USHA-MIB

File: USHA-MIB.mib (86869 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215 UPS-MIB

Imported symbols

enterprises Counter IpAddress
OBJECT-TYPE DisplayString TRAP-TYPE
PositiveInteger NonNegativeInteger

Defined Types

UpsInputGroupEntry  
SEQUENCE    
  upsInputGroupLineIndex PositiveInteger
  upsInputGroupFrequency NonNegativeInteger
  upsInputGroupVoltage NonNegativeInteger
  upsInputGroupCurrent NonNegativeInteger
  upsInputGroupTruePower NonNegativeInteger
  upsInputGroupVoltageMax NonNegativeInteger
  upsInputGroupVoltageMin NonNegativeInteger

UpsOutputGroupEntry  
SEQUENCE    
  upsOutputGroupLineIndex PositiveInteger
  upsOutputGroupVoltage NonNegativeInteger
  upsOutputGroupCurrent NonNegativeInteger
  upsOutputGroupPower NonNegativeInteger
  upsOutputGroupPercentLoad INTEGER

UpsBypassGroupEntry  
SEQUENCE    
  upsBypassGroupLineIndex PositiveInteger
  upsBypassGroupVoltage NonNegativeInteger
  upsBypassGroupCurrent NonNegativeInteger
  upsBypassGroupPower NonNegativeInteger

UpsBatteryTestScheduleEntry  
SEQUENCE    
  upsBatteryTestScheduleIndex INTEGER
  upsBatteryTestScheduleDay INTEGER
  upsBatteryTestScheduleTime DisplayString
  upsBatteryTestScheduleType INTEGER
  upsBatteryTestScheduleTestWithTime INTEGER
  upsBatteryTestScheduleSpecialDay DisplayString

UpsControlShutdownParametersEntry  
SEQUENCE    
  upsControlEvent INTEGER
  upsControlEventStatus INTEGER
  upsControlDelay INTEGER
  upsControlFirstWarning INTEGER
  upsControlWarningInterval INTEGER

UpsControlWeeklyScheduleEntry  
SEQUENCE    
  upsControlWeeklyIndex INTEGER
  upsControlWeeklyShutdownDay INTEGER
  upsControlWeeklyShutdownTime DisplayString
  upsControlWeeklyRestartDay INTEGER
  upsControlWeeklyRestartTime DisplayString

UpsControlSpecialScheduleEntry  
SEQUENCE    
  upsControlSpecialIndex INTEGER
  upsControlSpecialShutdownDay DisplayString
  upsControlSpecialShutdownTime DisplayString
  upsControlSpecialRestartDay DisplayString
  upsControlSpecialRestartTime DisplayString

UpsDevicesEntry  
SEQUENCE    
  indexOfDevice NonNegativeInteger
  addrOfDevice IpAddress
  nameOfDevice DisplayString
  timeOfConnection DisplayString
  timeOfConnectionTime DisplayString
  timeOfConnectionTimeout INTEGER

AgentConfigTrapsReceiversEntry  
SEQUENCE    
  trapsIndex INTEGER
  trapsReceiverAddr IpAddress
  receiverCommunityString DisplayString
  receiverNmsType INTEGER
  receiverSeverityLevel INTEGER
  receiverDescription DisplayString

AgentConfigAccessControlEntry  
SEQUENCE    
  accessIndex INTEGER
  accessControlAddr IpAddress
  accessCommunityString DisplayString
  accessControlMode INTEGER

Defined Values

ingrasys 1.3.6.1.4.1.2468
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.2468.1
OBJECT IDENTIFIER    

