EMD-MIB

File: EMD-MIB.mib (116513 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC
INET-ADDRESS-MIB RFC1213-MIB

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises Integer32 Unsigned32
MODULE-COMPLIANCE OBJECT-GROUP NOTIFICATION-GROUP
TEXTUAL-CONVENTION DisplayString MacAddress
TruthValue InetAddressType InetAddress
InetPortNumber sysContact sysName
sysLocation

Defined Types

SensorTypeEnumeration  
The types a sensor can be.
TEXTUAL-CONVENTION    
  INTEGER rmsCurrent(1), peakCurrent(2), unbalancedCurrent(3), rmsVoltage(4), activePower(5), apparentPower(6), powerFactor(7), activeEnergy(8), apparentEnergy(9), temperature(10), humidity(11), airFlow(12), airPressure(13), onOff(14), trip(15), vibration(16), waterDetection(17), smokeDetection(18), binary(19), contact(20), fanSpeed(21), absoluteHumidity(28), other(30), none(31), illuminance(42), doorContact(43), tamperDetection(44), motionDetection(45)  

SensorStateEnumeration  
The states a sensor can be in.
TEXTUAL-CONVENTION    
  INTEGER unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11)  

SensorUnitsEnumeration  
The types a sensor can be.
TEXTUAL-CONVENTION    
  INTEGER none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19), degrees(20), lux(21), grampercubicmeter(22), voltampReactive(23)  

ExternalSensorsZCoordinateUnitsEnumeration  
The units of the external Sensor Z Coordinate. rackUnits implies that the Z Coordinate for all external sensors is in rack Units (U) text implies that the Z Coordinate for all external sensors is a text string (label)
TEXTUAL-CONVENTION    
  INTEGER rackUnits(0), text(1)  

HundredthsOfAPercentage  
Data type for reporting values in hundredths of percentage, i.e. 0.01 %.
TEXTUAL-CONVENTION    
  Unsigned32 0..10000  

DeviceIdentificationParameterEnumeration  
The configurable parameters.
TEXTUAL-CONVENTION    
  INTEGER deviceName(0), sysContact(1), sysName(2), sysLocation(3)  

PeripheralDeviceFirmwareUpdateStateEnumeration  
The state of an peripheral device firmware update.
TEXTUAL-CONVENTION    
  INTEGER started(1), successful(2), failed(3)  

ExternalSensorConfigurationEntryStruct  
SEQUENCE    
  sensorID Integer32
  externalSensorType SensorTypeEnumeration
  externalSensorSerialNumber DisplayString
  externalSensorName DisplayString
  externalSensorDescription DisplayString
  externalSensorXCoordinate DisplayString
  externalSensorYCoordinate DisplayString
  externalSensorZCoordinate DisplayString
  externalSensorChannelNumber Integer32
  externalOnOffSensorSubtype SensorTypeEnumeration
  externalSensorUnits SensorUnitsEnumeration
  externalSensorDecimalDigits Unsigned32
  externalSensorAccuracy HundredthsOfAPercentage
  externalSensorResolution Unsigned32
  externalSensorTolerance Unsigned32
  externalSensorMaximum Integer32
  externalSensorMinimum Integer32
  externalSensorHysteresis Unsigned32
  externalSensorStateChangeDelay Unsigned32
  externalSensorLowerCriticalThreshold Integer32
  externalSensorLowerWarningThreshold Integer32
  externalSensorUpperCriticalThreshold Integer32
  externalSensorUpperWarningThreshold Integer32
  externalSensorEnabledThresholds BITS
  externalSensorPort DisplayString
  externalSensorIsActuator TruthValue
  externalSensorAlarmedToNormalDelay Integer32
  externalSensorUseDefaultThresholds TruthValue

