TOSHIBAUPS-MIB
File:
TOSHIBAUPS-MIB.mib (175215 bytes)
Imported modules
Imported symbols
Defined Types
UpsOutputEntry |
|
SEQUENCE |
|
|
|
|
upsOutputIndex |
PositiveInteger |
|
|
upsOutputFrequency |
INTEGER |
|
|
upsOutputVoltage |
INTEGER |
|
|
upsOutputCurrent |
INTEGER |
|
|
upsOutputActivePower |
INTEGER |
|
|
upsOutputApparentPower |
INTEGER |
|
UpsOutputRatedEntry |
|
SEQUENCE |
|
|
|
|
upsOutputSlotIndex |
PositiveInteger |
|
|
upsOutputRatedFrequency |
INTEGER |
|
|
upsOutputRatedVoltage |
INTEGER |
|
|
upsOutputRatedCurrent |
INTEGER |
|
|
upsOutputRatedActivePower |
INTEGER |
|
|
upsOutputRatedApparentPower |
INTEGER |
|
UpsBypassEntry |
|
SEQUENCE |
|
|
|
|
upsBypassIndex |
PositiveInteger |
|
|
upsBypassFrequency |
INTEGER |
|
|
upsBypassVoltage |
INTEGER |
|
|
upsBypassCurrent |
INTEGER |
|
UpsBatteryExtEntry |
|
SEQUENCE |
|
|
|
|
upsBatteryExtIndex |
PositiveInteger |
|
|
upsBatteryExtInSeries |
INTEGER |
|
|
upsBatteryExtInParallel |
INTEGER |
|
|
upsBatteryExtRatedAmpereHour |
INTEGER |
|
|
upsBatteryExtCRate |
INTEGER |
|
|
upsBatteryExtInstallDate |
DisplayString |
|
UpsConnectedClientsEntry |
|
SEQUENCE |
|
|
|
|
upsConnectedClientsIndex |
PositiveInteger |
|
|
upsConnectedClientsIPAddress |
IpAddress |
|
|
upsConnectedClientsName |
DisplayString |
|
|
upsConnectedClientsTimeAtConnection |
DisplayString |
|
|
upsConnectedClientsShutdownDelay |
DisplayString |
|
|
upsConnectedClientsConnectionTimeout |
INTEGER |
|
|
upsConnectedClientsShutdownTest |
INTEGER |
|
UpsEmailClientsEntry |
|
SEQUENCE |
|
|
|
|
upsEmailClientsIndex |
PositiveInteger |
|
|
upsEmailClientsEmailAddress |
DisplayString |
|
|
upsEmailClientsDescription |
DisplayString |
|
|
upsEmailClientsDailyStatusReportType |
INTEGER |
|
|
upsEmailClientsEventStatusReportType |
INTEGER |
|
|
upsEmailClientsInfoLevel |
INTEGER |
|
UpsSNMPTrapsReceiversEntry |
|
SEQUENCE |
|
|
|
|
upsSNMPTrapsReceiversIndex |
PositiveInteger |
|
|
upsSNMPTrapsReceiversIPAddress |
IpAddress |
|
|
upsSNMPTrapReceiversCommunityString |
DisplayString |
|
|
upsSNMPTrapReceiversTrapType |
INTEGER |
|
|
upsSNMPTrapReceiversInfoReceivingSeverityLevel |
INTEGER |
|
|
upsSNMPTrapReceiversDescription |
DisplayString |
|
UpsSNMPCommunitiesEntry |
|
SEQUENCE |
|
|
|
|
upsSNMPCommunitiesIndex |
PositiveInteger |
|
|
upsSNMPCommunitiesIPAddress |
IpAddress |
|
|
upsSNMPCommunitiesAccessString |
DisplayString |
|
|
upsSNMPCommunitiesAccessMode |
INTEGER |
|
Defined Values
toshiba |
1.3.6.1.4.1.186 |
OBJECT IDENTIFIER |
|
|
|
equ |
1.3.6.1.4.1.186.1 |
OBJECT IDENTIFIER |
|
|
|
equUPS |
1.3.6.1.4.1.186.1.19 |
OBJECT IDENTIFIER |
|
|
|
ticUPS |
1.3.6.1.4.1.186.1.19.2 |
OBJECT IDENTIFIER |
|
|
|
rmti3 |
1.3.6.1.4.1.186.1.19.2.3 |
OBJECT IDENTIFIER |
|
|
|
upsIdent |
1.3.6.1.4.1.186.1.19.2.3.1 |
OBJECT IDENTIFIER |
|
|
|
upsOutput |
1.3.6.1.4.1.186.1.19.2.3.3 |
OBJECT IDENTIFIER |
|
|
|
upsBypass |
1.3.6.1.4.1.186.1.19.2.3.4 |
OBJECT IDENTIFIER |
|
|
|
upsDCBus |
1.3.6.1.4.1.186.1.19.2.3.5 |
OBJECT IDENTIFIER |
|
|
|
upsBattery |
1.3.6.1.4.1.186.1.19.2.3.6 |
OBJECT IDENTIFIER |
|
|
|
upsHistory |
1.3.6.1.4.1.186.1.19.2.3.8 |
OBJECT IDENTIFIER |
|
|
|
upsDisplay |
1.3.6.1.4.1.186.1.19.2.3.9 |
OBJECT IDENTIFIER |
|
|
|
upsAlarm |
1.3.6.1.4.1.186.1.19.2.3.10 |
OBJECT IDENTIFIER |
|
|
|
upsPassword |
1.3.6.1.4.1.186.1.19.2.3.11 |
OBJECT IDENTIFIER |
|
|
|
upsAgent |
1.3.6.1.4.1.186.1.19.2.3.12 |
OBJECT IDENTIFIER |
|
|
|
upsEmail |
1.3.6.1.4.1.186.1.19.2.3.14 |
OBJECT IDENTIFIER |
|
|
|
upsSNMP |
1.3.6.1.4.1.186.1.19.2.3.15 |
OBJECT IDENTIFIER |
|
|
|
upsEMD |
1.3.6.1.4.1.186.1.19.2.3.16 |
OBJECT IDENTIFIER |
|
|
|
upsTrap |
1.3.6.1.4.1.186.1.19.2.3.21 |
OBJECT IDENTIFIER |
|
|
|
upsIdentMainFirmwareVersion |
1.3.6.1.4.1.186.1.19.2.3.1.4 |
The UPS firmware version of the main controller. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
upsIdentMainBootSectorVersion |
1.3.6.1.4.1.186.1.19.2.3.1.5 |
The UPS boot sector version of the main controller. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
upsIdentMainBootLoaderVersion |
1.3.6.1.4.1.186.1.19.2.3.1.6 |
The UPS Boot Loader version of the main controller. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
upsIdentTestDate |
1.3.6.1.4.1.186.1.19.2.3.1.9 |
The test date displayed as YYYYMMDD format. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..8) |
|
upsIdentSysName |
1.3.6.1.4.1.186.1.19.2.3.1.12 |
A string identifying the UPS. This object should be
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
upsIdentAttachedDevices |
1.3.6.1.4.1.186.1.19.2.3.1.13 |
A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
upsInputEntry |
1.3.6.1.4.1.186.1.19.2.3.2.3.1 |
An entry containing information applicable to a
