LHX-MIB

File: LHX-MIB.mib (36455 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC
INET-ADDRESS-MIB RFC1213-MIB

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises Integer32 Unsigned32
MODULE-COMPLIANCE OBJECT-GROUP NOTIFICATION-GROUP
TEXTUAL-CONVENTION DisplayString TruthValue
InetAddressType InetAddress InetPortNumber
sysContact sysName sysLocation

Defined Types

OperationalStateEnumeration  
The operational states of an lhx controller.
TEXTUAL-CONVENTION    
  INTEGER disconnected(0), offline(1), online(2)  

GwSensorTypeEnumeration  
The types an lhx sensor can be.
TEXTUAL-CONVENTION    
  INTEGER airTemperature(0), waterTemperature(1), fanSpeed(2), doorContact(3), valvePosition(4)  

SensorUnitsEnumeration  
The units an lhx sensor can be.
TEXTUAL-CONVENTION    
  INTEGER none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19)  

SensorStateEnumeration  
The states a sensor can be in.
TEXTUAL-CONVENTION    
  INTEGER unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11)  

SensorCountEntryStruct  
SEQUENCE    
  sensorCount Integer32

LhxConfigurationEntryStruct  
SEQUENCE    
  operationalState OperationalStateEnumeration
  setpointVentilators Integer32
  setpointWaterValve Integer32
  defaultFanSpeed Integer32
  maximumCoolingState TruthValue
  alertState TruthValue
  model DisplayString
  fwVersion DisplayString

SensorConfigurationEntryStruct  
SEQUENCE    
  portIdx Integer32
  sensorTypeIdx Integer32
  sensorIdx Integer32
  sensorLabel DisplayString
  sensorUnit SensorUnitsEnumeration
  sensorDecimalDigits Unsigned32
  sensorMaximum Integer32
  sensorMinimum Integer32
  sensorHysteresis Unsigned32
  sensorLowerCriticalThreshold Integer32
  sensorLowerWarningThreshold Integer32
  sensorUpperCriticalThreshold Integer32
  sensorUpperWarningThreshold Integer32
  sensorEnabledThresholds BITS
  sensorThresholdMaximum Integer32
  sensorThresholdMinimum Integer32
  sensorName DisplayString

SensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsSensorIsAvailable TruthValue
  measurementsSensorState SensorStateEnumeration
  measurementsSensorValue Integer32
  measurementsSensorTimeStamp Unsigned32

Defined Values

raritan 1.3.6.1.4.1.13742
This MIB describes the SNMP functions of the Schroff Varistar LHX heat exchanger supported by Raritan devices.
MODULE-IDENTITY    

lhxgw 1.3.6.1.4.1.13742.9
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.13742.9.0
OBJECT IDENTIFIER    

configuration 1.3.6.1.4.1.13742.9.1
OBJECT IDENTIFIER    

measurements 1.3.6.1.4.1.13742.9.2
OBJECT IDENTIFIER    

conformance 1.3.6.1.4.1.13742.9.3
OBJECT IDENTIFIER    

lhx 1.3.6.1.4.1.13742.9.1.3
OBJECT IDENTIFIER    

gwSensors 1.3.6.1.4.1.13742.9.1.4
OBJECT IDENTIFIER    

trapInformation 1.3.6.1.4.1.13742.9.0.0
OBJECT IDENTIFIER    

compliances 1.3.6.1.4.1.13742.9.3.1
OBJECT IDENTIFIER    

groups 1.3.6.1.4.1.13742.9.3.2
OBJECT IDENTIFIER    

lhxSensorFailure 1.3.6.1.4.1.13742.9.0.1
A sensor failure (broken or short circuit) occurred.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxFanFailure 1.3.6.1.4.1.13742.9.0.2
A fan motor failure occurred.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxPowerSupplyFailure 1.3.6.1.4.1.13742.9.0.3
A power supply failure occurred.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxThresholdAirOutlet 1.3.6.1.4.1.13742.9.0.4
The air outlet temperature threshold was crossed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxThresholdAirInlet 1.3.6.1.4.1.13742.9.0.5
The air inlet temperature threshold was crossed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxThresholdWaterInlet 1.3.6.1.4.1.13742.9.0.6
The water inlet temperature threshold was crossed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxDoorOpened 1.3.6.1.4.1.13742.9.0.7
The door was opened.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxMaximumCoolingRequest 1.3.6.1.4.1.13742.9.0.8
Maximum cooling was requested.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxEmergencyCooling 1.3.6.1.4.1.13742.9.0.9
Emergency cooling was activated.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxWaterLeak 1.3.6.1.4.1.13742.9.0.10
Water leakage was detected.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxThresholdHumidity 1.3.6.1.4.1.13742.9.0.11
The humidity threshold was crossed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxExternalWaterCoolingFailure 1.3.6.1.4.1.13742.9.0.12
An external water cooling failure occurred.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxThresholdWaterOutlet 1.3.6.1.4.1.13742.9.0.13
The water outlet temperature threshold was crossed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxParameterDataLoss 1.3.6.1.4.1.13742.9.0.14
Data loss in parameter memory was detected.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxStBusError 1.3.6.1.4.1.13742.9.0.15
An ST-Bus communication error was detected.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxCollectiveFault 1.3.6.1.4.1.13742.9.0.16
An error was detected.
Status: current Access: read-only
NOTIFICATION-TYPE    