ExternalSensorTypeDefaultThresholdsEntryStruct  
SEQUENCE    
  externalSensorTypeDefaultHysteresis Unsigned32
  externalSensorTypeDefaultStateChangeDelay Unsigned32
  externalSensorTypeDefaultLowerCriticalThreshold Integer32
  externalSensorTypeDefaultLowerWarningThreshold Integer32
  externalSensorTypeDefaultUpperCriticalThreshold Integer32
  externalSensorTypeDefaultUpperWarningThreshold Integer32
  externalSensorTypeDefaultEnabledThresholds BITS

PeripheralDevicePackageEntryStruct  
SEQUENCE    
  peripheralDevicePackageId Integer32
  peripheralDevicePackageSerialNumber DisplayString
  peripheralDevicePackageModel DisplayString
  peripheralDevicePackageFirmwareVersion DisplayString
  peripheralDevicePackageMinFirmwareVersion DisplayString
  peripheralDevicePackageFirmwareTimeStamp Unsigned32
  peripheralDevicePackagePosition DisplayString
  peripheralDevicePackageState DisplayString

ServerReachabilityEntryStruct  
SEQUENCE    
  serverID Integer32
  serverIPAddress DisplayString
  serverPingEnabled TruthValue

LogTimeStampEntryStruct  
SEQUENCE    
  logIndex Integer32
  logTimeStamp Unsigned32

ExternalSensorLogEntryStruct  
SEQUENCE    
  logExternalSensorDataAvailable TruthValue
  logExternalSensorState SensorStateEnumeration
  logExternalSensorAvgValue Integer32
  logExternalSensorMaxValue Integer32
  logExternalSensorMinValue Integer32

ExternalSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsExternalSensorIsAvailable TruthValue
  measurementsExternalSensorState SensorStateEnumeration
  measurementsExternalSensorValue Integer32
  measurementsExternalSensorTimeStamp Unsigned32

ActuatorControlEntryStruct  
SEQUENCE    
  actuatorState SensorStateEnumeration

Defined Values

raritan 1.3.6.1.4.1.13742
This MIB describes the SNMP functions of the EMX Environmental Monitoring Device by Raritan Computer.
MODULE-IDENTITY    

emd 1.3.6.1.4.1.13742.8
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.13742.8.0
OBJECT IDENTIFIER    

trapInformation 1.3.6.1.4.1.13742.8.0.0
OBJECT IDENTIFIER    

configuration 1.3.6.1.4.1.13742.8.1
OBJECT IDENTIFIER    

measurements 1.3.6.1.4.1.13742.8.2
OBJECT IDENTIFIER    

conformance 1.3.6.1.4.1.13742.8.3
OBJECT IDENTIFIER    

log 1.3.6.1.4.1.13742.8.4
OBJECT IDENTIFIER    

control 1.3.6.1.4.1.13742.8.5
OBJECT IDENTIFIER    

unit 1.3.6.1.4.1.13742.8.1.1
OBJECT IDENTIFIER    

externalSensors 1.3.6.1.4.1.13742.8.1.2
OBJECT IDENTIFIER    

serverReachability 1.3.6.1.4.1.13742.8.1.3
OBJECT IDENTIFIER    

measurementsExternalSensor 1.3.6.1.4.1.13742.8.2.1
OBJECT IDENTIFIER    

compliances 1.3.6.1.4.1.13742.8.3.1
OBJECT IDENTIFIER    

groups 1.3.6.1.4.1.13742.8.3.2
OBJECT IDENTIFIER    

logUnit 1.3.6.1.4.1.13742.8.4.1
OBJECT IDENTIFIER    

logExternalSensor 1.3.6.1.4.1.13742.8.4.2
OBJECT IDENTIFIER    

actuatorControl 1.3.6.1.4.1.13742.8.5.1
OBJECT IDENTIFIER    

complianceRev1 1.3.6.1.4.1.13742.8.3.1.1
The requirements for conformance to the EMD-MIB.
Status: current Access: read-only
MODULE-COMPLIANCE    

configGroup 1.3.6.1.4.1.13742.8.3.2.1
A collection of objects representing configuration data.
Status: current Access: read-only
OBJECT-GROUP    

