IT-WATCHDOGS-MIB

File: IT-WATCHDOGS-MIB.mib (124063 bytes)

Imported modules

SNMPv2-TC SNMPv2-SMI RFC-1215

Imported symbols

DisplayString TruthValue MODULE-IDENTITY
OBJECT-TYPE enterprises Unsigned32
TRAP-TYPE

Defined Types

ClimateEntry  
SEQUENCE    
  climateIndex INTEGER 1..1
  climateSerial DisplayString
  climateName DisplayString
  climateAvail Unsigned32
  climateTempC INTEGER -40..123
  climateHumidity INTEGER 0..100
  climateAirflow INTEGER 0..100
  climateLight INTEGER 0..100
  climateSound INTEGER 0..100
  climateIO1 INTEGER 0..100
  climateIO2 INTEGER 0..100
  climateIO3 INTEGER 0..100

PowerMonitorEntry  
SEQUENCE    
  powMonIndex INTEGER 1..100
  powMonSerial DisplayString
  powMonName DisplayString
  powMonAvail Unsigned32
  powMonKWattHrs Unsigned32
  powMonVolts Unsigned32
  powMonVoltMax Unsigned32
  powMonVoltMin Unsigned32
  powMonVoltPeak Unsigned32
  powMonDeciAmps Unsigned32
  powMonRealPower Unsigned32
  powMonApparentPower Unsigned32
  powMonPowerFactor INTEGER 0..100
  powMonDeciAmpsOutlet1 INTEGER 0..100
  powMonDeciAmpsOutlet2 INTEGER 0..100

TempSensorEntry  
SEQUENCE    
  tempSensorIndex INTEGER 1..100
  tempSensorSerial DisplayString
  tempSensorName DisplayString
  tempSensorAvail Unsigned32
  tempSensorTempC INTEGER -40..123

AirFlowSensorEntry  
SEQUENCE    
  airFlowSensorIndex INTEGER 1..100
  airFlowSensorSerial DisplayString
  airFlowSensorName DisplayString
  airFlowSensorAvail Unsigned32
  airFlowSensorFlow INTEGER 0..100
  airFlowSensorTempC INTEGER -50..100
  airFlowSensorHumidity INTEGER 0..100
  airFlowSensorDewPoint INTEGER -40..123

PowerOnlyEntry  
SEQUENCE    
  powerIndex INTEGER 1..100
  powerSerial DisplayString
  powerName DisplayString
  powerAvail Unsigned32
  powerVolts Unsigned32
  powerDeciAmps Unsigned32
  powerRealPower Unsigned32
  powerApparentPower Unsigned32
  powerPowerFactor INTEGER 0..100

DoorSensorEntry  
SEQUENCE    
  doorSensorIndex INTEGER 1..100
  doorSensorSerial DisplayString
  doorSensorName DisplayString
  doorSensorAvail Unsigned32
  doorSensorStatus INTEGER 0..100

WaterSensorEntry  
SEQUENCE    
  waterSensorIndex INTEGER 1..100
  waterSensorSerial DisplayString
  waterSensorName DisplayString
  waterSensorAvail Unsigned32
  waterSensorDampness INTEGER 0..100

CurrentMonitorEntry  
SEQUENCE    
  currentMonitorIndex INTEGER 1..100
  currentMonitorSerial DisplayString
  currentMonitorName DisplayString
  currentMonitorAvail Unsigned32
  currentMonitorDeciAmps INTEGER 0..30

MillivoltMonitorEntry  
SEQUENCE    
  millivoltMonitorIndex INTEGER 1..100
  millivoltMonitorSerial DisplayString
  millivoltMonitorName DisplayString
  millivoltMonitorAvail Unsigned32
  millivoltMonitorMV INTEGER 0..5000

Power3ChEntry  
SEQUENCE    
  pow3ChIndex INTEGER 1..100
  pow3ChSerial DisplayString
  pow3ChName DisplayString
  pow3ChAvail Unsigned32
  pow3ChKWattHrsA Unsigned32
  pow3ChVoltsA Unsigned32
  pow3ChVoltMaxA Unsigned32
  pow3ChVoltMinA Unsigned32
  pow3ChVoltPeakA Unsigned32
  pow3ChDeciAmpsA Unsigned32
  pow3ChRealPowerA Unsigned32
  pow3ChApparentPowerA Unsigned32
  pow3ChPowerFactorA INTEGER 0..100
  pow3ChKWattHrsB Unsigned32
  pow3ChVoltsB Unsigned32
  pow3ChVoltMaxB Unsigned32
  pow3ChVoltMinB Unsigned32
  pow3ChVoltPeakB Unsigned32
  pow3ChDeciAmpsB Unsigned32
  pow3ChRealPowerB Unsigned32
  pow3ChApparentPowerB Unsigned32
  pow3ChPowerFactorB INTEGER 0..100
  pow3ChKWattHrsC Unsigned32
  pow3ChVoltsC Unsigned32
  pow3ChVoltMaxC Unsigned32
  pow3ChVoltMinC Unsigned32
  pow3ChVoltPeakC Unsigned32
  pow3ChDeciAmpsC Unsigned32
  pow3ChRealPowerC Unsigned32
  pow3ChApparentPowerC Unsigned32
  pow3ChPowerFactorC INTEGER 0..100

OutletEntry  
SEQUENCE    
  outletIndex INTEGER 1..100
  outletSerial DisplayString
  outletName DisplayString
  outletAvail Unsigned32
  outlet1Status INTEGER 0..100
  outlet2Status INTEGER 0..100

VsfcEntry  
SEQUENCE    
  vsfcIndex INTEGER 1..1
  vsfcSerial DisplayString
  vsfcName DisplayString
  vsfcAvail Unsigned32
  vsfcSetPointC INTEGER 18..38
  vsfcIntTempC INTEGER -20..50
  vsfcExt1TempC INTEGER -20..50
  vsfcExt2TempC INTEGER -20..50
  vsfcExt3TempC INTEGER -20..50
  vsfcExt4TempC INTEGER -20..50
  vsfcFanSpeed INTEGER 0..100

Ctrl3ChEntry  
SEQUENCE    
  ctrl3ChIndex INTEGER 1..1
  ctrl3ChSerial DisplayString
  ctrl3ChName DisplayString
  ctrl3ChAvail Unsigned32
  ctrl3ChVoltsA Unsigned32
  ctrl3ChVoltPeakA Unsigned32
  ctrl3ChDeciAmpsA Unsigned32
  ctrl3ChDeciAmpsPeakA Unsigned32
  ctrl3ChRealPowerA Unsigned32
  ctrl3ChApparentPowerA Unsigned32
  ctrl3ChPowerFactorA INTEGER 0..100
  ctrl3ChVoltsB Unsigned32
  ctrl3ChVoltPeakB Unsigned32
  ctrl3ChDeciAmpsB Unsigned32
  ctrl3ChDeciAmpsPeakB Unsigned32
  ctrl3ChRealPowerB Unsigned32
  ctrl3ChApparentPowerB Unsigned32
  ctrl3ChPowerFactorB INTEGER 0..100
  ctrl3ChVoltsC Unsigned32
  ctrl3ChVoltPeakC Unsigned32
  ctrl3ChDeciAmpsC Unsigned32
  ctrl3ChDeciAmpsPeakC Unsigned32
  ctrl3ChRealPowerC Unsigned32
  ctrl3ChApparentPowerC Unsigned32
  ctrl3ChPowerFactorC INTEGER 0..100