upsAgent 1.3.6.1.4.1.2468.1.2
OBJECT IDENTIFIER    

ushap 1.3.6.1.4.1.2468.1.2.1
OBJECT IDENTIFIER    

upsObjectGroup 1.3.6.1.4.1.2468.1.2.1.1
OBJECT IDENTIFIER    

upsTrapGroup 1.3.6.1.4.1.2468.1.2.1.2
OBJECT IDENTIFIER    

upsIdentGroup 1.3.6.1.4.1.2468.1.2.1.1.1
OBJECT IDENTIFIER    

upsBatteryGroup 1.3.6.1.4.1.2468.1.2.1.1.2
OBJECT IDENTIFIER    

upsInputGroup 1.3.6.1.4.1.2468.1.2.1.1.3
OBJECT IDENTIFIER    

upsOutputGroup 1.3.6.1.4.1.2468.1.2.1.1.4
OBJECT IDENTIFIER    

upsBypassGroup 1.3.6.1.4.1.2468.1.2.1.1.5
OBJECT IDENTIFIER    

upsTestGroup 1.3.6.1.4.1.2468.1.2.1.1.6
OBJECT IDENTIFIER    

upsControlGroup 1.3.6.1.4.1.2468.1.2.1.1.7
OBJECT IDENTIFIER    

upsConfigGroup 1.3.6.1.4.1.2468.1.2.1.1.8
OBJECT IDENTIFIER    

upsClients 1.3.6.1.4.1.2468.1.2.1.1.9
OBJECT IDENTIFIER    

agentConfig 1.3.6.1.4.1.2468.1.2.1.1.10
OBJECT IDENTIFIER    

emdStatus 1.3.6.1.4.1.2468.1.2.1.1.11
OBJECT IDENTIFIER    

emdConfig 1.3.6.1.4.1.2468.1.2.1.1.12
OBJECT IDENTIFIER    

upsIdentGroupManufacturer 1.3.6.1.4.1.2468.1.2.1.1.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdentGroupModel 1.3.6.1.4.1.2468.1.2.1.1.1.2
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsIdentGroupUPSFirmwareVersion 1.3.6.1.4.1.2468.1.2.1.1.1.3
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentGroupAgentSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsIdentGroupAgentSoftwareVersion 1.3.6.1.4.1.2468.1.2.1.1.1.4
The USHA software/firmware version. This variable may or may not have the same value as upsIdentGroupUPSSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdentGroupName 1.3.6.1.4.1.2468.1.2.1.1.1.5
A string identifying the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdentGroupAttachedDevices 1.3.6.1.4.1.2468.1.2.1.1.1.6
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsIdentGroupUpsSerialNumber 1.3.6.1.4.1.2468.1.2.1.1.1.7
The UPS serial no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsBatteryGroupStatus 1.3.6.1.4.1.2468.1.2.1.1.2.1
The indication of the status in the UPS system's batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6)  

upsBatteryGroupSecondsOnBattery 1.3.6.1.4.1.2468.1.2.1.1.2.2
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryGroupEstimatedMinutesRemaining 1.3.6.1.4.1.2468.1.2.1.1.2.3
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryGroupEstimatedChargeRemaining 1.3.6.1.4.1.2468.1.2.1.1.2.4
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.2.5
The magnitude of the present battery voltage in 0.1 Volt DC.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryGroupMandatory 1.3.6.1.4.1.2468.1.2.1.1.2.6
The present battery mandatory.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryGroupTemperature 1.3.6.1.4.1.2468.1.2.1.1.2.7
The ambient temperature at or near the UPS Battery casing.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputGroupLineBads 1.3.6.1.4.1.2468.1.2.1.1.3.1
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Counter  

upsInputGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.3.2
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputGroupTable 1.3.6.1.4.1.2468.1.2.1.1.3.3
A list of input table entries. The number of entries is given by the value of upsInputGroupNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputGroupEntry

upsInputGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.3.3.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputGroupEntry  

upsInputGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.1
The index of UpsInputGroupEntry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 0..65535  

upsInputGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.2
The present input frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.3
The input utility line voltage in 0.1 volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.4
The magnitude of the present input current in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputGroupTruePower 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.5
The magnitude of the present input true power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputGroupVoltageMax 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.6
The maximum utility line voltage in 0.1 VAC for last 1 minute.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInputGroupVoltageMin 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.7
The minimum utility line voltage in 0.1 VAC for last 1 minute.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputGroupSource 1.3.6.1.4.1.2468.1.2.1.1.4.1
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7)  

upsOutputGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.4.2
The current output frequency of the UPS system in 0.1 of HZ.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.4.3
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputGroupTable 1.3.6.1.4.1.2468.1.2.1.1.4.4
A list of output table entries. The number of entries is given by the value of upsOutputGroupNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputGroupEntry

upsOutputGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.4.4.1
An entry containing information applicable to a particular output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputGroupEntry  

upsOutputGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.1
The output line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 0..65535  

upsOutputGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.2
The output voltage of the UPS system in 0.1 volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.3
The output current of the UPS system in 0.1 Amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputGroupPower 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.4
The present output true power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutputGroupPercentLoad 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.5
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.5.1
The present bypass frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.5.2
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassGroupTable 1.3.6.1.4.1.2468.1.2.1.1.5.3
A list of bypass table entries. The number of entries is given by the value of upsBypassGroupNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBypassGroupEntry

upsBypassGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.5.3.1
An entry containing information applicable to a particular bypass input.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBypassGroupEntry  

upsBypassGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.1
The bypass line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 0..65535  

upsBypassGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.2
The present bypass voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.3
The present bypass current.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBypassGroupPower 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.4
The present true power conveyed by the bypass.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsTestBatteryTestSettingTime 1.3.6.1.4.1.2468.1.2.1.1.6.1
The object specify the test time for battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsBatteryTest 1.3.6.1.4.1.2468.1.2.1.1.6.2
This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), battTest10sec(2), battTestUntilLow(3), battTestWithTime(4), battTestCancelTest(5), battTestClearInfo(6)  

upsTestBatteryTestResult 1.3.6.1.4.1.2468.1.2.1.1.6.3
The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6)  

upsTestBatteryTestStartTime 1.3.6.1.4.1.2468.1.2.1.1.6.4
The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..19)  

upsTestBatteryTestElapsedTime 1.3.6.1.4.1.2468.1.2.1.1.6.5
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 00:00:00.00.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(11..11)  

upsBatteryTestScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.6.6
Table which describes the schedule for automatically battery test.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBatteryTestScheduleEntry

upsBatteryTestScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.6.6.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBatteryTestScheduleEntry  

upsBatteryTestScheduleIndex 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.1
The index of battery test scheduled.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsBatteryTestScheduleDay 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.2
The weekday on which the UPS should start battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), specialDay(8), none(9)  

upsBatteryTestScheduleTime 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.3
The time that the battery test will be initiated in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsBatteryTestScheduleType 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.4
The type of battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), battTest10sec(2), battTestUntilLow(3), battTestWithTime(4)  

upsBatteryTestScheduleTestWithTime 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.5
The battTestWithTime of battery test is supported or not.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER supported(1), notSupported(2)  

upsBatteryTestScheduleSpecialDay 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.6
The special day that the battery test will be initiated in dd/mm/yyyy format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsControlUpsShutdownDelay 1.3.6.1.4.1.2468.1.2.1.1.7.1
The delay in seconds the UPS remains on after being told to turn off.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsControlUpsSleepTime 1.3.6.1.4.1.2468.1.2.1.1.7.2
The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsControlUpsOnOffControl 1.3.6.1.4.1.2468.1.2.1.1.7.3
Setting this variable to control UPS output status. turnUpsOff(1) will set UPS turn off output after upsControlUpsShutdownDelay period expired. putUpsToSleep(2) will set UPS turn off output after upsControlUpsShutdownDelay period expired, UPS output will stay off with the period defined by upsControlUpsSleepTime, then turn output on. turnOnUpsOrCancelShutdown(3) can used to turn on UPS output, or cancel any shutdown process.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER turnUpsOff(1), putUpsToSleep(2), turnOnUpsOrCancelShutdown(3), none(4)  

upsControlShutdownParametersTable 1.3.6.1.4.1.2468.1.2.1.1.7.4
Table which describes the parametes for shutdown process when shutdown event occurs
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlShutdownParametersEntry

upsControlShutdownParametersEntry 1.3.6.1.4.1.2468.1.2.1.1.7.4.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlShutdownParametersEntry  

upsControlEvent 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.1
The shutdown event identification
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER acFail(1), batteryLow(2), upsOverload(3), upsOverTempeature(4), weeklySchedule(5), specialDaySchedule(6), emdTemperatureOverThreshold(7), emdAlarm1(8), emdAlarm2(9)  

upsControlEventStatus 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.2
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), warning(2), clientShutdown(3), upsTurnOff(4)  

upsControlDelay 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.3
The Delay after the occurance of the curresponding shutdown event that USHA should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when USHA will start sending the warning message to the connected clients. The value is in units of minutes.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..10080  

upsControlFirstWarning 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.4
The delay after the occurance of the curresponding shutdown event that the USHA will start sending the warning message to the connected clients. The value is in units of seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3600  

upsControlWarningInterval 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.5
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3600  

upsControlWeeklyScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.7.5
The table to schedule shutting down the ups by weekly.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlWeeklyScheduleEntry

upsControlWeeklyScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.7.5.1
The entries for each day.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlWeeklyScheduleEntry  

upsControlWeeklyIndex 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.1
The index of scheduled events.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsControlWeeklyShutdownDay 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.2
The weekday on which the UPS should shut down.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlWeeklyShutdownTime 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlWeeklyRestartDay 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.4
The weekday on which the UPS should restart
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlWeeklyRestartTime 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.5
The time the UPS will restart in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlSpecialScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.7.6
The table to schedule shutting down the ups.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlSpecialScheduleEntry

upsControlSpecialScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.7.6.1
The entries for each day.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlSpecialScheduleEntry  

upsControlSpecialIndex 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.1
The index of scheduled events.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsControlSpecialShutdownDay 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.2
The date on which the UPS should shut down in dd/mm/yyyy format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsControlSpecialShutdownTime 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm format
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlSpecialRestartDay 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.4
The date on which the UPS should restart in dd/mm/yyyy format
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsControlSpecialRestartTime 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.5
The time the UPS will restart in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsConfigGroupInputVoltage 1.3.6.1.4.1.2468.1.2.1.1.8.1
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigGroupInputFreq 1.3.6.1.4.1.2468.1.2.1.1.8.2
The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigGroupOutputVoltage 1.3.6.1.4.1.2468.1.2.1.1.8.3
The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigGroupOutputFreq 1.3.6.1.4.1.2468.1.2.1.1.8.4
The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigGroupOutputVA 1.3.6.1.4.1.2468.1.2.1.1.8.5
The magnitude of the nominal Volt-Amp rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigGroupOutputPower 1.3.6.1.4.1.2468.1.2.1.1.8.6
The magnitude of the nominal true power rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsConfigGroupOverTemperatureSetPoint 1.3.6.1.4.1.2468.1.2.1.1.8.7
The maximum temperature allowed before the UPS operation temperature is too high.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger 10..70  

upsConfigGroupOverLoadSetPoint 1.3.6.1.4.1.2468.1.2.1.1.8.8
The maximum output load allowed before the load is too high for UPS operation.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger 0..120  

upsClientsConnectedNum 1.3.6.1.4.1.2468.1.2.1.1.9.1
The count of clients which have resgistered for UPS shutdown control.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsDevicesTable 1.3.6.1.4.1.2468.1.2.1.1.9.2
The devices powered by UPS and registered to USHA
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsDevicesEntry

upsDevicesEntry 1.3.6.1.4.1.2468.1.2.1.1.9.2.1
The devices protected by USHA
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsDevicesEntry  

indexOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.1
The index of the device that is plugged into the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

addrOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.2
The ip address of the device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

nameOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.3
The name/description of the device plugged into the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

timeOfConnection 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.4
The device registered to USHA
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

timeOfConnectionTime 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.5
The device registered time to USHA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

timeOfConnectionTimeout 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.6
The device timeout counter. Unit: 10 seconds
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

agentConfigIpaddress 1.3.6.1.4.1.2468.1.2.1.1.10.1
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigGateway 1.3.6.1.4.1.2468.1.2.1.1.10.2
The default gateway that allow device managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigSubnetMask 1.3.6.1.4.1.2468.1.2.1.1.10.3
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigDate 1.3.6.1.4.1.2468.1.2.1.1.10.4
The date in agent, format is (dd/mm/yyyy)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

agentConfigTime 1.3.6.1.4.1.2468.1.2.1.1.10.5
The time in agent, format is (hh:mm:ss)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

agentConfigPrimaryTimeServer 1.3.6.1.4.1.2468.1.2.1.1.10.6
The primary time server is responsible for sending the correct time to the agent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigSecondaryTimeServer 1.3.6.1.4.1.2468.1.2.1.1.10.7
The secondary time server is responsible for sending the correct time to the agent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigHistoryLogFrequency 1.3.6.1.4.1.2468.1.2.1.1.10.8
The frequency of the updation of the history log. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 5..28800  

agentConfigExtHistoryLogFrequency 1.3.6.1.4.1.2468.1.2.1.1.10.9
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10080  

agentConfigPollRate 1.3.6.1.4.1.2468.1.2.1.1.10.10
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..999  

agentConfigBaudRate 1.3.6.1.4.1.2468.1.2.1.1.10.11
The serial port communication speed. only 9600 allowed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

