MITSUBISHI-UPS-MIB

File: MITSUBISHI-UPS-MIB.mib (39929 bytes)

Imported modules

RFC-1215 RFC1213-MIB RFC-1212
RFC1155-SMI

Imported symbols

TRAP-TYPE DisplayString OBJECT-TYPE
enterprises Gauge Counter
TimeTicks

Defined Types

PositiveInteger  
INTEGER    

NonNegativeInteger  
INTEGER    

TimeStamp  
TimeTicks    

TimeInterval  
INTEGER 0..2147483647    

TestAndIncr  
INTEGER 0..2147483647    

AutonomousType  
DisplayString    

UpsInputEntry  
SEQUENCE    
  upsInputLineIndex PositiveInteger
  upsInputFrequency NonNegativeInteger
  upsInputVoltage NonNegativeInteger
  upsInputCurrent NonNegativeInteger
  upsInputTruePower NonNegativeInteger

UpsOutputEntry  
SEQUENCE    
  upsOutputLineIndex PositiveInteger
  upsOutputVoltage NonNegativeInteger
  upsOutputCurrent NonNegativeInteger
  upsOutputPower NonNegativeInteger
  upsOutputPercentLoad INTEGER

UpsBypassEntry  
SEQUENCE    
  upsBypassLineIndex PositiveInteger
  upsBypassVoltage NonNegativeInteger
  upsBypassCurrent NonNegativeInteger
  upsBypassPower NonNegativeInteger

UpsAlarmEntry  
SEQUENCE    
  upsAlarmId PositiveInteger
  upsAlarmDescr AutonomousType
  upsAlarmTime TimeStamp

Defined Values

tag 1.3.6.1.4.1.13891
OBJECT IDENTIFIER    

mitsubishiUPS 1.3.6.1.4.1.13891.101
OBJECT IDENTIFIER    

upsIdent 1.3.6.1.4.1.13891.101.1
OBJECT IDENTIFIER    

upsIdentManufacturer 1.3.6.1.4.1.13891.101.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsIdentModel 1.3.6.1.4.1.13891.101.1.2
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsIdentUPSSoftwareVersion 1.3.6.1.4.1.13891.101.1.3
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsIdentAgentSoftwareVersion 1.3.6.1.4.1.13891.101.1.4
The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsIdentName 1.3.6.1.4.1.13891.101.1.5
A string identifying the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

upsIdentAttachedDevices 1.3.6.1.4.1.13891.101.1.6
A string identifying the devices attached to the output of the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

upsBattery 1.3.6.1.4.1.13891.101.2
OBJECT IDENTIFIER    

upsBatteryStatus 1.3.6.1.4.1.13891.101.2.1
The indication of the capacity remaining in the UPS batteries. A value of batteryNormal indicates a normal battery condition. A value of batteryLow indicates the remaining battery run-time will not maintain the output load for an extended period of time. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4)  

upsSecondsOnBattery 1.3.6.1.4.1.13891.101.2.2
If the unit is on battery power, the elapsed time in seconds since the UPS last switched to battery power, or the time since the network management system was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEstimatedMinutesRemaining 1.3.6.1.4.1.13891.101.2.3
An estimate of the time in minutes until the battery is depleted under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsEstimatedChargeRemaining 1.3.6.1.4.1.13891.101.2.4
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryVoltage 1.3.6.1.4.1.13891.101.2.5
The magnitude of the present battery voltage (0.1 Volt DC).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatteryCurrent 1.3.6.1.4.1.13891.101.2.6
The present battery current (0.1 Amp DC).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -2147483648..2147483647  

upsBatteryTemperature 1.3.6.1.4.1.13891.101.2.7
The ambient temperature at or near the UPS Battery casing (degrees Centigrade).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -2147483648..2147483647  

upsInput 1.3.6.1.4.1.13891.101.3
OBJECT IDENTIFIER    

upsInputLineBads 1.3.6.1.4.1.13891.101.3.1
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Counter  

upsInputNumLines 1.3.6.1.4.1.13891.101.3.2
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputTable 1.3.6.1.4.1.13891.101.3.3
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputEntry

upsInputEntry 1.3.6.1.4.1.13891.101.3.3.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputEntry  

upsInputLineIndex 1.3.6.1.4.1.13891.101.3.3.1.1
The input line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsInputFrequency 1.3.6.1.4.1.13891.101.3.3.1.2
The present input frequency (0.1 Hertz).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputVoltage 1.3.6.1.4.1.13891.101.3.3.1.3
The magnitude of the present input voltage (0.1 RMS Volt).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputCurrent 1.3.6.1.4.1.13891.101.3.3.1.4
The magnitude of the present input current (0.1 RMS Amp).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputTruePower 1.3.6.1.4.1.13891.101.3.3.1.5
The magnitude of the present input true power (watts).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutput 1.3.6.1.4.1.13891.101.4
OBJECT IDENTIFIER    

upsOutputSource 1.3.6.1.4.1.13891.101.4.1
The present source of output power. A value of none (2) indicates there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7)  

