DESCH-PSC3-BASE-MIB

File: DESCH-PSC3-BASE-MIB.mib (44578 bytes)

Imported modules

SNMPv2-TC SNMPv2-CONF DESCH-GLOBAL-REG
SNMPv2-SMI

Imported symbols

DisplayString OBJECT-GROUP NOTIFICATION-GROUP
MODULE-COMPLIANCE deschModules deschPsc3
enterprises MODULE-IDENTITY OBJECT-TYPE
NOTIFICATION-TYPE Gauge32 Integer32
IpAddress

Defined Types

DcEventHistoryEntry  
SEQUENCE    
  dcEventHistoryIndex Integer32
  dcEventHistoryTimestamp DisplayString
  dcEventHistoryMessage DisplayString

DcAlarmEntry  
SEQUENCE    
  dcAlarmIndex Integer32
  dcAlarmEventCategory INTEGER
  dcAlarmEventName DisplayString
  dcAlarmEventIdentifier Gauge32
  dcAlarmEventValue INTEGER

DcRectifierEntry  
SEQUENCE    
  dcRectifierIndex Integer32
  dcRectifierIdentifier DisplayString
  dcRectifierStatus INTEGER

DcGenericAlarmEntry  
SEQUENCE    
  dcGenericAlarmIndex Integer32
  dcGenericAlarmEventName DisplayString
  dcGenericAlarmEventIdentifier Gauge32
  dcGenericAlarmEventValue INTEGER

DcControlEventEntry  
SEQUENCE    
  dcControlEventIndex Integer32
  dcControlEventName DisplayString
  dcControlEventIdentifier Gauge32
  dcControlEventValue INTEGER

DcTrapDestinationEntry  
SEQUENCE    
  dcTrapDestinationIndex Integer32
  dcTrapDestinationIp IpAddress
  dcTrapDestinationPort Gauge32

Defined Values

deschPsc3BaseMibModule 1.3.6.1.4.1.20246.2.1.1.2
MIB for managing a DC power system with PSC 3.
MODULE-IDENTITY    

deschPsc3BaseMib 1.3.6.1.4.1.20246.2.3.1.1.1
OBJECT IDENTIFIER    

deschControllerConfs 1.3.6.1.4.1.20246.2.3.1.1.1.1
OBJECT IDENTIFIER    

deschControllerGroups 1.3.6.1.4.1.20246.2.3.1.1.1.1.1
OBJECT IDENTIFIER    

deschControllerCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2
OBJECT IDENTIFIER    

deschControllerObjects 1.3.6.1.4.1.20246.2.3.1.1.1.2
OBJECT IDENTIFIER    

dcSystemInfo 1.3.6.1.4.1.20246.2.3.1.1.1.2.1
OBJECT IDENTIFIER    

dcSystemAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2
OBJECT IDENTIFIER    

dcSystemMonitor 1.3.6.1.4.1.20246.2.3.1.1.1.2.3
OBJECT IDENTIFIER    

dcRectifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4
OBJECT IDENTIFIER    

dcBattery 1.3.6.1.4.1.20246.2.3.1.1.1.2.5
OBJECT IDENTIFIER    

dcFloatCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1
OBJECT IDENTIFIER    

dcBatteryTest 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2
OBJECT IDENTIFIER    

dcBatteryTestParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1
OBJECT IDENTIFIER    

dcBatteryTestResult 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2
OBJECT IDENTIFIER    

dcBatteryParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3
OBJECT IDENTIFIER    

dcEqualize 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4
OBJECT IDENTIFIER    

dcBoostCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5
OBJECT IDENTIFIER    

dcInputOutput 1.3.6.1.4.1.20246.2.3.1.1.1.2.6
OBJECT IDENTIFIER    

dcMisc 1.3.6.1.4.1.20246.2.3.1.1.1.2.7
OBJECT IDENTIFIER    

deschControllerEvents 1.3.6.1.4.1.20246.2.3.1.1.1.3
OBJECT IDENTIFIER    

deschControllerEventObjects 1.3.6.1.4.1.20246.2.3.1.1.1.3.1
OBJECT IDENTIFIER    

deschControllerEventsV2 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0
OBJECT IDENTIFIER    

