ALPHA-INVERTER-SYS-MIB

File: ALPHA-INVERTER-SYS-MIB.mib (17753 bytes)

Imported modules

SNMPv2-SMI ALPHA-RESOURCE-MIB SNMPv2-CONF

Imported symbols

MODULE-IDENTITY OBJECT-TYPE Integer32
ScaledNumber simple MODULE-COMPLIANCE
OBJECT-GROUP

Defined Types

InvSysAcPhaseEntry  
SEQUENCE    
  invSysAcPhaseAcOutputPowerVa ScaledNumber
  invSysAcPhaseOutputVoltageMeasured ScaledNumber
  invSysAcPhaseOutputCurrent ScaledNumber
  invSysAcPhaseFrequency ScaledNumber
  invSysAcPhaseLoadingOfInstalledPowerVa ScaledNumber
  invSysAcPhaseNumberOfModulesOn ScaledNumber
  invSysAcPhaseLoadingOfInstalledPowerWatts ScaledNumber
  invSysAcPhaseDcInputToOutputPowerRatioMeasured ScaledNumber
  invSysAcPhaseAcInputPowerWatts ScaledNumber
  invSysAcPhaseAcInputPowerVa ScaledNumber
  invSysAcPhaseAcOutputPowerWatts ScaledNumber
  invSysAcPhaseDCInputPowerWatts ScaledNumber
  invSysAcPhaseNumberOfRedundantModulesMeasured ScaledNumber
  invSysAcPhaseNumberOfModulesDetected ScaledNumber
  invSysAcPhaseNumberOfModulesOff ScaledNumber
  invSysAcPhaseNumberOfModulesFailed ScaledNumber

InvSysAcInputEntry  
SEQUENCE    
  invSysAcInputInputVoltage ScaledNumber
  invSysAcInputInputCurrent ScaledNumber
  invSysAcInputFrequency ScaledNumber
  invSysAcInputAcInputPowerVa ScaledNumber
  invSysAcInputNumberOfModulesOn ScaledNumber
  invSysAcInputAcInputPowerWatts ScaledNumber
  invSysAcInputNumberOfModulesDetected ScaledNumber
  invSysAcInputNumberOfModulesOff ScaledNumber
  invSysAcInputNumberOfModulesFailed ScaledNumber

InvSysDcInputEntry  
SEQUENCE    
  invSysDcInputInputVoltage ScaledNumber
  invSysDcInputInputCurrent ScaledNumber
  invSysDcInputDcInputPowerWatts ScaledNumber
  invSysDcInputNumberOfModulesOn ScaledNumber
  invSysDcInputNumberOfModulesOff ScaledNumber
  invSysDcInputNumberOfModulesFailed ScaledNumber
  invSysDcInputNumberOfModulesDetected ScaledNumber

Defined Values

inverterSystem 1.3.6.1.4.1.7309.5.3.3
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
MODULE-IDENTITY    

phaseGroup 1.3.6.1.4.1.7309.5.3.3.80
OBJECT IDENTIFIER    

acInputGroup 1.3.6.1.4.1.7309.5.3.3.81
OBJECT IDENTIFIER    

dcInputGroup 1.3.6.1.4.1.7309.5.3.3.82
OBJECT IDENTIFIER    

invTotalAcOutputPowerVa 1.3.6.1.4.1.7309.5.3.3.1
The total output power summed from all the phases (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAverageLoadingOfInstalledPowerVa 1.3.6.1.4.1.7309.5.3.3.2
The average output loading of all phases (% VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAverageDcInputToOutputPowerRatio 1.3.6.1.4.1.7309.5.3.3.3
The percentage of the output that is taken from the DC input (%).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysSystemMode 1.3.6.1.4.1.7309.5.3.3.4
The mode of the system. See manual for decoding the number.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysPhase1OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.5
The total output power from the phase 1 (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysPhase2OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.6
The total output power from phase 2 (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysPhase3OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.7
The total output power from the phase 3 (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAverageOutputVoltageMeasured 1.3.6.1.4.1.7309.5.3.3.8
The average output voltage of all the phases (V).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysEnabledDisconnects 1.3.6.1.4.1.7309.5.3.3.9
The number of disconnects that are enabled.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysActivatedDisconnects 1.3.6.1.4.1.7309.5.3.3.10
The number of disconnects that are active.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysTotalDCInputCurrent 1.3.6.1.4.1.7309.5.3.3.11
Total DC input current for the inverter system (A).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAverageDcInputVoltage 1.3.6.1.4.1.7309.5.3.3.12
Average DC input voltage reading for the inverter system (V).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysTotalDcInputPower 1.3.6.1.4.1.7309.5.3.3.13
Total DC input power reading for the inverter system (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysSystemOnBypass 1.3.6.1.4.1.7309.5.3.3.14
True when the bypass switch is on. The AC input from the grid is fed to the AC load directly.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysTotalAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.18
Total AC input power reading of the Inverter System (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseCount 1.3.6.1.4.1.7309.5.3.3.80.1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