upsOutputFrequency 1.3.6.1.4.1.13891.101.4.2
The present output frequency (0.1 Hertz).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputNumLines 1.3.6.1.4.1.13891.101.4.3
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputTable 1.3.6.1.4.1.13891.101.4.4
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputEntry

upsOutputEntry 1.3.6.1.4.1.13891.101.4.4.1
An entry containing information applicable to a particular output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputEntry  

upsOutputLineIndex 1.3.6.1.4.1.13891.101.4.4.1.1
The output line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsOutputVoltage 1.3.6.1.4.1.13891.101.4.4.1.2
The present output voltage (0.1 RMS Volt).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputCurrent 1.3.6.1.4.1.13891.101.4.4.1.3
The present output current (0.1 RMS Amp).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputPower 1.3.6.1.4.1.13891.101.4.4.1.4
The present output true power (watts).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputPercentLoad 1.3.6.1.4.1.13891.101.4.4.1.5
The percentage of the UPS power capacity presently being used on this output line (the greater of the percent load of true power capacity and the percent load of VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypass 1.3.6.1.4.1.13891.101.5
OBJECT IDENTIFIER    

upsBypassFrequency 1.3.6.1.4.1.13891.101.5.1
The present bypass frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassNumLines 1.3.6.1.4.1.13891.101.5.2
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassTable 1.3.6.1.4.1.13891.101.5.3
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBypassEntry

upsBypassEntry 1.3.6.1.4.1.13891.101.5.3.1
An entry containing information applicable to a particular bypass input.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBypassEntry  

upsBypassLineIndex 1.3.6.1.4.1.13891.101.5.3.1.1
The bypass line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsBypassVoltage 1.3.6.1.4.1.13891.101.5.3.1.2
The present bypass voltage (0.1 RMS Volt).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassCurrent 1.3.6.1.4.1.13891.101.5.3.1.3
The present bypass current (0.1 RMS Amp).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassPower 1.3.6.1.4.1.13891.101.5.3.1.4
The present true power conveyed by the bypass (watts).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsAlarm 1.3.6.1.4.1.13891.101.6
OBJECT IDENTIFIER    

upsAlarmsPresent 1.3.6.1.4.1.13891.101.6.1
The present number of active alarm conditions.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

upsAlarmTable 1.3.6.1.4.1.13891.101.6.2
A list of alarm table entries. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAlarmEntry

upsAlarmEntry 1.3.6.1.4.1.13891.101.6.2.1
An entry containing information applicable to a particular alarm.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAlarmEntry  

upsAlarmId 1.3.6.1.4.1.13891.101.6.2.1.1
A unique identifier for an alarm condition. This value must remain constant.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsAlarmDescr 1.3.6.1.4.1.13891.101.6.2.1.2
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
Status: mandatory Access: read-only
OBJECT-TYPE    
  AutonomousType  

upsAlarmTime 1.3.6.1.4.1.13891.101.6.2.1.3
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

upsAlarmID 1.3.6.1.4.1.13891.101.6.4
A unique identifier for an alarm condition. This value must remain constant.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDESCR 1.3.6.1.4.1.13891.101.6.5
A reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm condition.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsWellKnownAlarms 1.3.6.1.4.1.13891.101.6.3
OBJECT IDENTIFIER    

upsAlarmBatteryBad 1.3.6.1.4.1.13891.101.6.3.1
One or more batteries have been determined to require replacement.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOnBattery 1.3.6.1.4.1.13891.101.6.3.2
The UPS is drawing power from the batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmLowBattery 1.3.6.1.4.1.13891.101.6.3.3
The remaining battery run-time is less than or equal to upsConfigLowBattTime.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDepletedBattery 1.3.6.1.4.1.13891.101.6.3.4
The UPS will be unable to sustain the present load when and if the utility power is lost.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmTempBad 1.3.6.1.4.1.13891.101.6.3.5
A temperature is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputBad 1.3.6.1.4.1.13891.101.6.3.6
An input condition is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputBad 1.3.6.1.4.1.13891.101.6.3.7
An output condition (other than OutputOverload) is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOverload 1.3.6.1.4.1.13891.101.6.3.8
The output load exceeds the UPS output capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOnBypass 1.3.6.1.4.1.13891.101.6.3.9
The Bypass is presently engaged on the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassBad 1.3.6.1.4.1.13891.101.6.3.10
The Bypass is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOffAsRequested 1.3.6.1.4.1.13891.101.6.3.11
The UPS has shut down as requested, i.e., the output is off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsOffAsRequested 1.3.6.1.4.1.13891.101.6.3.12
The entire UPS has shutdown as commanded.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmChargerFailed 1.3.6.1.4.1.13891.101.6.3.13
An uncorrected problem has been detected within the UPS charger subsystem.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsOutputOff 1.3.6.1.4.1.13891.101.6.3.14
The output of the UPS is in the off state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsSystemOff 1.3.6.1.4.1.13891.101.6.3.15
The UPS system is in the off state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmFanFailure 1.3.6.1.4.1.13891.101.6.3.16
The failure of one or more fans in the UPS has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmFuseFailure 1.3.6.1.4.1.13891.101.6.3.17
The failure of one or more fuses has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmGeneralFault 1.3.6.1.4.1.13891.101.6.3.18
A general fault in the UPS has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDiagnosticTestFailed 1.3.6.1.4.1.13891.101.6.3.19
The result of the last diagnostic test indicates a failure.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmCommunicationsLost 1.3.6.1.4.1.13891.101.6.3.20
A problem has been encountered in the communications between the agent and the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAwaitingPower 1.3.6.1.4.1.13891.101.6.3.21
The UPS output is off and the UPS is awaiting the return of input power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShutdownPending 1.3.6.1.4.1.13891.101.6.3.22
A upsShutdownAfterDelay countdown is underway.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShutdownImminent 1.3.6.1.4.1.13891.101.6.3.23
The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmTestInProgress 1.3.6.1.4.1.13891.101.6.3.24
A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTest 1.3.6.1.4.1.13891.101.7
OBJECT IDENTIFIER    