agentConfigDhcpStatue 1.3.6.1.4.1.2468.1.2.1.1.10.12
Enable or disable DHCP/BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigTelnetStatue 1.3.6.1.4.1.2468.1.2.1.1.10.13
Enable or disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigTftpStatue 1.3.6.1.4.1.2468.1.2.1.1.10.14
Enable or disable network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigResetToDefault 1.3.6.1.4.1.2468.1.2.1.1.10.15
Reset all parameters of USHA to default value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER reset(1), nothing(2)  

agentConfigRestart 1.3.6.1.4.1.2468.1.2.1.1.10.16
Restart USHA
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restart(1), nothing(2)  

agentConfigClearAgentLog 1.3.6.1.4.1.2468.1.2.1.1.10.17
Clear agent log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearEventLog 1.3.6.1.4.1.2468.1.2.1.1.10.18
Clear event log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearExtHistoryLog 1.3.6.1.4.1.2468.1.2.1.1.10.19
Clear extented history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearHistoryLog 1.3.6.1.4.1.2468.1.2.1.1.10.20
Clear history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigTrapRetryCount 1.3.6.1.4.1.2468.1.2.1.1.10.21
The count of repeat traps to send to NMS before trap acknowledge received.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigTrapRetryTime 1.3.6.1.4.1.2468.1.2.1.1.10.22
The time between retry traps sned to NMS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigTrapAckSignature 1.3.6.1.4.1.2468.1.2.1.1.10.23
The signature of trap acknowledge.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigMibVersion 1.3.6.1.4.1.2468.1.2.1.1.10.24
The version of MIB spec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

agentConfigTrapsReceiversTable 1.3.6.1.4.1.2468.1.2.1.1.10.25
A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AgentConfigTrapsReceiversEntry

agentConfigTrapsReceiversEntry 1.3.6.1.4.1.2468.1.2.1.1.10.25.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  AgentConfigTrapsReceiversEntry  

trapsIndex 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

trapsReceiverAddr 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

receiverCommunityString 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

receiverNmsType 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.4
The trap group that NMS desired.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), rfc1628-trap(2), usha-trap(3)  

receiverSeverityLevel 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.5
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), severe(3)  

receiverDescription 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.6
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

agentConfigAccessControlTable 1.3.6.1.4.1.2468.1.2.1.1.10.26
A list of managers which can access USHA with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AgentConfigAccessControlEntry

agentConfigAccessControlEntry 1.3.6.1.4.1.2468.1.2.1.1.10.26.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  AgentConfigAccessControlEntry  

accessIndex 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

accessControlAddr 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.2
The IP address of the manager to access USHA
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

accessCommunityString 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.3
The community name to use in the manager when access USHA
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

accessControlMode 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.4
Access type, only read/Write access type can change parameter of USHA
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), readWrite(2), notAccess(3)  

agentConfigDefaultLanguage 1.3.6.1.4.1.2468.1.2.1.1.10.27
The default languauge for browser, when set to auto(1) USHA will send page in the language depends on the request language of browser.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), english(2), traditionalChinese(3), simplifiedChinese(4)  

emdSatatusEmdType 1.3.6.1.4.1.2468.1.2.1.1.11.1
The type of EMD plugged into the port.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), emdHT(3), emdT(4)  

emdSatatusTemperature 1.3.6.1.4.1.2468.1.2.1.1.11.2
The measurement of EMD temperature, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

emdSatatusHumidity 1.3.6.1.4.1.2468.1.2.1.1.11.3
The measurement of EMD humidity, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

emdSatatusAlarm1 1.3.6.1.4.1.2468.1.2.1.1.11.4
The EMD alarm-1 status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

emdSatatusAlarm2 1.3.6.1.4.1.2468.1.2.1.1.11.5
The EMD alarm-2 status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

usahEmdConfigEmdConfig 1.3.6.1.4.1.2468.1.2.1.1.12.1
Enable or disable to detect presence of EMD
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

emdConfigEmdName 1.3.6.1.4.1.2468.1.2.1.1.12.2
Description of EMD
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigTemperature 1.3.6.1.4.1.2468.1.2.1.1.12.3
OBJECT IDENTIFIER    

