AUTOMATION-SYSTEM-MIB
File:
AUTOMATION-SYSTEM-MIB.mib (42847 bytes)
Imported modules
Imported symbols
Defined Values
automationSystemMIB |
1.3.6.1.4.1.4329.6.3.2 |
Definition of generic management objects
which describe a general I IA product.
|
MODULE-IDENTITY |
|
|
|
automationManufacturerId |
1.3.6.1.4.1.4329.6.3.2.1.1.1 |
A code which identifies the vendor of the
component (e. g. the specific department
or OEM).
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Unsigned32 |
0..65535 |
|
automationRevisionCounter |
1.3.6.1.4.1.4329.6.3.2.1.1.6 |
This value will be incremented every time
one of the other values of
automationIM0Group or automationIM1Group
(cp. conformance statements) changes.
The counter starts with 1
(default configuration).
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Counter32 |
|
|
automationRevisionDate |
1.3.6.1.4.1.4329.6.3.2.1.1.7 |
The time of the last change of the value of
automationRevisionCounter. The value starts
with the date of the default configuration.
If a system doesn't support an absolute time
it must not support the value
(cp. conformance statements).
If the system supports the ENTITY-MIB the
value of this entry correlates to
entLastChangeTime.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DateAndTime |
|
|
automationFunctionTag |
1.3.6.1.4.1.4329.6.3.2.1.1.8 |
A code which describes the function of the
component within the plant. This value will
be set by the engineering system. It is
comparable to the 'sysName'of MIB-II
but from the automation point of view.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AutomationFunctionStringTC |
|
|
automationLocationTag |
1.3.6.1.4.1.4329.6.3.2.1.1.9 |
A code which describes the location where
the component is installed within the plant.
This value will be set by the engineering
system. It is comparable to the
'sysLocation' of MIB-II but from the
automation point of view.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AutomationLocationStringTC |
|
|
automationGeoLatitude |
1.3.6.1.4.1.4329.6.3.2.1.1.10 |
geographical latitude of the equipment site
shown in one of the following formats:
- DD.DDDDDD^
- DD^MM.MMMM'
- DD^MM'SS.SS.
a leading '+' sign or the trailing letter 'N'
indicates northern latitude,
a leading '-' sign or the trailing letter 'S'
indicates southern latitude.
The geodesic reference system is WGS84.
Only so many shall be written for fractional
digits until the desired precision is
represented.
Examples: 49.025^, 49^01.5224',
49^01'31.343 N,
+49^01'31.343
or 49^01'31.343
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
automationGeoLongitude |
1.3.6.1.4.1.4329.6.3.2.1.1.11 |
geographical longitude of the equipment site
shown in one of the following formats:
- DDD.DDDDD^
- DDD^MM.MMMM'
- DDD^MM'SS.SS
a leading '+' sign or the trailing letter
'O' or 'E' indicates eastern longitude,
a leading '-' sign or the trailing letter 'W'
indicates western longitude,
The geodesic reference system is WGS84.
Only so many shall be written for fractional
digits until the desired precision is
represented.
Examples: 8.3498^,
8^20.986',
8^20'59.2 E,
+8^20'59.2
or 8^20'59.2
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
automationGeoHeight |
1.3.6.1.4.1.4329.6.3.2.1.1.12 |
geographical height of the equipment site
in the following format:
- dddddd m (high-order zeros are suppressed)
a leading sign '-' indicates a height
below zero.
The geodesic reference system is WGS84.
Examples: 158 m, - 20 m
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
automationSwUser |
1.3.6.1.4.1.4329.6.3.2.1.1.15 |
The name of the user who made the last
firmware update.
The value 'unknown' shall be
given, if the user is not known.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
automationSwDate |
1.3.6.1.4.1.4329.6.3.2.1.1.16 |
The time of the last firmware update.
The value starts with the date of the
default configuration.
If a system doesn't support an absolute time
it must not support the value.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DateAndTime |
|
|
automationOperState |
1.3.6.1.4.1.4329.6.3.2.1.2.1 |
General operational status of the component.
ok(0) indicates that the component works,
no errors.
maintenanceRequired(1) indicates, that at
the moment there aren't any problems
but maintenace is required e. g.
because a service interval has expired
or the component determined a software
update and so on.
maintenanceDemanded(2) indicates,
that the component works, but there are
problems which could lead to fault
situations.
fault(3) indicates a failure condition on
the component.
If a fault-LED is available (on front panel),
the fault-LED indication shall be synchronized
with the fault value of automationOperState.
If the automationOperState signals a fault,
the fault-LED must be lit (ON).
In all other states of automationOperState
the fault-LED is off.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(0), maintenanceRequired(1), maintenanceDemanded(2), fault(3) |
|
automationApplicationOperState |
1.3.6.1.4.1.4329.6.3.2.1.2.2 |
Operating status of the application within the
automation system.
This status indicates whether the device
context is part of an automation system that is
in operation (run or stop) or not (no_control).
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noControl(1), run(2), stop(3) |
|
automationSystemRestart |
1.3.6.1.4.1.4329.6.3.2.1.3.1 |
Restart the system. Setting the value to 1
causes a coldstart, a value of 2 causes a
warmstart. The different behaviour of
coldstart and warmstart depends on the
component and is described in the user
manual of the component.
If a warmstart is triggered by the values
of 3 or 4 the settings of the component will
be reseted to factory defaults. The value of
3 means that only the basic parameters will
be reseted, the value of 4 causes a complete
reset. Which parameters are affected by this
action is described in the components
manual.
If write access is not allowed, no matter what reason
(e.g. an active PROFINET configuration), write requests
must be rejected with error 'noSuchName' (SNMPv1 agents) or
'notWriteable' (SNMPv2 and SNMPv3 agents) respectively.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noOperation(0), coldstart(1), warmstart(2), restartBasicDefaults(3), restartCompleteDefaults(4) |
|
automationResetCounters |
1.3.6.1.4.1.4329.6.3.2.1.3.4 |
Reset all statistic counters of the
component. On write access only a value of
set(1) will be accepted (and causes a reset
of the counters of the system), all other
values will be rejected.
If write access is not allowed, no matter what reason
(e.g. an active PROFINET configuration), write requests
must be rejected with error 'noSuchName' (SNMPv1 agents) or
'notWriteable' (SNMPv2 and SNMPv3 agents) respectively.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
AutomationTriggerTC |
|
|
automationConfigId |
1.3.6.1.4.1.4329.6.3.2.1.3.5 |
Signature of all configuration parameter
values.
The special value of all bytes 0x00 denotes the
situation of a temporarily not available
signature, what might happen during a
configuration download while the signature
is under construction.
If the ConfigId cannot be built, no matter what reason
(e.g. incompatibilities between parameter layout and
build algorithm, out of resources, ...), get requestes
must be responded with error 'noSuchInstance'.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OCTET STRING |
Size(64) |
|
automationConfigUser |
1.3.6.1.4.1.4329.6.3.2.1.3.6 |
The name of the user who made the last
change to any parameter of the configuration
parameter set. The value 'unknown' shall be
given, if the user is not known.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
automationConfigDate |
1.3.6.1.4.1.4329.6.3.2.1.3.7 |
The time of the last change to a parameter
of the configuration parameter set.
The value starts with the date of the
default configuration.
If a system doesn't support an absolute time
it must not support the value
(cp. conformance statements).
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DateAndTime |
|
|
automationSystemIpAddress |
1.3.6.1.4.1.4329.6.3.2.1.4.1 |
This object contains the IP address of the
system (which is used to connect to the SNMP
agent, the web entity etc.). If the
component features an outbandport, this
object contains the inband IP address.
|
Status: deprecated |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
automationSystemIpSubnetMask |
1.3.6.1.4.1.4329.6.3.2.1.4.2 |
This object contains the subnet mask of
the system (which is used to connect to
the SNMP agent, the webentity etc.).
If the component features an outbandport,
this object contains the inband subnet mask.
|
Status: deprecated |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
automationSystemOutbandIp |
1.3.6.1.4.1.4329.6.3.2.1.4.4 |
If the system features an outband port, this
object contains its IP address.
|
Status: deprecated |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
automationOperStateChanged |
1.3.6.1.4.1.4329.6.3.2.2.0.1 |
The system triggers this event in case the
value of automationOperState changed. |
Status: current |
Access: read-write |
NOTIFICATION-TYPE |
|
|
|
automationRevisionChanged |
1.3.6.1.4.1.4329.6.3.2.2.0.2 |
The system triggers this event in case the
configuration changed (e. g. the hardware
configuration, a firmware update or IP
parameter).
|
Status: current |
Access: read-write |
NOTIFICATION-TYPE |
|
|
|
automationIM0Group |
1.3.6.1.4.1.4329.6.3.2.3.1.1 |
This group collects the named parameters
according to the referenced guideline.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationIM1Group |
1.3.6.1.4.1.4329.6.3.2.3.1.2 |
This group collects the named parameters
according to the referenced guideline.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationIM2Group |
1.3.6.1.4.1.4329.6.3.2.3.1.3 |
This group collects the named parameters
according to the referenced guideline.
The revision date is only available if
the system supports an absolute time,
therefore this group must be only
supported if the absolute time is
available.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationStatusGroup |
1.3.6.1.4.1.4329.6.3.2.3.1.4 |
Generic status information. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationIpGroup |
1.3.6.1.4.1.4329.6.3.2.3.1.7 |
IP configuration of the agent. |
Status: deprecated |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationOutbandGroup |
1.3.6.1.4.1.4329.6.3.2.3.1.8 |
Configuration of the outband port. |
Status: deprecated |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationStatusEvents |
1.3.6.1.4.1.4329.6.3.2.3.1.9 |
Notifications about status changes. |
Status: current |
Access: read-write |
NOTIFICATION-GROUP |
|
|
|
automationConfigurationEvents |
1.3.6.1.4.1.4329.6.3.2.3.1.10 |
Notifications about configuration changes. |
Status: current |
Access: read-write |
NOTIFICATION-GROUP |
|
|
|
automationGeoLocation |
1.3.6.1.4.1.4329.6.3.2.3.1.11 |
This group collects the named parameters
according to the geographical coordinates.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationGeoLocationTimeShift |
1.3.6.1.4.1.4329.6.3.2.3.1.12 |
This group collects the named parameters
according to the geographical coordinates
and the location dependent time shift.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationConfigIdGroup |
1.3.6.1.4.1.4329.6.3.2.3.1.13 |
This group collects the named parameters
for the suppport of a config signature.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationSwDownloadGroup |
1.3.6.1.4.1.4329.6.3.2.3.1.14 |
This group collects the named parameters
for a firmware download.
|
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
automationSystemBasicCompliance |
1.3.6.1.4.1.4329.6.3.2.3.2.1 |
Minimum implementation requirements for all
Industry Automation Division systems
with SNMP support. |
Status: current |
Access: read-write |
MODULE-COMPLIANCE |
|
|
|
automationSystemExtCompliance |
1.3.6.1.4.1.4329.6.3.2.3.2.2 |
Extended requirements for
Industry Automation Division systems. |
Status: deprecated |
Access: read-write |
MODULE-COMPLIANCE |
|
|
|
automationSystemExtCompliance2 |
1.3.6.1.4.1.4329.6.3.2.3.2.3 |
Extended requirements for
Industry Automation Division systems. |
Status: current |
Access: read-write |
MODULE-COMPLIANCE |
|
|
|