particular input line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsInputEntry |
|
|
upsInputRatedEntry |
1.3.6.1.4.1.186.1.19.2.3.2.7.1 |
An entry containing information applicable to a
particular input line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsInputRatedEntry |
|
|
upsOutputPowerSupplyConfiguration |
1.3.6.1.4.1.186.1.19.2.3.3.1 |
This parameter summarizes the measured and collected data describing
the output power supply. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
undefined(1), volt200Hz60(2), volt200Hz50(3), volt208Hz60(4), volt208Hz50(5), volt230Hz60(6), volt230Hz50(7), volt240Hz60(8), volt240Hz50(9), volt220Hz60(10), volt220Hz50(11), volt120Hz60(12), volt120Hz50(13), reserved0(14), reserved1(15), reserved2(16) |
|
upsOutputNumLines |
1.3.6.1.4.1.186.1.19.2.3.3.2 |
The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
one(1), two(2) |
|
upsOutputTable |
1.3.6.1.4.1.186.1.19.2.3.3.3 |
A list of Output table entries. The number of entries
is given by the value of upsOutputNumLines. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsOutputEntry |
|
upsOutputEntry |
1.3.6.1.4.1.186.1.19.2.3.3.3.1 |
An entry containing information applicable to a
particular Output line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsOutputEntry |
|
|
upsOutputFrequency |
1.3.6.1.4.1.186.1.19.2.3.3.3.1.2 |
The present output frequency of the UPS system in 1/10 of Hz. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputVoltage |
1.3.6.1.4.1.186.1.19.2.3.3.3.1.3 |
The Output voltage in RMS volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputCurrent |
1.3.6.1.4.1.186.1.19.2.3.3.3.1.4 |
The magnitude of the present output current in 1/10 RMS Amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputActivePower |
1.3.6.1.4.1.186.1.19.2.3.3.3.1.5 |
The present output active power in Watt. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputApparentPower |
1.3.6.1.4.1.186.1.19.2.3.3.3.1.6 |
The output apparent power in Volt-Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputLoadPercentage |
1.3.6.1.4.1.186.1.19.2.3.3.4 |
The present UPS ouput load percentage which is current percent or
active power whichever greater. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedTable |
1.3.6.1.4.1.186.1.19.2.3.3.5 |
A list of Output table entries. The number of entries
is given by the value of upsOutputNumLines. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsOutputRatedEntry |
|
upsOutputRatedEntry |
1.3.6.1.4.1.186.1.19.2.3.3.5.1 |
An entry containing information applicable to a
particular Output line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsOutputRatedEntry |
|
|
upsOutputRatedFrequency |
1.3.6.1.4.1.186.1.19.2.3.3.5.1.2 |
The present output rated frequency of the UPS system in 1/10 of Hz. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedVoltage |
1.3.6.1.4.1.186.1.19.2.3.3.5.1.3 |
The rated output voltage in RMS volts. This is set by the
administrator |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedCurrent |
1.3.6.1.4.1.186.1.19.2.3.3.5.1.4 |
The output rated current in 1/10 RMS Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedActivePower |
1.3.6.1.4.1.186.1.19.2.3.3.5.1.5 |
The output rated active power in Watt. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedApparentPower |
1.3.6.1.4.1.186.1.19.2.3.3.5.1.6 |
The output rated apparent power in Volt-Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputUndervoltagelevel |
1.3.6.1.4.1.186.1.19.2.3.3.6 |
This parameter displays the minimum allowable voltage before
it falls into under voltage range. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputOverVoltagelevel |
1.3.6.1.4.1.186.1.19.2.3.3.7 |
This is the maximum limit of the output voltage before the
UPS enters the over voltage state. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputVoltageAdjust |
1.3.6.1.4.1.186.1.19.2.3.3.9 |
This parameter allows UPS to be configured to have
adjustable voltages. This is set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputRatedPowerFactor |
1.3.6.1.4.1.186.1.19.2.3.3.10 |
The rated output power factor. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassPowerSupplyConfiguration |
1.3.6.1.4.1.186.1.19.2.3.4.1 |
This parameter summarizes the measured and collected data
describing the power supply into the bypass circuit. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
undefined(1), volt200Hz60(2), volt200Hz50(3), volt208Hz60(4), volt208Hz50(5), volt230Hz60(6), volt230Hz50(7), volt240Hz60(8), volt240Hz50(9), volt220Hz60(10), volt220Hz50(11), volt120Hz60(12), volt120Hz50(13), reserved0(14), reserved1(15), reserved2(16) |
|
upsBypassNumLine |
1.3.6.1.4.1.186.1.19.2.3.4.2 |
The number of bypass lines utilized in this device.
This variable indicates the number of rows in the
bypass table. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
one(1), two(2) |
|
upsBypassTable |
1.3.6.1.4.1.186.1.19.2.3.4.3 |
A list of Bypass table entries. The number of entries
is given by the value of upsBypassNumLines. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsBypassEntry |
|
upsBypassEntry |
1.3.6.1.4.1.186.1.19.2.3.4.3.1 |
An entry containing information applicable to a
particular line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsBypassEntry |
|
|
upsBypassFrequency |
1.3.6.1.4.1.186.1.19.2.3.4.3.1.2 |
The present Bypass frequency of the UPS system in 1/10 of Hz
of each phase. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassVoltage |
1.3.6.1.4.1.186.1.19.2.3.4.3.1.3 |
The Bypass utility line voltage in RMS volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassCurrent |
1.3.6.1.4.1.186.1.19.2.3.4.3.1.4 |
The magnitude of the present bypass Current in 1/10 RMS Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassApparentPower |
1.3.6.1.4.1.186.1.19.2.3.4.4 |
The Bypass Apparent power in Volt-Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassUnderVoltageDetectionlevel |
1.3.6.1.4.1.186.1.19.2.3.4.5 |
This parameter displays the minimum allowable voltage before
it falls into bypass undervoltage range. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassUnderVoltageRecoverylevel |
1.3.6.1.4.1.186.1.19.2.3.4.6 |
This parameter displays the allowable voltage that it can recover from. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassOverVoltageDetectionlevel |
1.3.6.1.4.1.186.1.19.2.3.4.7 |
This parameter displays the maximum allowable voltage before
it falls into over voltage range. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBypassOverVoltageRecoverylevel |
1.3.6.1.4.1.186.1.19.2.3.4.8 |
This parameter displays the allowable voltage that it can recover from. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsDCBusTotalVoltage |
1.3.6.1.4.1.186.1.19.2.3.5.1 |
The DC Bus voltage in DC volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsDCBusPositiveVoltage |
1.3.6.1.4.1.186.1.19.2.3.5.2 |
The DC Bus positive voltage in DC volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsDCBusNegativeVoltage |
1.3.6.1.4.1.186.1.19.2.3.5.3 |
The DC Bus negative voltage in DC volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsDCBusRatedVoltage |
1.3.6.1.4.1.186.1.19.2.3.5.4 |
The DC Bus rated voltage in DC volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryStatus |
1.3.6.1.4.1.186.1.19.2.3.6.1 |
The indication of the capacity remaining in the UPS system's batteries.
A value of batteryNormal indicates that the remaining run-time sufficient
to handle the load. A value of batteryLow indicates the battery level is
low. Continued operation in battery mode will deplate batteries. A value
of batteryDepleted indicates that the UPS will be unable to sustain the
present load when and if the utility power is lost (including the
possibility that the utility power is currently absent and the UPS is
unable to sustain the output). A value of batteryDischarging indicates UPS
system is in Battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6) |
|
upsSecondsOnBattery |
1.3.6.1.4.1.186.1.19.2.3.6.2 |
If the unit is on battery power, the elapsed time
since the UPS on battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsBatteryVoltage |
1.3.6.1.4.1.186.1.19.2.3.6.3 |
The magnitude of the present battery voltage in DC Volt. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryDischargeCurrent |
1.3.6.1.4.1.186.1.19.2.3.6.4 |
The present battery discharge current in 1/10 DC Amp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryChargeStatus |
1.3.6.1.4.1.186.1.19.2.3.6.5 |
The UPS charger status. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal-charging(1), preventative-charging(2), stop-charging(3) |
|
upsBatteryLifeRemaining |
1.3.6.1.4.1.186.1.19.2.3.6.8 |
The number of hours of UPS operation in the present environment
until the batteries must be replaced. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsBatteryRatedAmpereHour |
1.3.6.1.4.1.186.1.19.2.3.6.9 |
The battery capacity in Amp-Hour. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryInSeries |
1.3.6.1.4.1.186.1.19.2.3.6.10 |
The number of batteries in each string connected in series. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryInParallel |
1.3.6.1.4.1.186.1.19.2.3.6.11 |
The number of batteries connected in parallel. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryVoltageShutdownLevel |
1.3.6.1.4.1.186.1.19.2.3.6.13 |
The UPS battery voltage shutdown level. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryExtEntry |
1.3.6.1.4.1.186.1.19.2.3.6.14.1 |
An entry containing information applicable to a
particular Battery. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsBatteryExtEntry |
|
|
upsBatteryExtInSeries |
1.3.6.1.4.1.186.1.19.2.3.6.14.1.2 |
Specifies the number of batteries in the external cabinet
that are connected in series. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryExtInParallel |
1.3.6.1.4.1.186.1.19.2.3.6.14.1.3 |
Specifies the number of batteries in the external cabinet
that are connected in parallel. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryExtCRate |
1.3.6.1.4.1.186.1.19.2.3.6.14.1.5 |
The external battery's C rate. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryLowBattLevel |
1.3.6.1.4.1.186.1.19.2.3.6.15 |