gwSensorStateChange 1.3.6.1.4.1.13742.9.0.17
Sensor State Change.
Status: current Access: read-only
NOTIFICATION-TYPE    

gwLhxOperationalStateChange 1.3.6.1.4.1.13742.9.0.18
Operational State Change.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxVoltageLow 1.3.6.1.4.1.13742.9.0.19
The supply voltage of an LHX became low.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxBaseElectronicsFailure 1.3.6.1.4.1.13742.9.0.20
The base electronics of an LHX controller failed.
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxCondenserPumpFailure 1.3.6.1.4.1.13742.9.0.21
An LHX condenser pump failed.
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceName 1.3.6.1.4.1.13742.9.0.0.1
The user-defined name for the Device.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

deviceInetAddressType 1.3.6.1.4.1.13742.9.0.0.2
The type of address format
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  InetAddressType  

deviceInetIPAddress 1.3.6.1.4.1.13742.9.0.0.3
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  InetAddress  

lhxErrorCode 1.3.6.1.4.1.13742.9.0.0.4
The LHX error code (F1 - F25, EP).
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

portId 1.3.6.1.4.1.13742.9.0.0.5
A unique value for the physical port, the LHX controlller is connected to. Its value ranges between 1 and the value of portCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

probeId 1.3.6.1.4.1.13742.9.0.0.6
The physical Sensor ID (F1 - F7).
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

fanId 1.3.6.1.4.1.13742.9.0.0.7
The Fan ID (M1 - M6).
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

powerSupplyId 1.3.6.1.4.1.13742.9.0.0.8
The Power Supply ID (1, 2).
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

oldSensorState 1.3.6.1.4.1.13742.9.0.0.9
The old sensor state used in Sensor State Transition traps.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  SensorStateEnumeration  

sensorTypeId 1.3.6.1.4.1.13742.9.0.0.10
A unique value for the type of sensor.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  GwSensorTypeEnumeration  

sensorId 1.3.6.1.4.1.13742.9.0.0.11
A unique value for each sensor. Its value ranges between 1 and the value of sensorCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

oldOperationalState 1.3.6.1.4.1.13742.9.0.0.12
The old operational state used in Operational State Transition traps.
Status: current Access: read-only
OBJECT-TYPE    
  OperationalStateEnumeration  

agentInetPortNumber 1.3.6.1.4.1.13742.9.0.0.13
The UDP port number used for accessing the SNMP agent on the device. Examples: If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to portForwarding, then master: 50500 slave 1:50501 slave 2: 50502 ...... If cascading mode is not portForwarding and default (Standard) ports are being used, then port: 161
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  InetPortNumber  

portCount 1.3.6.1.4.1.13742.9.1.1
The number of lhx units supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..255  

sensorCountTable 1.3.6.1.4.1.13742.9.1.2
A list of lhx sensor count extries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SensorCountEntryStruct

sensorCountEntry 1.3.6.1.4.1.13742.9.1.2.1
An entry containing the number of lhx sensors of a certain type.
Status: current Access: not-accessible
OBJECT-TYPE    
  SensorCountEntryStruct  

sensorCount 1.3.6.1.4.1.13742.9.1.2.1.1
The number of sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lhxConfigurationTable 1.3.6.1.4.1.13742.9.1.3.1
A list of lhx controller configuration extries. The number of entries is given by the value of portCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LhxConfigurationEntryStruct

lhxConfigurationEntry 1.3.6.1.4.1.13742.9.1.3.1.1
An entry containing parameters for an lhx.
Status: current Access: not-accessible
OBJECT-TYPE    
  LhxConfigurationEntryStruct  

operationalState 1.3.6.1.4.1.13742.9.1.3.1.1.1
The operational state of the lhx controller. To switch LHX power state while controller is connected, set operationalState to 1 (off) or 2 (on). Switching power state while LHX is disconnected or to 0 (disconnected) is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  OperationalStateEnumeration  

setpointVentilators 1.3.6.1.4.1.13742.9.1.3.1.1.2
The setpoint of the ventilators.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

setpointWaterValve 1.3.6.1.4.1.13742.9.1.3.1.1.3
The setpoint of the water valve.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

defaultFanSpeed 1.3.6.1.4.1.13742.9.1.3.1.1.4
The 'default' fan speed during normal operation in per mill. Default is 80% (= 800).
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

