AISLCANALOG-MIB

File: AISLCANALOG-MIB.mib (16989 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC

Imported symbols

MODULE-IDENTITY OBJECT-TYPE enterprises
TruthValue DisplayString

Defined Types

PositiveInteger  
INTEGER 1..2147483647    

NonNegativeInteger  
INTEGER 0..2147483647    

AISLCAnalogInputEntry  
SEQUENCE    
  aislcainPointNumber PositiveInteger
  aislcainScanningEnabled INTEGER
  aislcainDescription DisplayString
  aislcainTrapEnable INTEGER
  aislcainNormalStateTrap INTEGER
  aislcainHighAlarmSeverity INTEGER
  aislcainHighAlarmStateText DisplayString
  aislcainLowAlarmSeverity INTEGER
  aislcainLowAlarmStateText DisplayString
  aislcainNormalStateText DisplayString
  aislcainUserUnits DisplayString
  aislcainMinInputmA DisplayString
  aislcainMinInputuu DisplayString
  aislcainMaxInputmA DisplayString
  aislcainMaxInputuu DisplayString
  aislcainHighLimitScan INTEGER
  aislcainHighAlarmThresholduu DisplayString
  aislcainHighAlarmThresholdIntervaluu DisplayString
  aislcainHighAlarmMinPeriod INTEGER
  aislcainHighAlarmHysteresisuu DisplayString
  aislcainLowLimitScan INTEGER
  aislcainLowAlarmThresholduu DisplayString
  aislcainLowAlarmThresholdIntervaluu DisplayString
  aislcainLowAlarmMinPeriod INTEGER
  aislcainLowAlarmHysteresisuu DisplayString
  aislcainCurrentValueuu DisplayString
  aislcainCurrentValuemA DisplayString
  aislcainLastChangeTime DisplayString
  aislcaintl1AccessID DisplayString
  aislcaintl1Provisioned TruthValue
  aislcaintl1AccessIDType INTEGER
  aislcaintl1HighAlarmType DisplayString
  aislcaintl1HighAlarmMessage DisplayString
  aislcaintl1LowAlarmType DisplayString
  aislcaintl1LowAlarmMessage DisplayString
  aislcaintl1HighAlarmNotificationCode DisplayString
  aislcaintl1HighAlarmServiceAffecting INTEGER
  aislcaintl1HighAlarmConditionType DisplayString
  aislcaintl1HighAlarmConditionDesc DisplayString
  aislcaintl1LowAlarmNotificationCode DisplayString
  aislcaintl1LowAlarmServiceAffecting INTEGER
  aislcaintl1LowAlarmConditionType DisplayString
  aislcaintl1LowAlarmConditionDesc DisplayString
  aislcainAnalogStatus INTEGER
  aislcainCurrentStateText DisplayString
  aislcainAnalogAlarmState INTEGER

Defined Values

aii 1.3.6.1.4.1.539
OBJECT IDENTIFIER    

aiSLCAnalog 1.3.6.1.4.1.539.28
MIB module for SLCs with analog input points.
MODULE-IDENTITY    

aiSLCAnalogInputTable 1.3.6.1.4.1.539.28.1
Table of analog inputs points indexed by point number. Includes description, configuration and status information.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AISLCAnalogInputEntry

aiSLCAnalogInputEntry 1.3.6.1.4.1.539.28.1.1
Entry of aiSLCAnalogInputTable.
Status: current Access: not-accessible
OBJECT-TYPE    
  AISLCAnalogInputEntry  

aislcainPointNumber 1.3.6.1.4.1.539.28.1.1.1
Input point number to which this table row applies.
Status: current Access: read-only
OBJECT-TYPE    
  PositiveInteger  

aislcainScanningEnabled 1.3.6.1.4.1.539.28.1.1.2
Enable or disable scanning of the input.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

aislcainDescription 1.3.6.1.4.1.539.28.1.1.3
Textual description of the point. Maximum length is 80 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..80)  

aislcainTrapEnable 1.3.6.1.4.1.539.28.1.1.4
Enable or disable alarm traps.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

aislcainNormalStateTrap 1.3.6.1.4.1.539.28.1.1.5
If enabled, transitions from an alarm state to the normal state will generate an SNMP trap or TL1 message.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

aislcainHighAlarmSeverity 1.3.6.1.4.1.539.28.1.1.6
Severity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), major(2), minor(3), info(4), notReported(5)  

aislcainHighAlarmStateText 1.3.6.1.4.1.539.28.1.1.7
Textual description of the point's alarm state. Maximum length is 80 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..80)  

aislcainLowAlarmSeverity 1.3.6.1.4.1.539.28.1.1.8
Severity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), major(2), minor(3), info(4), notReported(5)  

aislcainLowAlarmStateText 1.3.6.1.4.1.539.28.1.1.9
Textual description of the point's alarm state. Maximum length is 80 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..80)  

aislcainNormalStateText 1.3.6.1.4.1.539.28.1.1.10
Textual description of the point's normal state. Maximum length is 80 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..80)  

aislcainUserUnits 1.3.6.1.4.1.539.28.1.1.11
The user-defined units for this input (e.g. degC, degF, etc.).
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