CtrlGrpAmpsEntry  
SEQUENCE    
  ctrlGrpAmpsIndex INTEGER 1..1
  ctrlGrpAmpsSerial DisplayString
  ctrlGrpAmpsName DisplayString
  ctrlGrpAmpsAvail Unsigned32
  ctrlGrpAmpsA Unsigned32
  ctrlGrpAmpsB Unsigned32
  ctrlGrpAmpsC Unsigned32
  ctrlGrpAmpsD Unsigned32
  ctrlGrpAmpsE Unsigned32
  ctrlGrpAmpsF Unsigned32

CtrlOutletEntry  
SEQUENCE    
  ctrlOutletIndex INTEGER 1..100
  ctrlOutletName DisplayString
  ctrlOutletStatus Unsigned32
  ctrlOutletFeedback Unsigned32
  ctrlOutletPending Unsigned32
  ctrlOutletDeciAmps Unsigned32
  ctrlOutletGroup DisplayString
  ctrlOutletUpDelay Unsigned32
  ctrlOutletDwnDelay Unsigned32
  ctrlOutletRbtDelay Unsigned32
  ctrlOutletURL DisplayString
  ctrlOutletPOAAction Unsigned32
  ctrlOutletPOADelay Unsigned32

DewPointSensorEntry  
SEQUENCE    
  dewPointSensorIndex INTEGER 1..100
  dewPointSensorSerial DisplayString
  dewPointSensorName DisplayString
  dewPointSensorAvail Unsigned32
  dewPointSensorDewPoint INTEGER -40..123
  dewPointSensorTempC INTEGER -40..123
  dewPointSensorHumidity INTEGER 0..100

DigitalSensorEntry  
SEQUENCE    
  digitalSensorIndex INTEGER 1..100
  digitalSensorSerial DisplayString
  digitalSensorName DisplayString
  digitalSensorAvail Unsigned32
  digitalSensorDigital INTEGER 0..100

DstsEntry  
SEQUENCE    
  dstsIndex INTEGER 1..1
  dstsSerial DisplayString
  dstsName DisplayString
  dstsAvail Unsigned32
  dstsVoltsA Unsigned32
  dstsAmpsA Unsigned32
  dstsVoltsB Unsigned32
  dstsAmpsB Unsigned32
  dstsSourceAActive Unsigned32
  dstsSourceBActive Unsigned32
  dstsPowerStatusA Unsigned32
  dstsPowerStatusB Unsigned32
  dstsSourceATempC INTEGER -20..50
  dstsSourceBTempC INTEGER -20..50

CpmSensorEntry  
SEQUENCE    
  cpmSensorIndex INTEGER 1..100
  cpmSensorSerial DisplayString
  cpmSensorName DisplayString
  cpmSensorAvail Unsigned32
  cpmSensorStatus INTEGER 0..100

SmokeAlarmEntry  
SEQUENCE    
  smokeAlarmIndex INTEGER 1..100
  smokeAlarmSerial DisplayString
  smokeAlarmName DisplayString
  smokeAlarmAvail Unsigned32
  smokeAlarmStatus INTEGER 0..100

Neg48VdcSensorEntry  
SEQUENCE    
  neg48VdcSensorIndex INTEGER 1..100
  neg48VdcSensorSerial DisplayString
  neg48VdcSensorName DisplayString
  neg48VdcSensorAvail Unsigned32
  neg48VdcSensorVoltage INTEGER -100..10

Pos30VdcSensorEntry  
SEQUENCE    
  pos30VdcSensorIndex INTEGER 1..100
  pos30VdcSensorSerial DisplayString
  pos30VdcSensorName DisplayString
  pos30VdcSensorAvail Unsigned32
  pos30VdcSensorVoltage INTEGER -10..100

AnalogSensorEntry  
SEQUENCE    
  analogSensorIndex INTEGER 1..100
  analogSensorSerial DisplayString
  analogSensorName DisplayString
  analogSensorAvail Unsigned32
  analogSensorAnalog INTEGER 0..100

Ctrl3ChIECEntry  
SEQUENCE    
  ctrl3ChIECIndex INTEGER 1..100
  ctrl3ChIECSerial DisplayString
  ctrl3ChIECName DisplayString
  ctrl3ChIECAvail Unsigned32
  ctrl3ChIECKWattHrsA Unsigned32
  ctrl3ChIECVoltsA Unsigned32
  ctrl3ChIECVoltPeakA Unsigned32
  ctrl3ChIECDeciAmpsA Unsigned32
  ctrl3ChIECDeciAmpsPeakA Unsigned32
  ctrl3ChIECRealPowerA Unsigned32
  ctrl3ChIECApparentPowerA Unsigned32
  ctrl3ChIECPowerFactorA INTEGER 0..100
  ctrl3ChIECKWattHrsB Unsigned32
  ctrl3ChIECVoltsB Unsigned32
  ctrl3ChIECVoltPeakB Unsigned32
  ctrl3ChIECDeciAmpsB Unsigned32
  ctrl3ChIECDeciAmpsPeakB Unsigned32
  ctrl3ChIECRealPowerB Unsigned32
  ctrl3ChIECApparentPowerB Unsigned32
  ctrl3ChIECPowerFactorB INTEGER 0..100
  ctrl3ChIECKWattHrsC Unsigned32
  ctrl3ChIECVoltsC Unsigned32
  ctrl3ChIECVoltPeakC Unsigned32
  ctrl3ChIECDeciAmpsC Unsigned32
  ctrl3ChIECDeciAmpsPeakC Unsigned32
  ctrl3ChIECRealPowerC Unsigned32
  ctrl3ChIECApparentPowerC Unsigned32
  ctrl3ChIECPowerFactorC INTEGER 0..100

AirSpeedSwitchSensorEntry  
SEQUENCE    
  airSpeedSwitchSensorIndex INTEGER 1..100
  airSpeedSwitchSensorSerial DisplayString
  airSpeedSwitchSensorName DisplayString
  airSpeedSwitchSensorAvail Unsigned32
  airSpeedSwitchSensorAirSpeed INTEGER 0..100