measurementsGroup 1.3.6.1.4.1.13742.8.3.2.2
A collection of objects providing the measurement capability of EMD.
Status: current Access: read-only
OBJECT-GROUP    

trapInformationGroup 1.3.6.1.4.1.13742.8.3.2.3
A collection of objects providing information in the traps.
Status: current Access: read-only
OBJECT-GROUP    

trapsGroup 1.3.6.1.4.1.13742.8.3.2.4
A collection of traps.
Status: current Access: read-only
NOTIFICATION-GROUP    

logGroup 1.3.6.1.4.1.13742.8.3.2.5
A collection of objects providing the logging capabilities about the EMD.
Status: current Access: read-only
OBJECT-GROUP    

controlGroup 1.3.6.1.4.1.13742.8.3.2.6
A collection of objects providing the ability to control actuators of the EMD.
Status: current Access: read-only
OBJECT-GROUP    

unitConfiguration 1.3.6.1.4.1.13742.8.1.1.1
OBJECT IDENTIFIER    

deviceName 1.3.6.1.4.1.13742.8.1.1.1.1
The user-defined name for the EMD.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

hardwareVersion 1.3.6.1.4.1.13742.8.1.1.1.2
The main boards hardware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

firmwareVersion 1.3.6.1.4.1.13742.8.1.1.1.3
The firmware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

utcOffset 1.3.6.1.4.1.13742.8.1.1.1.4
The current UTC offset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

externalSensorCount 1.3.6.1.4.1.13742.8.1.1.1.5
The number of external sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

managedExternalSensorCount 1.3.6.1.4.1.13742.8.1.1.1.6
The number of managed external sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

externalSensorsZCoordinateUnits 1.3.6.1.4.1.13742.8.1.1.1.7
External Sensor Z Coordinate units: Freeform Text or Rack Units (U). Default is U.
Status: current Access: read-write
OBJECT-TYPE    
  ExternalSensorsZCoordinateUnitsEnumeration  

deviceMACAddress 1.3.6.1.4.1.13742.8.1.1.1.8
The current MAC address.
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

deviceInetAddressType 1.3.6.1.4.1.13742.8.1.1.1.9
The type of address format
Status: current Access: read-only
OBJECT-TYPE    
  InetAddressType  

deviceInetIPAddress 1.3.6.1.4.1.13742.8.1.1.1.10
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

deviceInetNetmask 1.3.6.1.4.1.13742.8.1.1.1.11
The current netmask. A value of 0.0.0.0 indicates an error or an unset option.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

deviceInetGateway 1.3.6.1.4.1.13742.8.1.1.1.12
The current gateway. A value of 0.0.0.0 indicates an error or an unset option.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

serverCount 1.3.6.1.4.1.13742.8.1.1.1.13
The number of entries in serverReachabilityTable
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

model 1.3.6.1.4.1.13742.8.1.1.1.14
The EMD device model.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

cascadedDeviceConnected 1.3.6.1.4.1.13742.8.1.1.1.15
Indicates whether a device is connected using an USB cable to the USB-A port of this EMX in a cascaded configuration. true: Connected false: Not Connected
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

peripheralDevicesAutoManagement 1.3.6.1.4.1.13742.8.1.1.1.16
Set enabled state of auto management for new peripheral devices.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

synchronizeWithNTPServer 1.3.6.1.4.1.13742.8.1.1.1.17
Set enabled state of the device's NTP client.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

useDHCPProvidedNTPServer 1.3.6.1.4.1.13742.8.1.1.1.18
Enable usage of the DHCP/BOOTP provided NTP server addresses; the value is used only if synchronizeWithNTPServer is enabled.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

firstNTPServerAddressType 1.3.6.1.4.1.13742.8.1.1.1.19
Represents the type of firstNTPServerAddress.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddressType  

firstNTPServerAddress 1.3.6.1.4.1.13742.8.1.1.1.20
The address of the primary NTP server.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddress  