The low battery level of the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryChargerOverVoltageDelay |
1.3.6.1.4.1.186.1.19.2.3.6.16 |
The UPS's charger over voltage detection delay in seconds. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryCalcLBLevel |
1.3.6.1.4.1.186.1.19.2.3.6.17 |
The calculated low battery level. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryCapacity |
1.3.6.1.4.1.186.1.19.2.3.6.18 |
The UPS battery capacity in percent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryRuntime |
1.3.6.1.4.1.186.1.19.2.3.6.19 |
The UPS battery runtime in minutes. It will return -1 or N/A if not available. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgSystemTemperature |
1.3.6.1.4.1.186.1.19.2.3.7.1 |
The UPS system temperature in Celsius. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgBatteryTemperature |
1.3.6.1.4.1.186.1.19.2.3.7.2 |
The UPS Battery temperature in Celsius. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgPresentMode |
1.3.6.1.4.1.186.1.19.2.3.7.3 |
The present mode of the UPS system. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
shutdown0(1), shutdown1(2), shutdown2(3), online(4), backup(5), battery-test(6), bypass6(7), bypass7(8), bypass8(9), startup(10) |
|
upsStsCtlCfgModeRequest |
1.3.6.1.4.1.186.1.19.2.3.7.4 |
The mode of the UPS system requested by the user. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), shutdown(2), bypass(3), online(4), battery-test(5) |
|
upsStsCtlCfgRunStopSwitchState |
1.3.6.1.4.1.186.1.19.2.3.7.7 |
The Run/Stop switch state of the UPS system. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
stop(1), run(2) |
|
upsStsCtlCfgServicePortCommStatus |
1.3.6.1.4.1.186.1.19.2.3.7.8 |
The service port communication status. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), normal-OK(2), off(3), error(4) |
|
upsStsCtlCfgInternalCommStatus |
1.3.6.1.4.1.186.1.19.2.3.7.9 |
The internal communication status of the UPS system such as display panel. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), normal-OK(2), off(3), error(4) |
|
upsStsCtlCfgPresentTimeStamp |
1.3.6.1.4.1.186.1.19.2.3.7.13 |
Present system timestamp. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgEnableRMTIToControlMode |
1.3.6.1.4.1.186.1.19.2.3.7.14 |
Allow to enable or disable SNMP to control the UPS Shutdown and Online Mode. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgEnableStartupDelay |
1.3.6.1.4.1.186.1.19.2.3.7.15 |
This delay timer, when enabled, will begin counting down at UPS startup
immediately following a UPS shutdown by any means other than battery
exhaustion. UPS output of any kind will be prohibited. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgStartUpDelayMode |
1.3.6.1.4.1.186.1.19.2.3.7.16 |
UPS mode into which the UPS will transition at the expiration
of the Start-Up delay timer. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bypass(1), online(2) |
|
upsStsCtlCfgStartUpDelay |
1.3.6.1.4.1.186.1.19.2.3.7.17 |
When the timer is counting down, its changing value is reflected,
otherwise its starting value is reported. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsStsCtlCfgEnableStartupBattTest |
1.3.6.1.4.1.186.1.19.2.3.7.24 |
Forces a battery test when UPS starts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgEnableBatteryTest |
1.3.6.1.4.1.186.1.19.2.3.7.25 |
Allow to enable or disable battery test. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgBatteryTestConditionStatus |
1.3.6.1.4.1.186.1.19.2.3.7.26 |
This notifies the user of the availability of the battery test feature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
battery-test-prohibited(1), battery-test-ok(2) |
|
upsStsCtlCfgMaxBatteryTestFreq |
1.3.6.1.4.1.186.1.19.2.3.7.27 |
This specified how often the battery test should occur. This is set by
the administrator |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
daily(1), weekly(2), monthly(3) |
|
upsStsCtlCfgEnableRestartAfterBattShutdown |
1.3.6.1.4.1.186.1.19.2.3.7.28 |
Mode set for UPS input power detection immediately after a shutdown while
on batteries. This is set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgRestartDelay |
1.3.6.1.4.1.186.1.19.2.3.7.29 |
Countdown begins only when UPS input power is restored immediately
following a UPS Shutdown while on batteries. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgEnableAutoTransferMode |
1.3.6.1.4.1.186.1.19.2.3.7.30 |
This feature allows the administrators to enable or to disable the auto
transfer feature of the UPS. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsStsCtlCfgAutoRetransferDelay |
1.3.6.1.4.1.186.1.19.2.3.7.31 |
Time period to wait after fault occurrence before attempting transfer
back Online |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsStsCtlCfgServicePortCommSetting |
1.3.6.1.4.1.186.1.19.2.3.7.32 |
The UPS baud rate settings. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bd9600(1), bd19200(2), bd38400(3), bd57600(4) |
|
upsStsCtlCfgRestartMode |
1.3.6.1.4.1.186.1.19.2.3.7.34 |
Restart Mode. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bypass(1), online(2) |
|
upsHistorySysOperationTime |
1.3.6.1.4.1.186.1.19.2.3.8.1 |
The amount of time the UPS has been on. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryInverterOperationTime |
1.3.6.1.4.1.186.1.19.2.3.8.2 |
The amount of time the UPS has been in On-Line Mode. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryBackupOperationTime |
1.3.6.1.4.1.186.1.19.2.3.8.3 |