Defined Values

itwatchdogs 1.3.6.1.4.1.17373
The MIB for I.T. Watchdogs Products
MODULE-IDENTITY    

itwatchdogs 1.3.6.1.4.1.17373
OBJECT IDENTIFIER    

wxGoos 1.3.6.1.4.1.17373.2
OBJECT IDENTIFIER    

deviceInfo 1.3.6.1.4.1.17373.2.1
OBJECT IDENTIFIER    

productTitle 1.3.6.1.4.1.17373.2.1.1
Product name
OBJECT-TYPE    
  DisplayString  

productVersion 1.3.6.1.4.1.17373.2.1.2
Product version
OBJECT-TYPE    
  DisplayString  

productFriendlyName 1.3.6.1.4.1.17373.2.1.3
User-assigned name
OBJECT-TYPE    
  DisplayString  

productMacAddress 1.3.6.1.4.1.17373.2.1.4
Product's unique MAC address
OBJECT-TYPE    
  DisplayString  

productUrl 1.3.6.1.4.1.17373.2.1.5
Product's main URL access point
OBJECT-TYPE    
  DisplayString  

alarmTripType 1.3.6.1.4.1.17373.2.1.6
Type of alarm trip. 0 = None, 1 = Low, 2 = High, 3 = Unplugged
OBJECT-TYPE    
  INTEGER 0..9  

productHardware 1.3.6.1.4.1.17373.2.1.7
Product's hardware type
OBJECT-TYPE    
  DisplayString  

sensorCountsBase 1.3.6.1.4.1.17373.2.1.8
OBJECT IDENTIFIER    

sensorCounts 1.3.6.1.4.1.17373.2.1.8.1
OBJECT IDENTIFIER    

climateCount 1.3.6.1.4.1.17373.2.1.8.1.2
Number of climate monitors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

powerMonitorCount 1.3.6.1.4.1.17373.2.1.8.1.3
Number of power monitors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

tempSensorCount 1.3.6.1.4.1.17373.2.1.8.1.4
Number of temperature sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

airflowSensorCount 1.3.6.1.4.1.17373.2.1.8.1.5
Number of airflow sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

powerOnlyCount 1.3.6.1.4.1.17373.2.1.8.1.6
Number of power only monitors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

doorSensorCount 1.3.6.1.4.1.17373.2.1.8.1.7
Number of door sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

waterSensorCount 1.3.6.1.4.1.17373.2.1.8.1.8
Number of water sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

currentSensorCount 1.3.6.1.4.1.17373.2.1.8.1.9
Number of current sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

millivoltSensorCount 1.3.6.1.4.1.17373.2.1.8.1.10
Number of millivolt sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

power3ChSensorCount 1.3.6.1.4.1.17373.2.1.8.1.11
Number of 3 channel power monitors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

outletCount 1.3.6.1.4.1.17373.2.1.8.1.12
Number of outlets currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

vsfcCount 1.3.6.1.4.1.17373.2.1.8.1.13
Number of fan controller monitors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

ctrl3ChCount 1.3.6.1.4.1.17373.2.1.8.1.14
Number of 3 channel controllers currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

ctrlGrpAmpsCount 1.3.6.1.4.1.17373.2.1.8.1.15
Number of amperage controllers currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

ctrlOutputCount 1.3.6.1.4.1.17373.2.1.8.1.16
Number of output controllers currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

dewpointSensorCount 1.3.6.1.4.1.17373.2.1.8.1.17
Number of dewpoint sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

digitalSensorCount 1.3.6.1.4.1.17373.2.1.8.1.18
Number of digital sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

dstsSensorCount 1.3.6.1.4.1.17373.2.1.8.1.19
Number of DSTS controllers currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

cpmSensorCount 1.3.6.1.4.1.17373.2.1.8.1.20
Number of city power sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

smokeAlarmSensorCount 1.3.6.1.4.1.17373.2.1.8.1.21
Number of smoke alarm sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

neg48VdcSensorCount 1.3.6.1.4.1.17373.2.1.8.1.22
Number of -48Vdc sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

pos30VdcSensorCount 1.3.6.1.4.1.17373.2.1.8.1.23
Number of 30Vdc sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

analogSensorCount 1.3.6.1.4.1.17373.2.1.8.1.24
Number of remote analog inputs currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

ctrl3ChIECCount 1.3.6.1.4.1.17373.2.1.8.1.25
Number of IEC 3 channel controllers currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

airSpeedSwitchSensorCount 1.3.6.1.4.1.17373.2.1.8.1.26
Number of air speed switch sensors currently plugged in
OBJECT-TYPE    
  INTEGER 0..16  

climateTable 1.3.6.1.4.1.17373.2.2
Climate sensors (internal sensors for climate units)
OBJECT-TYPE    
  SEQUENCE OF  
    ClimateEntry

powerMonitorTable 1.3.6.1.4.1.17373.2.3
A table of Power Monitors
OBJECT-TYPE    
  SEQUENCE OF  
    PowerMonitorEntry

tempSensorTable 1.3.6.1.4.1.17373.2.4
A table of temperature sensors
OBJECT-TYPE    
  SEQUENCE OF  
    TempSensorEntry

airFlowSensorTable 1.3.6.1.4.1.17373.2.5
A table of airflow sensors
OBJECT-TYPE    
  SEQUENCE OF  
    AirFlowSensorEntry

powerOnlyTable 1.3.6.1.4.1.17373.2.6
A table of Power-Only devices
OBJECT-TYPE    
  SEQUENCE OF  
    PowerOnlyEntry

doorSensorTable 1.3.6.1.4.1.17373.2.7
A table of door sensors
OBJECT-TYPE    
  SEQUENCE OF  
    DoorSensorEntry

waterSensorTable 1.3.6.1.4.1.17373.2.8
A table of water sensors
OBJECT-TYPE    
  SEQUENCE OF  
    WaterSensorEntry

currentMonitorTable 1.3.6.1.4.1.17373.2.9
A table of current monitors
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorEntry

millivoltMonitorTable 1.3.6.1.4.1.17373.2.10
A table of millivolt monitors
OBJECT-TYPE    
  SEQUENCE OF  
    MillivoltMonitorEntry

power3ChTable 1.3.6.1.4.1.17373.2.11
A table of Power Monitor 3 Channel
OBJECT-TYPE    
  SEQUENCE OF  
    Power3ChEntry

outletTable 1.3.6.1.4.1.17373.2.12
A table of outlets
OBJECT-TYPE    
  SEQUENCE OF  
    OutletEntry

vsfcTable 1.3.6.1.4.1.17373.2.13
VSFC sensors (internal sensors for VSFC units)
OBJECT-TYPE    
  SEQUENCE OF  
    VsfcEntry

ctrl3ChTable 1.3.6.1.4.1.17373.2.14
A table of a 3 phase outlet control
OBJECT-TYPE    
  SEQUENCE OF  
    Ctrl3ChEntry

ctrlGrpAmpsTable 1.3.6.1.4.1.17373.2.15
A table of Control Group Amp readings
OBJECT-TYPE    
  SEQUENCE OF  
    CtrlGrpAmpsEntry

ctrlOutletTable 1.3.6.1.4.1.17373.2.16
A table of outlet information
OBJECT-TYPE    
  SEQUENCE OF  
    CtrlOutletEntry

dewPointSensorTable 1.3.6.1.4.1.17373.2.17
A table of dew point sensors
OBJECT-TYPE    
  SEQUENCE OF  
    DewPointSensorEntry

digitalSensorTable 1.3.6.1.4.1.17373.2.18
A table of digital sensors
OBJECT-TYPE    
  SEQUENCE OF  
    DigitalSensorEntry

dstsTable 1.3.6.1.4.1.17373.2.19
Digital Static Transfer Switch status
OBJECT-TYPE    
  SEQUENCE OF  
    DstsEntry

cpmSensorTable 1.3.6.1.4.1.17373.2.20
A table of city power sensors
OBJECT-TYPE    
  SEQUENCE OF  
    CpmSensorEntry