secondNTPServerAddressType 1.3.6.1.4.1.13742.8.1.1.1.21
Represents the type of secondNTPServerAddress.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddressType  

secondNTPServerAddress 1.3.6.1.4.1.13742.8.1.1.1.22
The address of the secondary NTP server.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddress  

logConfiguration 1.3.6.1.4.1.13742.8.1.1.2
OBJECT IDENTIFIER    

dataLogging 1.3.6.1.4.1.13742.8.1.1.2.1
Data Retrieval: enabled/disabled.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

measurementPeriod 1.3.6.1.4.1.13742.8.1.1.2.2
Data Collection periodicity. This is the periodicity of the data collected by the PX. This value is fixed at 1 second.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

measurementsPerLogEntry 1.3.6.1.4.1.13742.8.1.1.2.3
The number of measurements used for each entry in the log.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

logSize 1.3.6.1.4.1.13742.8.1.1.2.4
The number of entries in the log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dataLoggingEnableForAllSensors 1.3.6.1.4.1.13742.8.1.1.2.5
Operation to control data logging for all sensors. If this OID is set to true, then all xxxSensorLogAvailable are set to true If this OID is set to false, then all xxxSensorLogAvailable are set to false
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

externalSensorConfigurationTable 1.3.6.1.4.1.13742.8.1.2.1
A list of externalSensor configuration entries. The number of entries is given by the value of externalSensorCount for the EMD.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorConfigurationEntryStruct

externalSensorConfigurationEntry 1.3.6.1.4.1.13742.8.1.2.1.1
An entry containing parameters for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorConfigurationEntryStruct  

sensorID 1.3.6.1.4.1.13742.8.1.2.1.1.1
A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

externalSensorType 1.3.6.1.4.1.13742.8.1.2.1.1.2
The type of sensor.
Status: current Access: read-only
OBJECT-TYPE    
  SensorTypeEnumeration  

externalSensorSerialNumber 1.3.6.1.4.1.13742.8.1.2.1.1.3
The sensor serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

externalSensorName 1.3.6.1.4.1.13742.8.1.2.1.1.4
The user-defined name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorDescription 1.3.6.1.4.1.13742.8.1.2.1.1.5
The user-defined description.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorXCoordinate 1.3.6.1.4.1.13742.8.1.2.1.1.6
The X coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorYCoordinate 1.3.6.1.4.1.13742.8.1.2.1.1.7
The Y coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorZCoordinate 1.3.6.1.4.1.13742.8.1.2.1.1.8
The Z coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorChannelNumber 1.3.6.1.4.1.13742.8.1.2.1.1.9
The channel number, applies only to contact sensors; -1 for other sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalOnOffSensorSubtype 1.3.6.1.4.1.13742.8.1.2.1.1.10
Type of measurement in case sensor type is discrete OnOff
Status: current Access: read-write
OBJECT-TYPE    
  SensorTypeEnumeration  

externalSensorUnits 1.3.6.1.4.1.13742.8.1.2.1.1.11
The base units. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

externalSensorDecimalDigits 1.3.6.1.4.1.13742.8.1.2.1.1.12
The number of digits displayed to the right of the decimal point This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorAccuracy 1.3.6.1.4.1.13742.8.1.2.1.1.13
The accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

externalSensorResolution 1.3.6.1.4.1.13742.8.1.2.1.1.14
The resolution: the minimum difference between any two measured values. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorTolerance 1.3.6.1.4.1.13742.8.1.2.1.1.15
The resolution: the difference between a sensor value and the actual value. The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1). For example, if the value is 50 and externalSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorMaximum 1.3.6.1.4.1.13742.8.1.2.1.1.16
The largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorMinimum 1.3.6.1.4.1.13742.8.1.2.1.1.17
The smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorHysteresis 1.3.6.1.4.1.13742.8.1.2.1.1.18
The hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorStateChangeDelay 1.3.6.1.4.1.13742.8.1.2.1.1.19
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. At present, this value cannot be written (set)
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.8.1.2.1.1.20
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorLowerWarningThreshold 1.3.6.1.4.1.13742.8.1.2.1.1.21
The lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.8.1.2.1.1.22
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorUpperWarningThreshold 1.3.6.1.4.1.13742.8.1.2.1.1.23
The upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorEnabledThresholds 1.3.6.1.4.1.13742.8.1.2.1.1.24
A bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

