UPS2-MIB

File: UPS2-MIB.mib (45334 bytes)

Imported modules

CTRON-MIB-NAMES RFC1213-MIB RFC-1212

Imported symbols

ctUPS DisplayString OBJECT-TYPE

Defined Types

UpsIdEntry  
SEQUENCE    
  upsIndex INTEGER
  upsName DisplayString
  upsModelType INTEGER
  upsFwVersion DisplayString
  upsSerialNumber DisplayString
  upsManufDate DisplayString

UpsBatteryEntry  
SEQUENCE    
  upsBatteryCapacity INTEGER
  upsBatteryVoltage INTEGER
  upsBatteryTest INTEGER
  upsBatteryTestResult INTEGER
  upsRunTimeCalibration INTEGER
  upsEstimatedRunTimeRemaining INTEGER
  upsTransferCause INTEGER
  upsBatteryTestTime INTEGER
  upsLowBatteryWarning INTEGER

UpsInputEntry  
SEQUENCE    
  upsInputUtilityVoltage INTEGER
  upsInputVoltage INTEGER
  upsInputFailureSensitivity INTEGER
  upsInputMaxVoltage INTEGER
  upsInputMinVoltage INTEGER
  upsInputFrequency INTEGER

UpsOutputEntry  
SEQUENCE    
  upsOutputVoltage INTEGER
  upsOutputUtilityVoltage INTEGER
  upsOutputPower INTEGER

UpsStatusEntry  
SEQUENCE    
  upsStatusOperational INTEGER
  upsStatusFault INTEGER
  upsStatusTemp INTEGER

UpsConfigEntry  
SEQUENCE    
  upsConfigAlarm INTEGER
  upsConfigRestoreDefaults INTEGER

UpsExtMeasEntry  
SEQUENCE    
  upsExtMeasFwVersion DisplayString
  upsExtMeasTemp INTEGER
  upsExtMeasHumidity INTEGER
  upsExtMeasAlarmStatus INTEGER
  upsExtMeasMaxTemp INTEGER
  upsExtMeasMinTemp INTEGER
  upsExtMeasMaxHumidity INTEGER
  upsExtMeasMinHumidity INTEGER
  upsExtMeasContact1AlarmControl INTEGER
  upsExtMeasContact2AlarmControl INTEGER
  upsExtMeasContact3AlarmControl INTEGER
  upsExtMeasContact4AlarmControl INTEGER
  upsExtMeasMaxTempAlarmControl INTEGER
  upsExtMeasMinTempAlarmControl INTEGER
  upsExtMeasMaxHumidityAlarmControl INTEGER
  upsExtMeasMinHumidityAlarmControl INTEGER

UpsAddlFuncsEntry  
SEQUENCE    
  upsAddlFuncsNumBatteryPacks INTEGER
  upsAddlFuncsNumBadBatteryPacks INTEGER
  upsAddlFuncsOutputCurrent INTEGER
  upsAddlFuncsOutputApparentPower INTEGER
  upsAddlFuncsStatusOperational INTEGER
  upsAddlFuncsStatusFault INTEGER
  upsAddlFuncsConfigPassword OCTET STRING
  upsAddlFuncsConfigDisable INTEGER
  upsAddlFuncsConfigBypass INTEGER

Defined Values

upsSystem 1.3.6.1.4.1.52.4.1.1.10.1
OBJECT IDENTIFIER    

upsId 1.3.6.1.4.1.52.4.1.1.10.2
OBJECT IDENTIFIER    

upsBattery 1.3.6.1.4.1.52.4.1.1.10.3
OBJECT IDENTIFIER    

upsInput 1.3.6.1.4.1.52.4.1.1.10.4
OBJECT IDENTIFIER    

upsOutput 1.3.6.1.4.1.52.4.1.1.10.5
OBJECT IDENTIFIER    

upsStatus 1.3.6.1.4.1.52.4.1.1.10.6
OBJECT IDENTIFIER    

upsConfig 1.3.6.1.4.1.52.4.1.1.10.7
OBJECT IDENTIFIER    

upsExtMeas 1.3.6.1.4.1.52.4.1.1.10.8
OBJECT IDENTIFIER    

upsAddlFuncs 1.3.6.1.4.1.52.4.1.1.10.9
OBJECT IDENTIFIER    

upsNumUPSs 1.3.6.1.4.1.52.4.1.1.10.1.1
The number of UPSs available.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2  

upsIdTable 1.3.6.1.4.1.52.4.1.1.10.2.1
A list of identification table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsIdEntry

upsIdEntry 1.3.6.1.4.1.52.4.1.1.10.2.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsIdEntry  

