TERACOM-MIB

File: TERACOM-MIB.mib (36508 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC SNMPv2-CONF

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises IpAddress Integer32
snmpModules DateAndTime MacAddress
DisplayString TEXTUAL-CONVENTION MODULE-COMPLIANCE
OBJECT-GROUP NOTIFICATION-GROUP

Defined Types

CONTROLLED  
This textual convention enumerates the authentication and privledge protocol for USM configuration.
TEXTUAL-CONVENTION    
  INTEGER manual(0), sensor11(1), sensor21(2), sensor31(3), sensor41(4), sensor51(5), sensor61(6), sensor71(7), sensor81(8), sensor12(9), sensor22(10), sensor32(11), sensor42(12), sensor52(13), sensor62(14), sensor72(15), sensor82(16), analog1(17), analog2(18), analog3(19), analog4(20), digital1(21), digital2(22), digital3(23), digital4(24), scheduler1(25), scheduler2(26), scheduler3(27), scheduler4(28)  

Defined Values

snmpMIB 1.3.6.1.6.3.1
The MIB module for TCW240 SNMP entities.
MODULE-IDENTITY    

teracom 1.3.6.1.4.1.38783
OBJECT IDENTIFIER    

tcw240b 1.3.6.1.4.1.38783.1
OBJECT IDENTIFIER    

trapNotifications 1.3.6.1.4.1.38783.1.0
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.38783.1.1
OBJECT IDENTIFIER    

setup 1.3.6.1.4.1.38783.1.2
OBJECT IDENTIFIER    

network 1.3.6.1.4.1.38783.1.2.1
OBJECT IDENTIFIER    

monitorNcontrol 1.3.6.1.4.1.38783.1.3
OBJECT IDENTIFIER    

tcw240bMIBConformance 1.3.6.1.4.1.38783.1.4
OBJECT IDENTIFIER    

tcw240bMIBCompliances 1.3.6.1.4.1.38783.1.4.1
OBJECT IDENTIFIER    

tcw240bMIBGroups 1.3.6.1.4.1.38783.1.4.2
OBJECT IDENTIFIER    

name 1.3.6.1.4.1.38783.1.1.1
Name of product. e.g. teracom.cc etc.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

version 1.3.6.1.4.1.38783.1.1.2
Version string. e.g. 1.0
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

dateTime 1.3.6.1.4.1.38783.1.1.3
Date and time
Status: current Access: read-only
OBJECT-TYPE    
  DateAndTime  

deviceID 1.3.6.1.4.1.38783.1.2.1.1
Device ID is Default MAC Address
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

hostName 1.3.6.1.4.1.38783.1.2.1.2
Host Name
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..38)  

deviceIP 1.3.6.1.4.1.38783.1.2.1.3
Device IP Address
Status: current Access: read-only
OBJECT-TYPE    
  IpAddress  

io 1.3.6.1.4.1.38783.1.2.2
OBJECT IDENTIFIER    

sensorsSetup 1.3.6.1.4.1.38783.1.2.2.1
OBJECT IDENTIFIER    

sensor1setup 1.3.6.1.4.1.38783.1.2.2.1.1
OBJECT IDENTIFIER    

sensor2setup 1.3.6.1.4.1.38783.1.2.2.1.2
OBJECT IDENTIFIER    

sensor3setup 1.3.6.1.4.1.38783.1.2.2.1.3
OBJECT IDENTIFIER    

sensor4setup 1.3.6.1.4.1.38783.1.2.2.1.4
OBJECT IDENTIFIER    

sensor5setup 1.3.6.1.4.1.38783.1.2.2.1.5
OBJECT IDENTIFIER    

sensor6setup 1.3.6.1.4.1.38783.1.2.2.1.6
OBJECT IDENTIFIER    

sensor7setup 1.3.6.1.4.1.38783.1.2.2.1.7
OBJECT IDENTIFIER    

sensor8setup 1.3.6.1.4.1.38783.1.2.2.1.8
OBJECT IDENTIFIER    

s1description 1.3.6.1.4.1.38783.1.2.2.1.1.1
Sensor1 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor11setup 1.3.6.1.4.1.38783.1.2.2.1.1.2
OBJECT IDENTIFIER    