aislcainMinInputmA 1.3.6.1.4.1.539.28.1.1.12
The current in mA corresponding to the minimum input in user-defined units.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainMinInputuu 1.3.6.1.4.1.539.28.1.1.13
The minimum value in user-defined units corresponding to the minimum input in mA.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainMaxInputmA 1.3.6.1.4.1.539.28.1.1.14
The current in mA corresponding to the maximum input in user-defined units.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainMaxInputuu 1.3.6.1.4.1.539.28.1.1.15
The maximum value in user-defined units corresponding to the maximum input in mA.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainHighLimitScan 1.3.6.1.4.1.539.28.1.1.16
If enabled, the high limit threshold will be checked when the input is scanned.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

aislcainHighAlarmThresholduu 1.3.6.1.4.1.539.28.1.1.17
The high alarm level in user-defined units.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainHighAlarmThresholdIntervaluu 1.3.6.1.4.1.539.28.1.1.18
The high alarm level threshold interval in user-defined units. When the high alarm is active, each time the input rises another interval higher, a new alarm is sent.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainHighAlarmMinPeriod 1.3.6.1.4.1.539.28.1.1.19
The minimum number of seconds the input(s) should be energized when the input exceeds the high alarm threshold.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..600  

aislcainHighAlarmHysteresisuu 1.3.6.1.4.1.539.28.1.1.20
The amount by which the input must drop below the High Alarm Threshold before the High Alarm will be cleared.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainLowLimitScan 1.3.6.1.4.1.539.28.1.1.21
If enabled, the low limit threshold will be checked when the input is scanned.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

aislcainLowAlarmThresholduu 1.3.6.1.4.1.539.28.1.1.22
The low alarm level in user-defined units.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainLowAlarmThresholdIntervaluu 1.3.6.1.4.1.539.28.1.1.23
The low alarm level threshold interval in user-defined units. When the low alarm is active, each time the input drops another interval lower, a new alarm is sent.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainLowAlarmMinPeriod 1.3.6.1.4.1.539.28.1.1.24
The minimum number of seconds the input(s) should be energized when the input falls below the low alarm threshold.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..600  

aislcainLowAlarmHysteresisuu 1.3.6.1.4.1.539.28.1.1.25
The amount by which the input must rise above the Low Alarm Threshold before the Low Alarm will be cleared.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainCurrentValueuu 1.3.6.1.4.1.539.28.1.1.26
The current input value in user-defined units.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

aislcainCurrentValuemA 1.3.6.1.4.1.539.28.1.1.27
The current input value in mA.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

aislcainLastChangeTime 1.3.6.1.4.1.539.28.1.1.28
Textural representation of the time of the most recent output change. 24-hour format YYYY-MM-DD HH:MM:SS.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(19..23)  

aislcaintl1AccessID 1.3.6.1.4.1.539.28.1.1.29
Unique TL1 access identifier for this point. Maximum length is 22 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..22)  

aislcaintl1Provisioned 1.3.6.1.4.1.539.28.1.1.30
Enable TL1 management of this point.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

aislcaintl1AccessIDType 1.3.6.1.4.1.539.28.1.1.31
Identifies the point as either an equipment(1) alarm condition or an environmental(2) alarm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER equipment(1), environmental(2)  

aislcaintl1HighAlarmType 1.3.6.1.4.1.539.28.1.1.32
String indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

aislcaintl1HighAlarmMessage 1.3.6.1.4.1.539.28.1.1.33
Textual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..40)  

aislcaintl1LowAlarmType 1.3.6.1.4.1.539.28.1.1.34
String indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

aislcaintl1LowAlarmMessage 1.3.6.1.4.1.539.28.1.1.35
Textual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..40)  

aislcaintl1HighAlarmNotificationCode 1.3.6.1.4.1.539.28.1.1.36
Severity of the point's alarm state.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), major(2), minor(3)  

aislcaintl1HighAlarmServiceAffecting 1.3.6.1.4.1.539.28.1.1.37
Indicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER serviceAffecting(1), notServiceAffecting(2)  

aislcaintl1HighAlarmConditionType 1.3.6.1.4.1.539.28.1.1.38
String indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

aislcaintl1HighAlarmConditionDesc 1.3.6.1.4.1.539.28.1.1.39
Textual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..64)  

aislcaintl1LowAlarmNotificationCode 1.3.6.1.4.1.539.28.1.1.40
Severity of the point's alarm state.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), major(2), minor(3)  

aislcaintl1LowAlarmServiceAffecting 1.3.6.1.4.1.539.28.1.1.41
Indicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER serviceAffecting(1), notServiceAffecting(2)  

aislcaintl1LowAlarmConditionType 1.3.6.1.4.1.539.28.1.1.42
String indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

aislcaintl1LowAlarmConditionDesc 1.3.6.1.4.1.539.28.1.1.43
Textual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..64)  

aislcainAnalogStatus 1.3.6.1.4.1.539.28.1.1.44
The current alarm status of the analog input.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), highLimitExceeded(2), lowLimitExceeded(3), lossOfSignal(4), saturated(5)  

aislcainCurrentStateText 1.3.6.1.4.1.539.28.1.1.45
Textual description of the point's current state. This is either aislcainNormalStateText or aislcainAlarmStateText.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..80)  

aislcainAnalogAlarmState 1.3.6.1.4.1.539.28.1.1.46
The point's current alarm state, or normal(5).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER critical(1), major(2), minor(3), info(4), normal(5)