externalSensorPort 1.3.6.1.4.1.13742.8.1.2.1.1.25
The position of the sensor. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples 1) Onboard Sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old style sensor connected to end of new style sensor chain DEVICE-1WIREPORT:2;
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

externalSensorIsActuator 1.3.6.1.4.1.13742.8.1.2.1.1.26
Is this an actuator? True: It is an actuator False: It is not an actuator
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

externalSensorAlarmedToNormalDelay 1.3.6.1.4.1.13742.8.1.2.1.1.27
The delay in seconds for transitions from the alarmed state to the normal state. If the sensor type is motionDetection, then it can set to a value greater >= 0 For all other sensor types, the value is 0 and cannot be set to any other value.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorUseDefaultThresholds 1.3.6.1.4.1.13742.8.1.2.1.1.28
Use default thresholds for this sensor? True: Use default thresholds for this sensor False: Do not use default thresholds for this sensor
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

externalSensorTypeDefaultThresholdsTable 1.3.6.1.4.1.13742.8.1.2.4
A list of entries listing the default thresholds for each sensor type.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorTypeDefaultThresholdsEntryStruct

externalSensorTypeDefaultThresholdsEntry 1.3.6.1.4.1.13742.8.1.2.4.1
An entry containing default thresholds for a sensor type.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorTypeDefaultThresholdsEntryStruct  

externalSensorTypeDefaultHysteresis 1.3.6.1.4.1.13742.8.1.2.4.1.3
The hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorTypeDefaultStateChangeDelay 1.3.6.1.4.1.13742.8.1.2.4.1.4
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. At present, this value cannot be written (set)
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorTypeDefaultLowerCriticalThreshold 1.3.6.1.4.1.13742.8.1.2.4.1.5
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultLowerWarningThreshold 1.3.6.1.4.1.13742.8.1.2.4.1.6
The lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultUpperCriticalThreshold 1.3.6.1.4.1.13742.8.1.2.4.1.7
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultUpperWarningThreshold 1.3.6.1.4.1.13742.8.1.2.4.1.8
The upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultEnabledThresholds 1.3.6.1.4.1.13742.8.1.2.4.1.9
A bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

peripheralDevicePackageTable 1.3.6.1.4.1.13742.8.1.2.5
A list of entries for the peripheral Device Packages connected to an EMX. The number of entries is given by the value of peripheralDevicePackagesCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PeripheralDevicePackageEntryStruct

peripheralDevicePackageEntry 1.3.6.1.4.1.13742.8.1.2.5.1
An entry containing objects for a controller.
Status: current Access: not-accessible
OBJECT-TYPE    
  PeripheralDevicePackageEntryStruct  

peripheralDevicePackageId 1.3.6.1.4.1.13742.8.1.2.5.1.1
A unique value for each peripheral device package.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

peripheralDevicePackageSerialNumber 1.3.6.1.4.1.13742.8.1.2.5.1.3
The peripheral device package serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageModel 1.3.6.1.4.1.13742.8.1.2.5.1.4
The peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageFirmwareVersion 1.3.6.1.4.1.13742.8.1.2.5.1.5
The peripheral device package firmware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageMinFirmwareVersion 1.3.6.1.4.1.13742.8.1.2.5.1.6
The peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral device firmware to a version < minimum firmware version number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageFirmwareTimeStamp 1.3.6.1.4.1.13742.8.1.2.5.1.7
The time when the peripheralDevicePackage firmware was updated in UNIX(epoch)time. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