sensor12setup 1.3.6.1.4.1.38783.1.2.2.1.1.3
OBJECT IDENTIFIER    

s11MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.2.1
S11 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s11MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.2.2
S11 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s11HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.2.3
S11 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s12MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.3.1
S12 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s12MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.3.2
S12 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s12HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.1.3.3
S12 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s2description 1.3.6.1.4.1.38783.1.2.2.1.2.1
sensor2 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor21setup 1.3.6.1.4.1.38783.1.2.2.1.2.2
OBJECT IDENTIFIER    

sensor22setup 1.3.6.1.4.1.38783.1.2.2.1.2.3
OBJECT IDENTIFIER    

s21MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.2.1
s21 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s21MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.2.2
s21 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s21HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.2.3
s21 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s22MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.3.1
s22 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s22MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.3.2
s22 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s22HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.2.3.3
s22 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s3description 1.3.6.1.4.1.38783.1.2.2.1.3.1
sensor3 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor31setup 1.3.6.1.4.1.38783.1.2.2.1.3.2
OBJECT IDENTIFIER    

sensor32setup 1.3.6.1.4.1.38783.1.2.2.1.3.3
OBJECT IDENTIFIER    

s31MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.2.1
s31 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s31MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.2.2
s31 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s31HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.2.3
s31 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s32MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.3.1
s32 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s32MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.3.2
s32 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s32HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.3.3.3
s32 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s4description 1.3.6.1.4.1.38783.1.2.2.1.4.1
sensor4 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor41setup 1.3.6.1.4.1.38783.1.2.2.1.4.2
OBJECT IDENTIFIER    

sensor42setup 1.3.6.1.4.1.38783.1.2.2.1.4.3
OBJECT IDENTIFIER    

s41MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.2.1
s41 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s41MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.2.2
s41 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s41HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.2.3
s41 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s42MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.3.1
s42 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s42MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.3.2
s42 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s42HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.4.3.3
s42 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s5description 1.3.6.1.4.1.38783.1.2.2.1.5.1
sensor5 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor51setup 1.3.6.1.4.1.38783.1.2.2.1.5.2
OBJECT IDENTIFIER    

sensor52setup 1.3.6.1.4.1.38783.1.2.2.1.5.3
OBJECT IDENTIFIER    

s51MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.2.1
s51 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s51MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.2.2
s51 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s51HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.2.3
s51 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s52MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.3.1
s52 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s52MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.3.2
s52 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s52HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.5.3.3
s52 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s6description 1.3.6.1.4.1.38783.1.2.2.1.6.1
sensor6 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor61setup 1.3.6.1.4.1.38783.1.2.2.1.6.2
OBJECT IDENTIFIER    

sensor62setup 1.3.6.1.4.1.38783.1.2.2.1.6.3
OBJECT IDENTIFIER    

s61MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.2.1
s61 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s61MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.2.2
s61 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s61HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.2.3
s61 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s62MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.3.1
s62 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s62MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.3.2
s62 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s62HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.6.3.3
s62 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s7description 1.3.6.1.4.1.38783.1.2.2.1.7.1
sensor7 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor71setup 1.3.6.1.4.1.38783.1.2.2.1.7.2
OBJECT IDENTIFIER    

sensor72setup 1.3.6.1.4.1.38783.1.2.2.1.7.3
OBJECT IDENTIFIER    

s71MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.2.1
s71 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s71MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.2.2
s71 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s71HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.2.3
s71 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s72MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.3.1
s72 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s72MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.3.2
s72 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s72HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.7.3.3
s72 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s8description 1.3.6.1.4.1.38783.1.2.2.1.8.1
sensor8 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

sensor81setup 1.3.6.1.4.1.38783.1.2.2.1.8.2
OBJECT IDENTIFIER    

sensor82setup 1.3.6.1.4.1.38783.1.2.2.1.8.3
OBJECT IDENTIFIER    

s81MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.2.1
s81 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s81MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.2.2
s81 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s81HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.2.3
s81 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s82MAXx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.3.1
s82 maximum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s82MINx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.3.2
s82 minimum value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

s82HYSTx10Int 1.3.6.1.4.1.38783.1.2.2.1.8.3.3
s82 hysteresis value x10 in Integer format
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