upsTestId 1.3.6.1.4.1.13891.101.7.1
The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of a test, including the well known tests identified in this document.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OBJECT IDENTIFIER  

upsTestSpinLock 1.3.6.1.4.1.13891.101.7.2
A spin lock on the test subsystem.
Status: mandatory Access: read-write
OBJECT-TYPE    
  TestAndIncr  

upsTestResultsSummary 1.3.6.1.4.1.13891.101.7.3
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6)  

upsTestResultsDetail 1.3.6.1.4.1.13891.101.7.4
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsTestStartTime 1.3.6.1.4.1.13891.101.7.5
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

upsTestElapsedTime 1.3.6.1.4.1.13891.101.7.6
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeInterval  

upsWellKnownTests 1.3.6.1.4.1.13891.101.7.7
OBJECT IDENTIFIER    

upsTestNoTestsInitiated 1.3.6.1.4.1.13891.101.7.7.1
No tests have been initiated and no test is in progress.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestAbortTestInProgress 1.3.6.1.4.1.13891.101.7.7.2
The test in progress is to be aborted / the test in progress was aborted.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestGeneralSystemsTest 1.3.6.1.4.1.13891.101.7.7.3
The manufacturer's standard test of UPS device systems.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestQuickBatteryTest 1.3.6.1.4.1.13891.101.7.7.4
A test that is sufficient to determine if the battery needs replacement.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestDeepBatteryCalibration 1.3.6.1.4.1.13891.101.7.7.5
The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsControl 1.3.6.1.4.1.13891.101.8
OBJECT IDENTIFIER    

upsShutdownType 1.3.6.1.4.1.13891.101.8.1
This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER output(1), system(2)  

upsShutdownAfterDelay 1.3.6.1.4.1.13891.101.8.2
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsStartupAfterDelay 1.3.6.1.4.1.13891.101.8.3
Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsRebootWithDuration 1.3.6.1.4.1.13891.101.8.4
Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsAutoRestart 1.3.6.1.4.1.13891.101.8.5
Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

upsConfig 1.3.6.1.4.1.13891.101.9
OBJECT IDENTIFIER    

upsConfigInputVoltage 1.3.6.1.4.1.13891.101.9.1
The magnitude of the nominal input voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigInputFreq 1.3.6.1.4.1.13891.101.9.2
The nominal input frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigOutputVoltage 1.3.6.1.4.1.13891.101.9.3
The magnitude of the nominal output voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigOutputFreq 1.3.6.1.4.1.13891.101.9.4
The nominal output frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigOutputVA 1.3.6.1.4.1.13891.101.9.5
The magnitude of the nominal Volt-Amp rating (Volt-Amps).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigOutputPower 1.3.6.1.4.1.13891.101.9.6
The magnitude of the nominal true power rating (watts).
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigLowBattTime 1.3.6.1.4.1.13891.101.9.7
The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigAudibleStatus 1.3.6.1.4.1.13891.101.9.8
The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2), muted(3)  

upsConfigLowVoltageTransferPoint 1.3.6.1.4.1.13891.101.9.9
The minimum input line voltage (RMS Volts) allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigHighVoltageTransferPoint 1.3.6.1.4.1.13891.101.9.10
The maximum line voltage (RMS Volts) allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsTrapInfo 1.3.6.1.4.1.13891.101.10
OBJECT IDENTIFIER    

trapCode 1.3.6.1.4.1.13891.101.10.1
A number identifying the event for that last trap that was sent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

trapDescription 1.3.6.1.4.1.13891.101.10.2
A string identifying the event for that last trap that was sent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

alarmCritical 1
Critical alarm.
TRAP-TYPE    

alarmWarning 2
Warning alarm.
TRAP-TYPE    

alarmInformation 3
Information alarm.
TRAP-TYPE    

upsAlarmCleared 4
Alarm cleared.
TRAP-TYPE    

upsTrapInitialization 5
This trap is sent each time a NetCom device is initialized.
TRAP-TYPE