emdConfigTempName 1.3.6.1.4.1.2468.1.2.1.1.12.3.1
Description of EMD temperature sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigTempHighSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.3.2
The set point for high temperature warning, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigTempHighStatus 1.3.6.1.4.1.2468.1.2.1.1.12.3.3
To enable/disable high set point check with emd temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigTempLowSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.3.4
The set point for low temperature warning, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigTempLowStatus 1.3.6.1.4.1.2468.1.2.1.1.12.3.5
To enable/disable low set point check with emd temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigTempOffset 1.3.6.1.4.1.2468.1.2.1.1.12.3.6
The offset to calibrate temperature of EMD, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidity 1.3.6.1.4.1.2468.1.2.1.1.12.4
OBJECT IDENTIFIER    

emdConfigHumidityName 1.3.6.1.4.1.2468.1.2.1.1.12.4.1
Description of EMD humidity sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigHumidityHighSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.4.2
The set point for high humidity warning, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidityLowStatus 1.3.6.1.4.1.2468.1.2.1.1.12.4.3
To enable/disable high set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigHumidityLowSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.4.4
The set point for low humidity warning, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidityHighStatus 1.3.6.1.4.1.2468.1.2.1.1.12.4.5
To enable/disable low set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigHumidityOffset 1.3.6.1.4.1.2468.1.2.1.1.12.4.6
The offset to calibrate humidity of EMD, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigAlarm1 1.3.6.1.4.1.2468.1.2.1.1.12.5
OBJECT IDENTIFIER    

emdConfigAlarm1Name 1.3.6.1.4.1.2468.1.2.1.1.12.5.1
Description of EMD alarm-1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigAlarm1Type 1.3.6.1.4.1.2468.1.2.1.1.12.5.2
The alarm-1 operation type
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), nomralOpen(2), normalClose(3)  

emdConfigAlarm2 1.3.6.1.4.1.2468.1.2.1.1.12.6
OBJECT IDENTIFIER    

emdConfigAlarm2Name 1.3.6.1.4.1.2468.1.2.1.1.12.6.1
Description of EMD alarm-2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigAlarm2Type 1.3.6.1.4.1.2468.1.2.1.1.12.6.2
The alarm-1 operation type
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), nomralOpen(2), normalClose(3)  

ushaPowerRestored 1
INFORMATION: Utility power has been restore.
TRAP-TYPE    

ushaPowerFail 2
WARNING: Utility power not available.
TRAP-TYPE    

ushaReturnFromLowBattery 3
INFORMATION: The UPS has return from a low battery condition.
TRAP-TYPE    

ushaLowBattery 4
SEVERE: The UPS batteries are low and will soon be exhausted.
TRAP-TYPE    

ushaUpsOk 5
INFORMATION: The ups is working fine.
TRAP-TYPE    

ushaUpsFailed 6
SEVERE: The ups is not working fine.
TRAP-TYPE    

ushaUpsNotOnBattery 7
INFORMATION: The UPS is not on battery power.
TRAP-TYPE    

ushaUpsOnBattery 8
WARNING: The UPS has switched to battery backup power.
TRAP-TYPE    

ushaTestOver 9
INFORMATION: The testing of UPS is completed.
TRAP-TYPE    

ushaTestInProgress 10
INFORMATION: The testing is going on ups.
TRAP-TYPE    

ushaBypassOn 11
INFORMATION: The UPS has enabled bypass.
TRAP-TYPE    

ushaUpsOnline 12
INFORMATION: The UPS is not on Bypass and return to normal status.
TRAP-TYPE    

ushaCommunicationLost 13
SEVERE: Communication to the UPS has been lost.
TRAP-TYPE    

ushaCommunicationEstablished 14
INFORMATION: Communication with the UPS has been established.
TRAP-TYPE    

ushaUpsGoingDown 15
WARNING: The ups has been given shutdown command.
TRAP-TYPE    

ushaUpsTurnedOff 16
INFORMATION: UPS turn off.
TRAP-TYPE    

ushaUpsSleeping 17
INFORMATION: UPS has entered sleep mode.
TRAP-TYPE    

ushaUpsWokeUp 18
INFORMATION: The UPS woke up from sleep mode.
TRAP-TYPE    

ushaUpsRebooted 19
INFORMATION: The UPS is reboot.
TRAP-TYPE    

ushaUpsShutdownCancelled 20
INFORMATION: The UPS shutdown process had been cancelled.
TRAP-TYPE    

ushaUpsNotOverTemperature 21
INFORMATION: The UPS internal temperature return to normal.
TRAP-TYPE    

