TELDAT-CFG-PROTOCOL-GW104-MIB
File:
TELDAT-CFG-PROTOCOL-GW104-MIB.mib (13089 bytes)
Imported modules
Imported symbols
Defined Types
TelProdNpGW104AgentEntry |
|
SEQUENCE |
|
|
|
|
telProdNpGW104AgentIndex |
INTEGER |
|
|
telProdNpGW104AgentStatus |
INTEGER |
|
|
telProdNpGW104AgentName |
DisplayString |
|
|
telProdNpGW104AgentAlarmBuf |
INTEGER |
|
|
telProdNpGW104AgentK |
INTEGER |
|
|
telProdNpGW104AgentLocTcpPort |
INTEGER |
|
|
telProdNpGW104AgentT0 |
INTEGER |
|
|
telProdNpGW104AgentT1 |
INTEGER |
|
|
telProdNpGW104AgentT2 |
INTEGER |
|
|
telProdNpGW104AgentT3 |
INTEGER |
|
|
telProdNpGW104AgentW |
INTEGER |
|
|
telProdNpGW104AgentVrf |
DisplayString |
|
TelProdNpGW104AgentCcIpEntry |
|
SEQUENCE |
|
|
|
|
telProdNpGW104AgentCcIpAgIndex |
INTEGER |
|
|
telProdNpGW104AgentCcIpIndex |
INTEGER |
|
|
telProdNpGW104AgentCcIpStatus |
INTEGER |
|
|
telProdNpGW104AgentCcIpAddr |
IpAddress |
|
Defined Values
telProdNpGW104GloEnable |
1.3.6.1.4.1.2007.4.1.1.5.14.1.1 |
Enables Gateway IEC-104/101 operation. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104Glo101-On |
1.3.6.1.4.1.2007.4.1.1.5.14.1.2 |
Enables IEC-101 operation regardless IEC-104 agents status. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104Glo104-On |
1.3.6.1.4.1.2007.4.1.1.5.14.1.3 |
Enables IEC-104 agents operation regardless IEC-101
interfaces status. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104GloASDUComAddr |
1.3.6.1.4.1.2007.4.1.1.5.14.1.4 |
Set ASDU Common Address field value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..65534 |
|
telProdNpGW104GloASDUComAddrSz |
1.3.6.1.4.1.2007.4.1.1.5.14.1.5 |
Set ASDU Common Address field size. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
telProdNpGW104GloCauseTransfSz |
1.3.6.1.4.1.2007.4.1.1.5.14.1.6 |
Set Cause of Transfer field size. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
telProdNpGW104GloInfoObjAddrSz |
1.3.6.1.4.1.2007.4.1.1.5.14.1.7 |
Set Information Object Address field size. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..3 |
|
telProdNpGW104GloIoa10000 |
1.3.6.1.4.1.2007.4.1.1.5.14.1.8 |
Enable use of IOA 10000. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104GloIoa10007 |
1.3.6.1.4.1.2007.4.1.1.5.14.1.9 |
Enable use of IOA 10007. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104GloOrigFilter |
1.3.6.1.4.1.2007.4.1.1.5.14.1.10 |
Enable originator address filter for messages received from
Control Center . |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
telProdNpGW104AgentEntry |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1 |
Each entry consists in an IEC-104 Agent. Each entry contains the
corresponding IEC-104 agent configuration. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
TelProdNpGW104AgentEntry |
|
|
telProdNpGW104AgentIndex |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.1 |
IEC-104 agent position in the table. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
telProdNpGW104AgentStatus |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.2 |
Table control variable.
Set to 1 does nothing.
Set to 2 adds a new row (IEC-104 Agent) in the table with default
values and returns 2. If it already exists, then it returns error.
It must be added immediately after the last index.
Set to 3 deletes all table fields corresponding to that Agent,
and returns 3.
Get returns 1 if the control exists. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
valid(1), add(2), delete(3) |
|
telProdNpGW104AgentName |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.3 |
IEC-104 agent name. Agents names must be different, can not be
repeated. If name already exists, then it returns error. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(1..20) |
|
telProdNpGW104AgentAlarmBuf |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.4 |
Alarm buffer queue length. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..64 |
|
telProdNpGW104AgentK |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.5 |
Max. number of IEC-104 send messages without confirmation. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..33767 |
|
telProdNpGW104AgentLocTcpPort |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.6 |
Local TCP port for IEC-104 agent listen. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..65535 |
|
telProdNpGW104AgentT0 |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.7 |
T0 defined by IEC-104, establish connection timeout.
Value indicates in seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..255 |
|
telProdNpGW104AgentT1 |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.8 |
T1 defined by IEC-104, SEND or TEST APDU type timeout.
Value indicates in seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..255 |
|
telProdNpGW104AgentT2 |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.9 |
T2 defined by IEC-104, data message confirmation timeout.
Value indicates in seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..255 |
|
telProdNpGW104AgentT3 |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.10 |
T3 defined by IEC-104, sending S message timeout on long inactivity
periods. Value indicates in seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..255 |
|
telProdNpGW104AgentW |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.11 |
Max. number of IEC-104 received messages confirmed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..33767 |
|
telProdNpGW104AgentVrf |
1.3.6.1.4.1.2007.4.1.1.5.14.2.1.12 |
VRF name. If VRF is configured on router, can be asociate in
agent. Return error if VRF name don't exist. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(1..32) |
|
telProdNpGW104AgentCcIpEntry |
1.3.6.1.4.1.2007.4.1.1.5.14.3.1 |
Each entry contains a Control Center IP address for an IEC-104
Agent. First index indicates IEC-104 Agent this value must correspond
with same in Agent global parameters table. The second table index
indicates the order number of that Control Center IP address inside
that Agent. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
TelProdNpGW104AgentCcIpEntry |
|
|
telProdNpGW104AgentCcIpAgIndex |
1.3.6.1.4.1.2007.4.1.1.5.14.3.1.1 |
IEC-104 agent position index, must be the same that agents table. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
telProdNpGW104AgentCcIpIndex |
1.3.6.1.4.1.2007.4.1.1.5.14.3.1.2 |
Control Center IP address position in the table. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
telProdNpGW104AgentCcIpStatus |
1.3.6.1.4.1.2007.4.1.1.5.14.3.1.3 |
Table control variable.
Set to 1 does nothing.
Set to 2 deletes corresponding Control Center IP address to that Agent.
Get returns 1 if the control exists.
It returns ERROR if agent don't exist, index don't was greated. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
valid(1), delete(2) |
|
telProdNpGW104AgentCcIpAddr |
1.3.6.1.4.1.2007.4.1.1.5.14.3.1.4 |
Control Center IP address for IEC-104 agents filter. Adding a new IP
address, that don't exist in the table, create a new row in the table. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|