upsIndex 1.3.6.1.4.1.52.4.1.1.10.2.1.1.1
A unique value which identifies a particular UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsName 1.3.6.1.4.1.52.4.1.1.10.2.1.1.2
The UPS's name. A maximum of 8 characters may be specified. This object is initialized to the UPS's model name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsModelType 1.3.6.1.4.1.52.4.1.1.10.2.1.1.3
The UPS's base model type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER smartUps250(1), smartUps400(2), smartUps600(3), smartUps900(4), smartUps1250(5), smartUps2000(6), matrixUps3000(7), matrixUps5000(8), other(9)  

upsFwVersion 1.3.6.1.4.1.52.4.1.1.10.2.1.1.4
The UPS's firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsSerialNumber 1.3.6.1.4.1.52.4.1.1.10.2.1.1.5
The UPS's serial number as set at the factory.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

upsManufDate 1.3.6.1.4.1.52.4.1.1.10.2.1.1.6
The UPS's date of manufacture in the format mm/dd/yy.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

upsBatteryTable 1.3.6.1.4.1.52.4.1.1.10.3.1
A list of battery table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBatteryEntry

upsBatteryEntry 1.3.6.1.4.1.52.4.1.1.10.3.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBatteryEntry  

upsBatteryCapacity 1.3.6.1.4.1.52.4.1.1.10.3.1.1.1
The UPS's remaining battery capacity expressed as a percent of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryVoltage 1.3.6.1.4.1.52.4.1.1.10.3.1.1.2
The UPS's present battery voltage. The value of this object is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this object by 100).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryTest 1.3.6.1.4.1.52.4.1.1.10.3.1.1.3
This object may be written to initiate testing of the UPS's battery packs. Reading this object will always return a 0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER initiateTest(1)  

upsBatteryTestResult 1.3.6.1.4.1.52.4.1.1.10.3.1.1.4
The result of the last battery test performed.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER batteryOK(1), batteryBad(2), noRecentTest(3), invalidTestDueToOverload(4)  

upsRunTimeCalibration 1.3.6.1.4.1.52.4.1.1.10.3.1.1.5
This object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRunTimeRemaining. Valid values for writing are 1 (initiate test) and 2 (terminate test). In addition, this object may be read to determine whether the test is currently running. Valid values for reading are 3 (test is in progress) and 4 (test is not in progress).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER performTest(1), abortTest(2), testInProgress(3), testNotInProgress(4)  

upsEstimatedRunTimeRemaining 1.3.6.1.4.1.52.4.1.1.10.3.1.1.6
The UPS's estimated remaining run time in minutes. The UPS may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time estimate is based on available battery capacity and output load.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTransferCause 1.3.6.1.4.1.52.4.1.1.10.3.1.1.7
The reason for the most recent transfer to on-battery operation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER noTransfer(1), selfTest(2), inputLineSpike(3), inputLowVoltage(4), inputHighVoltage(5), inputLineFrequencyBad(6)  

upsBatteryTestTime 1.3.6.1.4.1.52.4.1.1.10.3.1.1.8
The frequency of execution of the UPS's automatic battery test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon startup and every 14 days thereafter, or never.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER twoWeeks(1), oneWeek(2), startupOnly(3), off(4)  

upsLowBatteryWarning 1.3.6.1.4.1.52.4.1.1.10.3.1.1.9
The interval between activation of the UPS's low battery alarm warnings and shutdown of the UPS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER twoMinutes(1), fiveMinutes(2), sevenMinutes(3), tenMinutes(4)  

upsInputTable 1.3.6.1.4.1.52.4.1.1.10.4.1
A list of input table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputEntry

upsInputEntry 1.3.6.1.4.1.52.4.1.1.10.4.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputEntry  

upsInputUtilityVoltage 1.3.6.1.4.1.52.4.1.1.10.4.1.1.1
The UPS's utility voltage version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER vac100(1), vac120(2), vac208(3), vac220(4)  

upsInputVoltage 1.3.6.1.4.1.52.4.1.1.10.4.1.1.2
The UPS's measured utility input voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputFailureSensitivity 1.3.6.1.4.1.52.4.1.1.10.4.1.1.3
The sensitivity of the UPS to rapid changes in utility voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER high(1), medium(2), low(3), auto(4)  

upsInputMaxVoltage 1.3.6.1.4.1.52.4.1.1.10.4.1.1.4
The UPS's maximum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputMinVoltage 1.3.6.1.4.1.52.4.1.1.10.4.1.1.5
The UPS's minimum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputFrequency 1.3.6.1.4.1.52.4.1.1.10.4.1.1.6
The UPS's present internal operating frequency in Hz. The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divide the value of this object by 100).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputTable 1.3.6.1.4.1.52.4.1.1.10.5.1
A list of output table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputEntry

upsOutputEntry 1.3.6.1.4.1.52.4.1.1.10.5.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputEntry  

upsOutputVoltage 1.3.6.1.4.1.52.4.1.1.10.5.1.1.1
The measured UPS output voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputUtilityVoltage 1.3.6.1.4.1.52.4.1.1.10.5.1.1.2
The UPS's current on-battery output voltage setting (valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always return a 0 and writing this object will have no effect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER vac225(1), vac230(2), vac240(3), vac220(4)  

upsOutputPower 1.3.6.1.4.1.52.4.1.1.10.5.1.1.3
The UPS's output load represented as a percentage of full rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStatusTable 1.3.6.1.4.1.52.4.1.1.10.6.1
A list of status table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsStatusEntry

upsStatusEntry 1.3.6.1.4.1.52.4.1.1.10.6.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsStatusEntry  

upsStatusOperational 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1
This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=replace battery condition BIT 6: 1=low battery condition BIT 5: 1=overloaded output condition BIT 4: 1=on-battery mode of operation BIT 3: 1=on-line mode of operation BIT 2: 1=Smart Boost mode of operation (where applicable) BIT 1: 1=UPS shut down due to low battery, overload, or `sleep' mode BIT 0: 1=run time calibration running Note that bit 0 is the low-order bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStatusFault 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2
This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: 1=UPS fault - internal temperature has exceeded nominal limits BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction BIT 5: 1=UPS fault - battery charger failure BIT 4: 1=UPS in shut down mode via `S' command BIT 3: 1=UPS in `sleep' mode via `@ddd' command BIT 2: 1=UPS fault - main relay malfunction BIT 1: 1=UPS unable to transfer to on-battery operation due to overload BIT 0: 1=UPS's output unpowered due to low battery shut down Note that bit 0 is the low-order bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsStatusTemp 1.3.6.1.4.1.52.4.1.1.10.6.1.1.3
The UPS's present internal operating temperature in degrees Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actual temperature, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigTable 1.3.6.1.4.1.52.4.1.1.10.7.1
A list of configuration table entries. The number of entries is given by the value of upsNumUPSs.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsConfigEntry

upsConfigEntry 1.3.6.1.4.1.52.4.1.1.10.7.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsConfigEntry  

upsConfigAlarm 1.3.6.1.4.1.52.4.1.1.10.7.1.1.1
The UPS's current audible alarm setting. The alarm may be set to activate immediately upon utility failure and for low battery condition, to activate 30 seconds after utility failure and immediately upon low battery condition, to activate upon low battery condition only, or to not activate under any conditions.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER uponUtilityFailure(1), thirtySecondsAfterUtilityFailure(2), lowBatteryOnly(3), noAudibleAlarm(4)  

upsConfigRestoreDefaults 1.3.6.1.4.1.52.4.1.1.10.7.1.1.2
This object may be written to force the UPS to restore the factory default settings for most of the UPS's customizable parameters. Reading this object will always return a 0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restoreDefaults(1)  

upsExtMeasTable 1.3.6.1.4.1.52.4.1.1.10.8.1
A list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsExtMeasEntry

upsExtMeasEntry 1.3.6.1.4.1.52.4.1.1.10.8.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsExtMeasEntry  

upsExtMeasFwVersion 1.3.6.1.4.1.52.4.1.1.10.8.1.1.1
The External Measurement Unit's firmware version letter.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..1)  

upsExtMeasTemp 1.3.6.1.4.1.52.4.1.1.10.8.1.1.2
The local ambient temperature in degrees Fahrenheit as measured by the External Measurement Unit. The value of this object is the actual temperature * 100 (that is, to determine the actual temperature, divide the value of this object by 100).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsExtMeasHumidity 1.3.6.1.4.1.52.4.1.1.10.8.1.1.3
The local ambient relative humidity in percent as measured by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to determine the actual humidity, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsExtMeasAlarmStatus 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4
This object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower temperature limit exceeded BIT 5: 1=Upper relative humidity limit exceeded BIT 4: 1=Lower relative humidity limit exceeded BIT 3: 1=Contact input channel #4 alarm state BIT 2: 1=Contact input channel #3 alarm state BIT 1: 1=Contact input channel #2 alarm state BIT 0: 1=Contact input channel #1 alarm state Note that bit 0 is the low-order bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsExtMeasMaxTemp 1.3.6.1.4.1.52.4.1.1.10.8.1.1.5
The upper temperature limit at which an alarm will be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER ninetyDegreesF(1), oneHundredFifteenDegreesF(2), oneHundredThirtyDegreesF(3), oneHundredSeventyFiveDegreesF(4)  