ushaUpsOverTemperature 22
SEVERE: The UPS temperature is too high.
TRAP-TYPE    

ushaUpsNotOverLoad 23
INFORMATION: The UPS load return from overload.
TRAP-TYPE    

ushaUpsOverLoad 24
SEVERE: The UPS is overload.
TRAP-TYPE    

ushaUpsModuleInserted 25
WARNING: UPS Battery Module plug-in.
TRAP-TYPE    

ushaUpsModuleRemoved 26
WARNING: UPS Battery Module unplug.
TRAP-TYPE    

emdTemperatureNotHigh 27
INFORMATION: EMD Temperature not over high Set point.
TRAP-TYPE    

emdTemperatureTooHigh 28
WARNING: EMD Temperature over high Set point.
TRAP-TYPE    

emdTemperatureNotLow 29
INFORMATION: EMD Temperature not under low Set point.
TRAP-TYPE    

emdTemperatureTooLow 30
WARNING: EMD Temperature under low Set point.
TRAP-TYPE    

emdHumidityNotHigh 31
INFORMATION: EMD Humidity not over high Set point.
TRAP-TYPE    

emdHumidityTooHigh 32
WARNING: EMD Humidity over high Set point.
TRAP-TYPE    

emdHumidityNotLow 33
INFORMATION: EMD Humidity not under low Set point.
TRAP-TYPE    

emdHumidityTooLow 34
WARNING: EMD Humidity under low Set point.
TRAP-TYPE    

emdAlarm1Normal 35
INFORMATION: EMD Alarm-1 not active.
TRAP-TYPE    

emdAlarm1Active 36
WARNING: EMD Alarm-1 activated.
TRAP-TYPE    

emdAlarm2Normal 37
INFORMATION: EMD Alarm-2 not active.
TRAP-TYPE    

emdAlarm2Active 38
WARNING: EMD Alarm-2 activated.
TRAP-TYPE    

ushaUpsInternalwarning 39
WARNING: Internal warning.
TRAP-TYPE    

ushaUpsReturnFromInternalwarning 40
INFORMATION: Return from Internal warning.
TRAP-TYPE    

ushaUpsEPOActive 41
WARNING: EPO Active.
TRAP-TYPE    

ushaUpsReturnFromEPOActive 42
INFORMATION: Return from EPO Active.
TRAP-TYPE    

ushaUpsModuleUnlock 43
WARNING: Module Unlock.
TRAP-TYPE    

ushaUpsReturnFromModuleUnlock 44
INFORMATION: Return from Module Unlock.
TRAP-TYPE    

ushaUpsMain1Neutralloss 45
WARNING: Main 1 Neutral loss.
TRAP-TYPE    

ushaUpsReturnFromMain1Neutralloss 46
INFORMATION: Return from Main 1 Neutral loss.
TRAP-TYPE    

ushaUpsMain1phaseerror 47
WARNING: Main 1 phase error.
TRAP-TYPE    

ushaUpsReturnFromMain1phaseerror 48
INFORMATION: Return from Main 1 phase error.
TRAP-TYPE    

ushaUpsSitefault 49
WARNING: Site fault.
TRAP-TYPE    

ushaUpsReturnFromSitefault 50
INFORMATION: Return from Site fault.
TRAP-TYPE    

ushaUpsBypassAbnormal 51
WARNING: Bypass Abnormal.
TRAP-TYPE    

ushaUpsReturnFromBypassAbnormal 52
INFORMATION: Return from Bypass Abnormal.
TRAP-TYPE    

ushaUpsBypassPhaseError 53
WARNING: Bypass Phase Error.
TRAP-TYPE    

ushaUpsReturnFromBypassPhaseError 54
INFORMATION: Return from Bypass Phase Error.
TRAP-TYPE    

ushaUpsBatteryOpen 55
WARNING: Battery Open.
TRAP-TYPE    

ushaUpsReturnFromBatteryOpen 56
INFORMATION: Return from Battery Open.
TRAP-TYPE    

ushaUpsBatteryOverCharge 57
WARNING: Battery Over Charge.
TRAP-TYPE    

ushaUpsReturnFromBatteryOverCharge 58
INFORMATION: Return from Battery Over Charge.
TRAP-TYPE    

ushaUpsBatteryReverse 59
WARNING: Battery Reverse.
TRAP-TYPE    

ushaUpsReturnFromBatteryReverse 60
INFORMATION: Return from Battery Reverse.
TRAP-TYPE    