peripheralDevicePackagePosition 1.3.6.1.4.1.13742.8.1.2.5.1.8
The position of the package. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples 1) Onboard Sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old style sensor connected to end of new style sensor chain DEVICE-1WIREPORT:2;
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageState 1.3.6.1.4.1.13742.8.1.2.5.1.9
The state of the package.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

serverReachabilityTable 1.3.6.1.4.1.13742.8.1.3.1
A list of server entries. The number of entries is given by the value of serverCount for the EMD.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ServerReachabilityEntryStruct

serverReachabilityEntry 1.3.6.1.4.1.13742.8.1.3.1.1
An entry containing parameters for a server.
Status: current Access: not-accessible
OBJECT-TYPE    
  ServerReachabilityEntryStruct  

serverID 1.3.6.1.4.1.13742.8.1.3.1.1.1
A unique value for each server. Its value ranges between 1 and the value of serverCount for that EMD
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

serverIPAddress 1.3.6.1.4.1.13742.8.1.3.1.1.2
The IP Address/host name of the server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

serverPingEnabled 1.3.6.1.4.1.13742.8.1.3.1.1.3
Is ping enabled for this server?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

oldestLogID 1.3.6.1.4.1.13742.8.4.1.1
The index of the oldest data in the buffer for this EMD.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

newestLogID 1.3.6.1.4.1.13742.8.4.1.2
The index of the newest data in the buffer for this EMD.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logTimeStampTable 1.3.6.1.4.1.13742.8.4.1.3
A list of entries containing the timestamps of the entries in the log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LogTimeStampEntryStruct

logTimeStampEntry 1.3.6.1.4.1.13742.8.4.1.3.1
An entry containing the timestamp for log entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  LogTimeStampEntryStruct  

logIndex 1.3.6.1.4.1.13742.8.4.1.3.1.1
A unique value for each entry in the log. Its value ranges between 1 and the value of logSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

logTimeStamp 1.3.6.1.4.1.13742.8.4.1.3.1.2
The time when the data was collected. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorLogTable 1.3.6.1.4.1.13742.8.4.2.1
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the EMD.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorLogEntryStruct

externalSensorLogEntry 1.3.6.1.4.1.13742.8.4.2.1.1
An entry containing log objects for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorLogEntryStruct  

logExternalSensorDataAvailable 1.3.6.1.4.1.13742.8.4.2.1.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logExternalSensorState 1.3.6.1.4.1.13742.8.4.2.1.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logExternalSensorAvgValue 1.3.6.1.4.1.13742.8.4.2.1.1.4
The sensor reading average value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logExternalSensorMaxValue 1.3.6.1.4.1.13742.8.4.2.1.1.5
The sensor reading maximum value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logExternalSensorMinValue 1.3.6.1.4.1.13742.8.4.2.1.1.6
The sensor reading minimum value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorMeasurementsTable 1.3.6.1.4.1.13742.8.2.1.1
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the EMD.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorMeasurementsEntryStruct

externalSensorMeasurementsEntry 1.3.6.1.4.1.13742.8.2.1.1.1
An entry containing measurement objects for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorMeasurementsEntryStruct  

measurementsExternalSensorIsAvailable 1.3.6.1.4.1.13742.8.2.1.1.1.1
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsExternalSensorState 1.3.6.1.4.1.13742.8.2.1.1.1.2
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsExternalSensorValue 1.3.6.1.4.1.13742.8.2.1.1.1.3
The sensor reading. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

measurementsExternalSensorTimeStamp 1.3.6.1.4.1.13742.8.2.1.1.1.4
The sensor reading timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

actuatorControlTable 1.3.6.1.4.1.13742.8.5.1.1
A list of actuators for an EMX.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ActuatorControlEntryStruct

actuatorControlEntry 1.3.6.1.4.1.13742.8.5.1.1.1
An entry for implementing user-initiated state changes for an actuator.
Status: current Access: not-accessible
OBJECT-TYPE    
  ActuatorControlEntryStruct  

