery test reported.
TRAP-TYPE    

upsTrapDCUnderVoltageAtTestClear 48
Warning Clear: A DC bus undervoltage during battery test reported.
TRAP-TYPE    

upsTrapBatteryLow 49
Warning: A low battery level reported.
TRAP-TYPE    

upsTrapBatteryLowClear 50
Warning Clear: A low battery level reported.
TRAP-TYPE    

upsTrapBatteryAtShutdownlevel 51
Warning: A shutdown battery level reported.
TRAP-TYPE    

upsTrapBatteryAtShutdownlevelClear 52
Warning Clear: A shutdown battery level reported.
TRAP-TYPE    

upsTrapReplaceBattery 53
Warning: A replacement of batteries reported.
TRAP-TYPE    

upsTrapReplaceBatteryClear 54
Warning Clear: A replacement of batteries reported.
TRAP-TYPE    

upsTrapChargerOverVoltageWarning 55
Warning: A charger overvoltage reported.
TRAP-TYPE    

upsTrapChargerOverVoltageWarningClear 56
Warning Clear: A charger overvoltage reported.
TRAP-TYPE    

upsTrapBatteryTestFailed 57
Warning: A battery test failed event reported.
TRAP-TYPE    

upsTrapBatteryTestFailedClear 58
Warning Clear: A battery test failed event reported.
TRAP-TYPE    

upsTrapBatteryDepleted 59
Warning: A battery depleted event reported.
TRAP-TYPE    

upsTrapBatteryDepletedClear 60
Warning Clear: A battery depleted event reported.
TRAP-TYPE    

upsTrapBatteryOverheat 61
Warning: A battery overheat reported.
TRAP-TYPE    

upsTrapBatteryOverheatClear 62
Warning Clear: A battery overheat reported.
TRAP-TYPE    

upsTrapSystemOverheat 63
Warning: A system overheat reported.
TRAP-TYPE    

upsTrapSystemOverheatClear 64
Warning Clear: A system overheat reported.
TRAP-TYPE    

upsTrapOutputOverloadWarning 65
Warning: An output overload reported.
TRAP-TYPE    

upsTrapOutputOverloadWarningClear 66
Warning Clear: An output overload reported.
TRAP-TYPE    

upsTrapCurrentLimitWarning 67
Warning: A current limit reported.
TRAP-TYPE    

upsTrapCurrentLimitWarningClear 68
Warning Clear: A current limit reported.
TRAP-TYPE    

upsTrapAsyncOperation 69
Warning: An Asynchronous operation reported.
TRAP-TYPE    

upsTrapAsyncOperationClear 70
Warning Clear: An Asynchronous operation reported.
TRAP-TYPE    

upsTrapServiceUPS 71
Warning: UPS is in need of service.
TRAP-TYPE    

upsTrapServiceUPSClear 72
Warning Clear: UPS is in need of service.
TRAP-TYPE    

upsTrapBatteryNearExpiration 73
Warning: A near expiration of batteries reported.
TRAP-TYPE    

upsTrapBatteryNearExpirationClear 74
Warning Clear: A near expiration of batteries reported.
TRAP-TYPE    

upsTrapBatteryExpired 75
Warning: A expiration of batteries reported.
TRAP-TYPE    

upsTrapBatteryExpiredClear 76
Warning Clear: A expiration of batteries reported.
TRAP-TYPE    

upsTrapDisplayCableError 77
Warning: A display cable error reported.
TRAP-TYPE    

upsTrapDisplayCableErrorClear 78
Warning Clear: A display cable error reported.
TRAP-TYPE    

upsTrapRemotEyeCommError 79
Warning: A communication error between the main control and the RemotEye III reported.
TRAP-TYPE    

upsTrapRemotEyeCommErrorClear 80
Warning Clear: A communication error between the main control and the RemotEye III reported.
TRAP-TYPE    

upsTrapRemotEyeUplinkCommError 81
Warning: A communication error between the RemotEye III and the network reported.
TRAP-TYPE    

upsTrapRemotEyeUplinkCommErrorClear 82
Warning Clear: A communication error between the RemotEye III and the network reported.
TRAP-TYPE    

upsTrapServicePortCommError 83
Warning: A communication error between the main controller and the service port reported.
TRAP-TYPE    

upsTrapServicePortCommErrorClear 84
Warning Clear: A communication error between the main controller and the service port reported.
TRAP-TYPE    

upsTrapDispCommError 85
Warning: A communication error between the main controller and the display controller reported.
TRAP-TYPE    

upsTrapDispCommErrorClear 86
Warning Clear: A communication error between the main controller and the display controller reported.
TRAP-TYPE    

upsTrapSystemTestFailed 87
Warning: A system test failed event reported.
TRAP-TYPE    

upsTrapSystemTestFailedClear 88
Warning Clear: A system test failed event reported.
TRAP-TYPE    

upsTrapBypassOn 89
Warning: The UPS is in Stop (Bypass) mode.
TRAP-TYPE    

upsTrapBypassOnClear 90
Warning Clear: The UPS is in Stop (Bypass) mode.
TRAP-TYPE    

upsTrapPowerFailure 91
Info: A power failure reported.
TRAP-TYPE    

upsTrapPowerFailureClear 92
Info Clear: A power failure reported.
TRAP-TYPE    

upsTrapShutdownPending 93
Info: A output shutdown in progress reported. Output will turn off after delay.
TRAP-TYPE    

upsTrapShutdownPendingClear 94
Info Clear: A output shutdown in progress reported. Output will turn off after delay.
TRAP-TYPE    

upsTrapOutputOffAsRequested 95
Info: An output shutdown mode requested.
TRAP-TYPE    

upsTrapOutputOffAsRequestedClear 96
Info Clear: An output shutdown mode requested.
TRAP-TYPE    

upsTrapOutputOff 97
Info: The UPS system output is off.
TRAP-TYPE    

upsTrapOutputOffClear 98
Info Clear: The UPS system output is off.
TRAP-TYPE    

upsTrapBatteryTestInProgress 99
Info: A battery test in progress reported.
TRAP-TYPE    

upsTrapBatteryTestInProgressClear 100
Info Clear: A battery test in progress reported.
TRAP-TYPE    

upsTrapBatteryOn 101
Info: The UPS is on Battery mode; it is supplying output power from its batteries.
TRAP-TYPE    

upsTrapBatteryOnClear 102
Info Clear: The UPS is on Battery mode; it is supplying output power from its batteries.
TRAP-TYPE    

upsTrapEMDSensor1AlarmTriggered 103
Warning: EMD sensor 1 alarm is triggered.
TRAP-TYPE    

upsTrapEMDSensor1AlarmTriggeredClear 104
Warning Clear: EMD sensor 1 alarm is triggered.
TRAP-TYPE    

upsTrapEMDSensor2AlarmTriggered 105
Warning: EMD sensor 2 alarm is triggered.
TRAP-TYPE    

upsTrapEMDSensor2AlarmTriggeredClear 106
Warning Clear: EMD sensor 2 alarm is triggered.
TRAP-TYPE    

upsTrapEMDHumidityAtLowCiriticalPoint 107
Warning: EMD humidity is at low critical point.
TRAP-TYPE    

upsTrapEMDHumidityAtLowCiriticalPointClear 108
Warning Clear: EMD humidity is at low critical point.
TRAP-TYPE    

upsTrapEMDHumidityAtHighCiriticalPoint 109
Warning: EMD humidity is at high critical point.
TRAP-TYPE    

upsTrapEMDHumidityAtHighCiriticalPointClear 110
Warning Clear: EMD humidity is at high critical point.
TRAP-TYPE    

upsTrapEMDHumidityAtLowWarningPoint 111
Warning: EMD humidity is at low warning point.
TRAP-TYPE    

upsTrapEMDHumidityAtLowWarningPointClear 112
Warning Clear: EMD humidity is at low warning point.
TRAP-TYPE    

upsTrapEMDHumidityAtHighWarningPoint 113
Warning: EMD humidity is at high warning point.
TRAP-TYPE    

upsTrapEMDHumidityAtHighWarningPointClear 114
Warning Clear: EMD humidity is at high warning point.
TRAP-TYPE    

upsTrapEMDTemperatureAtLowCiriticalPoint 115
Warning: EMD Temperature is at low critical point.
TRAP-TYPE    

upsTrapEMDTemperatureAtLowCiriticalPointClear 116
Warning Clear: EMD Temperature is at low critical point.
TRAP-TYPE    

upsTrapEMDTemperatureAtHighCiriticalPoint 117
Warning: EMD Temperature is at high critical point.
TRAP-TYPE    

upsTrapEMDTemperatureAtHighCiriticalPointClear 118
Warning Clear: EMD Temperature is at high critical point.
TRAP-TYPE    

upsTrapEMDTemperatureAtLowWarningPoint 119
Warning: EMD Temperature is at low warning point.
TRAP-TYPE    

upsTrapEMDTemperatureAtLowWarningPointClear 120
Warning Clear: EMD Temperature is at low warning point.
TRAP-TYPE    

upsTrapEMDTemperatureAtHighWarningPoint 121
Warning: EMD Temperature is at high warning point.
TRAP-TYPE    

upsTrapEMDTemperatureAtHighWarningPointClear 122
Warning Clear: EMD Temperature is at high warning point.
TRAP-TYPE    

upsTrapLogInError 123
Info: Username/Password information is incorrect.
TRAP-TYPE    

upsTrapLogInErrorClear 124
Info Clear: Username/Password information is incorrect.
TRAP-TYPE