smokeAlarmTable 1.3.6.1.4.1.17373.2.21
A table of smoke alarm sensors
OBJECT-TYPE    
  SEQUENCE OF  
    SmokeAlarmEntry

neg48VdcSensorTable 1.3.6.1.4.1.17373.2.22
A table of -48Vdc sensors
OBJECT-TYPE    
  SEQUENCE OF  
    Neg48VdcSensorEntry

pos30VdcSensorTable 1.3.6.1.4.1.17373.2.23
A table of 30Vdc sensors
OBJECT-TYPE    
  SEQUENCE OF  
    Pos30VdcSensorEntry

analogSensorTable 1.3.6.1.4.1.17373.2.24
A table of analog sensors
OBJECT-TYPE    
  SEQUENCE OF  
    AnalogSensorEntry

ctrl3ChIECTable 1.3.6.1.4.1.17373.2.25
A table of a 3 phase outlet control (IEC)
OBJECT-TYPE    
  SEQUENCE OF  
    Ctrl3ChIECEntry

airSpeedSwitchSensorTable 1.3.6.1.4.1.17373.2.26
A table of air speed switch sensors
OBJECT-TYPE    
  SEQUENCE OF  
    AirSpeedSwitchSensorEntry

climateEntry 1.3.6.1.4.1.17373.2.2.1
Entry in the climate table: each entry contains an index (climateIndex) and other details
OBJECT-TYPE    
  ClimateEntry  

climateIndex 1.3.6.1.4.1.17373.2.2.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..1  

climateSerial 1.3.6.1.4.1.17373.2.2.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

climateName 1.3.6.1.4.1.17373.2.2.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

climateAvail 1.3.6.1.4.1.17373.2.2.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

climateTempC 1.3.6.1.4.1.17373.2.2.1.5
Current reading for Temperature (C)
OBJECT-TYPE    
  INTEGER -40..123  

climateHumidity 1.3.6.1.4.1.17373.2.2.1.6
Current reading for Humidity
OBJECT-TYPE    
  INTEGER 0..100  

climateAirflow 1.3.6.1.4.1.17373.2.2.1.7
Current reading for Airflow
OBJECT-TYPE    
  INTEGER 0..100  

climateLight 1.3.6.1.4.1.17373.2.2.1.8
Current reading for Ambient Light
OBJECT-TYPE    
  INTEGER 0..100  

climateSound 1.3.6.1.4.1.17373.2.2.1.9
Current reading for Sound
OBJECT-TYPE    
  INTEGER 0..100  

climateIO1 1.3.6.1.4.1.17373.2.2.1.10
Current reading for Analog Input 1
OBJECT-TYPE    
  INTEGER 0..100  

climateIO2 1.3.6.1.4.1.17373.2.2.1.11
Current reading for Analog Input 2
OBJECT-TYPE    
  INTEGER 0..100  

climateIO3 1.3.6.1.4.1.17373.2.2.1.12
Current reading for Analog Input 3
OBJECT-TYPE    
  INTEGER 0..100  

powerMonitorEntry 1.3.6.1.4.1.17373.2.3.1
Entry in the power monitor table: each entry contains an index (powMonIndex) and other power monitoring details
OBJECT-TYPE    
  PowerMonitorEntry  

powMonIndex 1.3.6.1.4.1.17373.2.3.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

powMonSerial 1.3.6.1.4.1.17373.2.3.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

powMonName 1.3.6.1.4.1.17373.2.3.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

powMonAvail 1.3.6.1.4.1.17373.2.3.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

powMonKWattHrs 1.3.6.1.4.1.17373.2.3.1.5
Current reading for KWatt-Hours
OBJECT-TYPE    
  Unsigned32  

powMonVolts 1.3.6.1.4.1.17373.2.3.1.6
Current reading for Volts
OBJECT-TYPE    
  Unsigned32  

powMonVoltMax 1.3.6.1.4.1.17373.2.3.1.7
Current reading for Volts (Max)
OBJECT-TYPE    
  Unsigned32  

powMonVoltMin 1.3.6.1.4.1.17373.2.3.1.8
Current reading for Volts (Min)
OBJECT-TYPE    
  Unsigned32  

powMonVoltPeak 1.3.6.1.4.1.17373.2.3.1.9
Current reading for Volts (Peak)
OBJECT-TYPE    
  Unsigned32  

powMonDeciAmps 1.3.6.1.4.1.17373.2.3.1.10
Current reading for DeciAmps
OBJECT-TYPE    
  Unsigned32  

powMonRealPower 1.3.6.1.4.1.17373.2.3.1.11
Current reading for Real Power
OBJECT-TYPE    
  Unsigned32  

powMonApparentPower 1.3.6.1.4.1.17373.2.3.1.12
Current reading for Apparent Power
OBJECT-TYPE    
  Unsigned32  

powMonPowerFactor 1.3.6.1.4.1.17373.2.3.1.13
Current reading for Power Factor
OBJECT-TYPE    
  INTEGER 0..100  

powMonDeciAmpsOutlet1 1.3.6.1.4.1.17373.2.3.1.14
Current reading for Outlet 1
OBJECT-TYPE    
  INTEGER 0..100  

powMonDeciAmpsOutlet2 1.3.6.1.4.1.17373.2.3.1.15
Current reading for Outlet 2
OBJECT-TYPE    
  INTEGER 0..100  

tempSensorEntry 1.3.6.1.4.1.17373.2.4.1
Entry in the temperature sensor table: each entry contains an index (tempIndex) and other sensor details
OBJECT-TYPE    
  TempSensorEntry  

tempSensorIndex 1.3.6.1.4.1.17373.2.4.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

tempSensorSerial 1.3.6.1.4.1.17373.2.4.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

tempSensorName 1.3.6.1.4.1.17373.2.4.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

tempSensorAvail 1.3.6.1.4.1.17373.2.4.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

tempSensorTempC 1.3.6.1.4.1.17373.2.4.1.5
Temperature in Celsius
OBJECT-TYPE    
  INTEGER -40..123  

airFlowSensorEntry 1.3.6.1.4.1.17373.2.5.1
Entry in the air flow sensor table: each entry contains an index (airFlowSensorIndex) and other sensor details
OBJECT-TYPE    
  AirFlowSensorEntry  

airFlowSensorIndex 1.3.6.1.4.1.17373.2.5.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

airFlowSensorSerial 1.3.6.1.4.1.17373.2.5.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

airFlowSensorName 1.3.6.1.4.1.17373.2.5.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

airFlowSensorAvail 1.3.6.1.4.1.17373.2.5.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

airFlowSensorFlow 1.3.6.1.4.1.17373.2.5.1.5
Air flow reading
OBJECT-TYPE    
  INTEGER 0..100  

airFlowSensorTempC 1.3.6.1.4.1.17373.2.5.1.6
Temperature reading in C
OBJECT-TYPE    
  INTEGER -50..100  

airFlowSensorHumidity 1.3.6.1.4.1.17373.2.5.1.7
Humidity reading
OBJECT-TYPE    
  INTEGER 0..100  

airFlowSensorDewPoint 1.3.6.1.4.1.17373.2.5.1.8
Dew point reading in C
OBJECT-TYPE    
  INTEGER -40..123  

powerOnlyEntry 1.3.6.1.4.1.17373.2.6.1
Entry in the power-only device table: each entry contains an index (powerIndex) and other power details
OBJECT-TYPE    
  PowerOnlyEntry  

powerIndex 1.3.6.1.4.1.17373.2.6.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

powerSerial 1.3.6.1.4.1.17373.2.6.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

powerName 1.3.6.1.4.1.17373.2.6.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

powerAvail 1.3.6.1.4.1.17373.2.6.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

powerVolts 1.3.6.1.4.1.17373.2.6.1.5
Current reading for Volts
OBJECT-TYPE    
  Unsigned32  

powerDeciAmps 1.3.6.1.4.1.17373.2.6.1.6
Current reading for DeciAmps
OBJECT-TYPE    
  Unsigned32  

powerRealPower 1.3.6.1.4.1.17373.2.6.1.7
Current reading for Real Power
OBJECT-TYPE    
  Unsigned32  

powerApparentPower 1.3.6.1.4.1.17373.2.6.1.8
Current reading for Apparent Power
OBJECT-TYPE    
  Unsigned32  

powerPowerFactor 1.3.6.1.4.1.17373.2.6.1.9
Current reading for Power Factor
OBJECT-TYPE    
  INTEGER 0..100  

doorSensorEntry 1.3.6.1.4.1.17373.2.7.1
Entry in the door sensor table: each entry contains an index (doorSensorIndex) and other sensor details
OBJECT-TYPE    
  DoorSensorEntry  

doorSensorIndex 1.3.6.1.4.1.17373.2.7.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

doorSensorSerial 1.3.6.1.4.1.17373.2.7.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

doorSensorName 1.3.6.1.4.1.17373.2.7.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

doorSensorAvail 1.3.6.1.4.1.17373.2.7.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

doorSensorStatus 1.3.6.1.4.1.17373.2.7.1.5
Door sensor status
OBJECT-TYPE    
  INTEGER 0..100  

waterSensorEntry 1.3.6.1.4.1.17373.2.8.1
Entry in the water sensor table: each entry contains an index (waterSensorIndex) and other sensor details
OBJECT-TYPE    
  WaterSensorEntry  

waterSensorIndex 1.3.6.1.4.1.17373.2.8.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

waterSensorSerial 1.3.6.1.4.1.17373.2.8.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

waterSensorName 1.3.6.1.4.1.17373.2.8.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

waterSensorAvail 1.3.6.1.4.1.17373.2.8.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

waterSensorDampness 1.3.6.1.4.1.17373.2.8.1.5
Dampness of the water sensor
OBJECT-TYPE    
  INTEGER 0..100  

currentMonitorEntry 1.3.6.1.4.1.17373.2.9.1
Entry in the current monitor table: each entry contains an index (currentMonitorIndex) and other sensor details
OBJECT-TYPE    
  CurrentMonitorEntry  

currentMonitorIndex 1.3.6.1.4.1.17373.2.9.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

currentMonitorSerial 1.3.6.1.4.1.17373.2.9.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

currentMonitorName 1.3.6.1.4.1.17373.2.9.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

currentMonitorAvail 1.3.6.1.4.1.17373.2.9.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

currentMonitorDeciAmps 1.3.6.1.4.1.17373.2.9.1.5
Current in deciamps
OBJECT-TYPE    
  INTEGER 0..30  

millivoltMonitorEntry 1.3.6.1.4.1.17373.2.10.1
Entry in the millivolt monitor table: each entry contains an index (millivoltMonitorIndex) and other sensor details
OBJECT-TYPE    
  MillivoltMonitorEntry  

millivoltMonitorIndex 1.3.6.1.4.1.17373.2.10.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

millivoltMonitorSerial 1.3.6.1.4.1.17373.2.10.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

millivoltMonitorName 1.3.6.1.4.1.17373.2.10.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

millivoltMonitorAvail 1.3.6.1.4.1.17373.2.10.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

millivoltMonitorMV 1.3.6.1.4.1.17373.2.10.1.5
millivolts
OBJECT-TYPE    
  INTEGER 0..5000  

power3ChEntry 1.3.6.1.4.1.17373.2.11.1
Entry in the power monitor 3 channel table: each entry contains an index (pow3ChIndex) and other power monitoring details
OBJECT-TYPE    
  Power3ChEntry  

pow3ChIndex 1.3.6.1.4.1.17373.2.11.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

pow3ChSerial 1.3.6.1.4.1.17373.2.11.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

pow3ChName 1.3.6.1.4.1.17373.2.11.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

pow3ChAvail 1.3.6.1.4.1.17373.2.11.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

pow3ChKWattHrsA 1.3.6.1.4.1.17373.2.11.1.5
Current reading for KWatt-Hours (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltsA 1.3.6.1.4.1.17373.2.11.1.6
Current reading for Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMaxA 1.3.6.1.4.1.17373.2.11.1.7
Current reading for Max-Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMinA 1.3.6.1.4.1.17373.2.11.1.8
Current reading for Min-Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltPeakA 1.3.6.1.4.1.17373.2.11.1.9
Current reading for Peak-Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChDeciAmpsA 1.3.6.1.4.1.17373.2.11.1.10
Current reading for DeciAmps (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChRealPowerA 1.3.6.1.4.1.17373.2.11.1.11
Current reading for Real Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChApparentPowerA 1.3.6.1.4.1.17373.2.11.1.12
Current reading for Apparent Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

pow3ChPowerFactorA 1.3.6.1.4.1.17373.2.11.1.13
Current reading for Power Factor (Phase A)
OBJECT-TYPE    
  INTEGER 0..100  

pow3ChKWattHrsB 1.3.6.1.4.1.17373.2.11.1.14
Current reading for KWatt-Hours (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltsB 1.3.6.1.4.1.17373.2.11.1.15
Current reading for Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMaxB 1.3.6.1.4.1.17373.2.11.1.16
Current reading for Max-Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMinB 1.3.6.1.4.1.17373.2.11.1.17
Current reading for Min-Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltPeakB 1.3.6.1.4.1.17373.2.11.1.18
Current reading for Peak-Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChDeciAmpsB 1.3.6.1.4.1.17373.2.11.1.19
Current reading for DeciAmps (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChRealPowerB 1.3.6.1.4.1.17373.2.11.1.20
Current reading for Real Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChApparentPowerB 1.3.6.1.4.1.17373.2.11.1.21
Current reading for Apparent Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

pow3ChPowerFactorB 1.3.6.1.4.1.17373.2.11.1.22
Current reading for Power Factor (Phase B)
OBJECT-TYPE    
  INTEGER 0..100  

pow3ChKWattHrsC 1.3.6.1.4.1.17373.2.11.1.23
Current reading for KWatt-Hours (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltsC 1.3.6.1.4.1.17373.2.11.1.24
Current reading for Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMaxC 1.3.6.1.4.1.17373.2.11.1.25
Current reading for Max-Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltMinC 1.3.6.1.4.1.17373.2.11.1.26
Current reading for Min-Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChVoltPeakC 1.3.6.1.4.1.17373.2.11.1.27
Current reading for Peak-Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChDeciAmpsC 1.3.6.1.4.1.17373.2.11.1.28
Current reading for DeciAmps (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChRealPowerC 1.3.6.1.4.1.17373.2.11.1.29
Current reading for Real Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChApparentPowerC 1.3.6.1.4.1.17373.2.11.1.30
Current reading for Apparent Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