dcSiteName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1
An administratively-assigned site name for this DC-power system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..16)  

dcSystemName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2
An administratively-assigned system name for this DC-power system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..16)  

dcSystemDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3
ISO 8601 representation of controller's local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(19)  

dcSoftwareVersion 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4
The controller's software version e.g V2.50Build1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..25)  

dcNumberUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3
Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcNumberNonUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4
Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcMainsFailureAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5
Mains failure alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), active(2)  

dcUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6
Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7
Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER false(1), indeterminate(2), true(3)  

dcNonUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8
Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcNonUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9
Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER false(1), indeterminate(2), true(3)  

dcUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10
Current alarm name for urgent alarm that corresponds to urgent alarm identifier.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcNonUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11
Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcSystemVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1
The measured system voltage. The max. value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcLoadCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2
The measured load current. The max. value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcBatteryCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3
The measured battery current. The max. value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcBatteryTemperature 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4
The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcChargeState 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5
Battery charge state.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER float(1), discharge(2), equalize(3), boost(4), battTest(5), recharge(6), sepCharge(7), evCtrlCharge(8)  

dcCurrentLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6
Battery current limit.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), active(2)  

dcRectifierCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7
Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcSystemPower 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8
Calculated system power. The maximum value 4294967295 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcNumberRectifiers 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1
The configured number of rectifiers plugged into the system. The maximum number of rectifiers is 128.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32 0..128  

dcNumberRectifiersFailure 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2
Number of rectifiers that are not properly working.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32 0..128  

dcNumberRectifiersOkay 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3
Number of rectifiers that are properly working.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32 0..128  

dcUsys20 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1
Voltage to regulate to at 20oC. If temperature compensation is used, this voltage will vary. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcTcoeff 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.2
Temperature compensation coefficient for system voltage. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcTcLow 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.3
Low limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcTcHigh 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.4
High limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcUsupport 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1
Support charge voltage for the battery. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2
Battery test duration. Zero indicates that this value is not set.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcInterval 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3
Minimal time between programmed battery tests. Zero indicates that this value is not set.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcDischargeCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4
Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcTestDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1
ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(19)  

dcTestResult 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2
Result of last performed battery test.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none(1), failed(2), aborted(3), loadFailure(4), okay(5)  

dcTestEndVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3
System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcBatteryTestControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3
Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please not that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER start(1), stop(2)  

dcBatteryTestStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4
Current status of battery test.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), starting(2), stopping(3), constantCurrent(4), timeBased(5), energyBased(6), recovery(7), realLoad(8), stop(9)  

dcBatteryTestFailureEvent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5
Reset battery test failure event.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER reset(1)  

dcTotalBatteryCapacity 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1
Total battery capacity for all available batteries.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcEqualizeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1
Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER start(1), stop(2)  

dcEqualizeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2
Current status of battery equalize.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), starting(2), stopping(3), preparing(4), cooking(5), recovering(6)  

dcBoostChargeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1
Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER start(1), stop(2)  

dcBoostChargeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2
Current status of boost charge.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), starting(2), stopping(3), cooking(4), recovering(5)  

dcFileProcessingStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2
File processing status for software and setup up/downloads.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER idle(1), inProgress(2), successful(3), error(4), unknown(5)  

dcSetupConfiguration 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.3
Save current setup configuration to non-volatile memory.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER save(1)  

dcEventHistoryTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1
Controller's event history table that shows the content of the default log file.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcEventHistoryEntry

dcEventHistoryEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1
A particular Event History entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcEventHistoryEntry  

dcEventHistoryIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..10000  

dcEventHistoryTimestamp 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2
ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(19)  

dcEventHistoryMessage 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3
Event message of a particular entry.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2
Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s).
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcAlarmEntry

dcAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1
A particular active alarm source entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcAlarmEntry  

dcAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..16  

dcAlarmEventCategory 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2
Specifies the type of alarm source.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), urgent(2), nonUrgent(3)  

dcAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3
Name of a particular alarm source entry.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4
Unique alarm event identifier.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5
Event status that corresponds to alarm event identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER false(1), indeterminate(2), true(3)  

dcRectifierTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4
Table that shows all currently active rectifier modules.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcRectifierEntry

dcRectifierEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1
A particular rectifier entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcRectifierEntry  

dcRectifierIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..128  

dcRectifierIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2
Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

dcRectifierStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3
Specifies status of rectifiers.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), off(2), on(3)  

dcGenericAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12
Table that shows ten alarm event assignments that can be configured via WEB interface.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcGenericAlarmEntry

dcGenericAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1
A particular generic alarm entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcGenericAlarmEntry  

dcGenericAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..16  

dcGenericAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2
Plain text name of the assigned alarm event. Empty if not configured.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcGenericAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3
Unique numeric identifier of the assigned alarm event. Zero if not configured.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcGenericAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4
Current value of the assigned alarm event. Value is false if not configured.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER false(1), true(2)  

dcControlEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1
Table that shows ten output event assignments that can be configured via WEB interface.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcControlEventEntry

dcControlEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1
A particular generic output entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcControlEventEntry  

dcControlEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..16  

dcControlEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2
Plain text name of the assigned control event. Empty if not configure.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dcControlEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3
Unique numeric identifier of the assigned control event. Zero if not configured.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

dcControlEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4
Current value of the assigned control event. Value is false if not configured.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER false(1), true(2)  

dcTrapDestinationTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1
Trap table that shows all configured trap destinations.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcTrapDestinationEntry

dcTrapDestinationEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1
A particular trap destination entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  DcTrapDestinationEntry  

dcTrapDestinationIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1
Table index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..10  

dcTrapDestinationIp 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2
IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured.
Status: current Access: read-write
OBJECT-TYPE    
  IpAddress  

dcTrapDestinationPort 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3
Port number of the trap destination. By default port 162 is used.
Status: current Access: read-write
OBJECT-TYPE    
  Gauge32  

systemNonUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1
The controller reports that one or more elements have changed into none urgent alarm state.
Status: current Access: read-write
NOTIFICATION-TYPE    

systemUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2
The controller reports that one or more elements have changed into urgent alarm state.
Status: current Access: read-write
NOTIFICATION-TYPE    

deschSystemInfoGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1
The collection of system info scalar objects.
Status: current Access: read-write
OBJECT-GROUP    

deschSystemAlarmGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2
The collection of system alarm scalar objects.
Status: current Access: read-write
OBJECT-GROUP    

deschSystemMonitorGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3
The collection of system monitor scalar objects.
Status: current Access: read-write
OBJECT-GROUP    

deschRectifiersGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4
The collection of rectifier scalar objects.
Status: current Access: read-write
OBJECT-GROUP    

deschEventHistoryTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5
The collection of event history table objects.
Status: current Access: read-write
OBJECT-GROUP    

deschAlarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6
The collection of alarm table objects.
Status: current Access: read-write
OBJECT-GROUP    

deschRectifierTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7
The collection of rectifier table objects.
Status: current Access: read-write
OBJECT-GROUP    

deschNotificationsGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8
The group of all controller notifications.
Status: current Access: read-write
NOTIFICATION-GROUP    

deschGenericAlarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9
Assignment of events to alarm table entries.
Status: current Access: read-write
OBJECT-GROUP    

deschBatteryGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10
The collection of battery scalar objects.
Status: current Access: read-write
OBJECT-GROUP    

deschControlEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11
Assignment of control events to table entries.
Status: current Access: read-write
OBJECT-GROUP    

deschTrapDestinationTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12
Trap destionation table.
Status: current Access: read-write
OBJECT-GROUP    

deschMiscGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13
The collection of miscellaneous objects.
Status: current Access: read-write
OBJECT-GROUP    

deschControllerBasicCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1
The basic implementation requirements for the controller MIB.
Status: current Access: read-write
MODULE-COMPLIANCE