analogSetup 1.3.6.1.4.1.38783.1.2.2.2
OBJECT IDENTIFIER    

analog1setup 1.3.6.1.4.1.38783.1.2.2.2.1
OBJECT IDENTIFIER    

analog2setup 1.3.6.1.4.1.38783.1.2.2.2.2
OBJECT IDENTIFIER    

analog3setup 1.3.6.1.4.1.38783.1.2.2.2.3
OBJECT IDENTIFIER    

analog4setup 1.3.6.1.4.1.38783.1.2.2.2.4
OBJECT IDENTIFIER    

voltage1description 1.3.6.1.4.1.38783.1.2.2.2.1.1
Voltage 1 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

voltage1max 1.3.6.1.4.1.38783.1.2.2.2.1.2
Voltage 1 maximum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage1min 1.3.6.1.4.1.38783.1.2.2.2.1.3
Voltage 1 minimum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage1hyst 1.3.6.1.4.1.38783.1.2.2.2.1.4
Voltage 1 hysteresis
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage2description 1.3.6.1.4.1.38783.1.2.2.2.2.1
Voltage 2 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

voltage2max 1.3.6.1.4.1.38783.1.2.2.2.2.2
Voltage 2 maximum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage2min 1.3.6.1.4.1.38783.1.2.2.2.2.3
Voltage 2 minimum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage2hyst 1.3.6.1.4.1.38783.1.2.2.2.2.4
Voltage 2 hysteresis
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage3description 1.3.6.1.4.1.38783.1.2.2.2.3.1
Voltage 3 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

voltage3max 1.3.6.1.4.1.38783.1.2.2.2.3.2
Voltage 3 maximum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage3min 1.3.6.1.4.1.38783.1.2.2.2.3.3
Voltage 3 minimum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage3hyst 1.3.6.1.4.1.38783.1.2.2.2.3.4
Voltage 3 hysteresis
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage4description 1.3.6.1.4.1.38783.1.2.2.2.4.1
Voltage 4 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

voltage4max 1.3.6.1.4.1.38783.1.2.2.2.4.2
Voltage 4 maximum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage4min 1.3.6.1.4.1.38783.1.2.2.2.4.3
Voltage 4 minimum
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

voltage4hyst 1.3.6.1.4.1.38783.1.2.2.2.4.4
Voltage 4 hysteresis
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

digitalSetup 1.3.6.1.4.1.38783.1.2.2.3
OBJECT IDENTIFIER    

digitalInput1description 1.3.6.1.4.1.38783.1.2.2.3.1
Digital Input 1 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

digitalInput2description 1.3.6.1.4.1.38783.1.2.2.3.2
Digital Input 2 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

digitalInput3description 1.3.6.1.4.1.38783.1.2.2.3.3
Digital Input 3 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

digitalInput4description 1.3.6.1.4.1.38783.1.2.2.3.4
Digital Input 4 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

relaysSetup 1.3.6.1.4.1.38783.1.2.2.4
OBJECT IDENTIFIER    

relay1setup 1.3.6.1.4.1.38783.1.2.2.4.1
OBJECT IDENTIFIER    

relay2setup 1.3.6.1.4.1.38783.1.2.2.4.2
OBJECT IDENTIFIER    

relay3setup 1.3.6.1.4.1.38783.1.2.2.4.3
OBJECT IDENTIFIER    

relay4setup 1.3.6.1.4.1.38783.1.2.2.4.4
OBJECT IDENTIFIER    

relay1description 1.3.6.1.4.1.38783.1.2.2.4.1.1
Relay 1 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

relay1pulseWidth 1.3.6.1.4.1.38783.1.2.2.4.1.2
Relay1 Pulse x100ms
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..65535  

relay1controlledBy 1.3.6.1.4.1.38783.1.2.2.4.1.3
Relay1 control logic
Status: current Access: read-write
OBJECT-TYPE    
  CONTROLLED  

relay2description 1.3.6.1.4.1.38783.1.2.2.4.2.1
Relay 2 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

relay2pulseWidth 1.3.6.1.4.1.38783.1.2.2.4.2.2
Relay2 Pulse x100ms
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..65535  

relay2controlledBy 1.3.6.1.4.1.38783.1.2.2.4.2.3
Relay2 control logic
Status: current Access: read-write
OBJECT-TYPE    
  CONTROLLED  