The amount of time the UPS has been in BackUp Mode. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryLifetimeRemaining |
1.3.6.1.4.1.186.1.19.2.3.8.4 |
The remaining lifetime of the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryHighestSystemTemp |
1.3.6.1.4.1.186.1.19.2.3.8.5 |
The highest system temperature of the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsHistoryHighestBatteryTemp |
1.3.6.1.4.1.186.1.19.2.3.8.6 |
The highest battery temperature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsHistoryTotalNumOverload |
1.3.6.1.4.1.186.1.19.2.3.8.8 |
Total number of times the UPS has been overloaded. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumTest |
1.3.6.1.4.1.186.1.19.2.3.8.9 |
Total number of tests that has been conducted on the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumBackup |
1.3.6.1.4.1.186.1.19.2.3.8.10 |
Total number of times the UPS has been in Back-Up mode. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumFaults |
1.3.6.1.4.1.186.1.19.2.3.8.11 |
Total number of faults that has occurred on the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumOperationModeChange |
1.3.6.1.4.1.186.1.19.2.3.8.12 |
The number of mode changes that has occurred. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumWarnings |
1.3.6.1.4.1.186.1.19.2.3.8.13 |
The number of warnings that has occurred on the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumSystemSettingsChanged |
1.3.6.1.4.1.186.1.19.2.3.8.14 |
The number of times the System settings have been changed. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsHistoryTotalNumResets |
1.3.6.1.4.1.186.1.19.2.3.8.15 |
The number of times the UPS has reset. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsDisplayBuzzerMode |
1.3.6.1.4.1.186.1.19.2.3.9.5 |
Configures buzzer mode. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), enable(2) |
|
upsDisplayBuzzerStatus |
1.3.6.1.4.1.186.1.19.2.3.9.6 |
Shows the current state of the buzzer. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(1), idle(2), sound(3), silenced(4) |
|
upsDisplayRMTIInstallStatus |
1.3.6.1.4.1.186.1.19.2.3.9.8 |
Shows the installation status of the RMTI. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
uninstalled(1), installed(2) |
|
upsDisplayRMTIBaudRate |
1.3.6.1.4.1.186.1.19.2.3.9.9 |
Configures the baud rate. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bd9600(1), bd19200(2), bd38400(3), bd57600(4) |
|
upsDisplayRMTIDataLink |
1.3.6.1.4.1.186.1.19.2.3.9.10 |
Shows the data status of the RMTI. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), link-down(2), link-up(3) |
|
upsDisplayRMTINetworkLink |
1.3.6.1.4.1.186.1.19.2.3.9.11 |
Shows the network status of the RMTI. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), link-down(2), link-up(3) |
|
upsAlarmsPresent |
1.3.6.1.4.1.186.1.19.2.3.10.1 |
The present number of active alarm conditions. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge32 |
|
|
upsAlarmTable |
1.3.6.1.4.1.186.1.19.2.3.10.2 |
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsAlarmEntry |
|
upsAlarmEntry |
1.3.6.1.4.1.186.1.19.2.3.10.2.1 |
An entry containing information applicable to a
particular alarm. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsAlarmEntry |
|
|
upsAlarmId |
1.3.6.1.4.1.186.1.19.2.3.10.2.1.1 |
An unique identifier for an alarm condition. This
value must remain constant. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
upsAlarmDescr |
1.3.6.1.4.1.186.1.19.2.3.10.2.1.2 |
A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AutonomousType |
|
|
upsAlarmTime |
1.3.6.1.4.1.186.1.19.2.3.10.2.1.3 |
The value of upsConfigSystemTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal 0. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
TimeStamp |
|
|
upsAlarmFault |
1.3.6.1.4.1.186.1.19.2.3.10.3.1 |
Fault: One or more fault reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOpenFuse |
1.3.6.1.4.1.186.1.19.2.3.10.3.2 |
Fault: An open fuse reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmCurrentLimitFault |
1.3.6.1.4.1.186.1.19.2.3.10.3.3 |
Fault: A current limit reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusOverCurrent |
1.3.6.1.4.1.186.1.19.2.3.10.3.4 |
Fault: A DC bus overcurrent reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCOverVoltage |
1.3.6.1.4.1.186.1.19.2.3.10.3.5 |
Fault: A DC bus overvoltage repoprted. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusImbalance |
1.3.6.1.4.1.186.1.19.2.3.10.3.6 |
Fault: A DC bus imbalance reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputUnderVoltage |
1.3.6.1.4.1.186.1.19.2.3.10.3.7 |
Fault: An inverter output undervoltage reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOverVoltage |
1.3.6.1.4.1.186.1.19.2.3.10.3.8 |
Fault: An inverter output overvoltage reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmHeatSinkOverheat |
1.3.6.1.4.1.186.1.19.2.3.10.3.9 |
Fault: Heat sink or device overheat reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassOverload |
1.3.6.1.4.1.186.1.19.2.3.10.3.10 |
Fault: A bypass overload reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmChargerOverVoltageFault |
1.3.6.1.4.1.186.1.19.2.3.10.3.11 |
Fault: Charger overvoltage reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOverCurrent |
1.3.6.1.4.1.186.1.19.2.3.10.3.12 |
Fault: A output overcurrent reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCUnderVoltAtBoostUp |
1.3.6.1.4.1.186.1.19.2.3.10.3.13 |
Fault: A DC bus undervoltage reported during DC bus boost-up. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCUnderVoltAtCharge |
1.3.6.1.4.1.186.1.19.2.3.10.3.14 |
Fault: A DC bus undervoltage during DC bus charging reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassOverheat |
1.3.6.1.4.1.186.1.19.2.3.10.3.15 |
Fault: A bypass Overheat reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmResettableInverterOverload |
1.3.6.1.4.1.186.1.19.2.3.10.3.16 |
Fault: An inverter overload reported. It is resetable. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmUnresettableInverterOverload |
1.3.6.1.4.1.186.1.19.2.3.10.3.17 |
Fault: An inverter overload reported. It is not resetable. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassOverVoltage |
1.3.6.1.4.1.186.1.19.2.3.10.3.21 |
Warning: A bypass overvoltage reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassUnderVoltage |
1.3.6.1.4.1.186.1.19.2.3.10.3.22 |
Warning: A bypass undervoltage reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassFrequencyError |
1.3.6.1.4.1.186.1.19.2.3.10.3.23 |
Warning: An bypass frequency error reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusUnderVoltAtBattTest |
1.3.6.1.4.1.186.1.19.2.3.10.3.24 |
Warning: A DC bus undervoltage reported during battery test |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryLow |
1.3.6.1.4.1.186.1.19.2.3.10.3.25 |
Warning: A Low battery reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryAtShutdownlevel |
1.3.6.1.4.1.186.1.19.2.3.10.3.26 |
Warning: A Battery shutdown voltage level reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmReplaceBattery |
1.3.6.1.4.1.186.1.19.2.3.10.3.27 |
Warning: Batteries are in need of replacement. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryTestFailed |
1.3.6.1.4.1.186.1.19.2.3.10.3.29 |
Warning: A battery test failed event reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryDepleted |
1.3.6.1.4.1.186.1.19.2.3.10.3.30 |
Warning: A battery depleted event reported. It will not be able to support critical loads. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryOverheat |
1.3.6.1.4.1.186.1.19.2.3.10.3.31 |
Warning: A Battery overheat reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmSystemOverheat |
1.3.6.1.4.1.186.1.19.2.3.10.3.32 |
Warning: A system overheat reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOverloadWarning |
1.3.6.1.4.1.186.1.19.2.3.10.3.33 |
Warning: An inverter output overload reported. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmCurrentLimitWarning |
1.3.6.1.4.1.186.1.19.2.3.10.3.34 |
Warning: A current limit reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmAsyncOperation |
1.3.6.1.4.1.186.1.19.2.3.10.3.35 |
Warning: An Asynchronous operation reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmServiceUPS |
1.3.6.1.4.1.186.1.19.2.3.10.3.36 |
Warning: UPS is in need of service. Please contact authorized Toshiba service center for assistance. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryNearExpiration |
1.3.6.1.4.1.186.1.19.2.3.10.3.37 |
Warning: Batteries are nearing the end of their expected lifetime. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryExpired |
1.3.6.1.4.1.186.1.19.2.3.10.3.38 |
Warning: Batteries have reached their expected lifetime. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDisplayCableError |
1.3.6.1.4.1.186.1.19.2.3.10.3.39 |
Warning: A display cable error reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmRemotEyeCommError |
1.3.6.1.4.1.186.1.19.2.3.10.3.40 |
Warning: A Communication error between the main control and the RemotEye reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmRemotEyeUplinkCommError |
1.3.6.1.4.1.186.1.19.2.3.10.3.41 |
Warning: A communication error between the RemotEye III and the network reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmServicePortCommError |
1.3.6.1.4.1.186.1.19.2.3.10.3.42 |
Warning: A communication error between the main controller and the service communication
port reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDispCommError |
1.3.6.1.4.1.186.1.19.2.3.10.3.43 |
Warning: A communication error between the main controller and display controller reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmSystemTestFailed |
1.3.6.1.4.1.186.1.19.2.3.10.3.44 |
Warning: A system test failed event reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBypassOn |
1.3.6.1.4.1.186.1.19.2.3.10.3.45 |
Warning: The UPS is in Stop (Bypass) mode |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmPowerFailure |
1.3.6.1.4.1.186.1.19.2.3.10.3.46 |
Info: A power failure reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmShutdownPending |
1.3.6.1.4.1.186.1.19.2.3.10.3.47 |
Info: An output shutdown in progress reported. Output will turn off after delay. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOffAsRequested |
1.3.6.1.4.1.186.1.19.2.3.10.3.48 |
Info: An output shutdown mode requested. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOff |
1.3.6.1.4.1.186.1.19.2.3.10.3.49 |
Info: An output off reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryTestInProgress |
1.3.6.1.4.1.186.1.19.2.3.10.3.50 |
Info: A battery test in progress reported. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryOn |
1.3.6.1.4.1.186.1.19.2.3.10.3.51 |
Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmEMDSensor1AlarmTriggered |
1.3.6.1.4.1.186.1.19.2.3.10.3.52 |
Info: EMD sensor 1 alarm is triggered. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmEMDSensor2AlarmTriggered |