actuatorState 1.3.6.1.4.1.13742.8.5.1.1.1.1
The actuator state. A Get operation retrieves the state of the actuator. A Set operation changes the stae of the sensor. The valid states for set operations are on and Off. Attempting to set the state to any other value will generate an error.
Status: current Access: read-write
OBJECT-TYPE    
  SensorStateEnumeration  

userName 1.3.6.1.4.1.13742.8.0.0.1
The user currently logged in.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

targetUser 1.3.6.1.4.1.13742.8.0.0.2
The user added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

imageVersion 1.3.6.1.4.1.13742.8.0.0.3
The version of the upgrade image.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

roleName 1.3.6.1.4.1.13742.8.0.0.4
The role added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpMessageRecipients 1.3.6.1.4.1.13742.8.0.0.5
Comma separated list of SMTP Message recipients
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpServer 1.3.6.1.4.1.13742.8.0.0.6
The IP address/host name of the SMTP server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

oldSensorState 1.3.6.1.4.1.13742.8.0.0.7
The old sensor state used in Sensor State Transition traps.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  SensorStateEnumeration  

externalSensorNumber 1.3.6.1.4.1.13742.8.0.0.8
A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

typeOfSensor 1.3.6.1.4.1.13742.8.0.0.9
The type of sensor.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  SensorTypeEnumeration  

errorDescription 1.3.6.1.4.1.13742.8.0.0.10
Description of the Error
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

deviceChangedParameter 1.3.6.1.4.1.13742.8.0.0.11
Description of the parameter(s) that changed.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DeviceIdentificationParameterEnumeration  

changedParameterNewValue 1.3.6.1.4.1.13742.8.0.0.12
The new value of the changed parameter
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

lhxSupportEnabled 1.3.6.1.4.1.13742.8.0.0.13
The new enabled state for Schroff LHX Support.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  TruthValue  

webcamModel 1.3.6.1.4.1.13742.8.0.0.14
The model of the Webcam
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

webcamConnectionPort 1.3.6.1.4.1.13742.8.0.0.15
The port to which the Webcam is connected
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

peripheralDeviceRomcode 1.3.6.1.4.1.13742.8.0.0.16
The Romcode of an peripheral device
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

peripheralDeviceFirmwareUpdateState 1.3.6.1.4.1.13742.8.0.0.17
The firmware update state of an peripheral device
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  PeripheralDeviceFirmwareUpdateStateEnumeration  

agentInetPortNumber 1.3.6.1.4.1.13742.8.0.0.18
The UDP port number used for accessing the SNMP agent on the device. Examples: If deviceCascadeType is portForwarding, then master: 50500 slave 1:50501 slave 2: 50502 ...... If cascading mode is not portForwarding and default (Standard) ports are being used, then port: 161
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  InetPortNumber  

phoneNumber 1.3.6.1.4.1.13742.8.0.0.19
The phone number of e.g. an SMS receiver.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

systemStarted 1.3.6.1.4.1.13742.8.0.1
The system has started.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

systemReset 1.3.6.1.4.1.13742.8.0.2
The system was reset. The conditions under which this trap is sent include, but are not limited to, the following. using the GUI - Maintenance->Reset Unit using the CLI - reset emd unit
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userLogin 1.3.6.1.4.1.13742.8.0.3
A user logged in.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userLogout 1.3.6.1.4.1.13742.8.0.4
A user logged out.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userAuthenticationFailure 1.3.6.1.4.1.13742.8.0.5
A user authentication attempt failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userSessionTimeout 1.3.6.1.4.1.13742.8.0.6
A user timed out from the device.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userAdded 1.3.6.1.4.1.13742.8.0.7
A user was added to the system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userModified 1.3.6.1.4.1.13742.8.0.8
A user account was modified.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userDeleted 1.3.6.1.4.1.13742.8.0.9
A user was deleted from the system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleAdded 1.3.6.1.4.1.13742.8.0.10
A role was added to the system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleModified 1.3.6.1.4.1.13742.8.0.11
A role was modified.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleDeleted 1.3.6.1.4.1.13742.8.0.12
A role was deleted from the system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceUpdateStarted 1.3.6.1.4.1.13742.8.0.13
The device update has started.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceUpdateCompleted 1.3.6.1.4.1.13742.8.0.14
The device update has completed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userBlocked 1.3.6.1.4.1.13742.8.0.15
A blocked user tried to log in.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userPasswordChanged 1.3.6.1.4.1.13742.8.0.16
User password was changed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