ushaUpsOverloadforewarning 61
WARNING: Overload forewarning.
TRAP-TYPE    

ushaUpsReturnFromOverloadforewarning 62
INFORMATION: Return from Overload forewarning.
TRAP-TYPE    

ushaUpsOverloadWarning 63
WARNING: Overload Warning.
TRAP-TYPE    

ushaUpsReturnFromOverloadWarning 64
INFORMATION: Return from Overload Warning.
TRAP-TYPE    

ushaUpsFanLock 65
WARNING: Fan Lock.
TRAP-TYPE    

ushaUpsReturnFromFanLock 66
INFORMATION: Return from Fan Lock.
TRAP-TYPE    

ushaUpsMaintaincoverisopen 67
WARNING: Maintain cover is open.
TRAP-TYPE    

ushaUpsReturnFromMaintaincoverisopen 68
INFORMATION: Return from Maintain cover is open.
TRAP-TYPE    

ushaUpsChargerfault 69
WARNING: Charger fault.
TRAP-TYPE    

ushaUpsReturnFromChargerfault 70
INFORMATION: Return from Charger fault.
TRAP-TYPE    

ushaUpsModulelocationerror 71
WARNING: Module location error.
TRAP-TYPE    

ushaUpsReturnFromModulelocationerror 72
INFORMATION: Return from Module location error.
TRAP-TYPE    

ushaUpsTurnonabnormal 73
WARNING: Turn on abnormal.
TRAP-TYPE    

ushaUpsReturnFromTurnonabnormal 74
INFORMATION: Return from Turn on abnormal.
TRAP-TYPE    

ushaUpsRedundancyloss 75
WARNING: Redundancy loss.
TRAP-TYPE    

ushaUpsReturnFromRedundancyloss 76
INFORMATION: Return from Redundancy loss.
TRAP-TYPE    

ushaUpsHotSwapActived 77
WARNING: Hot Swap Actived.
TRAP-TYPE    

ushaUpsReturnFromHotSwapActived 78
INFORMATION: Return from Hot Swap Actived.
TRAP-TYPE    

ushaUpsBatteryInform 79
WARNING: Battery Inform.
TRAP-TYPE    

ushaUpsReturnFromBatteryInform 80
INFORMATION: Return from Battery Inform.
TRAP-TYPE    

ushaUpsInspectionInform 81
WARNING: Inspection Inform.
TRAP-TYPE    

ushaUpsReturnFromInspectionInform 82
INFORMATION: Return from Inspection Inform.
TRAP-TYPE    

ushaUpsGuaranteeInform 83
WARNING: Guarantee Inform.
TRAP-TYPE    

ushaUpsReturnFromGuaranteeInform 84
INFORMATION: Return from Guarantee Inform.
TRAP-TYPE    

ushaUpsTemperatureLow 85
WARNING: Temperature Low.
TRAP-TYPE    

ushaUpsReturnFromTemperatureLow 86
INFORMATION: Return from Temperature Low.
TRAP-TYPE    

ushaUpsTemperatureHigh 87
WARNING: Temperature High.
TRAP-TYPE    

ushaUpsReturnFromTemperatureHigh 88
INFORMATION: Return from Temperature High.
TRAP-TYPE    

ushaUpsBatteryOverTemperature 89
WARNING: Battery Over Temperature.
TRAP-TYPE    

ushaUpsReturnFromBatteryOverTemperature 90
INFORMATION: Return from Battery Over Temperature.
TRAP-TYPE    

ushaUpsFanMaintainInform 91
WARNING: Fan Maintain Inform.
TRAP-TYPE    

ushaUpsReturnFromFanMaintainInform 92
INFORMATION: Return from Fan Maintain Inform.
TRAP-TYPE    

ushaUpsBusCapacitanceMaintainInform 93
WARNING: Bus Capacitance Maintain Inform.
TRAP-TYPE    

ushaUpsReturnFromBusCapacitanceMaintainInform 94
INFORMATION: Return from Bus Capacitance Maintain Inform.
TRAP-TYPE    

ushaUpsSystemOverCapacity 95
WARNING: System Over Capacity.
TRAP-TYPE    

ushaUpsReturnFromSystemOverCapacity 96
INFORMATION: Return from System Over Capacity.
TRAP-TYPE