invSysAcPhaseTable 1.3.6.1.4.1.7309.5.3.3.80.2
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InvSysAcPhaseEntry

invSysAcPhaseEntry 1.3.6.1.4.1.7309.5.3.3.80.2.1
Status: current Access: not-accessible
OBJECT-TYPE    
  InvSysAcPhaseEntry  

invSysAcPhaseAcOutputPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.1
The power of the AC output (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseOutputVoltageMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.2
The output voltage of the phase or inverter (V).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseOutputCurrent 1.3.6.1.4.1.7309.5.3.3.80.2.1.3
The output current of the phase or inverter (A).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseFrequency 1.3.6.1.4.1.7309.5.3.3.80.2.1.4
Frequency to which the inverters will lock (Hz).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseLoadingOfInstalledPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.5
The ratio of output load to installed power (%VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.80.2.1.6
The number of inverters that are On and can deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseLoadingOfInstalledPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.7
The ratio of output load to installed power (% W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseDcInputToOutputPowerRatioMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.8
The measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseAcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.9
The power drawn by the AC input (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.10
The power drawn by the AC input (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseAcOutputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.11
The power of the AC output (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseDCInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.12
The power drawn by the DC input (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseNumberOfRedundantModulesMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.13
Number of inverters currently unneeded by the load.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.80.2.1.14
The number of inverters assigned to this phase that the T2S has detected.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.80.2.1.15
The number of inverters that are manually turned off.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcPhaseNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.80.2.1.16
The number of inverters that have failed and cannot deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputCount 1.3.6.1.4.1.7309.5.3.3.81.1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

invSysAcInputTable 1.3.6.1.4.1.7309.5.3.3.81.2
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InvSysAcInputEntry

invSysAcInputEntry 1.3.6.1.4.1.7309.5.3.3.81.2.1
Status: current Access: not-accessible
OBJECT-TYPE    
  InvSysAcInputEntry  

invSysAcInputInputVoltage 1.3.6.1.4.1.7309.5.3.3.81.2.1.1
The input voltage of the inverter or group (V).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputInputCurrent 1.3.6.1.4.1.7309.5.3.3.81.2.1.2
The input current of the inverter or group (A).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputFrequency 1.3.6.1.4.1.7309.5.3.3.81.2.1.3
The frequency of the input voltage and current of the inverter or group (Hz).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.81.2.1.4
The power drawn by the AC input (VA).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.81.2.1.5
The number of inverters that are On and can deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputAcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.81.2.1.6
The power drawn by the AC input (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.81.2.1.7
The number of inverters assigned to this phase that the T2S has detected.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.81.2.1.8
The number of inverters that are manually turned off.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysAcInputNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.81.2.1.9
The number of inverters that have failed and cannot deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputCount 1.3.6.1.4.1.7309.5.3.3.82.1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

invSysDcInputTable 1.3.6.1.4.1.7309.5.3.3.82.2
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InvSysDcInputEntry

invSysDcInputEntry 1.3.6.1.4.1.7309.5.3.3.82.2.1
Status: current Access: not-accessible
OBJECT-TYPE    
  InvSysDcInputEntry  

invSysDcInputInputVoltage 1.3.6.1.4.1.7309.5.3.3.82.2.1.1
The input voltage of the inverter or group (V).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputInputCurrent 1.3.6.1.4.1.7309.5.3.3.82.2.1.2
The input current of the inverter or group (A).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputDcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.82.2.1.3
The power drawn by the DC input (W).
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.82.2.1.4
The number of inverters that are On and can deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.82.2.1.5
The number of inverters that are manually turned off.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.82.2.1.6
The number of inverters that have failed and cannot deliver power.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber  

invSysDcInputNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.82.2.1.7
The number of inverters assigned to this phase that the T2S has detected.
Status: current Access: read-only
OBJECT-TYPE    
  ScaledNumber