passwordSettingsChanged 1.3.6.1.4.1.13742.8.0.17
Strong password settings changed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

firmwareValidationFailed 1.3.6.1.4.1.13742.8.0.18
Firmware validation failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

logFileCleared 1.3.6.1.4.1.13742.8.0.19
The log file has been cleared.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

bulkConfigurationSaved 1.3.6.1.4.1.13742.8.0.20
Bulk Configuration saved.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

bulkConfigurationCopied 1.3.6.1.4.1.13742.8.0.21
Bulk Configuration saved.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

externalSensorStateChange 1.3.6.1.4.1.13742.8.0.22
External Sensor State Change.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smtpMessageTransmissionFailure 1.3.6.1.4.1.13742.8.0.23
SMTP message transmission failure
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

ldapError 1.3.6.1.4.1.13742.8.0.24
LDAP Error occurred; errorDescription describes the error
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceUpdateFailed 1.3.6.1.4.1.13742.8.0.25
The device update has failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pingServerEnabled 1.3.6.1.4.1.13742.8.0.26
The ping feature has been enabled
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pingServerDisabled 1.3.6.1.4.1.13742.8.0.27
The ping feature has been disabled
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

serverNotReachable 1.3.6.1.4.1.13742.8.0.28
The server is not reachable
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

serverReachable 1.3.6.1.4.1.13742.8.0.29
The server is reachable
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceIdentificationChanged 1.3.6.1.4.1.13742.8.0.30
Device identification has changed
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

usbSlaveConnected 1.3.6.1.4.1.13742.8.0.31
USB Connectivity to slave has been established
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

usbSlaveDisconnected 1.3.6.1.4.1.13742.8.0.32
USB Connectivity to slave has been lost
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

lhxSupportChanged 1.3.6.1.4.1.13742.8.0.33
The Schroff LHX Support changed to state 'lhxSupportEnabled'.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userAcceptedRestrictedServiceAgreement 1.3.6.1.4.1.13742.8.0.34
The user accepted the Restricted Service Agreement.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userDeclinedRestrictedServiceAgreement 1.3.6.1.4.1.13742.8.0.35
The user declined the Restricted Service Agreement.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceSettingsSaved 1.3.6.1.4.1.13742.8.0.36
Device Settings have been saved.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

deviceSettingsRestored 1.3.6.1.4.1.13742.8.0.37
Device Settings have been restored.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

webcamInserted 1.3.6.1.4.1.13742.8.0.38
A webcam has been inserted
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

webcamRemoved 1.3.6.1.4.1.13742.8.0.39
A webcam has been removed
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

serverConnectivityUnrecoverable 1.3.6.1.4.1.13742.8.0.40
The connection to the server could not be recovered
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

radiusError 1.3.6.1.4.1.13742.8.0.41
LDAP Error occurred; errorDescription describes the error
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

serverReachabilityError 1.3.6.1.4.1.13742.8.0.42
Server Reachability Error occurred; errorDescription describes the error. This trap is sent when the Error state is entered. Reasons for transitioning to the Error state include the following: Unable to resolve the server hostname.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

unknownPeripheralDeviceAttached 1.3.6.1.4.1.13742.8.0.43
An unknown peripheral device was attached.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

peripheralDeviceFirmwareUpdate 1.3.6.1.4.1.13742.8.0.44
The firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smsMessageTransmissionFailure 1.3.6.1.4.1.13742.8.0.45
Sending an SMS message failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE