ALPHA-NOTIFICATION-MIB
File:
ALPHA-NOTIFICATION-MIB.mib (7974 bytes)
Imported modules
Imported symbols
Defined Values
alphaAlarmNotifications |
1.3.6.1.4.1.7309.100 |
This MIB defines the notification block(s) available in system controllers. |
MODULE-IDENTITY |
|
|
|
alphaAlarmActiveState |
1.3.6.1.4.1.7309.100.1 |
SNMPv2 notification varbinds start with SysUptime
and Notification Oid as the first two in the list
by default. The first varbind in this definition
would be the third varbind in the raw output of the
notification.
An instance of the alarm indicated by
alarmActiveModelPointer has been raised
against the entity indicated by
alarmActiveResourceId.
The state of the alarm is indicated by the
alarmModelState.
The description of the alarm along with its source
is indicated by the alarmModelDescription and
componentListStaticName respectively.
componentListSnmpId provides the Id set to the
source of the alarm.
The agent must throttle the generation of
consecutive alarmActiveState traps so that there is at
least a two-second gap between traps of this
type against the same alarmActiveModelPointer and
alarmActiveResourceId. When traps are throttled,
they are queued for sending at a future time.
A management application should periodically check
the value of alarmActiveLastChanged to detect any
missed alarmActiveState notification-events, e.g.,
due to throttling or transmission loss.
|
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alphaAlarmClearState |
1.3.6.1.4.1.7309.100.2 |
SNMPv2 notification varbinds start with SysUptime
and Notification Oid as the first two in the list
by default. The first varbind in this definition
would be the third varbind in the raw output of the
notification.
An instance of the alarm indicated by
alarmActiveModelPointer has been cleared against
the entity indicated by alarmActiveResourceId.
The state of the alarm is indicated by the
alarmModelState.
The description of the alarm along with its source
is indicated by the alarmModelDescription and
componentListStaticName respectively.
componentListSnmpId provides the Id set to the
source of the alarm.
The agent must throttle the generation of
consecutive alarmActiveClear traps so that there is at
least a two-second gap between traps of this
type against the same alarmActiveModelPointer and
alarmActiveResourceId. When traps are throttled,
they are queued for sending at a future time.
A management application should periodically check
the value of alarmActiveLastChanged to detect any
missed alarmClearState notification-events, e.g.,
due to throttling or transmission loss.
|
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmSeverity |
1.3.6.1.4.1.7309.101.1 |
User defined value used for filtering purposes.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
alarmCustomDescription |
1.3.6.1.4.1.7309.101.2 |
User defined value used for filtering purposes.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OCTET STRING |
|
|
alarmPriority |
1.3.6.1.4.1.7309.101.3 |
User defined value used for filtering purposes.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OCTET STRING |
|
|
alphaAlarmNotificationCompliance |
1.3.6.1.4.1.7309.100.102.1.1 |
The compliance statement for systems supporting
the alpha MIB. |
Status: current |
Access: read-only |
MODULE-COMPLIANCE |
|
|
|
alphaParameterGroup |
1.3.6.1.4.1.7309.100.102.1.2.1 |
Active alpha list group. |
Status: current |
Access: read-only |
OBJECT-GROUP |
|
|
|
alphaNotificationsGroup |
1.3.6.1.4.1.7309.100.102.1.2.2 |
The collection of notifications that can be used to
model alarms for faults lacking pre-existing
notification definitions. |
Status: current |
Access: read-only |
NOTIFICATION-GROUP |
|
|
|