TELDAT-CFG-INTERF-IEC101GW-MIB

File: TELDAT-CFG-INTERF-IEC101GW-MIB.mib (10731 bytes)

Imported modules

RFC-1212 TELDAT-SW-STRUCTURE-MIB

Imported symbols

OBJECT-TYPE telProdNpConfInterface

Defined Types

TelProdNpIec101GWEntry  
SEQUENCE    
  telProdNpIec101GWIfcIndex INTEGER
  telProdNpIec101GWIfcAsduCAddr INTEGER
  telProdNpIec101GWIfcBaudRate INTEGER
  telProdNpIec101GWIfcLinkAddr INTEGER
  telProdNpIec101GWIfcLinkAddrSz INTEGER
  telProdNpIec101GWIfcLongResp INTEGER
  telProdNpIec101GWIfcMultilink INTEGER
  telProdNpIec101GWIfcBuffNum INTEGER
  telProdNpIec101GWIfcOrigAddr INTEGER
  telProdNpIec101GWIfcRetransMax INTEGER
  telProdNpIec101GWIfcRetransTime INTEGER
  telProdNpIec101GWIfcRxTimeout INTEGER
  telProdNpIec101GWIfcSyncTime INTEGER
  telProdNpIec101GWIfcTestTime INTEGER
  telProdNpIec101GWIfcTestType INTEGER

TelProdNpIec101GWIfcRtuEntry  
SEQUENCE    
  telProdNpIec101GWIfcRtuIfcIndex INTEGER
  telProdNpIec101GWIfcRtuIndex INTEGER
  telProdNpIec101GWIfcRtuStatus INTEGER
  telProdNpIec101GWIfcRtuAddress INTEGER

Defined Values

telProdNpConfInterfIec101GW 1.3.6.1.4.1.2007.4.1.1.4.16
OBJECT IDENTIFIER    

telProdNpIec101GWTable 1.3.6.1.4.1.2007.4.1.1.4.16.1
Table of global configuration for IEC101 GW interfaces. Each row represents an interface
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TelProdNpIec101GWEntry

telProdNpIec101GWEntry 1.3.6.1.4.1.2007.4.1.1.4.16.1.1
A base list of objects that are configuration information about an IEC101 GW interface. The index is the number of the interface.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  TelProdNpIec101GWEntry  

telProdNpIec101GWIfcIndex 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.1
IEC101-GW interface index. It is the index table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpIec101GWIfcAsduCAddr 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.2
Set RTU ASDU common Adress for no multilink mode.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65534  

telProdNpIec101GWIfcBaudRate 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.3
Set baud reate for serial interface.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER a(300), b(600), c(1200), d(2400), e(4800), f(9600), g(19200), h(28800), i(38400), j(57600)  

telProdNpIec101GWIfcLinkAddr 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.4
Set RTU Link Adress for no multilink mode.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65534  

telProdNpIec101GWIfcLinkAddrSz 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.5
Set Link Adress field size.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

telProdNpIec101GWIfcLongResp 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.6
Enable sends long frame responses to RTU's.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  


telProdNpIec101GWIfcBuffNum 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.8
Configure number of IEC-101 transmission buffers.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..1024  

telProdNpIec101GWIfcOrigAddr 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.9
Configure IEC-101 Originator Address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65534  

telProdNpIec101GWIfcRetransMax 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.10
Configure maximum number of IEC-101 messages retransmissions.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..300  

telProdNpIec101GWIfcRetransTime 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.11
Configure time for IEC-101 messages retransmissions. Time in milliseconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10000  

telProdNpIec101GWIfcRxTimeout 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.12
Configure input frame timeout. Time in milliseconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10000  

telProdNpIec101GWIfcSyncTime 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.13
Configure period time to sent IEC-101 Synchronization message to RTU. Time in minutes
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..43200  

telProdNpIec101GWIfcTestTime 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.14
Configure period time to sent IEC-101 Link Test message to RTU. Time in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..86400  

telProdNpIec101GWIfcTestType 1.3.6.1.4.1.2007.4.1.1.4.16.1.1.15
Configure type of IEC-101 Link Test message to send to RTU. 0 Don't send message, 1 Send Test message, 2 Send Status message.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(0), test(1), status(2)  

telProdNpIec101GWIfcRtuTable 1.3.6.1.4.1.2007.4.1.1.4.16.2
Table of RTU Link Address configuration for IEC101 GW interfaces. There are two table indexes: the interface and the RTU index.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TelProdNpIec101GWIfcRtuEntry

telProdNpIec101GWIfcRtuEntry 1.3.6.1.4.1.2007.4.1.1.4.16.2.1
Each entry contains an RTU link address. Each entry consist on an interfece index and an RTU index.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  TelProdNpIec101GWIfcRtuEntry  

telProdNpIec101GWIfcRtuIfcIndex 1.3.6.1.4.1.2007.4.1.1.4.16.2.1.1
IEC101-GW interface index. It is the index table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpIec101GWIfcRtuIndex 1.3.6.1.4.1.2007.4.1.1.4.16.2.1.2
RTU table index.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

telProdNpIec101GWIfcRtuStatus 1.3.6.1.4.1.2007.4.1.1.4.16.2.1.3
Table control variable. Set to 1 does nothing. Set to 2 adds a new row (RTU link address) in the table with default value(65534) and returns 2. If it already exists, then it returns error. It must be added immediately after the last index. To greate a new row RTU address 65534 must not exist. After greate you must modify RTU address. Set to 3 deletes all table fields corresponding to that Agent, and returns 3. Get returns 1 if the control exists.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER valid(1), add(2), delete(3)  

telProdNpIec101GWIfcRtuAddress 1.3.6.1.4.1.2007.4.1.1.4.16.2.1.4
Set link address for a RTU in multilink mode. RTU link address can not be repeated. If address already exists, then it returns error.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65534