pow3ChPowerFactorC 1.3.6.1.4.1.17373.2.11.1.31
Current reading for Power Factor (Phase C)
OBJECT-TYPE    
  INTEGER 0..100  

outletEntry 1.3.6.1.4.1.17373.2.12.1
Entry in the outlet table: each entry contains an index (outletIndex) and other sensor details
OBJECT-TYPE    
  OutletEntry  

outletIndex 1.3.6.1.4.1.17373.2.12.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

outletSerial 1.3.6.1.4.1.17373.2.12.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

outletName 1.3.6.1.4.1.17373.2.12.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

outletAvail 1.3.6.1.4.1.17373.2.12.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

outlet1Status 1.3.6.1.4.1.17373.2.12.1.5
Outlet 1 status
OBJECT-TYPE    
  INTEGER 0..100  

outlet2Status 1.3.6.1.4.1.17373.2.12.1.6
Outlet 2 status
OBJECT-TYPE    
  INTEGER 0..100  

vsfcEntry 1.3.6.1.4.1.17373.2.13.1
Entry in the vsfc table: each entry contains an index (vsfcIndex) and other details
OBJECT-TYPE    
  VsfcEntry  

vsfcIndex 1.3.6.1.4.1.17373.2.13.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..1  

vsfcSerial 1.3.6.1.4.1.17373.2.13.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

vsfcName 1.3.6.1.4.1.17373.2.13.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

vsfcAvail 1.3.6.1.4.1.17373.2.13.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

vsfcSetPointC 1.3.6.1.4.1.17373.2.13.1.5
Current temperature set point in C
OBJECT-TYPE    
  INTEGER 18..38  

vsfcIntTempC 1.3.6.1.4.1.17373.2.13.1.6
Current internal temperature reading in C
OBJECT-TYPE    
  INTEGER -20..50  

vsfcExt1TempC 1.3.6.1.4.1.17373.2.13.1.7
Current reading for external temp 1 in C
OBJECT-TYPE    
  INTEGER -20..50  

vsfcExt2TempC 1.3.6.1.4.1.17373.2.13.1.8
Current reading for external temp 2 in C
OBJECT-TYPE    
  INTEGER -20..50  

vsfcExt3TempC 1.3.6.1.4.1.17373.2.13.1.9
Current reading for external temp 3 in C
OBJECT-TYPE    
  INTEGER -20..50  

vsfcExt4TempC 1.3.6.1.4.1.17373.2.13.1.10
Current reading for external temp 4 in C
OBJECT-TYPE    
  INTEGER -20..50  

vsfcFanSpeed 1.3.6.1.4.1.17373.2.13.1.11
Current reading for Fan Speed
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChEntry 1.3.6.1.4.1.17373.2.14.1
Entry in the 3 phase outlet control table: each entry contains an index (ctrl3ChIndex) and other outlet control monitoring details
OBJECT-TYPE    
  Ctrl3ChEntry  

ctrl3ChIndex 1.3.6.1.4.1.17373.2.14.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..1  

ctrl3ChSerial 1.3.6.1.4.1.17373.2.14.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

ctrl3ChName 1.3.6.1.4.1.17373.2.14.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

ctrl3ChAvail 1.3.6.1.4.1.17373.2.14.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

ctrl3ChVoltsA 1.3.6.1.4.1.17373.2.14.1.5
Current reading for Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChVoltPeakA 1.3.6.1.4.1.17373.2.14.1.6
Current reading for Peak-Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsA 1.3.6.1.4.1.17373.2.14.1.7
Current reading for DeciAmps (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsPeakA 1.3.6.1.4.1.17373.2.14.1.8
Current reading for Peak-DeciAmps (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChRealPowerA 1.3.6.1.4.1.17373.2.14.1.9
Current reading for Real Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChApparentPowerA 1.3.6.1.4.1.17373.2.14.1.10
Current reading for Apparent Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChPowerFactorA 1.3.6.1.4.1.17373.2.14.1.11
Current reading for Power Factor (Phase A)
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChVoltsB 1.3.6.1.4.1.17373.2.14.1.12
Current reading for Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChVoltPeakB 1.3.6.1.4.1.17373.2.14.1.13
Current reading for Peak-Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsB 1.3.6.1.4.1.17373.2.14.1.14
Current reading for DeciAmps (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsPeakB 1.3.6.1.4.1.17373.2.14.1.15
Current reading for Peak-DeciAmps (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChRealPowerB 1.3.6.1.4.1.17373.2.14.1.16
Current reading for Real Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChApparentPowerB 1.3.6.1.4.1.17373.2.14.1.17
Current reading for Apparent Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChPowerFactorB 1.3.6.1.4.1.17373.2.14.1.18
Current reading for Power Factor (Phase B)
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChVoltsC 1.3.6.1.4.1.17373.2.14.1.19
Current reading for Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChVoltPeakC 1.3.6.1.4.1.17373.2.14.1.20
Current reading for Peak-Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsC 1.3.6.1.4.1.17373.2.14.1.21
Current reading for DeciAmps (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChDeciAmpsPeakC 1.3.6.1.4.1.17373.2.14.1.22
Current reading for Peak-DeciAmps (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChRealPowerC 1.3.6.1.4.1.17373.2.14.1.23
Current reading for Real Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChApparentPowerC 1.3.6.1.4.1.17373.2.14.1.24
Current reading for Apparent Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChPowerFactorC 1.3.6.1.4.1.17373.2.14.1.25
Current reading for Power Factor (Phase C)
OBJECT-TYPE    
  INTEGER 0..100  

ctrlGrpAmpsEntry 1.3.6.1.4.1.17373.2.15.1
Entry in the Control Group Amps table: each entry contains an index (ctrlGrpAmpsIndex) and other sensor details
OBJECT-TYPE    
  CtrlGrpAmpsEntry  

ctrlGrpAmpsIndex 1.3.6.1.4.1.17373.2.15.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..1  

ctrlGrpAmpsSerial 1.3.6.1.4.1.17373.2.15.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

ctrlGrpAmpsName 1.3.6.1.4.1.17373.2.15.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

ctrlGrpAmpsAvail 1.3.6.1.4.1.17373.2.15.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsA 1.3.6.1.4.1.17373.2.15.1.5
DeciAmps Group A
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsB 1.3.6.1.4.1.17373.2.15.1.6
DeciAmps Group B
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsC 1.3.6.1.4.1.17373.2.15.1.7
DeciAmps Group C
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsD 1.3.6.1.4.1.17373.2.15.1.8
DeciAmps Group D
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsE 1.3.6.1.4.1.17373.2.15.1.9
DeciAmps Group E
OBJECT-TYPE    
  Unsigned32  

ctrlGrpAmpsF 1.3.6.1.4.1.17373.2.15.1.10
DeciAmps Group F
OBJECT-TYPE    
  Unsigned32  

ctrlOutletEntry 1.3.6.1.4.1.17373.2.16.1
Entry in the control outlet table: each entry contains an index (ctrlOutletIndex) and other sensor details
OBJECT-TYPE    
  CtrlOutletEntry  

ctrlOutletIndex 1.3.6.1.4.1.17373.2.16.1.1
Outlet Number
OBJECT-TYPE    
  INTEGER 1..100  

ctrlOutletName 1.3.6.1.4.1.17373.2.16.1.2
Outlet Friendly Name
OBJECT-TYPE    
  DisplayString  

ctrlOutletStatus 1.3.6.1.4.1.17373.2.16.1.3
Current Outlet Status: 0 = Off, 1 = On
OBJECT-TYPE    
  Unsigned32  

ctrlOutletFeedback 1.3.6.1.4.1.17373.2.16.1.4
Outlet Feedback Value, should be equal to status
OBJECT-TYPE    
  Unsigned32  

ctrlOutletPending 1.3.6.1.4.1.17373.2.16.1.5
Outlet Status to change to: 0 = Off, 1 = On
OBJECT-TYPE    
  Unsigned32  

ctrlOutletDeciAmps 1.3.6.1.4.1.17373.2.16.1.6
Outlet DeciAmps reading
OBJECT-TYPE    
  Unsigned32  

ctrlOutletGroup 1.3.6.1.4.1.17373.2.16.1.7
Outlet Group (A to F)
OBJECT-TYPE    
  DisplayString  

ctrlOutletUpDelay 1.3.6.1.4.1.17373.2.16.1.8
Outlet Power Up Delay
OBJECT-TYPE    
  Unsigned32  

ctrlOutletDwnDelay 1.3.6.1.4.1.17373.2.16.1.9
Outlet Power Down Delay
OBJECT-TYPE    
  Unsigned32  

ctrlOutletRbtDelay 1.3.6.1.4.1.17373.2.16.1.10
Outlet Reboot Delay
OBJECT-TYPE    
  Unsigned32  

ctrlOutletURL 1.3.6.1.4.1.17373.2.16.1.11
Outlet URL
OBJECT-TYPE    
  DisplayString  

ctrlOutletPOAAction 1.3.6.1.4.1.17373.2.16.1.12
POA Action: 1 = Off, 2 = On, 4 = Last, 0 = POA not supported on this unit type
OBJECT-TYPE    
  Unsigned32  

ctrlOutletPOADelay 1.3.6.1.4.1.17373.2.16.1.13
POA Delay
OBJECT-TYPE    
  Unsigned32  

dewPointSensorEntry 1.3.6.1.4.1.17373.2.17.1
Entry in the dew point sensor table: each entry contains an index (dewPointSensorIndex) and other sensor details
OBJECT-TYPE    
  DewPointSensorEntry  

dewPointSensorIndex 1.3.6.1.4.1.17373.2.17.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

dewPointSensorSerial 1.3.6.1.4.1.17373.2.17.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

dewPointSensorName 1.3.6.1.4.1.17373.2.17.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

dewPointSensorAvail 1.3.6.1.4.1.17373.2.17.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

dewPointSensorDewPoint 1.3.6.1.4.1.17373.2.17.1.5
Dew point reading in C
OBJECT-TYPE    
  INTEGER -40..123  

dewPointSensorTempC 1.3.6.1.4.1.17373.2.17.1.6
Temperature reading in C
OBJECT-TYPE    
  INTEGER -40..123  

dewPointSensorHumidity 1.3.6.1.4.1.17373.2.17.1.7
Humidity reading
OBJECT-TYPE    
  INTEGER 0..100  

digitalSensorEntry 1.3.6.1.4.1.17373.2.18.1
Entry in the digital sensor table: each entry contains an index (digitalSensorIndex) and other sensor details
OBJECT-TYPE    
  DigitalSensorEntry  

digitalSensorIndex 1.3.6.1.4.1.17373.2.18.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

digitalSensorSerial 1.3.6.1.4.1.17373.2.18.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

digitalSensorName 1.3.6.1.4.1.17373.2.18.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

digitalSensorAvail 1.3.6.1.4.1.17373.2.18.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

digitalSensorDigital 1.3.6.1.4.1.17373.2.18.1.5
Digital sensor status
OBJECT-TYPE    
  INTEGER 0..100  

dstsEntry 1.3.6.1.4.1.17373.2.19.1
Entry in the DSTS table: each entry contains an index (dstsIndex) and other details
OBJECT-TYPE    
  DstsEntry  

dstsIndex 1.3.6.1.4.1.17373.2.19.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..1  

dstsSerial 1.3.6.1.4.1.17373.2.19.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

dstsName 1.3.6.1.4.1.17373.2.19.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

dstsAvail 1.3.6.1.4.1.17373.2.19.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

dstsVoltsA 1.3.6.1.4.1.17373.2.19.1.5
RMS Voltage of Side A
OBJECT-TYPE    
  Unsigned32  

dstsAmpsA 1.3.6.1.4.1.17373.2.19.1.6
RMS Current of Side A in deciamps
OBJECT-TYPE    
  Unsigned32  

dstsVoltsB 1.3.6.1.4.1.17373.2.19.1.7
RMS Voltage of Side B
OBJECT-TYPE    
  Unsigned32  

dstsAmpsB 1.3.6.1.4.1.17373.2.19.1.8
RMS Current of Side B in deciamps
OBJECT-TYPE    
  Unsigned32  

dstsSourceAActive 1.3.6.1.4.1.17373.2.19.1.9
If 99, source A active
OBJECT-TYPE    
  Unsigned32  

dstsSourceBActive 1.3.6.1.4.1.17373.2.19.1.10
If 99, source B active
OBJECT-TYPE    
  Unsigned32  

dstsPowerStatusA 1.3.6.1.4.1.17373.2.19.1.11
Power Quality of source A
OBJECT-TYPE    
  Unsigned32  

dstsPowerStatusB 1.3.6.1.4.1.17373.2.19.1.12
Power Quality of Source B
OBJECT-TYPE    
  Unsigned32  

dstsSourceATempC 1.3.6.1.4.1.17373.2.19.1.13
Current reading for Source A temp in C
OBJECT-TYPE    
  INTEGER -20..50  

dstsSourceBTempC 1.3.6.1.4.1.17373.2.19.1.14
Current reading for Source B temp in C
OBJECT-TYPE    
  INTEGER -20..50  

cpmSensorEntry 1.3.6.1.4.1.17373.2.20.1
Entry in the city power sensor table: each entry contains an index (cpmSensorIndex) and other sensor details
OBJECT-TYPE    
  CpmSensorEntry  

cpmSensorIndex 1.3.6.1.4.1.17373.2.20.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

cpmSensorSerial 1.3.6.1.4.1.17373.2.20.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

cpmSensorName 1.3.6.1.4.1.17373.2.20.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

cpmSensorAvail 1.3.6.1.4.1.17373.2.20.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

cpmSensorStatus 1.3.6.1.4.1.17373.2.20.1.5
City Power sensor status
OBJECT-TYPE    
  INTEGER 0..100  

smokeAlarmEntry 1.3.6.1.4.1.17373.2.21.1
Entry in the smoke alarm sensor table: each entry contains an index (smokeAlarmIndex) and other sensor details
OBJECT-TYPE    
  SmokeAlarmEntry  

smokeAlarmIndex 1.3.6.1.4.1.17373.2.21.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

smokeAlarmSerial 1.3.6.1.4.1.17373.2.21.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

smokeAlarmName 1.3.6.1.4.1.17373.2.21.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

smokeAlarmAvail 1.3.6.1.4.1.17373.2.21.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

smokeAlarmStatus 1.3.6.1.4.1.17373.2.21.1.5
Smoke alarm status
OBJECT-TYPE    
  INTEGER 0..100  

neg48VdcSensorEntry 1.3.6.1.4.1.17373.2.22.1
Entry in the -48Vdc sensor table: each entry contains an index (neg48VdcSensorIndex) and other sensor details
OBJECT-TYPE    
  Neg48VdcSensorEntry  

neg48VdcSensorIndex 1.3.6.1.4.1.17373.2.22.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

neg48VdcSensorSerial 1.3.6.1.4.1.17373.2.22.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

neg48VdcSensorName 1.3.6.1.4.1.17373.2.22.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

neg48VdcSensorAvail 1.3.6.1.4.1.17373.2.22.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

neg48VdcSensorVoltage 1.3.6.1.4.1.17373.2.22.1.5
-48Vdc Sensor value
OBJECT-TYPE    
  INTEGER -100..10  

pos30VdcSensorEntry 1.3.6.1.4.1.17373.2.23.1
Entry in the 30Vdc sensor table: each entry contains an index (pos30VdcSensorIndex) and other sensor details
OBJECT-TYPE    
  Pos30VdcSensorEntry  

pos30VdcSensorIndex 1.3.6.1.4.1.17373.2.23.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

pos30VdcSensorSerial 1.3.6.1.4.1.17373.2.23.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

pos30VdcSensorName 1.3.6.1.4.1.17373.2.23.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

pos30VdcSensorAvail 1.3.6.1.4.1.17373.2.23.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

pos30VdcSensorVoltage 1.3.6.1.4.1.17373.2.23.1.5
30Vdc Sensor value
OBJECT-TYPE    
  INTEGER -10..100  

analogSensorEntry 1.3.6.1.4.1.17373.2.24.1
Entry in the analog input table: each entry contains an index (analogSensorIndex) and other sensor details
OBJECT-TYPE    
  AnalogSensorEntry  

analogSensorIndex 1.3.6.1.4.1.17373.2.24.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

analogSensorSerial 1.3.6.1.4.1.17373.2.24.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

analogSensorName 1.3.6.1.4.1.17373.2.24.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

analogSensorAvail 1.3.6.1.4.1.17373.2.24.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

analogSensorAnalog 1.3.6.1.4.1.17373.2.24.1.5
Analog Sensor Value
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChIECEntry 1.3.6.1.4.1.17373.2.25.1
Entry in the 3 phase outlet control table: each entry contains an index (ctrl3ChIECIndex) and other outlet control monitoring details
OBJECT-TYPE    
  Ctrl3ChIECEntry  

ctrl3ChIECIndex 1.3.6.1.4.1.17373.2.25.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

ctrl3ChIECSerial 1.3.6.1.4.1.17373.2.25.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

ctrl3ChIECName 1.3.6.1.4.1.17373.2.25.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

ctrl3ChIECAvail 1.3.6.1.4.1.17373.2.25.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECKWattHrsA 1.3.6.1.4.1.17373.2.25.1.5
Current Reading for KWatt-Hours (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltsA 1.3.6.1.4.1.17373.2.25.1.6
Current reading for Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltPeakA 1.3.6.1.4.1.17373.2.25.1.7
Current reading for Peak-Volts (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsA 1.3.6.1.4.1.17373.2.25.1.8
Current reading for DeciAmps (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsPeakA 1.3.6.1.4.1.17373.2.25.1.9
Current reading for Peak-DeciAmps (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECRealPowerA 1.3.6.1.4.1.17373.2.25.1.10
Current reading for Real Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECApparentPowerA 1.3.6.1.4.1.17373.2.25.1.11
Current reading for Apparent Power (Phase A)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECPowerFactorA 1.3.6.1.4.1.17373.2.25.1.12
Current reading for Power Factor (Phase A)
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChIECKWattHrsB 1.3.6.1.4.1.17373.2.25.1.13
Current Reading for KWatt-Hours (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltsB 1.3.6.1.4.1.17373.2.25.1.14
Current reading for Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltPeakB 1.3.6.1.4.1.17373.2.25.1.15
Current reading for Peak-Volts (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsB 1.3.6.1.4.1.17373.2.25.1.16
Current reading for DeciAmps (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsPeakB 1.3.6.1.4.1.17373.2.25.1.17
Current reading for Peak-DeciAmps (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECRealPowerB 1.3.6.1.4.1.17373.2.25.1.18
Current reading for Real Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECApparentPowerB 1.3.6.1.4.1.17373.2.25.1.19
Current reading for Apparent Power (Phase B)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECPowerFactorB 1.3.6.1.4.1.17373.2.25.1.20
Current reading for Power Factor (Phase B)
OBJECT-TYPE    
  INTEGER 0..100  

ctrl3ChIECKWattHrsC 1.3.6.1.4.1.17373.2.25.1.21
Current Reading for KWatt-Hours (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltsC 1.3.6.1.4.1.17373.2.25.1.22
Current reading for Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECVoltPeakC 1.3.6.1.4.1.17373.2.25.1.23
Current reading for Peak-Volts (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsC 1.3.6.1.4.1.17373.2.25.1.24
Current reading for DeciAmps (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECDeciAmpsPeakC 1.3.6.1.4.1.17373.2.25.1.25
Current reading for Peak-DeciAmps (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECRealPowerC 1.3.6.1.4.1.17373.2.25.1.26
Current reading for Real Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECApparentPowerC 1.3.6.1.4.1.17373.2.25.1.27
Current reading for Apparent Power (Phase C)
OBJECT-TYPE    
  Unsigned32  

ctrl3ChIECPowerFactorC 1.3.6.1.4.1.17373.2.25.1.28
Current reading for Power Factor (Phase C)
OBJECT-TYPE    
  INTEGER 0..100  

airSpeedSwitchSensorEntry 1.3.6.1.4.1.17373.2.26.1
Entry in the air speed switch sensor table: each entry contains an index (airSpeedSwitchIndex) and other sensor details
OBJECT-TYPE    
  AirSpeedSwitchSensorEntry  

airSpeedSwitchSensorIndex 1.3.6.1.4.1.17373.2.26.1.1
Table entry index value
OBJECT-TYPE    
  INTEGER 1..100  

airSpeedSwitchSensorSerial 1.3.6.1.4.1.17373.2.26.1.2
Serial Number
OBJECT-TYPE    
  DisplayString  

airSpeedSwitchSensorName 1.3.6.1.4.1.17373.2.26.1.3
Friendly Name
OBJECT-TYPE    
  DisplayString  

airSpeedSwitchSensorAvail 1.3.6.1.4.1.17373.2.26.1.4
Is device currently plugged in?
OBJECT-TYPE    
  Unsigned32  

airSpeedSwitchSensorAirSpeed 1.3.6.1.4.1.17373.2.26.1.5
Air Speed Switch Status
OBJECT-TYPE    
  INTEGER 0..100