relay3description 1.3.6.1.4.1.38783.1.2.2.4.3.1
Relay 3 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

relay3pulseWidth 1.3.6.1.4.1.38783.1.2.2.4.3.2
Relay3 Pulse x100ms
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..65535  

relay3controlledBy 1.3.6.1.4.1.38783.1.2.2.4.3.3
Relay3 control logic
Status: current Access: read-write
OBJECT-TYPE    
  CONTROLLED  

relay4description 1.3.6.1.4.1.38783.1.2.2.4.4.1
Relay 4 description
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..12)  

relay4pulseWidth 1.3.6.1.4.1.38783.1.2.2.4.4.2
Relay4 Pulse x100ms
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..65535  

relay4controlledBy 1.3.6.1.4.1.38783.1.2.2.4.4.3
Relay4 control logic
Status: current Access: read-write
OBJECT-TYPE    
  CONTROLLED  

sensors 1.3.6.1.4.1.38783.1.3.1
OBJECT IDENTIFIER    

sensor1 1.3.6.1.4.1.38783.1.3.1.1
OBJECT IDENTIFIER    

s11x10Int 1.3.6.1.4.1.38783.1.3.1.1.1
S11 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s12x10Int 1.3.6.1.4.1.38783.1.3.1.1.2
S12 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s1ID 1.3.6.1.4.1.38783.1.3.1.1.3
S1 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor2 1.3.6.1.4.1.38783.1.3.1.2
OBJECT IDENTIFIER    

s21x10Int 1.3.6.1.4.1.38783.1.3.1.2.1
S21 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s22x10Int 1.3.6.1.4.1.38783.1.3.1.2.2
S22 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s2ID 1.3.6.1.4.1.38783.1.3.1.2.3
S2 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor3 1.3.6.1.4.1.38783.1.3.1.3
OBJECT IDENTIFIER    

s31x10Int 1.3.6.1.4.1.38783.1.3.1.3.1
S31 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s32x10Int 1.3.6.1.4.1.38783.1.3.1.3.2
S32 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s3ID 1.3.6.1.4.1.38783.1.3.1.3.3
S3 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor4 1.3.6.1.4.1.38783.1.3.1.4
OBJECT IDENTIFIER    

s41x10Int 1.3.6.1.4.1.38783.1.3.1.4.1
S41 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s42x10Int 1.3.6.1.4.1.38783.1.3.1.4.2
S42 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s4ID 1.3.6.1.4.1.38783.1.3.1.4.3
S4 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor5 1.3.6.1.4.1.38783.1.3.1.5
OBJECT IDENTIFIER    

s51x10Int 1.3.6.1.4.1.38783.1.3.1.5.1
S51 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s52x10Int 1.3.6.1.4.1.38783.1.3.1.5.2
S52 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s5ID 1.3.6.1.4.1.38783.1.3.1.5.3
S5 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor6 1.3.6.1.4.1.38783.1.3.1.6
OBJECT IDENTIFIER    

s61x10Int 1.3.6.1.4.1.38783.1.3.1.6.1
S61 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s62x10Int 1.3.6.1.4.1.38783.1.3.1.6.2
S62 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s6ID 1.3.6.1.4.1.38783.1.3.1.6.3
S6 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor7 1.3.6.1.4.1.38783.1.3.1.7
OBJECT IDENTIFIER    

s71x10Int 1.3.6.1.4.1.38783.1.3.1.7.1
S71 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s72x10Int 1.3.6.1.4.1.38783.1.3.1.7.2
S72 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s7ID 1.3.6.1.4.1.38783.1.3.1.7.3
S7 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

sensor8 1.3.6.1.4.1.38783.1.3.1.8
OBJECT IDENTIFIER    

s81x10Int 1.3.6.1.4.1.38783.1.3.1.8.1
S81 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s82x10Int 1.3.6.1.4.1.38783.1.3.1.8.2
S82 value x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

s8ID 1.3.6.1.4.1.38783.1.3.1.8.3
S8 ID value
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