upsExtMeasMinTemp 1.3.6.1.4.1.52.4.1.1.10.8.1.1.6
The lower temperature limit at which an alarm will be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER fortyDegreesF(1), fiftyDegreesF(2), fiftyEightDegreesF(3), sixtyFiveDegreesF(4)  

upsExtMeasMaxHumidity 1.3.6.1.4.1.52.4.1.1.10.8.1.1.7
The upper humidity limit at which an alarm will be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER seventyPercent(1), eightyPercent(2), eightyFivePercent(3), ninetyPercent(4)  

upsExtMeasMinHumidity 1.3.6.1.4.1.52.4.1.1.10.8.1.1.8
The lower humidity limit at which an alarm will be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER tenPercent(1), twentyPercent(2), thirtyPercent(3), fortyPercent(4)  

upsExtMeasContact1AlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.9
The alarm enable state for the External Measurement Unit's contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has changed to abnormal state.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasContact2AlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.10
The alarm enable state for the External Measurement Unit's contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has changed to abnormal state.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasContact3AlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.11
The alarm enable state for the External Measurement Unit's contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has changed to abnormal state.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasContact4AlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.12
The alarm enable state for the External Measurement Unit's contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has changed to abnormal state.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasMaxTempAlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.13
The alarm enable state for the External Measurement Unit's upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above the upper temperature limit.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasMinTempAlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.14
The alarm enable state for the External Measurement Unit's lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below the lower temperature limit.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasMaxHumidityAlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.15
The alarm enable state for the External Measurement Unit's upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises above the upper humidity limit.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsExtMeasMinHumidityAlarmControl 1.3.6.1.4.1.52.4.1.1.10.8.1.1.16
The alarm enable state for the External Measurement Unit's lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls below the lower humidity limit.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsAddlFuncsTable 1.3.6.1.4.1.52.4.1.1.10.9.1
A list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAddlFuncsEntry

upsAddlFuncsEntry 1.3.6.1.4.1.52.4.1.1.10.9.1.1
An entry containing objects for a particular UPS.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAddlFuncsEntry  

upsAddlFuncsNumBatteryPacks 1.3.6.1.4.1.52.4.1.1.10.9.1.1.1
The number of battery pack units connected to the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsNumBadBatteryPacks 1.3.6.1.4.1.52.4.1.1.10.9.1.1.2
The number of bad (faulty) battery pack units connected to the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsOutputCurrent 1.3.6.1.4.1.52.4.1.1.10.9.1.1.3
The true rms load current drawn from the UPS. The value of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the value of this object by 100).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsOutputApparentPower 1.3.6.1.4.1.52.4.1.1.10.9.1.1.4
The UPS's output load represented as a percentage of full rated load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsStatusOperational 1.3.6.1.4.1.52.4.1.1.10.9.1.1.5
This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=UPS ready to power load upon return of normal line or upon user command BIT 6: 1=UPS ready to power load upon user command BIT 5: 1=UPS in bypass mode as a result of manual bypass control BIT 4: 1=UPS is returning from bypass mode BIT 3: 1=UPS in bypass mode as a result of UPS-Link or key command BIT 2: 1=UPS going to bypass mode as a result of UPS-Link or key command BIT 1: 1=not defined BIT 0: 1=wakeup mode - startup test lasting < 2 sec Note that bit 0 is the low-order bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsStatusFault 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6
This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved for future use BIT 4: 1=UPS fault - DC imbalance, UPS in bypass BIT 3: 1=UPS fault - output voltage select failure, UPS in bypass BIT 2: 1=UPS fault - bypass supply failure BIT 1: 1=UPS fault - Isolation Unit fan failure BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS in bypass Note that bit 0 is the low-order bit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAddlFuncsConfigPassword 1.3.6.1.4.1.52.4.1.1.10.9.1.1.7
The password that controls access to the UPS's LCD display. A maximum of 4 characters may be entered.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OCTET STRING  

upsAddlFuncsConfigDisable 1.3.6.1.4.1.52.4.1.1.10.9.1.1.8
This object may be written to immediately shut down the UPS, requiring a manual reset. Reading this object will always return a 0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disableUps(1)  

upsAddlFuncsConfigBypass 1.3.6.1.4.1.52.4.1.1.10.9.1.1.9
This object may be written to cause the UPS to transfer to or from the bypass mode. Reading this object will always return a 0.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER bypassMode(1), exitBypassMode(2)