maximumCoolingState 1.3.6.1.4.1.13742.9.1.3.1.1.5
Indicates whether maximum cooling was requested or not. To request maximum cooling, set maximumCoolingState to 1 (true). Setting maximumCoolingState to 2 (false) is undefined, set alertState to 2 (false) instead.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

alertState 1.3.6.1.4.1.13742.9.1.3.1.1.6
Indicates whether LHX controler is in alert state or not. To acknowledge alert status, set alertState to 2 (false). Setting alertState to 1 (true) is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

model 1.3.6.1.4.1.13742.9.1.3.1.1.7
The model indentifier of an LHX controller.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

fwVersion 1.3.6.1.4.1.13742.9.1.3.1.1.8
The firmware version of an LHX controller.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

sensorConfigurationTable 1.3.6.1.4.1.13742.9.1.4.1
A list of lhx sensor configuration extries. The number of entries is given by the value of portCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SensorConfigurationEntryStruct

sensorConfigurationEntry 1.3.6.1.4.1.13742.9.1.4.1.1
An entry containing parameters for an lhx.
Status: current Access: not-accessible
OBJECT-TYPE    
  SensorConfigurationEntryStruct  

portIdx 1.3.6.1.4.1.13742.9.1.4.1.1.1
A unique value for each port. Its value ranges between 1 and the value of portCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

sensorTypeIdx 1.3.6.1.4.1.13742.9.1.4.1.1.2
A unique value for the type of sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

sensorIdx 1.3.6.1.4.1.13742.9.1.4.1.1.3
A unique value for each sensor. Its value ranges between 1 and the value of sensorCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

sensorLabel 1.3.6.1.4.1.13742.9.1.4.1.1.4
The short ID of the sensor (e.g. F1, M2).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

sensorUnit 1.3.6.1.4.1.13742.9.1.4.1.1.5
The base units. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

sensorDecimalDigits 1.3.6.1.4.1.13742.9.1.4.1.1.6
The number of digits displayed to the right of the decimal point. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

sensorMaximum 1.3.6.1.4.1.13742.9.1.4.1.1.7
The largest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

sensorMinimum 1.3.6.1.4.1.13742.9.1.4.1.1.8
The smallest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

sensorHysteresis 1.3.6.1.4.1.13742.9.1.4.1.1.9
The hysteresis used for deassertions. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

sensorLowerCriticalThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.10
The lower critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorLowerWarningThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.11
The lower non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorUpperCriticalThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.12
The upper critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorUpperWarningThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.13
The upper non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorEnabledThresholds 1.3.6.1.4.1.13742.9.1.4.1.1.14
A bit string which indicates which thresholds are enabled. This parameter does not apply to state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

sensorThresholdMaximum 1.3.6.1.4.1.13742.9.1.4.1.1.15
The largest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

sensorThresholdMinimum 1.3.6.1.4.1.13742.9.1.4.1.1.16
The smallest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

sensorName 1.3.6.1.4.1.13742.9.1.4.1.1.17
The descriptive ID of the sensor (e.g. Fan Speed 1).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

sensorMeasurementsTable 1.3.6.1.4.1.13742.9.2.1
A list of external sensor entries. The number of entries is given by the value of sensorCount for the LHX.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SensorMeasurementsEntryStruct

sensorMeasurementsEntry 1.3.6.1.4.1.13742.9.2.1.1
An entry containing measurement objects for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SensorMeasurementsEntryStruct  

measurementsSensorIsAvailable 1.3.6.1.4.1.13742.9.2.1.1.1
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsSensorState 1.3.6.1.4.1.13742.9.2.1.1.2
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsSensorValue 1.3.6.1.4.1.13742.9.2.1.1.3
The sensor reading. This parameter does not apply to state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

measurementsSensorTimeStamp 1.3.6.1.4.1.13742.9.2.1.1.4
The sensor reading timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

complianceRev1 1.3.6.1.4.1.13742.9.3.1.1
The requirements for conformance to the LHX-MIB.
Status: current Access: read-only
MODULE-COMPLIANCE    

configurationGroup 1.3.6.1.4.1.13742.9.3.2.1
A collection of objects representing configuration data.
Status: current Access: read-only
OBJECT-GROUP    

measurementsGroup 1.3.6.1.4.1.13742.9.3.2.2
A collection of objects providing the measurement capability of LHX.
Status: current Access: read-only
OBJECT-GROUP    

trapInformationGroup 1.3.6.1.4.1.13742.9.3.2.3
A collection of objects providing information in the traps.
Status: current Access: read-only
OBJECT-GROUP    

trapsGroup 1.3.6.1.4.1.13742.9.3.2.4
A collection of traps.
Status: current Access: read-only
NOTIFICATION-GROUP