analog 1.3.6.1.4.1.38783.1.3.2
OBJECT IDENTIFIER    

voltage1x10Int 1.3.6.1.4.1.38783.1.3.2.1
Voltage1 x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage2x10Int 1.3.6.1.4.1.38783.1.3.2.2
Voltage2 x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage3x10Int 1.3.6.1.4.1.38783.1.3.2.3
Voltage3 x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage4x10Int 1.3.6.1.4.1.38783.1.3.2.4
Voltage4 x10 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage1x100Int 1.3.6.1.4.1.38783.1.3.2.5
Voltage1 x100 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage2x100Int 1.3.6.1.4.1.38783.1.3.2.6
Voltage2 x100 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage3x100Int 1.3.6.1.4.1.38783.1.3.2.7
Voltage3 x100 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

voltage4x100Int 1.3.6.1.4.1.38783.1.3.2.8
Voltage4 x100 in Integer format
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

digital 1.3.6.1.4.1.38783.1.3.3
OBJECT IDENTIFIER    

digitalInput1State 1.3.6.1.4.1.38783.1.3.3.1
Digital1 Input State
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

digitalInput2State 1.3.6.1.4.1.38783.1.3.3.2
Digital2 Input State
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

digitalInput3State 1.3.6.1.4.1.38783.1.3.3.3
Digital3 Input State
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

digitalInput4State 1.3.6.1.4.1.38783.1.3.3.4
Digital4 Input State
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

relays 1.3.6.1.4.1.38783.1.3.4
OBJECT IDENTIFIER    

relay1 1.3.6.1.4.1.38783.1.3.4.1
OBJECT IDENTIFIER    

relay1State 1.3.6.1.4.1.38783.1.3.4.1.1
Relay1 State
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay1Pulse 1.3.6.1.4.1.38783.1.3.4.1.2
Relay1 Pulse
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay2 1.3.6.1.4.1.38783.1.3.4.2
OBJECT IDENTIFIER    

relay2State 1.3.6.1.4.1.38783.1.3.4.2.1
Relay2 State
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay2Pulse 1.3.6.1.4.1.38783.1.3.4.2.2
Relay2 Pulse
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay3 1.3.6.1.4.1.38783.1.3.4.3
OBJECT IDENTIFIER    

relay3State 1.3.6.1.4.1.38783.1.3.4.3.1
Relay3 State
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay3Pulse 1.3.6.1.4.1.38783.1.3.4.3.2
Relay3 Pulse
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay4 1.3.6.1.4.1.38783.1.3.4.4
OBJECT IDENTIFIER    

relay4State 1.3.6.1.4.1.38783.1.3.4.4.1
Relay4 State
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

relay4Pulse 1.3.6.1.4.1.38783.1.3.4.4.2
Relay4 Pulse
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

configurationSaved 1.3.6.1.4.1.38783.1.3.5
Configuration save status SAVED/UNSAVED
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unsaved(0), saved(1)  

restartDevice 1.3.6.1.4.1.38783.1.3.6
Restart Device
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER cancel(0), restart(1)  

temperatureUnit 1.3.6.1.4.1.38783.1.3.7
Unit of the all temperature values
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER celcius(0), fahrenheit(1)  

hardwareErr 1.3.6.1.4.1.38783.1.3.8
Hardware Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER noErr(0), owErr(1), hwErr(2)  

snmp-trap-notification 1.3.6.1.4.1.38783.1.0.1
SMIV2 Trap notification information for the SNMP Manager.
Status: current Access: read-only
NOTIFICATION-TYPE    

tcw240bMIBCompliances1 1.3.6.1.4.1.38783.1.4.1.1
This group is for SNMP applications.
Status: current Access: read-only
MODULE-COMPLIANCE    

tcw240bProductGroup 1.3.6.1.4.1.38783.1.4.2.1
A collection of objects providing basic product info.
Status: current Access: read-only
OBJECT-GROUP    

tcw240bSetupGroup 1.3.6.1.4.1.38783.1.4.2.2
A collection of objects providing basic setup.
Status: current Access: read-only
OBJECT-GROUP    

tcw240bMonitorGroup 1.3.6.1.4.1.38783.1.4.2.3
A collection of objects providing basic monitoring and control of a product.
Status: current Access: read-only
OBJECT-GROUP    

tcw240bTrapGroup 1.3.6.1.4.1.38783.1.4.2.4
SNMP Trap Notification object.
Status: current Access: read-only
NOTIFICATION-GROUP