ALPHA-NOTIFICATION-MIB

File: ALPHA-NOTIFICATION-MIB.mib (7974 bytes)

Imported modules

SNMPv2-SMI ALARM-MIB ALPHA-RESOURCE-MIB
SNMPv2-CONF

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
Integer32 alarmActiveModelPointer alarmActiveResourceId
alarmModelDescription alpha controllerInfoName
componentListStaticName componentListReference MODULE-COMPLIANCE
OBJECT-GROUP NOTIFICATION-GROUP

Defined Values

alphaAlarmNotifications 1.3.6.1.4.1.7309.100
This MIB defines the notification block(s) available in system controllers.
MODULE-IDENTITY    

alphaAlarmNotificationsExtension 1.3.6.1.4.1.7309.101
OBJECT IDENTIFIER    

alphaAlarmActiveState 1.3.6.1.4.1.7309.100.1
SNMPv2 notification varbinds start with SysUptime and Notification Oid as the first two in the list by default. The first varbind in this definition would be the third varbind in the raw output of the notification. An instance of the alarm indicated by alarmActiveModelPointer has been raised against the entity indicated by alarmActiveResourceId. The state of the alarm is indicated by the alarmModelState. The description of the alarm along with its source is indicated by the alarmModelDescription and componentListStaticName respectively. componentListSnmpId provides the Id set to the source of the alarm. The agent must throttle the generation of consecutive alarmActiveState traps so that there is at least a two-second gap between traps of this type against the same alarmActiveModelPointer and alarmActiveResourceId. When traps are throttled, they are queued for sending at a future time. A management application should periodically check the value of alarmActiveLastChanged to detect any missed alarmActiveState notification-events, e.g., due to throttling or transmission loss.
Status: current Access: read-only
NOTIFICATION-TYPE    

alphaAlarmClearState 1.3.6.1.4.1.7309.100.2
SNMPv2 notification varbinds start with SysUptime and Notification Oid as the first two in the list by default. The first varbind in this definition would be the third varbind in the raw output of the notification. An instance of the alarm indicated by alarmActiveModelPointer has been cleared against the entity indicated by alarmActiveResourceId. The state of the alarm is indicated by the alarmModelState. The description of the alarm along with its source is indicated by the alarmModelDescription and componentListStaticName respectively. componentListSnmpId provides the Id set to the source of the alarm. The agent must throttle the generation of consecutive alarmActiveClear traps so that there is at least a two-second gap between traps of this type against the same alarmActiveModelPointer and alarmActiveResourceId. When traps are throttled, they are queued for sending at a future time. A management application should periodically check the value of alarmActiveLastChanged to detect any missed alarmClearState notification-events, e.g., due to throttling or transmission loss.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmSeverity 1.3.6.1.4.1.7309.101.1
User defined value used for filtering purposes.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

alarmCustomDescription 1.3.6.1.4.1.7309.101.2
User defined value used for filtering purposes.
Status: current Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alarmPriority 1.3.6.1.4.1.7309.101.3
User defined value used for filtering purposes.
Status: current Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alphaAlarmNotificationConformance 1.3.6.1.4.1.7309.100.102
OBJECT IDENTIFIER    

alphaAlarmNotificationCompliances 1.3.6.1.4.1.7309.100.102.1
OBJECT IDENTIFIER    

alphaAlarmNotificationCompliance 1.3.6.1.4.1.7309.100.102.1.1
The compliance statement for systems supporting the alpha MIB.
Status: current Access: read-only
MODULE-COMPLIANCE    

alphaAlarmNotificationGroups 1.3.6.1.4.1.7309.100.102.1.2
OBJECT IDENTIFIER    

alphaParameterGroup 1.3.6.1.4.1.7309.100.102.1.2.1
Active alpha list group.
Status: current Access: read-only
OBJECT-GROUP    

alphaNotificationsGroup 1.3.6.1.4.1.7309.100.102.1.2.2
The collection of notifications that can be used to model alarms for faults lacking pre-existing notification definitions.
Status: current Access: read-only
NOTIFICATION-GROUP