1.3.6.1.4.1.186.1.19.2.3.10.3.53 |
Info: EMD sensor 2 alarm is triggered. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmLogInError |
1.3.6.1.4.1.186.1.19.2.3.10.3.62 |
Info: Username/Password information is incorrect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAgentHardwareAddress |
1.3.6.1.4.1.186.1.19.2.3.12.2 |
The hardware/MAC address that NMS can identify the managed device |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(20) |
|
upsAgentIPAddress |
1.3.6.1.4.1.186.1.19.2.3.12.3 |
The ip address that NMS can identify the managed device |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
upsAgentGatewayAddress |
1.3.6.1.4.1.186.1.19.2.3.12.4 |
The default gateway that allow device managed through routers |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
upsAgentSubnetMask |
1.3.6.1.4.1.186.1.19.2.3.12.5 |
Internet address subnet mask |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
upsAgentDate |
1.3.6.1.4.1.186.1.19.2.3.12.6 |
The date in agent, format is MM/DD/YYYY. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
upsAgentTime |
1.3.6.1.4.1.186.1.19.2.3.12.7 |
The time in agent, format is HH:MM:SS. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(8) |
|
upsAgentGeneralRecordLogFrequency |
1.3.6.1.4.1.186.1.19.2.3.12.8 |
The interval frequency of the general record log. The value is in seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
5..28800 |
|
upsAgentPollingRate |
1.3.6.1.4.1.186.1.19.2.3.12.9 |
The frequency that proxy agent polls the connected
UPS in RemotEye III protocols. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..999 |
|
upsAgentDHCPControl |
1.3.6.1.4.1.186.1.19.2.3.12.10 |
Enable or disable DHCP/BootP capability |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentTelnetControl |
1.3.6.1.4.1.186.1.19.2.3.12.11 |
Enable or disable telnet access |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentTFTPControl |
1.3.6.1.4.1.186.1.19.2.3.12.12 |
Enable or disable network upgrade capability |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentResetToDefault |
1.3.6.1.4.1.186.1.19.2.3.12.13 |
Reset all parameters of REMOTEYE III to default value |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentRestart |
1.3.6.1.4.1.186.1.19.2.3.12.14 |
Restart REMOTEYE III |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentDefaultLanguage |
1.3.6.1.4.1.186.1.19.2.3.12.18 |
Current Default Language |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
auto(1), english(2) |
|
upsAgentClearGeneralHistory |
1.3.6.1.4.1.186.1.19.2.3.12.19 |
Clear general history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearTestHistory |
1.3.6.1.4.1.186.1.19.2.3.12.20 |
Clear test history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearBackupHistory |
1.3.6.1.4.1.186.1.19.2.3.12.21 |
Clear Backup history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearFaultHistory |
1.3.6.1.4.1.186.1.19.2.3.12.22 |
Clear Fault history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearOperationModeHistory |
1.3.6.1.4.1.186.1.19.2.3.12.23 |
Clear operation mode history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearWarningHistory |
1.3.6.1.4.1.186.1.19.2.3.12.24 |
Clear warning history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearSystemsettingsChangeHistory |
1.3.6.1.4.1.186.1.19.2.3.12.25 |
Clear System settings change history log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsAgentClearRMTIEventHistory |
1.3.6.1.4.1.186.1.19.2.3.12.26 |
Clear RemotEye Event History log data |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsConnectedClientsEntry |
1.3.6.1.4.1.186.1.19.2.3.13.2.1 |
The devices protected by RemotEye III |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsConnectedClientsEntry |
|
|
upsConnectedClientsName |
1.3.6.1.4.1.186.1.19.2.3.13.2.1.3 |
The name/description of the device plugged into the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsConnectedClientsShutdownTest |
1.3.6.1.4.1.186.1.19.2.3.13.2.1.7 |
The client will shutdown test after receive
shutdown request from REMOTEYE III. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEmailMailServer |
1.3.6.1.4.1.186.1.19.2.3.14.1 |
The Email mail server for REMOTEYE III. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsEmailDomainName |
1.3.6.1.4.1.186.1.19.2.3.14.4 |
The Email mail server domain name |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsEmailClientsTable |
1.3.6.1.4.1.186.1.19.2.3.14.7 |
The email addresses that RemotEye III will send logs and status reports to. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsEmailClientsEntry |
|
upsEmailClientsEntry |
1.3.6.1.4.1.186.1.19.2.3.14.7.1 |
The email addresses that RemotEye III will send logs and status
reports to. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsEmailClientsEntry |
|
|
upsEmailClientsDailyStatusReportType |
1.3.6.1.4.1.186.1.19.2.3.14.7.1.4 |
The type of daily information that clients would like to receive. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
general-test(1), test-records(2), backup-Records(3), fault-Records(4), operation-Mode-Records(5), warning-Records(6), system-Setting-Change-Record(7), remotEye-III-Events-Log(8) |
|
upsEmailClientsEventStatusReportType |
1.3.6.1.4.1.186.1.19.2.3.14.7.1.5 |
The type of event information that clients would like to receive when event occurs. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
general-test(1), test-records(2), backup-Records(3), fault-Records(4), operation-Mode-Records(5), warning-Records(6), system-Setting-Change-Record(7), remotEye-III-Events-Log(8) |
|
upsEmailClientsInfoLevel |
1.3.6.1.4.1.186.1.19.2.3.14.7.1.6 |
The type of information that clients would like to receive. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
fault(1), warning(2), informational(3) |
|
upsSNMPVersion |
1.3.6.1.4.1.186.1.19.2.3.15.1 |
The SNMP version |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), snmpv1(2), snmpv3(3) |
|
upsSNMPTrapsReceiversEntry |
1.3.6.1.4.1.186.1.19.2.3.15.2.1 |
The managers to send traps to. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsSNMPTrapsReceiversEntry |
|
|
upsSNMPTrapReceiversTrapType |
1.3.6.1.4.1.186.1.19.2.3.15.2.1.4 |
The trap group that NMS desired. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), toshiba-trap(2), jema-trap(3), rfc1628-trap(4) |
|
upsSNMPTrapReceiversInfoReceivingSeverityLevel |
1.3.6.1.4.1.186.1.19.2.3.15.2.1.5 |
The severity level of traps to be received by this manager. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
informational(1), warning(2), fault(3) |
|
upsSNMPCommunitiesEntry |
1.3.6.1.4.1.186.1.19.2.3.15.3.1 |
The managers. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsSNMPCommunitiesEntry |
|
|
upsSNMPCommunitiesAccessMode |
1.3.6.1.4.1.186.1.19.2.3.15.3.1.4 |
Access type, only read/Write access type can change parameter
of REMOTEYE III |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
readOnly(1), read-write(2), notAccess(3) |
|
upsEMDType |
1.3.6.1.4.1.186.1.19.2.3.16.1 |
The name assign to specific EMD. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
upsEMDTemperature |
1.3.6.1.4.1.186.1.19.2.3.16.2 |
The EMD temperature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDTemperatureHysteresis |
1.3.6.1.4.1.186.1.19.2.3.16.7 |
The EMD temperature hysteresis. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDHumidity |
1.3.6.1.4.1.186.1.19.2.3.16.9 |
The EMD Humidity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDHumidityLowWarningSetPoint |
1.3.6.1.4.1.186.1.19.2.3.16.10 |
The EMD Humidity low warning set point. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDHumidityHysteresis |
1.3.6.1.4.1.186.1.19.2.3.16.14 |
The EMD Humidity hysteresis. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDHumidityCalibrationOffset |
1.3.6.1.4.1.186.1.19.2.3.16.15 |
The EMD Humidity calibration offset. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDR1Status |
1.3.6.1.4.1.186.1.19.2.3.16.16 |
The EMD dry contact 1 status. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), disabled(2), active(3), inactive(4) |
|
upsEMDAlarmR1Enable |
1.3.6.1.4.1.186.1.19.2.3.16.17 |
The EMD contact R1 alarm enable setting. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), normalClose(2), normalOpen(3), highActive(4), lowActive(5) |
|
upsEMDAlarmR1Hysteresis |
1.3.6.1.4.1.186.1.19.2.3.16.18 |
The EMD Contact R1 alarm hysteresis. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEMDR2Status |
1.3.6.1.4.1.186.1.19.2.3.16.19 |
The EMD dry contact 2 status. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), disabled(2), active(3), inactive(4) |
|
upsEMDAlarmR2Enable |
1.3.6.1.4.1.186.1.19.2.3.16.20 |
The EMD contact R2 alarm enable setting. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), normalClose(2), normalOpen(3), highActive(4), lowActive(5) |
|
upsEMDAlarmR2Hysteresis |
1.3.6.1.4.1.186.1.19.2.3.16.21 |
The EMD Contact R2 alarm hysteresis. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsTrapCurrentLimitFault |
5 |
Fault: A current limit fault reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapCurrentLimitFaultClear |
6 |
Fault Clear: A current limit fault reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverCurrent |
7 |
Fault: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverCurrentClear |
8 |
Fault Clear: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverVoltage |
9 |
Fault: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverVoltageClear |
10 |
Fault Clear: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusImbalance |
11 |
Fault: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusImbalanceClear |
12 |
Fault Clear: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputUnderVoltage |
13 |
Fault: An output undervoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputUnderVoltageClear |
14 |
Fault Clear: An output undervoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputOverVoltage |
15 |
Fault: An output overvoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputOverVoltageClear |
16 |
Fault Clear: An output overvoltage reported. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapRemotEyeCommError |
79 |
Warning: A communication error between the main control and the RemotEye III reported. |
TRAP-TYPE |
|
|
|
upsTrapDispCommError |
85 |
Warning: A communication error between the main controller and the display controller reported. |
TRAP-TYPE |
|
|
|
upsTrapDispCommErrorClear |
86 |
Warning Clear: A communication error between the main controller and the display controller reported. |
TRAP-TYPE |
|
|
|
upsTrapShutdownPending |
93 |
Info: A output shutdown in progress reported. Output will turn off after delay. |
TRAP-TYPE |
|
|
|
upsTrapBatteryOn |
101 |
Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
TRAP-TYPE |
|
|
|
upsTrapBatteryOnClear |
102 |
Info Clear: The UPS is on Battery mode; it is supplying output power from its batteries. |
TRAP-TYPE |
|
|
|