TELDAT-CFG-PROTOCOL-GW104-MIB

File: TELDAT-CFG-PROTOCOL-GW104-MIB.mib (13089 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
TELDAT-SW-STRUCTURE-MIB

Imported symbols

IpAddress OBJECT-TYPE DisplayString
telProdNpConfProtocol

Defined Types

TelProdNpGW104AgentEntry  
SEQUENCE    
  telProdNpGW104AgentIndex INTEGER
  telProdNpGW104AgentStatus INTEGER
  telProdNpGW104AgentName DisplayString
  telProdNpGW104AgentAlarmBuf INTEGER
  telProdNpGW104AgentK INTEGER
  telProdNpGW104AgentLocTcpPort INTEGER
  telProdNpGW104AgentT0 INTEGER
  telProdNpGW104AgentT1 INTEGER
  telProdNpGW104AgentT2 INTEGER
  telProdNpGW104AgentT3 INTEGER
  telProdNpGW104AgentW INTEGER
  telProdNpGW104AgentVrf DisplayString

TelProdNpGW104AgentCcIpEntry  
SEQUENCE    
  telProdNpGW104AgentCcIpAgIndex INTEGER
  telProdNpGW104AgentCcIpIndex INTEGER
  telProdNpGW104AgentCcIpStatus INTEGER
  telProdNpGW104AgentCcIpAddr IpAddress

Defined Values

telProdNpConfProtGW104 1.3.6.1.4.1.2007.4.1.1.5.14
OBJECT IDENTIFIER    

telProdNpGW104Global 1.3.6.1.4.1.2007.4.1.1.5.14.1
OBJECT IDENTIFIER    

telProdNpGW104GloEnable 1.3.6.1.4.1.2007.4.1.1.5.14.1.1
Enables Gateway IEC-104/101 operation.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104Glo101-On 1.3.6.1.4.1.2007.4.1.1.5.14.1.2
Enables IEC-101 operation regardless IEC-104 agents status.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104Glo104-On 1.3.6.1.4.1.2007.4.1.1.5.14.1.3
Enables IEC-104 agents operation regardless IEC-101 interfaces status.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104GloASDUComAddr 1.3.6.1.4.1.2007.4.1.1.5.14.1.4
Set ASDU Common Address field value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65534  

telProdNpGW104GloASDUComAddrSz 1.3.6.1.4.1.2007.4.1.1.5.14.1.5
Set ASDU Common Address field size.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

telProdNpGW104GloCauseTransfSz 1.3.6.1.4.1.2007.4.1.1.5.14.1.6
Set Cause of Transfer field size.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

telProdNpGW104GloInfoObjAddrSz 1.3.6.1.4.1.2007.4.1.1.5.14.1.7
Set Information Object Address field size.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..3  

telProdNpGW104GloIoa10000 1.3.6.1.4.1.2007.4.1.1.5.14.1.8
Enable use of IOA 10000.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104GloIoa10007 1.3.6.1.4.1.2007.4.1.1.5.14.1.9
Enable use of IOA 10007.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104GloOrigFilter 1.3.6.1.4.1.2007.4.1.1.5.14.1.10
Enable originator address filter for messages received from Control Center .
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

telProdNpGW104AgentTable 1.3.6.1.4.1.2007.4.1.1.5.14.2
Agents list. The table index is the Agent position.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TelProdNpGW104AgentEntry

telProdNpGW104AgentEntry 1.3.6.1.4.1.2007.4.1.1.5.14.2.1
Each entry consists in an IEC-104 Agent. Each entry contains the corresponding IEC-104 agent configuration.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  TelProdNpGW104AgentEntry  

telProdNpGW104AgentIndex 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.1
IEC-104 agent position in the table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpGW104AgentStatus 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.2
Table control variable. Set to 1 does nothing. Set to 2 adds a new row (IEC-104 Agent) in the table with default values and returns 2. If it already exists, then it returns error. It must be added immediately after the last index. Set to 3 deletes all table fields corresponding to that Agent, and returns 3. Get returns 1 if the control exists.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER valid(1), add(2), delete(3)  

telProdNpGW104AgentName 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.3
IEC-104 agent name. Agents names must be different, can not be repeated. If name already exists, then it returns error.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..20)  

telProdNpGW104AgentAlarmBuf 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.4
Alarm buffer queue length.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..64  

telProdNpGW104AgentK 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.5
Max. number of IEC-104 send messages without confirmation.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..33767  

telProdNpGW104AgentLocTcpPort 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.6
Local TCP port for IEC-104 agent listen.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

telProdNpGW104AgentT0 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.7
T0 defined by IEC-104, establish connection timeout. Value indicates in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..255  

telProdNpGW104AgentT1 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.8
T1 defined by IEC-104, SEND or TEST APDU type timeout. Value indicates in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..255  

telProdNpGW104AgentT2 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.9
T2 defined by IEC-104, data message confirmation timeout. Value indicates in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..255  

telProdNpGW104AgentT3 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.10
T3 defined by IEC-104, sending S message timeout on long inactivity periods. Value indicates in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..255  

telProdNpGW104AgentW 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.11
Max. number of IEC-104 received messages confirmed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..33767  

telProdNpGW104AgentVrf 1.3.6.1.4.1.2007.4.1.1.5.14.2.1.12
VRF name. If VRF is configured on router, can be asociate in agent. Return error if VRF name don't exist.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..32)  

telProdNpGW104AgentCcIpTable 1.3.6.1.4.1.2007.4.1.1.5.14.3
Agents list. The table index is the Agent position.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TelProdNpGW104AgentCcIpEntry

telProdNpGW104AgentCcIpEntry 1.3.6.1.4.1.2007.4.1.1.5.14.3.1
Each entry contains a Control Center IP address for an IEC-104 Agent. First index indicates IEC-104 Agent this value must correspond with same in Agent global parameters table. The second table index indicates the order number of that Control Center IP address inside that Agent.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  TelProdNpGW104AgentCcIpEntry  

telProdNpGW104AgentCcIpAgIndex 1.3.6.1.4.1.2007.4.1.1.5.14.3.1.1
IEC-104 agent position index, must be the same that agents table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpGW104AgentCcIpIndex 1.3.6.1.4.1.2007.4.1.1.5.14.3.1.2
Control Center IP address position in the table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpGW104AgentCcIpStatus 1.3.6.1.4.1.2007.4.1.1.5.14.3.1.3
Table control variable. Set to 1 does nothing. Set to 2 deletes corresponding Control Center IP address to that Agent. Get returns 1 if the control exists. It returns ERROR if agent don't exist, index don't was greated.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER valid(1), delete(2)  

telProdNpGW104AgentCcIpAddr 1.3.6.1.4.1.2007.4.1.1.5.14.3.1.4
Control Center IP address for IEC-104 agents filter. Adding a new IP address, that don't exist in the table, create a new row in the table.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress