SP2-MIB

File: SP2-MIB.mib (275110 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC

Imported symbols

NOTIFICATION-TYPE OBJECT-TYPE MODULE-IDENTITY
enterprises Counter32 Integer32
NOTIFICATION-GROUP DateAndTime DisplayString

Defined Types

MainsVoltageEntry  
SEQUENCE    
  mainsVoltageIndex Integer32
  mainsVoltageStatus INTEGER
  mainsVoltageDescription DisplayString
  mainsVoltageTrapRepeatCounter Counter32
  mainsVoltageAlarmEnable INTEGER
  mainsVoltageValue Integer32
  mainsVoltageMajorHighLevel Integer32
  mainsVoltageMinorHighLevel Integer32
  mainsVoltageMinorLowLevel Integer32
  mainsVoltageMajorLowLevel Integer32

MainsMonitorsEntry  
SEQUENCE    
  mainsMonitorIndex Integer32
  mainsMonitorNumberOfVoltages Integer32
  mainsMonitorNumberOfCurrents Integer32
  mainsMonitorNumberOfFrequencies Integer32

MainsMonitorVoltageEntry  
SEQUENCE    
  mainsMonitorPhaseIndex Integer32
  mainsMonitorVoltageStatus INTEGER
  mainsMonitorVoltageDescription DisplayString
  mainsMonitorVoltageTrapRepeatCounter Counter32
  mainsMonitorVoltageAlarmEnable INTEGER
  mainsMonitorVoltageValue Integer32
  mainsMonitorVoltageMajorHighLevel Integer32
  mainsMonitorVoltageMinorHighLevel Integer32
  mainsMonitorVoltageMinorLowLevel Integer32
  mainsMonitorVoltageMajorLowLevel Integer32

MainsMonitorCurrentEntry  
SEQUENCE    
  mainsMonitorCurrentStatus INTEGER
  mainsMonitorCurrentDescription DisplayString
  mainsMonitorCurrentTrapRepeatCounter Counter32
  mainsMonitorCurrentAlarmEnable INTEGER
  mainsMonitorCurrentValue Integer32
  mainsMonitorCurrentMajorHighLevel Integer32
  mainsMonitorCurrentMinorHighLevel Integer32

MainsMonitorFrequencyEntry  
SEQUENCE    
  mainsMonitorFrequencyStatus INTEGER
  mainsMonitorFrequencyDescription DisplayString
  mainsMonitorFrequencyTrapRepeatCounter Counter32
  mainsMonitorFrequencyAlarmEnable INTEGER
  mainsMonitorFrequencyValue Integer32
  mainsMonitorFrequencyMajorHighLevel Integer32
  mainsMonitorFrequencyMinorHighLevel Integer32
  mainsMonitorFrequencyMinorLowLevel Integer32
  mainsMonitorFrequencyMajorLowLevel Integer32

MainsMonitorEnergyLogAccumulatedEntry  
SEQUENCE    
  mainsMonitorEnergyLogAccumulated Integer32

MainsMonitorEnergyLogLastHoursEntry  
SEQUENCE    
  mainsMonitorEnergyLogLastHoursIndex Integer32
  mainsMonitorEnergyLogLastHoursValue Integer32

MainsMonitorEnergyLogLastDaysEntry  
SEQUENCE    
  mainsMonitorEnergyLogLastDaysIndex Integer32
  mainsMonitorEnergyLogLastDaysValue Integer32

MainsMonitorEnergyLogLastWeeksEntry  
SEQUENCE    
  mainsMonitorEnergyLogLastWeeksIndex Integer32
  mainsMonitorEnergyLogLastWeeksValue Integer32

MainsOutageLogDaysEntry  
SEQUENCE    
  mainsOutageLogDaysIndex Integer32
  mainsOutageLogDaysValue Integer32

MainsOutageLogWeeksEntry  
SEQUENCE    
  mainsOutageLogWeeksIndex Integer32
  mainsOutageLogWeeksValue Integer32

MainsOutageLogMonthsEntry  
SEQUENCE    
  mainsOutageLogMonthsIndex Integer32
  mainsOutageLogMonthsValue Integer32

GeneratorDailyRunSetupEntry  
SEQUENCE    
  generatorDailyRunDayIndex INTEGER
  generatorDailyRunStartHour Integer32
  generatorDailyRunStopHour Integer32

GeneratorTankEntry  
SEQUENCE    
  generatorTankIndex Integer32
  generatorTankStatus INTEGER
  generatorTankDescription DisplayString
  generatorTankTrapRepeatCounter Counter32
  generatorTankEnable INTEGER
  generatorTankValue Integer32
  generatorTankMajorHighLevel Integer32
  generatorTankMinorHighLevel Integer32
  generatorTankMinorLowLevel Integer32
  generatorTankMajorLowLevel Integer32

GeneratorEnergyLogLastHoursEntry  
SEQUENCE    
  generatorEnergyLogLastHoursIndex Integer32
  generatorEnergyLogLastHoursValue Integer32

GeneratorEnergyLogLastDaysEntry  
SEQUENCE    
  generatorEnergyLogLastDaysIndex Integer32
  generatorEnergyLogLastDaysValue Integer32

GeneratorEnergyLogLastWeeksEntry  
SEQUENCE    
  generatorEnergyLogLastWeeksIndex Integer32
  generatorEnergyLogLastWeeksValue Integer32

GeneratorRunHoursLogLastDaysEntry  
SEQUENCE    
  generatorRunHoursLogLastDaysIndex Integer32
  generatorRunHoursLogLastDaysValue Integer32

GeneratorRunHoursLogLastWeeksEntry  
SEQUENCE    
  generatorRunHoursLogLastWeeksIndex Integer32
  generatorRunHoursLogLastWeeksValue Integer32

GeneratorRunHoursLogLastMonthsEntry  
SEQUENCE    
  generatorRunHoursLogLastMonthsIndex Integer32
  generatorRunHoursLogLastMonthsValue Integer32

GeneratorFuelConsumptionTotalUsedEntry  
SEQUENCE    
  generatorFuelConsumptionTotalUsed Integer32

GeneratorFuelConsumptionLogLastHoursEntry  
SEQUENCE    
  generatorFuelConsumptionLogLastHoursIndex Integer32
  generatorFuelConsumptionLogLastHoursValue Integer32

GeneratorFuelConsumptionLogLastDaysEntry  
SEQUENCE    
  generatorFuelConsumptionLogLastDaysIndex Integer32
  generatorFuelConsumptionLogLastDaysValue Integer32

GeneratorFuelConsumptionLogLastWeeksEntry  
SEQUENCE    
  generatorFuelConsumptionLogLastWeeksIndex Integer32
  generatorFuelConsumptionLogLastWeeksValue Integer32

RectifierEntry  
SEQUENCE    
  rectifierIndex Integer32
  rectifierStatus INTEGER
  rectifierOutputCurrentValue Integer32
  rectifierInputVoltageValue Integer32
  rectifierType DisplayString
  rectifierHwPartNumber DisplayString
  rectifierHwVersion DisplayString
  rectifierSwPartNumber DisplayString
  rectifierSwVersion DisplayString

RectifiersEnergyLogLastHoursEntry  
SEQUENCE    
  rectifiersEnergyLogLastHoursIndex Integer32
  rectifiersEnergyLogLastHoursValue Integer32

RectifiersEnergyLogLastDaysEntry  
SEQUENCE    
  rectifiersEnergyLogLastDaysIndex Integer32
  rectifiersEnergyLogLastDaysValue Integer32

RectifiersEnergyLogLastWeeksEntry  
SEQUENCE    
  rectifiersEnergyLogLastWeeksIndex Integer32
  rectifiersEnergyLogLastWeeksValue Integer32

DcdcGroupsEntry  
SEQUENCE    
  dcdcGroupIndex Integer32
  dcdcGroupStatus INTEGER
  dcdcGroupNumberOfDcdcConverters Integer32
  dcdcGroupOutputVoltage Integer32
  dcdcNumberOfCurrents Integer32
  dcdcNumberOfCapacities Integer32
  dcdcNumberOfAlarms Integer32

DcdcCurrentEntry  
SEQUENCE    
  dcdcCurrentStatus INTEGER
  dcdcCurrentDescription DisplayString
  dcdcCurrentTrapRepeatCounter Counter32
  dcdcCurrentAlarmEnable INTEGER
  dcdcCurrentValue Integer32
  dcdcCurrentMajorAlarmLevel Integer32
  dcdcCurrentMinorAlarmLevel Integer32

DcdcCapacityEntry  
SEQUENCE    
  dcdcCapacityStatus INTEGER
  dcdcCapacityDescription DisplayString
  dcdcCapacityTrapRepeatCounter Counter32
  dcdcCapacityAlarmEnable INTEGER
  dcdcCapacityValue Integer32
  dcdcCapacityMajorAlarmLevel Integer32
  dcdcCapacityMinorAlarmLevel Integer32

DcdcEntry  
SEQUENCE    
  dcdcIndex Integer32
  dcdcStatus INTEGER
  dcdcOutputCurrentValue Integer32
  dcdcInputVoltageValue Integer32
  dcdcType DisplayString
  dcdcHwPartNumber DisplayString
  dcdcHwVersion DisplayString
  dcdcSwPartNumber DisplayString
  dcdcSwVersion DisplayString

DcdcErrorEntry  
SEQUENCE    
  dcdcErrorStatus INTEGER
  dcdcErrorDescription DisplayString
  dcdcErrorTrapRepeatCounter Counter32
  dcdcErrorEnable INTEGER
  dcdcErrorValue Integer32
  dcdcErrorMajorAlarmLevel Integer32
  dcdcErrorMinorAlarmLevel Integer32

DcdcEnergyLogAccumulatedEntry  
SEQUENCE    
  dcdcEnergyLogAccumulated Integer32

DcdcEnergyLogLastHoursEntry  
SEQUENCE    
  dcdcEnergyLogLastHoursIndex Integer32
  dcdcEnergyLogLastHoursValue Integer32

DcdcEnergyLogLastDaysEntry  
SEQUENCE    
  dcdcEnergyLogLastDaysIndex Integer32
  dcdcEnergyLogLastDaysValue Integer32

DcdcEnergyLogLastWeeksEntry  
SEQUENCE    
  dcdcEnergyLogLastWeeksIndex Integer32
  dcdcEnergyLogLastWeeksValue Integer32

SolarChargerEntry  
SEQUENCE    
  solarChargerIndex Integer32
  solarChargerStatus INTEGER
  solarChargerOutputCurrentValue Integer32
  solarChargerInputVoltageValue Integer32
  solarChargerType DisplayString
  solarChargerHwPartNumber DisplayString
  solarChargerHwVersion DisplayString
  solarChargerSwPartNumber DisplayString
  solarChargerSwVersion DisplayString

SolarChargersEnergyLogLastHoursEntry  
SEQUENCE    
  solarChargersEnergyLogLastHoursIndex Integer32
  solarChargersEnergyLogLastHoursValue Integer32

SolarChargersEnergyLogLastDaysEntry  
SEQUENCE    
  solarChargersEnergyLogLastDaysIndex Integer32
  solarChargersEnergyLogLastDaysValue Integer32

SolarChargersEnergyLogLastWeeksEntry  
SEQUENCE    
  solarChargersEnergyLogLastWeeksIndex Integer32
  solarChargersEnergyLogLastWeeksValue Integer32

WindChargerEntry  
SEQUENCE    
  windChargerIndex Integer32
  windChargerStatus INTEGER
  windChargerOutputCurrentValue Integer32
  windChargerInputVoltageValue Integer32
  windChargerType DisplayString
  windChargerHwPartNumber DisplayString
  windChargerHwVersion DisplayString
  windChargerSwPartNumber DisplayString
  windChargerSwVersion DisplayString

WindChargersEnergyLogLastHoursEntry  
SEQUENCE    
  windChargersEnergyLogLastHoursIndex Integer32
  windChargersEnergyLogLastHoursValue Integer32

WindChargersEnergyLogLastDaysEntry  
SEQUENCE    
  windChargersEnergyLogLastDaysIndex Integer32
  windChargersEnergyLogLastDaysValue Integer32

WindChargersEnergyLogLastWeeksEntry  
SEQUENCE    
  windChargersEnergyLogLastWeeksIndex Integer32
  windChargersEnergyLogLastWeeksValue Integer32

LoadGroupEntry  
SEQUENCE    
  loadGroupIndex Integer32
  loadGroupStatus INTEGER
  loadNumberOfLVLDs Integer32

LoadLVLDEntry  
SEQUENCE    
  loadLVLDIndex Integer32
  loadLVLDStatus INTEGER
  loadLVLDDescription DisplayString
  loadLVLDTrapRepeatCounter Counter32
  loadLVLDEnable INTEGER
  loadLVLDValue Integer32
  loadLVLDConnectVoltage Integer32
  loadLVLDDisconnectVoltage Integer32

LoadFuseEntry  
SEQUENCE    
  loadFuseStatus INTEGER
  loadFuseDescription DisplayString
  loadFuseTrapRepeatCounter Counter32
  loadFuseAlarmEnable INTEGER
  loadFuseValue Integer32

LoadEnergyLogLastHoursEntry  
SEQUENCE    
  loadEnergyLogLastHoursIndex Integer32
  loadEnergyLogLastHoursValue Integer32

LoadEnergyLogLastDaysEntry  
SEQUENCE    
  loadEnergyLogLastDaysIndex Integer32
  loadEnergyLogLastDaysValue Integer32

LoadEnergyLogLastWeeksEntry  
SEQUENCE    
  loadEnergyLogLastWeeksIndex Integer32
  loadEnergyLogLastWeeksValue Integer32

BatteryTestResultEntry  
SEQUENCE    
  batteryTestResultIndex Integer32
  batteryTestResultStartDateTime DateAndTime
  batteryTestResultDuration Integer32
  batteryTestResultDischarged Integer32
  batteryTestResultQuality Integer32

BatteryBankEntry  
SEQUENCE    
  batteryBankIndex Integer32
  batteryBankStatus INTEGER
  batteryBankNumberOfTemperatures Integer32
  batteryBankNumberOfCurrents Integer32
  batteryBankNumberOfFuses Integer32

BatteryBankTemperatureEntry  
SEQUENCE    
  batteryTemperatureIndex Integer32
  batteryTemperatureStatus INTEGER
  batteryTemperatureDescription DisplayString
  batteryTemperatureTrapRepeatCounter Counter32
  batteryTemperatureAlarmEnable INTEGER
  batteryTemperatureValue Integer32
  batteryTemperatureMajorHighLevel Integer32
  batteryTemperatureMinorHighLevel Integer32
  batteryTemperatureMinorLowLevel Integer32
  batteryTemperatureMajorLowLevel Integer32

BatteryBankCurrentEntry  
SEQUENCE    
  batteryCurrentIndex Integer32
  batteryCurrentStatus INTEGER
  batteryCurrentDescription DisplayString
  batteryCurrentTrapRepeatCounter Counter32
  batteryCurrentAlarmEnable INTEGER
  batteryCurrentValue Integer32
  batteryCurrentMajorHighLevel Integer32
  batteryCurrentMinorHighLevel Integer32
  batteryCurrentMinorLowLevel Integer32
  batteryCurrentMajorLowLevel Integer32

BatteryBankFuseEntry  
SEQUENCE    
  batteryFuseIndex Integer32
  batteryFuseStatus INTEGER
  batteryFuseDescription DisplayString
  batteryFuseTrapRepeatCounter Counter32
  batteryFuseAlarmEnable INTEGER
  batteryFuseValue Integer32

BatteryMonitorsEntry  
SEQUENCE    
  batteryMonitorIndex Integer32
  batteryMonitorNumberOfTemperatures Integer32
  batteryMonitorNumberOfCurrents Integer32
  batteryMonitorNumberOfFuses Integer32
  batteryMonitorNumberOfSymmetries Integer32

BatteryMonitorTemperatureEntry  
SEQUENCE    
  batteryMonitorTemperatureIndex Integer32
  batteryMonitorTemperatureStatus INTEGER
  batteryMonitorTemperatureDescription DisplayString
  batteryMonitorTemperatureTrapRepeatCounter Counter32
  batteryMonitorTemperatureAlarmEnable INTEGER
  batteryMonitorTemperatureValue Integer32
  batteryMonitorTemperatureMajorHighLevel Integer32
  batteryMonitorTemperatureMinorHighLevel Integer32
  batteryMonitorTemperatureMinorLowLevel Integer32
  batteryMonitorTemperatureMajorLowLevel Integer32

BatteryMonitorCurrentEntry  
SEQUENCE    
  batteryMonitorCurrentIndex Integer32
  batteryMonitorCurrentStatus INTEGER
  batteryMonitorCurrentDescription DisplayString
  batteryMonitorCurrentTrapRepeatCounter Counter32
  batteryMonitorCurrentAlarmEnable INTEGER
  batteryMonitorCurrentValue Integer32
  batteryMonitorCurrentMajorHighLevel Integer32
  batteryMonitorCurrentMinorHighLevel Integer32
  batteryMonitorCurrentMinorLowLevel Integer32
  batteryMonitorCurrentMajorLowLevel Integer32

BatteryMonitorFuseEntry  
SEQUENCE    
  batteryMonitorFuseIndex Integer32
  batteryMonitorFuseStatus INTEGER
  batteryMonitorFuseDescription DisplayString
  batteryMonitorFuseTrapRepeatCounter Counter32
  batteryMonitorFuseAlarmEnable INTEGER
  batteryMonitorFuseValue Integer32

BatteryMonitorSymmetryEntry  
SEQUENCE    
  batteryMonitorSymmetryIndex Integer32
  batteryMonitorSymmetryStatus INTEGER
  batteryMonitorSymmetryDescription DisplayString
  batteryMonitorSymmetryTrapRepeatCounter Counter32
  batteryMonitorSymmetryAlarmEnable INTEGER
  batteryMonitorSymmetryMeasureValue Integer32
  batteryMonitorSymmetryDeltaValue Integer32
  batteryMonitorSymmetryMajorAlarmLevel Integer32
  batteryMonitorSymmetryMinorAlarmLevel Integer32

BatteryEnergyLogLastHoursEntry  
SEQUENCE    
  batteryEnergyLogLastHoursIndex Integer32
  batteryEnergyLogLastHoursValue Integer32

BatteryEnergyLogLastDaysEntry  
SEQUENCE    
  batteryEnergyLogLastDaysIndex Integer32
  batteryEnergyLogLastDaysValue Integer32

BatteryEnergyLogLastWeeksEntry  
SEQUENCE    
  batteryEnergyLogLastWeeksIndex Integer32
  batteryEnergyLogLastWeeksValue Integer32

BatteryCycleLogDaysEntry  
SEQUENCE    
  batteryCycleLogDaysIndex Integer32
  batteryCycleLogDaysValue Integer32

BatteryCycleLogWeeksEntry  
SEQUENCE    
  batteryCycleLogWeeksIndex Integer32
  batteryCycleLogWeeksValue Integer32

BatteryCycleLogMonthsEntry  
SEQUENCE    
  batteryCycleLogMonthsIndex Integer32
  batteryCycleLogMonthsValue Integer32

InputControlUnitsEntry  
SEQUENCE    
  inputControlUnitIndex Integer32
  inputControlUnitNumberOfInputs Integer32

InputControlUnitInputEntry  
SEQUENCE    
  inputControlUnitInputIndex Integer32
  inputControlUnitInputStatus INTEGER
  inputControlUnitInputDescription DisplayString
  inputControlUnitInputTrapRepeatCounter Counter32
  inputControlUnitInputAlarmEnable INTEGER
  inputControlUnitInputValue Integer32
  inputControlUnitInputConfiguration INTEGER

InputIoUnitsEntry  
SEQUENCE    
  inputIoUnitIndex Integer32
  inputIoUnitNumberOfInputs Integer32

InputIoUnitProgInputEntry  
SEQUENCE    
  inputIoUnitProgInputIndex Integer32
  inputIoUnitProgInputStatus INTEGER
  inputIoUnitProgInputDescription DisplayString
  inputIoUnitProgInputTrapRepeatCounter Counter32
  inputIoUnitProgInputAlarmEnable INTEGER
  inputIoUnitProgInputValue Integer32
  inputIoUnitProgInputConfiguration INTEGER

OutputControlUnitEntry  
SEQUENCE    
  outputControlUnitIndex Integer32
  outputControlUnitNumberOfOutputs Integer32

OutputControlUnitOutputEntry  
SEQUENCE    
  outputControlUnitOutputIndex Integer32
  outputControlUnitOutputStatus INTEGER
  outputControlUnitOutputDescription DisplayString

OutputIoUnitEntry  
SEQUENCE    
  outputIoUnitIndex Integer32
  outputIoUnitNumberOfOutputs Integer32

OutputIoUnitOutputEntry  
SEQUENCE    
  outputIoUnitOutputIndex Integer32
  outputIoUnitOutputStatus INTEGER
  outputIoUnitOutputDescription DisplayString

ControlSystemIoUnitsEntry  
SEQUENCE    
  controlSystemIoUnitIndex Integer32
  controlSystemIoUnitNumberOfTemperatures Integer32
  controlSystemIoUnitNumberOfFans Integer32

ControlSystemIoUnitTemperatureEntry  
SEQUENCE    
  controlSystemIoUnitTemperatureIndex Integer32
  controlSystemIoUnitTemperatureStatus INTEGER
  controlSystemIoUnitTemperatureDescription DisplayString
  controlSystemIoUnitTemperatureTrapRepeatCounter Counter32
  controlSystemIoUnitTemperatureAlarmEnable INTEGER
  controlSystemIoUnitTemperatureValue Integer32
  controlSystemIoUnitTemperatureMajorHighLevel Integer32
  controlSystemIoUnitTemperatureMinorHighLevel Integer32
  controlSystemIoUnitTemperatureMinorLowLevel Integer32
  controlSystemIoUnitTemperatureMajorLowLevel Integer32

ControlSystemIoUnitFanEntry  
SEQUENCE    
  controlSystemIoUnitFanIndex Integer32
  controlSystemIoUnitFanSpeedValue Integer32
  controlSystemIoUnitFanSpeedDeviation Integer32
  controlSystemIoUnitFanControl Integer32

ControlUnitEntry  
SEQUENCE    
  controlUnitIndex Integer32
  controlUnitDescription DisplayString
  controlUnitStatus INTEGER
  controlUnitSerialNumber DisplayString
  controlUnitHwPartNumber DisplayString
  controlUnitHwVersion DisplayString
  controlUnitSwPartNumber DisplayString
  controlUnitSwVersion DisplayString

CurrentMonitorsEntry  
SEQUENCE    
  currentMonitorIndex Integer32
  currentMonitorType INTEGER
  currentMonitorId Integer32
  currentMonitorNumberOfFuses Integer32
  currentMonitorNumberOfCurrents Integer32

CurrentMonitorFuseEntry  
SEQUENCE    
  currentMonitorFuseIndex Integer32
  currentMonitorFuseStatus INTEGER
  currentMonitorFuseDescription DisplayString
  currentMonitorFuseTrapRepeatCounter Counter32
  currentMonitorFuseAlarmEnable INTEGER
  currentMonitorFuseValue Integer32

CurrentMonitorCurrentEntry  
SEQUENCE    
  currentMonitorCurrentIndex Integer32
  currentMonitorCurrentStatus INTEGER
  currentMonitorCurrentDescription DisplayString
  currentMonitorCurrentTrapRepeatCounter Counter32
  currentMonitorCurrentAlarmEnable INTEGER
  currentMonitorCurrentValue Integer32
  currentMonitorCurrentMajorAlarmLevel Integer32
  currentMonitorCurrentMinorAlarmLevel Integer32

CurrentMonitorEnergyLogAccumulatedEntry  
SEQUENCE    
  currentMonitorEnergyLogAccumulated Integer32

CurrentMonitorEnergyLogLastHoursEntry  
SEQUENCE    
  currentMonitorEnergyLogLastHoursIndex Integer32
  currentMonitorEnergyLogLastHoursValue Integer32

CurrentMonitorEnergyLogLastDaysEntry  
SEQUENCE    
  currentMonitorEnergyLogLastDaysIndex Integer32
  currentMonitorEnergyLogLastDaysValue Integer32

CurrentMonitorEnergyLogLastWeeksEntry  
SEQUENCE    
  currentMonitorEnergyLogLastWeeksIndex Integer32
  currentMonitorEnergyLogLastWeeksValue Integer32

AlarmGroupEntry  
SEQUENCE    
  alarmGroupIndex Integer32
  alarmGroupStatus INTEGER
  alarmGroupDescription DisplayString

Defined Values

eltek 1.3.6.1.4.1.12148
An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.xx) ELTEK eNexus MIB branch will be 10 (SmartPack2 and Compack) ELTEK Brasil office will have branch 11
MODULE-IDENTITY    

eNexus 1.3.6.1.4.1.12148.10
OBJECT IDENTIFIER    

eltekTraps 1.3.6.1.4.1.12148.10.1
OBJECT IDENTIFIER    

powerAlarmVars 1.3.6.1.4.1.12148.10.1.1
OBJECT IDENTIFIER    

powerSystemTraps 1.3.6.1.4.1.12148.10.1.2
OBJECT IDENTIFIER    

powerSystem 1.3.6.1.4.1.12148.10.2
OBJECT IDENTIFIER    

mains 1.3.6.1.4.1.12148.10.3
OBJECT IDENTIFIER    

mainsMainsFailure 1.3.6.1.4.1.12148.10.3.2
OBJECT IDENTIFIER    

mainsMonitors 1.3.6.1.4.1.12148.10.3.5
OBJECT IDENTIFIER    

mainsOutageLog 1.3.6.1.4.1.12148.10.3.6
OBJECT IDENTIFIER    

generator 1.3.6.1.4.1.12148.10.4
OBJECT IDENTIFIER    

generatorEnergyLog 1.3.6.1.4.1.12148.10.4.23
OBJECT IDENTIFIER    

generatorRunHoursLog 1.3.6.1.4.1.12148.10.4.24
OBJECT IDENTIFIER    

generatorFuelConsumptionLog 1.3.6.1.4.1.12148.10.4.25
OBJECT IDENTIFIER    

rectifiers 1.3.6.1.4.1.12148.10.5
OBJECT IDENTIFIER    

rectifiersCurrent 1.3.6.1.4.1.12148.10.5.2
OBJECT IDENTIFIER    

rectifiersCapacity 1.3.6.1.4.1.12148.10.5.3
OBJECT IDENTIFIER    

rectifiersError 1.3.6.1.4.1.12148.10.5.4
OBJECT IDENTIFIER    

rectifiersEnergyLog 1.3.6.1.4.1.12148.10.5.7
OBJECT IDENTIFIER    

dcdc 1.3.6.1.4.1.12148.10.6
OBJECT IDENTIFIER    

dcdcEnergyLog 1.3.6.1.4.1.12148.10.6.7
OBJECT IDENTIFIER    

solarChargers 1.3.6.1.4.1.12148.10.7
OBJECT IDENTIFIER    

solarChargersCurrent 1.3.6.1.4.1.12148.10.7.2
OBJECT IDENTIFIER    

solarChargersCapacity 1.3.6.1.4.1.12148.10.7.3
OBJECT IDENTIFIER    

solarChargersError 1.3.6.1.4.1.12148.10.7.4
OBJECT IDENTIFIER    

solarChargersEnergyLog 1.3.6.1.4.1.12148.10.7.7
OBJECT IDENTIFIER    

windChargers 1.3.6.1.4.1.12148.10.8
OBJECT IDENTIFIER    

windChargersCurrent 1.3.6.1.4.1.12148.10.8.2
OBJECT IDENTIFIER    

windChargersCapacity 1.3.6.1.4.1.12148.10.8.3
OBJECT IDENTIFIER    

windChargersError 1.3.6.1.4.1.12148.10.8.4
OBJECT IDENTIFIER    

windChargersEnergyLog 1.3.6.1.4.1.12148.10.8.7
OBJECT IDENTIFIER    

load 1.3.6.1.4.1.12148.10.9
OBJECT IDENTIFIER    

loadCurrent 1.3.6.1.4.1.12148.10.9.2
OBJECT IDENTIFIER    

loadEnergyLog 1.3.6.1.4.1.12148.10.9.8
OBJECT IDENTIFIER    

battery 1.3.6.1.4.1.12148.10.10
OBJECT IDENTIFIER    

batteryVoltage 1.3.6.1.4.1.12148.10.10.5
OBJECT IDENTIFIER    

batteryCurrents 1.3.6.1.4.1.12148.10.10.6
OBJECT IDENTIFIER    

batteryTemperatures 1.3.6.1.4.1.12148.10.10.7
OBJECT IDENTIFIER    

batteryTimeLeft 1.3.6.1.4.1.12148.10.10.8
OBJECT IDENTIFIER    

batteryRemainingCapacity 1.3.6.1.4.1.12148.10.10.9
OBJECT IDENTIFIER    

batteryUsedCapacity 1.3.6.1.4.1.12148.10.10.10
OBJECT IDENTIFIER    

batteryTotalCapacity 1.3.6.1.4.1.12148.10.10.11
OBJECT IDENTIFIER    

batteryQuality 1.3.6.1.4.1.12148.10.10.12
OBJECT IDENTIFIER    

batteryLVBD 1.3.6.1.4.1.12148.10.10.13
OBJECT IDENTIFIER    

batteryChargeCurrentLimit 1.3.6.1.4.1.12148.10.10.14
OBJECT IDENTIFIER    

batteryBoost 1.3.6.1.4.1.12148.10.10.15
OBJECT IDENTIFIER    

batteryTest 1.3.6.1.4.1.12148.10.10.16
OBJECT IDENTIFIER    

batteryTempComp 1.3.6.1.4.1.12148.10.10.17
OBJECT IDENTIFIER    

batteryBank 1.3.6.1.4.1.12148.10.10.18
OBJECT IDENTIFIER    

batteryMonitors 1.3.6.1.4.1.12148.10.10.19
OBJECT IDENTIFIER    

batteryEnergyLog 1.3.6.1.4.1.12148.10.10.20
OBJECT IDENTIFIER    

batteryCycleLog 1.3.6.1.4.1.12148.10.10.21
OBJECT IDENTIFIER    

inputs 1.3.6.1.4.1.12148.10.11
OBJECT IDENTIFIER    

outputs 1.3.6.1.4.1.12148.10.12
OBJECT IDENTIFIER    

controlSystem 1.3.6.1.4.1.12148.10.13
OBJECT IDENTIFIER    

snmp 1.3.6.1.4.1.12148.10.13.4
OBJECT IDENTIFIER    

controlSystemIoUnits 1.3.6.1.4.1.12148.10.13.7
OBJECT IDENTIFIER    

controlSystemInventory 1.3.6.1.4.1.12148.10.13.8
OBJECT IDENTIFIER    

currentMonitors 1.3.6.1.4.1.12148.10.13.9
OBJECT IDENTIFIER    

alarmGroups 1.3.6.1.4.1.12148.10.14
OBJECT IDENTIFIER    

alarmSubsysSourceDescr 1.3.6.1.4.1.12148.10.1.1.1
A description of the source generating the trap for the Alarm Condition. Used in alarmSubSystemTrap to describe the alarm source. Example: 'batteryVoltageDescription'
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString Size(0..32)  

alarmSubsysStatusOid 1.3.6.1.4.1.12148.10.1.1.2
The OID (name) of the object indicating the alarm-status for which the alarm is generated. The Status must be an INTEGER type. Example: SP2-MIB::batteryVoltage.batteryVoltageStatus 1.3.6.1.4.1.12148.10.3.5.2: This object maybe polled by the SNMP management application, to monitor the current Status object.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  OBJECT IDENTIFIER  

alarmSubsysStatusValue 1.3.6.1.4.1.12148.10.1.1.3
The value of the Status object of the subsystem for which the alarm-status is generated. The OID (name) of this object is indicated by alarmSubsysStatusOid above. Example: the value of SP2-MIB::batteryVoltage.batteryVoltageStatus one of: error (0), normal (1), minorAlarm (2), etc.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

alarmSubsysStatusOnOff 1.3.6.1.4.1.12148.10.1.1.4
This indicates if the abnormal condition is on or goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER off(0), on(1)  

alarmMeasuredVarOid 1.3.6.1.4.1.12148.10.1.1.5
The OID (name) of the measured-object indicating some measurement (e.g voltage) for which the alarm is generated. Example: SP2-MIB::batteryVoltage.batteryVoltageValue 1.3.6.1.4.1.12148.10.3.5.1 This object maybe polled by the SNMP management application, to monitor the current measurement.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  OBJECT IDENTIFIER  

alarmMeasuredVarValue 1.3.6.1.4.1.12148.10.1.1.6
The value of the measured-object for which the alarm-status is generated, for example 13 volt. The actual value is in units defined by the actual variable (e.g volts). The units must use INTEGER type. The OID (name) of this object is indicated by alarmMeasuredVarOid above. Example: Value of SP2-MIB::batteryVoltage.batteryVoltageValue 'The measured battery voltage'
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

alarmTrapCounterVarValue 1.3.6.1.4.1.12148.10.1.1.7
Tok_String
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

alarmPowerSystemTrap 1.3.6.1.4.1.12148.10.1.2.1
This Trap is sent when an alarm condition occurs in the power system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmBatteryTrap 1.3.6.1.4.1.12148.10.1.2.2
This Trap is sent when an alarm condition occurs in the battery subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmLoadGroupTrap 1.3.6.1.4.1.12148.10.1.2.3
This Trap is sent when an alarm condition occurs in the Load subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmMainsTrap 1.3.6.1.4.1.12148.10.1.2.4
This Trap is sent when an alarm condition occurs in the Mains subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmRectifierTrap 1.3.6.1.4.1.12148.10.1.2.5
This Trap is sent when an alarm condition occurs in the Rectifier subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmControlSystemTrap 1.3.6.1.4.1.12148.10.1.2.6
This Trap is sent when an alarm condition occurs in the Control-system subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmDcDcTrap 1.3.6.1.4.1.12148.10.1.2.7
This Trap is sent when an alarm condition occurs in the DCDC converter subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmInputsTrap 1.3.6.1.4.1.12148.10.1.2.8
This Trap is sent when an alarm condition occurs in the Inputs subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmOutputsTrap 1.3.6.1.4.1.12148.10.1.2.9
This Trap is sent when an alarm condition occurs in the Outputs subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmGeneratorTrap 1.3.6.1.4.1.12148.10.1.2.10
This Trap is sent when an alarm condition occurs in the Generator subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmSolarChargerTrap 1.3.6.1.4.1.12148.10.1.2.11
This Trap is sent when an alarm condition occurs in the SolarCharger subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

alarmWindChargerTrap 1.3.6.1.4.1.12148.10.1.2.12
This Trap is sent when an alarm condition occurs in the WindCharger subsystem.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

infoHeartBeatTrap 1.3.6.1.4.1.12148.10.1.2.13
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

powerSystemStatus 1.3.6.1.4.1.12148.10.2.1
A status value showing the overall condition of the power system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

powerSystemType 1.3.6.1.4.1.12148.10.2.2
A value showing the type of the power system, which is named after the main controller.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER smartpack2(1), smartpackS(2), compack(3)  

powerSystemMode 1.3.6.1.4.1.12148.10.2.3
A summary status showing if the system is in test, boost or float mode
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(0), test(1), boost(2), float(3)  

powerSystemCompany 1.3.6.1.4.1.12148.10.2.4
The Copmany name (as stored in the Control Unit).
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

powerSystemSite 1.3.6.1.4.1.12148.10.2.5
The system/site Location details (as stored in the Control Unit).
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

powerSystemModel 1.3.6.1.4.1.12148.10.2.6
The model/part number of the power system (as stored in the Control Unit).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

powerSystemSerialNumber 1.3.6.1.4.1.12148.10.2.7
The serial number for the complete system.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

powerSystemInstallDate 1.3.6.1.4.1.12148.10.2.8
The system's Installation date (as stored in the Control Unit).
Status: current Access: read-write
OBJECT-TYPE    
  DateAndTime  

powerSystemNominalVoltage 1.3.6.1.4.1.12148.10.2.9
The nominal voltage rating. 12V/24V/48V/60V etc. systems.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 6..250  

powerSystemLongitude 1.3.6.1.4.1.12148.10.2.10
A part of the systems global positioning data. The range +-180degrees Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -180..180  

powerSystemLongitudeDecimal 1.3.6.1.4.1.12148.10.2.11
The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

powerSystemLatitude 1.3.6.1.4.1.12148.10.2.12
A part of the systems global positioning data. The latitude gives the location of a place on Earth (or other planetary body) north or south of the equator. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -90..90  

powerSystemLatitudeDecimal 1.3.6.1.4.1.12148.10.2.13
The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

powerSystemElevation 1.3.6.1.4.1.12148.10.2.14
A part of the systems global positioning data. This is the sites height above sealevel in Meters. The Elevation together with Latituse and Longitude is used for automagically placing system icons on NMS/Sitemonitors system that support this.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

powerSystemCurrentDecimalSetting 1.3.6.1.4.1.12148.10.2.15
A global flag telling if the current values in the system is Amperes or DeciAmpres
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER ampere(0), deciAmpere(1)  

powerSystemTemperatureScale 1.3.6.1.4.1.12148.10.2.16
A flag telling if the temperatures values in the system is of Celcius or Fahrenheit type
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER celcius(0), fahrenheit(1)  

powerSystemCapacityScale 1.3.6.1.4.1.12148.10.2.17
A flag telling if the system's battery capacity value is a percentage of a fully charged battery, or in AmpereHours
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER ah(0), percent(1)  

mainsStatus 1.3.6.1.4.1.12148.10.3.1
The overall status of mains/AC feed subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsMainsFailureStatus 1.3.6.1.4.1.12148.10.3.2.1
This status value shows if the number of failed phases is higher than the defined alarm level.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsMainsFailureDescription 1.3.6.1.4.1.12148.10.3.2.2
A textual description of the mains phase failure monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

mainsMainsFailureTrapRepeatCounter 1.3.6.1.4.1.12148.10.3.2.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

mainsMainsFailureAlarmEnable 1.3.6.1.4.1.12148.10.3.2.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

mainsMainsFailureValue 1.3.6.1.4.1.12148.10.3.2.5
The detected number of failed phases.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMainsFailureMajorAlarmLevel 1.3.6.1.4.1.12148.10.3.2.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMainsFailureMinorAlarmLevel 1.3.6.1.4.1.12148.10.3.2.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsNumberOfPhases 1.3.6.1.4.1.12148.10.3.3
This value showing the number of phases of the mains subsystem.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsVoltageTable 1.3.6.1.4.1.12148.10.3.4
This table contains information about mains voltage monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsVoltageEntry

mainsVoltageEntry 1.3.6.1.4.1.12148.10.3.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsVoltageEntry  

mainsVoltageIndex 1.3.6.1.4.1.12148.10.3.4.1.1
Index used for navigating the rows 1..12 of mainsVoltageTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..12  

mainsVoltageStatus 1.3.6.1.4.1.12148.10.3.4.1.2
The status of the measured mains voltage.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsVoltageDescription 1.3.6.1.4.1.12148.10.3.4.1.3
A textual description of the mains voltage monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

mainsVoltageTrapRepeatCounter 1.3.6.1.4.1.12148.10.3.4.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

mainsVoltageAlarmEnable 1.3.6.1.4.1.12148.10.3.4.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

mainsVoltageValue 1.3.6.1.4.1.12148.10.3.4.1.6
The value of the measured mains voltage.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsVoltageMajorHighLevel 1.3.6.1.4.1.12148.10.3.4.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsVoltageMinorHighLevel 1.3.6.1.4.1.12148.10.3.4.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsVoltageMinorLowLevel 1.3.6.1.4.1.12148.10.3.4.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsVoltageMajorLowLevel 1.3.6.1.4.1.12148.10.3.4.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorsNumberOfUnits 1.3.6.1.4.1.12148.10.3.5.1
This is the number of AC Mains Monitor CAN Nodes installed in the system.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..14  

mainsMonitorsTable 1.3.6.1.4.1.12148.10.3.5.2
This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorsEntry

mainsMonitorsEntry 1.3.6.1.4.1.12148.10.3.5.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorsEntry  

mainsMonitorIndex 1.3.6.1.4.1.12148.10.3.5.2.1.1
Index used for navigating the rows of mainsMonitorsTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

mainsMonitorNumberOfVoltages 1.3.6.1.4.1.12148.10.3.5.2.1.2
The number of voltage measurements in the AC Mains Monitor
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..3  

mainsMonitorNumberOfCurrents 1.3.6.1.4.1.12148.10.3.5.2.1.3
The number of current measurements in the AC Mains Monitor
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..3  

mainsMonitorNumberOfFrequencies 1.3.6.1.4.1.12148.10.3.5.2.1.4
The number of frequency measurements in the AC Mains Monitor
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..3  

mainsMonitorVoltageTable 1.3.6.1.4.1.12148.10.3.5.3
This table contains information about mains voltage in AC Mains Monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorVoltageEntry

mainsMonitorVoltageEntry 1.3.6.1.4.1.12148.10.3.5.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorVoltageEntry  

mainsMonitorPhaseIndex 1.3.6.1.4.1.12148.10.3.5.3.1.1
Index used for navigating the rows 1..3 of mainsMonitorVolatgeTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..3  

mainsMonitorVoltageStatus 1.3.6.1.4.1.12148.10.3.5.3.1.2
The status of the measured mains voltage in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsMonitorVoltageDescription 1.3.6.1.4.1.12148.10.3.5.3.1.3
A textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..16)  

mainsMonitorVoltageTrapRepeatCounter 1.3.6.1.4.1.12148.10.3.5.3.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

mainsMonitorVoltageAlarmEnable 1.3.6.1.4.1.12148.10.3.5.3.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

mainsMonitorVoltageValue 1.3.6.1.4.1.12148.10.3.5.3.1.6
The value of the measured mains voltage in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorVoltageMajorHighLevel 1.3.6.1.4.1.12148.10.3.5.3.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorVoltageMinorHighLevel 1.3.6.1.4.1.12148.10.3.5.3.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorVoltageMinorLowLevel 1.3.6.1.4.1.12148.10.3.5.3.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorVoltageMajorLowLevel 1.3.6.1.4.1.12148.10.3.5.3.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorCurrentTable 1.3.6.1.4.1.12148.10.3.5.4
This table contains information about mains current in AC Mains Monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorCurrentEntry

mainsMonitorCurrentEntry 1.3.6.1.4.1.12148.10.3.5.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorCurrentEntry  

mainsMonitorCurrentStatus 1.3.6.1.4.1.12148.10.3.5.4.1.1
The status of the measured mains current in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsMonitorCurrentDescription 1.3.6.1.4.1.12148.10.3.5.4.1.2
A textual description of the mains current in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..16)  

mainsMonitorCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.3.5.4.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

mainsMonitorCurrentAlarmEnable 1.3.6.1.4.1.12148.10.3.5.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

mainsMonitorCurrentValue 1.3.6.1.4.1.12148.10.3.5.4.1.5
The value of the measured mains current in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorCurrentMajorHighLevel 1.3.6.1.4.1.12148.10.3.5.4.1.6
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorCurrentMinorHighLevel 1.3.6.1.4.1.12148.10.3.5.4.1.7
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorFrequencyTable 1.3.6.1.4.1.12148.10.3.5.5
This table contains information about mains frequency in AC Mains Monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorFrequencyEntry

mainsMonitorFrequencyEntry 1.3.6.1.4.1.12148.10.3.5.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorFrequencyEntry  

mainsMonitorFrequencyStatus 1.3.6.1.4.1.12148.10.3.5.5.1.1
The status of the measured mains frequency in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

mainsMonitorFrequencyDescription 1.3.6.1.4.1.12148.10.3.5.5.1.2
A textual description of the mains frequency in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

mainsMonitorFrequencyTrapRepeatCounter 1.3.6.1.4.1.12148.10.3.5.5.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

mainsMonitorFrequencyAlarmEnable 1.3.6.1.4.1.12148.10.3.5.5.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

mainsMonitorFrequencyValue 1.3.6.1.4.1.12148.10.3.5.5.1.5
The value of the measured mains frequency in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorFrequencyMajorHighLevel 1.3.6.1.4.1.12148.10.3.5.5.1.6
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorFrequencyMinorHighLevel 1.3.6.1.4.1.12148.10.3.5.5.1.7
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorFrequencyMinorLowLevel 1.3.6.1.4.1.12148.10.3.5.5.1.8
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorFrequencyMajorLowLevel 1.3.6.1.4.1.12148.10.3.5.5.1.9
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

mainsMonitorEnergyLogAccumulatedTable 1.3.6.1.4.1.12148.10.3.5.6
This table contains the accumulated energy consumption measured in AC Mains Monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorEnergyLogAccumulatedEntry

mainsMonitorEnergyLogAccumulatedEntry 1.3.6.1.4.1.12148.10.3.5.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorEnergyLogAccumulatedEntry  

mainsMonitorEnergyLogAccumulated 1.3.6.1.4.1.12148.10.3.5.6.1.1
The accumulated energy consumption value
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.3.5.7
This is the maximal number of entries stored in hourly energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsMonitorEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.3.5.8
This table contains energy consumption values logged every hour in AC Mains Monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorEnergyLogLastHoursEntry

mainsMonitorEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.3.5.8.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorEnergyLogLastHoursEntry  

mainsMonitorEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.3.5.8.1.1
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsMonitorEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.3.5.8.1.2
Energy consumption value logged every hour in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.3.5.9
This is the maximal number of entries stored in daily energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsMonitorEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.3.5.10
This table contains energy consumption values logged every day in AC Mains Monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorEnergyLogLastDaysEntry

mainsMonitorEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.3.5.10.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorEnergyLogLastDaysEntry  

mainsMonitorEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.3.5.10.1.1
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsMonitorEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.3.5.10.1.2
Energy consumption value logged every day in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsMonitorEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.3.5.11
This is the maximal number of entries stored in weekly energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsMonitorEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.3.5.12
This table contains energy consumption values logged every week in AC Mains Monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsMonitorEnergyLogLastWeeksEntry

mainsMonitorEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.3.5.12.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsMonitorEnergyLogLastWeeksEntry  

mainsMonitorEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.3.5.12.1.1
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsMonitorEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.3.5.12.1.2
Energy consumption value logged every week in AC Mains Monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsOutageTotal 1.3.6.1.4.1.12148.10.3.6.1
This is the total mains outage time measured in hours.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsOutageLogDaysNumberOfEntries 1.3.6.1.4.1.12148.10.3.6.2
This is the maximal number of entries stored in daily mains outage log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsOutageLogDaysTable 1.3.6.1.4.1.12148.10.3.6.3
This table contains daily mains outage time log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsOutageLogDaysEntry

mainsOutageLogDaysEntry 1.3.6.1.4.1.12148.10.3.6.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsOutageLogDaysEntry  

mainsOutageLogDaysIndex 1.3.6.1.4.1.12148.10.3.6.3.1.1
Index used for navigating the rows 1..52 of mainsOutageLogDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsOutageLogDaysValue 1.3.6.1.4.1.12148.10.3.6.3.1.2
Mains outage time value in minutes, logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsOutageLogWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.3.6.4
This is the maximal number of entries stored in weekly mains outage time log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsOutageLogWeeksTable 1.3.6.1.4.1.12148.10.3.6.5
This table contains weekly mains outage time log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsOutageLogWeeksEntry

mainsOutageLogWeeksEntry 1.3.6.1.4.1.12148.10.3.6.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsOutageLogWeeksEntry  

mainsOutageLogWeeksIndex 1.3.6.1.4.1.12148.10.3.6.5.1.1
Index used for navigating the rows 1..52 of mainsOutageLogWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsOutageLogWeeksValue 1.3.6.1.4.1.12148.10.3.6.5.1.2
Mains outage time value in hours, logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

mainsOutageLogMonthsNumberOfEntries 1.3.6.1.4.1.12148.10.3.6.6
This is the maximal number of entries stored in monthly mains outage time log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

mainsOutageLogMonthsTable 1.3.6.1.4.1.12148.10.3.6.7
This table contains monthly mains outage time log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MainsOutageLogMonthsEntry

mainsOutageLogMonthsEntry 1.3.6.1.4.1.12148.10.3.6.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  MainsOutageLogMonthsEntry  

mainsOutageLogMonthsIndex 1.3.6.1.4.1.12148.10.3.6.7.1.1
Index used for navigating the rows 1..52 of mainsOutageLogMonthsTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

mainsOutageLogMonthsValue 1.3.6.1.4.1.12148.10.3.6.7.1.2
Mains outage time value in hours, logged every month.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorStatus 1.3.6.1.4.1.12148.10.4.1
The overall status of generator subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

generatorFailStatus 1.3.6.1.4.1.12148.10.4.2
The status of generator failure monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

generatorActivation 1.3.6.1.4.1.12148.10.4.3
Indicate if the generator run output signal is activated.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorDischargeValue 1.3.6.1.4.1.12148.10.4.4
This is the present discharge value in percentage of total capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorMainsDelay 1.3.6.1.4.1.12148.10.4.5
Elapsing time of mains failure.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorChargeTime 1.3.6.1.4.1.12148.10.4.6
Elapsing time of charging with generator running.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorCapacityControlledStartStopEnable 1.3.6.1.4.1.12148.10.4.7
Battery charge/discharge level control of starting and stopping of generator
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorCapacityStartOnDischargeLimit 1.3.6.1.4.1.12148.10.4.8
When the generatorCapacityControlled is enabled, the generator is started when the remaining battery capacity drops below this limit in percentage of the total capacity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

generatorCapacityStopOnChargeLimit 1.3.6.1.4.1.12148.10.4.9
When the generatorCapacityControlled is enabled, the generator is stopped when the remaining battery capacity is greater than this limit in percentage of the total capacity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

generatorCurrentLimitControlledStopEnable 1.3.6.1.4.1.12148.10.4.10
Enables the generator to stop when the charge current drops below generatorCurrentLimitControlledStopValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorCurrentLimitControlledStopValue 1.3.6.1.4.1.12148.10.4.11
Generator stops when the charge current drop drops below this level.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

generatorVoltageControlledStartEnable 1.3.6.1.4.1.12148.10.4.12
Enable/disable voltage controlled generator activation.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorVoltageControlStartVoltage 1.3.6.1.4.1.12148.10.4.13
The voltage limit to start generator.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorVoltageControlStopAfter 1.3.6.1.4.1.12148.10.4.14
A time delay for stopping generator when generator is activated by voltage.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorDailyRunEnable 1.3.6.1.4.1.12148.10.4.15
Enable/disable generator daily run function.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorDailyRunSetupTable 1.3.6.1.4.1.12148.10.4.16
This table contains configurations of generator daily run.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorDailyRunSetupEntry

generatorDailyRunSetupEntry 1.3.6.1.4.1.12148.10.4.16.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorDailyRunSetupEntry  

generatorDailyRunDayIndex 1.3.6.1.4.1.12148.10.4.16.1.1
Index used for navigating the rows 1..7 of generatorDailyRunSetupTable
Status: current Access: not-accessible
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)  

generatorDailyRunStartHour 1.3.6.1.4.1.12148.10.4.16.1.2
Generator daily starting time.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..23  

generatorDailyRunStopHour 1.3.6.1.4.1.12148.10.4.16.1.3
Generator daily stopping time.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..23  

generatorMonthlyRunEnable 1.3.6.1.4.1.12148.10.4.17
Enable/disable generator monthly run function.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorMonthlyRunStartTime 1.3.6.1.4.1.12148.10.4.18
Generator monthly run starting time.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..23  

generatorMonthlyRunStartDayinMonth1 1.3.6.1.4.1.12148.10.4.19
Generator monthly run starting day #1.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..32  

generatorMonthlyRunStartDayinMonth2 1.3.6.1.4.1.12148.10.4.20
Generator monthly run starting day #2.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..32  

generatorTankNumberOfTanks 1.3.6.1.4.1.12148.10.4.21
Number of fuel tanks.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..2  

generatorTankTable 1.3.6.1.4.1.12148.10.4.22
This table contains information about generator fuel tanks.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorTankEntry

generatorTankEntry 1.3.6.1.4.1.12148.10.4.22.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorTankEntry  

generatorTankIndex 1.3.6.1.4.1.12148.10.4.22.1.1
Index used for navigating the rows 1..2 of generatorTankTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..2  

generatorTankStatus 1.3.6.1.4.1.12148.10.4.22.1.2
The status of the measured fuel level in tank.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

generatorTankDescription 1.3.6.1.4.1.12148.10.4.22.1.3
A textual description of the fuel level monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

generatorTankTrapRepeatCounter 1.3.6.1.4.1.12148.10.4.22.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

generatorTankEnable 1.3.6.1.4.1.12148.10.4.22.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

generatorTankValue 1.3.6.1.4.1.12148.10.4.22.1.6
The value of the measured fuel level.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorTankMajorHighLevel 1.3.6.1.4.1.12148.10.4.22.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorTankMinorHighLevel 1.3.6.1.4.1.12148.10.4.22.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorTankMinorLowLevel 1.3.6.1.4.1.12148.10.4.22.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorTankMajorLowLevel 1.3.6.1.4.1.12148.10.4.22.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

generatorEnergyLogAccumulated 1.3.6.1.4.1.12148.10.4.23.1
This is the accumulated energy delivered through rectifiers from generator.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.4.23.2
This is the maximal number of entries stored in generator hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.4.23.3
This table contains hourly energy log of generator.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorEnergyLogLastHoursEntry

generatorEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.4.23.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorEnergyLogLastHoursEntry  

generatorEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.4.23.3.1.1
Index used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.4.23.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.4.23.4
This is the maximal number of entries stored in generator daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.4.23.5
This table contains daily energy log of generator.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorEnergyLogLastDaysEntry

generatorEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.4.23.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorEnergyLogLastDaysEntry  

generatorEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.4.23.5.1.1
Index used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.4.23.5.1.2
Energy value logged every day
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.4.23.6
This is the maximal number of entries stored in generator weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.4.23.7
This table contains weekly energy log of generator.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorEnergyLogLastWeeksEntry

generatorEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.4.23.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorEnergyLogLastWeeksEntry  

generatorEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.4.23.7.1.1
Index used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.4.23.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorRunHoursTotalHours 1.3.6.1.4.1.12148.10.4.24.1
This is the total generator running hours.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorRunHoursLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.4.24.2
This is the maximal number of entries stored in generator daily running hours log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorRunHoursLogLastDaysTable 1.3.6.1.4.1.12148.10.4.24.3
generator running time in minutes
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorRunHoursLogLastDaysEntry

generatorRunHoursLogLastDaysEntry 1.3.6.1.4.1.12148.10.4.24.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorRunHoursLogLastDaysEntry  

generatorRunHoursLogLastDaysIndex 1.3.6.1.4.1.12148.10.4.24.3.1.1
Index used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorRunHoursLogLastDaysValue 1.3.6.1.4.1.12148.10.4.24.3.1.2
Generator running time in minutes, logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorRunHoursLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.4.24.4
This is the maximal number of entries stored in generator weekly running hours log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorRunHoursLogLastWeeksTable 1.3.6.1.4.1.12148.10.4.24.5
generator running time in hours
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorRunHoursLogLastWeeksEntry

generatorRunHoursLogLastWeeksEntry 1.3.6.1.4.1.12148.10.4.24.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorRunHoursLogLastWeeksEntry  

generatorRunHoursLogLastWeeksIndex 1.3.6.1.4.1.12148.10.4.24.5.1.1
Index used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorRunHoursLogLastWeeksValue 1.3.6.1.4.1.12148.10.4.24.5.1.2
Generator running time in hours, logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorRunHoursLogLastMonthsNumberOfEntries 1.3.6.1.4.1.12148.10.4.24.6
This is the maximal number of entries stored in generator monthly running hours log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorRunHoursLogLastMonthsTable 1.3.6.1.4.1.12148.10.4.24.7
generator running time in hours
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorRunHoursLogLastMonthsEntry

generatorRunHoursLogLastMonthsEntry 1.3.6.1.4.1.12148.10.4.24.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorRunHoursLogLastMonthsEntry  

generatorRunHoursLogLastMonthsIndex 1.3.6.1.4.1.12148.10.4.24.7.1.1
Index used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorRunHoursLogLastMonthsValue 1.3.6.1.4.1.12148.10.4.24.7.1.2
Generator running time in hours, logged every month.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorFuelConsumptionTotalUsedTable 1.3.6.1.4.1.12148.10.4.25.1
This table contains total fuel consumption for each tank.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorFuelConsumptionTotalUsedEntry

generatorFuelConsumptionTotalUsedEntry 1.3.6.1.4.1.12148.10.4.25.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorFuelConsumptionTotalUsedEntry  

generatorFuelConsumptionTotalUsed 1.3.6.1.4.1.12148.10.4.25.1.1.1
Total fuel consumption value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorFuelConsumptionLogLastHoursNoOfEntries 1.3.6.1.4.1.12148.10.4.25.2
This is the maximal number of entries stored in generator hourly fuel consumption log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorFuelConsumptionLogLastHoursTable 1.3.6.1.4.1.12148.10.4.25.3
This table contains generator hourly fuel consumption log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorFuelConsumptionLogLastHoursEntry

generatorFuelConsumptionLogLastHoursEntry 1.3.6.1.4.1.12148.10.4.25.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorFuelConsumptionLogLastHoursEntry  

generatorFuelConsumptionLogLastHoursIndex 1.3.6.1.4.1.12148.10.4.25.3.1.1
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorFuelConsumptionLogLastHoursValue 1.3.6.1.4.1.12148.10.4.25.3.1.2
Generator fuel consumption value, logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorFuelConsumptionLogLastDaysNoOfEntries 1.3.6.1.4.1.12148.10.4.25.4
This is the maximal number of entries stored in generator daily fuel consumption log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorFuelConsumptionLogLastDaysTable 1.3.6.1.4.1.12148.10.4.25.5
This table contains generator daily fuel consumption log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorFuelConsumptionLogLastDaysEntry

generatorFuelConsumptionLogLastDaysEntry 1.3.6.1.4.1.12148.10.4.25.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorFuelConsumptionLogLastDaysEntry  

generatorFuelConsumptionLogLastDaysIndex 1.3.6.1.4.1.12148.10.4.25.5.1.1
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorFuelConsumptionLogLastDaysValue 1.3.6.1.4.1.12148.10.4.25.5.1.2
Generator fuel consumption value, logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

generatorFuelConsumptionLogLastWeeksNoOfEntries 1.3.6.1.4.1.12148.10.4.25.6
This is the maximal number of entries stored in generator weekly fuel consumption log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

generatorFuelConsumptionLogLastWeeksTable 1.3.6.1.4.1.12148.10.4.25.7
This table contains generator weekly fuel consumption log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    GeneratorFuelConsumptionLogLastWeeksEntry

generatorFuelConsumptionLogLastWeeksEntry 1.3.6.1.4.1.12148.10.4.25.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  GeneratorFuelConsumptionLogLastWeeksEntry  

generatorFuelConsumptionLogLastWeeksIndex 1.3.6.1.4.1.12148.10.4.25.7.1.1
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

generatorFuelConsumptionLogLastWeeksValue 1.3.6.1.4.1.12148.10.4.25.7.1.2
Generator fuel consumption value, logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersStatus 1.3.6.1.4.1.12148.10.5.1
The overall status of rectifier subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

rectifiersCurrentStatus 1.3.6.1.4.1.12148.10.5.2.1
The status of the measured total rectifier current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

rectifiersCurrentDescription 1.3.6.1.4.1.12148.10.5.2.2
A textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifiersCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.5.2.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

rectifiersCurrentAlarmEnable 1.3.6.1.4.1.12148.10.5.2.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rectifiersCurrentValue 1.3.6.1.4.1.12148.10.5.2.5
The value of the measured total rectifier current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersCurrentMajorAlarmLevel 1.3.6.1.4.1.12148.10.5.2.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersCurrentMinorAlarmLevel 1.3.6.1.4.1.12148.10.5.2.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersCapacityStatus 1.3.6.1.4.1.12148.10.5.3.1
The status of the measured used rectifier capacity.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

rectifiersCapacityDescription 1.3.6.1.4.1.12148.10.5.3.2
A textual description of the used rectifier capacity monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifiersCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.5.3.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

rectifiersCapacityAlarmEnable 1.3.6.1.4.1.12148.10.5.3.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rectifiersCapacityValue 1.3.6.1.4.1.12148.10.5.3.5
The used rectifier capacity value presented in percentage of the total installed rectifier capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersCapacityMajorAlarmLevel 1.3.6.1.4.1.12148.10.5.3.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersCapacityMinorAlarmLevel 1.3.6.1.4.1.12148.10.5.3.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersErrorStatus 1.3.6.1.4.1.12148.10.5.4.1
This status value shows if the number of failed units is higher than the defined alarm level.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

rectifiersErrorDescription 1.3.6.1.4.1.12148.10.5.4.2
A textual description of the rectifier error monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifiersErrorTrapRepeatCounter 1.3.6.1.4.1.12148.10.5.4.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

rectifiersErrorEnable 1.3.6.1.4.1.12148.10.5.4.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rectifiersErrorValue 1.3.6.1.4.1.12148.10.5.4.5
The number of failed rectifiers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersErrorMajorAlarmLevel 1.3.6.1.4.1.12148.10.5.4.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersErrorMinorAlarmLevel 1.3.6.1.4.1.12148.10.5.4.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

rectifiersNumberOfRectifiers 1.3.6.1.4.1.12148.10.5.5
Number of installed rectifiers.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

rectifierTable 1.3.6.1.4.1.12148.10.5.6
This table shows the information of each rectifier installed in the system.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifierEntry

rectifierEntry 1.3.6.1.4.1.12148.10.5.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifierEntry  

rectifierIndex 1.3.6.1.4.1.12148.10.5.6.1.1
Index used for navigating the rows 1..100 of rectifierTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..100  

rectifierStatus 1.3.6.1.4.1.12148.10.5.6.1.2
The overall status of rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

rectifierOutputCurrentValue 1.3.6.1.4.1.12148.10.5.6.1.3
The output current value of rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifierInputVoltageValue 1.3.6.1.4.1.12148.10.5.6.1.4
The input voltage value of rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifierType 1.3.6.1.4.1.12148.10.5.6.1.5
Type of rectifier
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..27)  

rectifierHwPartNumber 1.3.6.1.4.1.12148.10.5.6.1.6
Hardware part number of rectifier
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

rectifierHwVersion 1.3.6.1.4.1.12148.10.5.6.1.7
Hardware version number of rectifier
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

rectifierSwPartNumber 1.3.6.1.4.1.12148.10.5.6.1.8
Part number of secondary software in rectifier
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

rectifierSwVersion 1.3.6.1.4.1.12148.10.5.6.1.9
Version number of secondary software in rectifier
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

rectifiersEnergyLogAccumulated 1.3.6.1.4.1.12148.10.5.7.1
This is the accumulated energy delivered from rectifiers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.5.7.2
This is the maximal number of entries stored in rectifier hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

rectifiersEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.5.7.3
This table contains hourly energy log of rectifiers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifiersEnergyLogLastHoursEntry

rectifiersEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.5.7.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifiersEnergyLogLastHoursEntry  

rectifiersEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.5.7.3.1.1
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

rectifiersEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.5.7.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.5.7.4
This is the maximal number of entries stored in rectifier daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

rectifiersEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.5.7.5
This table contains daily energy log of rectifiers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifiersEnergyLogLastDaysEntry

rectifiersEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.5.7.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifiersEnergyLogLastDaysEntry  

rectifiersEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.5.7.5.1.1
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

rectifiersEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.5.7.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifiersEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.5.7.6
This is the maximal number of entries stored in rectifier weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

rectifiersEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.5.7.7
This table contains weekly energy log of rectifiers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifiersEnergyLogLastWeeksEntry

rectifiersEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.5.7.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifiersEnergyLogLastWeeksEntry  

rectifiersEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.5.7.7.1.1
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

rectifiersEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.5.7.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcNumberOfGroups 1.3.6.1.4.1.12148.10.6.1
Number of dcdc groups
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..5  

dcdcGroupsTable 1.3.6.1.4.1.12148.10.6.2
This table contains information about dcdc groups.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcGroupsEntry

dcdcGroupsEntry 1.3.6.1.4.1.12148.10.6.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcGroupsEntry  

dcdcGroupIndex 1.3.6.1.4.1.12148.10.6.2.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..5  

dcdcGroupStatus 1.3.6.1.4.1.12148.10.6.2.1.2
The overall status of dcdc group.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

dcdcGroupNumberOfDcdcConverters 1.3.6.1.4.1.12148.10.6.2.1.3
Number of installed dcdc converters.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcGroupOutputVoltage 1.3.6.1.4.1.12148.10.6.2.1.4
Output voltage of dcdc converters
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcNumberOfCurrents 1.3.6.1.4.1.12148.10.6.2.1.5
Number of dcdc currents
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..5  

dcdcNumberOfCapacities 1.3.6.1.4.1.12148.10.6.2.1.6
Number of dcdc capacities
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..5  

dcdcNumberOfAlarms 1.3.6.1.4.1.12148.10.6.2.1.7
Number of dcdc alarms
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..5  

dcdcCurrentTable 1.3.6.1.4.1.12148.10.6.3
This table contains information about the total dcdc current.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcCurrentEntry

dcdcCurrentEntry 1.3.6.1.4.1.12148.10.6.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcCurrentEntry  

dcdcCurrentStatus 1.3.6.1.4.1.12148.10.6.3.1.1
The status of the measured total dcdc current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

dcdcCurrentDescription 1.3.6.1.4.1.12148.10.6.3.1.2
A textual description of the total dcdc current monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

dcdcCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.6.3.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

dcdcCurrentAlarmEnable 1.3.6.1.4.1.12148.10.6.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

dcdcCurrentValue 1.3.6.1.4.1.12148.10.6.3.1.5
The value of the measured total dcdc current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcCurrentMajorAlarmLevel 1.3.6.1.4.1.12148.10.6.3.1.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcCurrentMinorAlarmLevel 1.3.6.1.4.1.12148.10.6.3.1.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcCapacityTable 1.3.6.1.4.1.12148.10.6.4
This table contains information about the used dcdc capacity.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcCapacityEntry

dcdcCapacityEntry 1.3.6.1.4.1.12148.10.6.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcCapacityEntry  

dcdcCapacityStatus 1.3.6.1.4.1.12148.10.6.4.1.1
The status of the measured used dcdc capacity.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

dcdcCapacityDescription 1.3.6.1.4.1.12148.10.6.4.1.2
A textual description of the used dcdc capacity monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

dcdcCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.6.4.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes of
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

dcdcCapacityAlarmEnable 1.3.6.1.4.1.12148.10.6.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

dcdcCapacityValue 1.3.6.1.4.1.12148.10.6.4.1.5
The used dcdc capacity value presented in percentage of the total installed dcdc capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcCapacityMajorAlarmLevel 1.3.6.1.4.1.12148.10.6.4.1.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcCapacityMinorAlarmLevel 1.3.6.1.4.1.12148.10.6.4.1.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcTable 1.3.6.1.4.1.12148.10.6.5
This table shows the information of each dcdc converter installed in the system.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcEntry

dcdcEntry 1.3.6.1.4.1.12148.10.6.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcEntry  

dcdcIndex 1.3.6.1.4.1.12148.10.6.5.1.1
Index used for navigating the rows 1..100 of dcdcTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..100  

dcdcStatus 1.3.6.1.4.1.12148.10.6.5.1.2
The overall status of dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

dcdcOutputCurrentValue 1.3.6.1.4.1.12148.10.6.5.1.3
The output current value of dcdc.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcInputVoltageValue 1.3.6.1.4.1.12148.10.6.5.1.4
The input voltage value of dcdc.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcType 1.3.6.1.4.1.12148.10.6.5.1.5
Type of dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..27)  

dcdcHwPartNumber 1.3.6.1.4.1.12148.10.6.5.1.6
Hardware part number of dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

dcdcHwVersion 1.3.6.1.4.1.12148.10.6.5.1.7
Hardware version number of dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

dcdcSwPartNumber 1.3.6.1.4.1.12148.10.6.5.1.8
Part number of secondary software in dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

dcdcSwVersion 1.3.6.1.4.1.12148.10.6.5.1.9
Version number of secondary software in dcdc converter
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

dcdcErrorTable 1.3.6.1.4.1.12148.10.6.6
This table contains information about the dcdc error monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcErrorEntry

dcdcErrorEntry 1.3.6.1.4.1.12148.10.6.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcErrorEntry  

dcdcErrorStatus 1.3.6.1.4.1.12148.10.6.6.1.1
This status value shows if the number of failed units is higher than the defined alarm level.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

dcdcErrorDescription 1.3.6.1.4.1.12148.10.6.6.1.2
A textual description of the dcdc error monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

dcdcErrorTrapRepeatCounter 1.3.6.1.4.1.12148.10.6.6.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

dcdcErrorEnable 1.3.6.1.4.1.12148.10.6.6.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

dcdcErrorValue 1.3.6.1.4.1.12148.10.6.6.1.5
The number of failed dcdc converters.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcErrorMajorAlarmLevel 1.3.6.1.4.1.12148.10.6.6.1.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcErrorMinorAlarmLevel 1.3.6.1.4.1.12148.10.6.6.1.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

dcdcEnergyLogAccumulatedTable 1.3.6.1.4.1.12148.10.6.7.1
This is the accumulated energy delivered from dcdc converters.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcEnergyLogAccumulatedEntry

dcdcEnergyLogAccumulatedEntry 1.3.6.1.4.1.12148.10.6.7.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcEnergyLogAccumulatedEntry  

dcdcEnergyLogAccumulated 1.3.6.1.4.1.12148.10.6.7.1.1.1
This is the accumulated energy delivered from dcdc converters.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.6.7.2
This is the maximal number of entries stored in dcdc hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

dcdcEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.6.7.3
This table contains hourly energy log of dcdc converters
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcEnergyLogLastHoursEntry

dcdcEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.6.7.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcEnergyLogLastHoursEntry  

dcdcEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.6.7.3.1.1
Index used for navigating the rows 1..52 of dcdcEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

dcdcEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.6.7.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.6.7.4
This is the maximal number of entries stored in dcdc daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

dcdcEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.6.7.5
This table contains daily energy log of dcdc converters.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcEnergyLogLastDaysEntry

dcdcEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.6.7.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcEnergyLogLastDaysEntry  

dcdcEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.6.7.5.1.1
Index used for navigating the rows 1..52 of dcdcEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

dcdcEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.6.7.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dcdcEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.6.7.6
This is the maximal number of entries stored in dcdc weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

dcdcEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.6.7.7
This table contains weekly energy log of dcdc converters.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    DcdcEnergyLogLastWeeksEntry

dcdcEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.6.7.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  DcdcEnergyLogLastWeeksEntry  

dcdcEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.6.7.7.1.1
Index used for navigating the rows 1..52 of dcdcEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

dcdcEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.6.7.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersStatus 1.3.6.1.4.1.12148.10.7.1
The overall status of solar charger subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

solarChargersCurrentStatus 1.3.6.1.4.1.12148.10.7.2.1
The status of the measured total solar current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

solarChargersCurrentDescription 1.3.6.1.4.1.12148.10.7.2.2
A textual description of the total solar current monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

solarChargersCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.7.2.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

solarChargersCurrentAlarmEnable 1.3.6.1.4.1.12148.10.7.2.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

solarChargersCurrentValue 1.3.6.1.4.1.12148.10.7.2.5
The value of the measured total solar current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersCurrentMajorAlarmLevel 1.3.6.1.4.1.12148.10.7.2.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersCurrentMinorAlarmLevel 1.3.6.1.4.1.12148.10.7.2.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersCapacityStatus 1.3.6.1.4.1.12148.10.7.3.1
The status of the measured used solar capacity.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

solarChargersCapacityDescription 1.3.6.1.4.1.12148.10.7.3.2
A textual description of the used solar charger capacity monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

solarChargersCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.7.3.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

solarChargersCapacityAlarmEnable 1.3.6.1.4.1.12148.10.7.3.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

solarChargersCapacityValue 1.3.6.1.4.1.12148.10.7.3.5
The used solar capacity value presented in percentage of the total installed solar capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersCapacityMajorAlarmLevel 1.3.6.1.4.1.12148.10.7.3.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersCapacityMinorAlarmLevel 1.3.6.1.4.1.12148.10.7.3.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersErrorStatus 1.3.6.1.4.1.12148.10.7.4.1
This status value shows if the number of failed units is higher than the defined alarm level.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

solarChargersErrorDescription 1.3.6.1.4.1.12148.10.7.4.2
A textual description of the solar error monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

solarChargersErrorTrapRepeatCounter 1.3.6.1.4.1.12148.10.7.4.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

solarChargersErrorEnable 1.3.6.1.4.1.12148.10.7.4.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

solarChargersErrorValue 1.3.6.1.4.1.12148.10.7.4.5
The number of failed solar chargers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersErrorMajorAlarmLevel 1.3.6.1.4.1.12148.10.7.4.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersErrorMinorAlarmLevel 1.3.6.1.4.1.12148.10.7.4.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

solarChargersNumberOfSolarChargers 1.3.6.1.4.1.12148.10.7.5
Number of installed solar chargers.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

solarChargerTable 1.3.6.1.4.1.12148.10.7.6
This table shows the information of each solar charger installed in the system.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarChargerEntry

solarChargerEntry 1.3.6.1.4.1.12148.10.7.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarChargerEntry  

solarChargerIndex 1.3.6.1.4.1.12148.10.7.6.1.1
Index used for navigating the rows 1..100 of solarChargerTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..100  

solarChargerStatus 1.3.6.1.4.1.12148.10.7.6.1.2
The overall status of solar charger.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

solarChargerOutputCurrentValue 1.3.6.1.4.1.12148.10.7.6.1.3
The output current value of solar charger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargerInputVoltageValue 1.3.6.1.4.1.12148.10.7.6.1.4
The input voltage value of solar charger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargerType 1.3.6.1.4.1.12148.10.7.6.1.5
Type of solar charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..27)  

solarChargerHwPartNumber 1.3.6.1.4.1.12148.10.7.6.1.6
Hardware part number of solar charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

solarChargerHwVersion 1.3.6.1.4.1.12148.10.7.6.1.7
Hardware version number of solar charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

solarChargerSwPartNumber 1.3.6.1.4.1.12148.10.7.6.1.8
Part number of secondary software in solar charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

solarChargerSwVersion 1.3.6.1.4.1.12148.10.7.6.1.9
Version number of secondary software in solar charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

solarChargersEnergyLogAccumulated 1.3.6.1.4.1.12148.10.7.7.1
This is the accumulated energy delivered from solar chargers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.7.7.2
This is the maximal number of entries stored in solar charger hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.7.7.3
This table contains hourly energy log of solar chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarChargersEnergyLogLastHoursEntry

solarChargersEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.7.7.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarChargersEnergyLogLastHoursEntry  

solarChargersEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.7.7.3.1.1
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

solarChargersEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.7.7.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.7.7.4
This is the maximal number of entries stored in solar charger daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.7.7.5
This table contains daily energy log of solar chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarChargersEnergyLogLastDaysEntry

solarChargersEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.7.7.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarChargersEnergyLogLastDaysEntry  

solarChargersEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.7.7.5.1.1
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

solarChargersEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.7.7.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.7.7.6
This is the maximal number of entries stored in solar charger weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargersEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.7.7.7
This table contains weekly energy log of solar chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarChargersEnergyLogLastWeeksEntry

solarChargersEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.7.7.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarChargersEnergyLogLastWeeksEntry  

solarChargersEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.7.7.7.1.1
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

solarChargersEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.7.7.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersStatus 1.3.6.1.4.1.12148.10.8.1
The overall status of wind charger subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

windChargersCurrentStatus 1.3.6.1.4.1.12148.10.8.2.1
The status of the measured total wind current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

windChargersCurrentDescription 1.3.6.1.4.1.12148.10.8.2.2
A textual description of the total wind current monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

windChargersCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.8.2.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

windChargersCurrentAlarmEnable 1.3.6.1.4.1.12148.10.8.2.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

windChargersCurrentValue 1.3.6.1.4.1.12148.10.8.2.5
The value of the measured total wind current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersCurrentMajorAlarmLevel 1.3.6.1.4.1.12148.10.8.2.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersCurrentMinorAlarmLevel 1.3.6.1.4.1.12148.10.8.2.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersCapacityStatus 1.3.6.1.4.1.12148.10.8.3.1
The status of the measured used wind charger capacity.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

windChargersCapacityDescription 1.3.6.1.4.1.12148.10.8.3.2
A textual description of the used wind charger capacity monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

windChargersCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.8.3.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

windChargersCapacityAlarmEnable 1.3.6.1.4.1.12148.10.8.3.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

windChargersCapacityValue 1.3.6.1.4.1.12148.10.8.3.5
The used wind charger capacity value presented in percentage of the total installed wind charger capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersCapacityMajorAlarmLevel 1.3.6.1.4.1.12148.10.8.3.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersCapacityMinorAlarmLevel 1.3.6.1.4.1.12148.10.8.3.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersErrorStatus 1.3.6.1.4.1.12148.10.8.4.1
This status value shows if the number of failed units is higher than the defined alarm level.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

windChargersErrorDescription 1.3.6.1.4.1.12148.10.8.4.2
A textual description of the wind error monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

windChargersErrorTrapRepeatCounter 1.3.6.1.4.1.12148.10.8.4.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

windChargersErrorEnable 1.3.6.1.4.1.12148.10.8.4.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

windChargersErrorValue 1.3.6.1.4.1.12148.10.8.4.5
The number of failed wind chargers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersErrorMajorAlarmLevel 1.3.6.1.4.1.12148.10.8.4.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersErrorMinorAlarmLevel 1.3.6.1.4.1.12148.10.8.4.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

windChargersNumberOfWindChargers 1.3.6.1.4.1.12148.10.8.5
Number of installed wind chargers.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..254  

windChargerTable 1.3.6.1.4.1.12148.10.8.6
This table shows the information of each wind charger installed in the system.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WindChargerEntry

windChargerEntry 1.3.6.1.4.1.12148.10.8.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  WindChargerEntry  

windChargerIndex 1.3.6.1.4.1.12148.10.8.6.1.1
Index used for navigating the rows 1..100 of windChargerTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..100  

windChargerStatus 1.3.6.1.4.1.12148.10.8.6.1.2
The overall status of wind charger.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

windChargerOutputCurrentValue 1.3.6.1.4.1.12148.10.8.6.1.3
The output current value of wind charger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargerInputVoltageValue 1.3.6.1.4.1.12148.10.8.6.1.4
The input voltage value of wind charger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargerType 1.3.6.1.4.1.12148.10.8.6.1.5
Type of wind charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..27)  

windChargerHwPartNumber 1.3.6.1.4.1.12148.10.8.6.1.6
Hardware part number of wind charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

windChargerHwVersion 1.3.6.1.4.1.12148.10.8.6.1.7
Hardware version number of wind charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

windChargerSwPartNumber 1.3.6.1.4.1.12148.10.8.6.1.8
Part number of secondary software in wind charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

windChargerSwVersion 1.3.6.1.4.1.12148.10.8.6.1.9
Version number of secondary software in wind charger
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..6)  

windChargersEnergyLogAccumulated 1.3.6.1.4.1.12148.10.8.7.1
This is the accumulated energy delivered to/from wind chargers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.8.7.2
This is the maximal number of entries stored in wind charger hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

windChargersEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.8.7.3
This table contains hourly energy log of wind chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WindChargersEnergyLogLastHoursEntry

windChargersEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.8.7.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  WindChargersEnergyLogLastHoursEntry  

windChargersEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.8.7.3.1.1
Index used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

windChargersEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.8.7.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.8.7.4
This is the maximal number of entries stored in wind charger daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

windChargersEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.8.7.5
This table contains daily energy log of wind chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WindChargersEnergyLogLastDaysEntry

windChargersEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.8.7.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  WindChargersEnergyLogLastDaysEntry  

windChargersEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.8.7.5.1.1
Index used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

windChargersEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.8.7.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

windChargersEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.8.7.6
This is the maximal number of entries stored in wind charger weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

windChargersEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.8.7.7
This table contains weekly energy log of wind chargers.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WindChargersEnergyLogLastWeeksEntry

windChargersEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.8.7.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  WindChargersEnergyLogLastWeeksEntry  

windChargersEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.8.7.7.1.1
Index used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

windChargersEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.8.7.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadStatus 1.3.6.1.4.1.12148.10.9.1
The overall status of load subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

loadCurrentStatus 1.3.6.1.4.1.12148.10.9.2.1
The status of the measured load current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

loadCurrentDescription 1.3.6.1.4.1.12148.10.9.2.2
A textual description of the load current monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

loadCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.9.2.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

loadCurrentAlarmEnable 1.3.6.1.4.1.12148.10.9.2.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadCurrentValue 1.3.6.1.4.1.12148.10.9.2.5
The value of the measured load current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadCurrentMajorHighLevel 1.3.6.1.4.1.12148.10.9.2.6
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadCurrentMinorHighLevel 1.3.6.1.4.1.12148.10.9.2.7
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadFusesStatus 1.3.6.1.4.1.12148.10.9.3
The overall status of the load fuses.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

loadNumberOfGroups 1.3.6.1.4.1.12148.10.9.4
Number of load groups
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..8  

loadGroupTable 1.3.6.1.4.1.12148.10.9.5
This table contains information about load groups.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadGroupEntry

loadGroupEntry 1.3.6.1.4.1.12148.10.9.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadGroupEntry  

loadGroupIndex 1.3.6.1.4.1.12148.10.9.5.1.1
Index used for navigating the rows 1..8 of loadGroupTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

loadGroupStatus 1.3.6.1.4.1.12148.10.9.5.1.2
The status of load group
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

loadNumberOfLVLDs 1.3.6.1.4.1.12148.10.9.5.1.3
Number of LVLDs installed in load group
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

loadLVLDTable 1.3.6.1.4.1.12148.10.9.6
This table contains information about LVLDs
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadLVLDEntry

loadLVLDEntry 1.3.6.1.4.1.12148.10.9.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadLVLDEntry  

loadLVLDIndex 1.3.6.1.4.1.12148.10.9.6.1.1
Index used for navigating the rows 1..8 of loadLVLDTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

loadLVLDStatus 1.3.6.1.4.1.12148.10.9.6.1.2
The status of LVLD
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

loadLVLDDescription 1.3.6.1.4.1.12148.10.9.6.1.3
A textual description of the LVLD. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

loadLVLDTrapRepeatCounter 1.3.6.1.4.1.12148.10.9.6.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

loadLVLDEnable 1.3.6.1.4.1.12148.10.9.6.1.5
This value once enabled, the alarm condition of the LVLD will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVLDValue 1.3.6.1.4.1.12148.10.9.6.1.6
The measured value of the LVLD.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadLVLDConnectVoltage 1.3.6.1.4.1.12148.10.9.6.1.7
The load Contactor's Reconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadLVLDDisconnectVoltage 1.3.6.1.4.1.12148.10.9.6.1.8
The load Contactor's Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadFuseTable 1.3.6.1.4.1.12148.10.9.7
This table contains information about load fuse
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadFuseEntry

loadFuseEntry 1.3.6.1.4.1.12148.10.9.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadFuseEntry  

loadFuseStatus 1.3.6.1.4.1.12148.10.9.7.1.1
The status of load fuse
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11)  

loadFuseDescription 1.3.6.1.4.1.12148.10.9.7.1.2
A textual description of the load fuse monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

loadFuseTrapRepeatCounter 1.3.6.1.4.1.12148.10.9.7.1.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

loadFuseAlarmEnable 1.3.6.1.4.1.12148.10.9.7.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadFuseValue 1.3.6.1.4.1.12148.10.9.7.1.5
The measured value of the load fuse.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadEnergyLogAccumulated 1.3.6.1.4.1.12148.10.9.8.1
This is the accumulated energy delivered to load.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.9.8.2
This is the maximal number of entries stored in load hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

loadEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.9.8.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadEnergyLogLastHoursEntry

loadEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.9.8.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadEnergyLogLastHoursEntry  

loadEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.9.8.3.1.1
Index used for navigating the rows 1..52 of loadEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

loadEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.9.8.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.9.8.4
This is the maximal number of entries stored in load daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

loadEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.9.8.5
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadEnergyLogLastDaysEntry

loadEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.9.8.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadEnergyLogLastDaysEntry  

loadEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.9.8.5.1.1
Index used for navigating the rows 1..52 of loadEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

loadEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.9.8.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.9.8.6
This is the maximal number of entries stored in load weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

loadEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.9.8.7
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadEnergyLogLastWeeksEntry

loadEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.9.8.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadEnergyLogLastWeeksEntry  

loadEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.9.8.7.1.1
Index used for navigating the rows 1..52 of loadEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

loadEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.9.8.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryStatus 1.3.6.1.4.1.12148.10.10.1
A toplevel status for the battery subsystem. The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data monitors' in the battery subsystem will propagate up to this status indicator.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryDescription 1.3.6.1.4.1.12148.10.10.2
A descriptive name of the battery installed in the system.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

batteryReferenceVoltage 1.3.6.1.4.1.12148.10.10.3
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 840..60417  

batteryFusesStatus 1.3.6.1.4.1.12148.10.10.4
The state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryVoltageStatus 1.3.6.1.4.1.12148.10.10.5.1
The status of the measured battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryVoltageDescription 1.3.6.1.4.1.12148.10.10.5.2
A textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryVoltageTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.5.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryVoltageAlarmEnable 1.3.6.1.4.1.12148.10.10.5.4
The measured battery voltage alarm enable/disable control
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryVoltageValue 1.3.6.1.4.1.12148.10.10.5.5
The value of the measured battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..7500  

batteryVoltageMajorHighLevel 1.3.6.1.4.1.12148.10.10.5.6
The Major High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryVoltageMinorHighLevel 1.3.6.1.4.1.12148.10.10.5.7
The Minor High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryVoltageMinorLowLevel 1.3.6.1.4.1.12148.10.10.5.8
The Minor Low Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryVoltageMajorLowLevel 1.3.6.1.4.1.12148.10.10.5.9
The Major Low Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryCurrentsStatus 1.3.6.1.4.1.12148.10.10.6.1
The status of the measured battery current
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryCurrentsDescription 1.3.6.1.4.1.12148.10.10.6.2
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryCurrentsTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.6.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryCurrentsAlarmEnable 1.3.6.1.4.1.12148.10.10.6.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryCurrentsValue 1.3.6.1.4.1.12148.10.10.6.5
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCurrentsMajorHighLevel 1.3.6.1.4.1.12148.10.10.6.6
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentsMinorHighLevel 1.3.6.1.4.1.12148.10.10.6.7
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentsMinorLowLevel 1.3.6.1.4.1.12148.10.10.6.8
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentsMajorLowLevel 1.3.6.1.4.1.12148.10.10.6.9
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperaturesStatus 1.3.6.1.4.1.12148.10.10.7.1
The state of the battery fuses/breakers can be either one of the defined enumerated values
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryTemperaturesDescription 1.3.6.1.4.1.12148.10.10.7.2
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryTemperaturesTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.7.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryTemperaturesAlarmEnable 1.3.6.1.4.1.12148.10.10.7.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryTemperaturesValue 1.3.6.1.4.1.12148.10.10.7.5
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..9999  

batteryTemperaturesMajorHighLevel 1.3.6.1.4.1.12148.10.10.7.6
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperaturesMinorHighLevel 1.3.6.1.4.1.12148.10.10.7.7
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperaturesMinorLowLevel 1.3.6.1.4.1.12148.10.10.7.8
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperaturesMajorLowLevel 1.3.6.1.4.1.12148.10.10.7.9
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTimeLeftStatus 1.3.6.1.4.1.12148.10.10.8.1
The status of the estimated battery remaining backup time.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryTimeLeftDescription 1.3.6.1.4.1.12148.10.10.8.2
A textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryTimeLeftTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.8.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryTimeLeftAlarmEnable 1.3.6.1.4.1.12148.10.10.8.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryTimeLeftValue 1.3.6.1.4.1.12148.10.10.8.5
The estimated value of battery remaining backup time.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTimeLeftMinorAlarmLevel 1.3.6.1.4.1.12148.10.10.8.6
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTimeLeftMajorAlarmLevel 1.3.6.1.4.1.12148.10.10.8.7
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryRemainingCapacityStatus 1.3.6.1.4.1.12148.10.10.9.1
The status of the battery remaining capacity monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryRemainingCapacityDescription 1.3.6.1.4.1.12148.10.10.9.2
A textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryRemainingCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.9.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryRemainingCapacityAlarmEnable 1.3.6.1.4.1.12148.10.10.9.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryRemainingCapacityValue 1.3.6.1.4.1.12148.10.10.9.5
Battery remaining capacity (SOC) value estimated from the latest battery test result.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryRemainingCapacityMinorLowLevel 1.3.6.1.4.1.12148.10.10.9.6
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryRemainingCapacityMajorLowLevel 1.3.6.1.4.1.12148.10.10.9.7
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryUsedCapacityStatus 1.3.6.1.4.1.12148.10.10.10.1
The status of the battery used capacity (DoD) monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryUsedCapacityDescription 1.3.6.1.4.1.12148.10.10.10.2
A textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryUsedCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.10.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryUsedCapacityAlarmEnable 1.3.6.1.4.1.12148.10.10.10.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryUsedCapacityValue 1.3.6.1.4.1.12148.10.10.10.5
This is the estimated battery used capacity (DoD).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryUsedCapacityMajorAlarmLevel 1.3.6.1.4.1.12148.10.10.10.6
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryUsedCapacityMinorAlarmLevel 1.3.6.1.4.1.12148.10.10.10.7
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTotalCapacityStatus 1.3.6.1.4.1.12148.10.10.11.1
The status of the total capacity monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryTotalCapacityDescription 1.3.6.1.4.1.12148.10.10.11.2
A textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryTotalCapacityTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.11.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryTotalCapacityAlarmEnable 1.3.6.1.4.1.12148.10.10.11.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryTotalCapacityValue 1.3.6.1.4.1.12148.10.10.11.5
This is the estimated total battery capacity (installed Ah - SoH) value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTotalCapacityMinorLowLevel 1.3.6.1.4.1.12148.10.10.11.6
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTotalCapacityMajorLowLevel 1.3.6.1.4.1.12148.10.10.11.7
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryQualityStatus 1.3.6.1.4.1.12148.10.10.12.1
The status of the battery quality (SoH) monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryQualityDescription 1.3.6.1.4.1.12148.10.10.12.2
A textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryQualityTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.12.3
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryQualityAlarmEnable 1.3.6.1.4.1.12148.10.10.12.4
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryQualityValue 1.3.6.1.4.1.12148.10.10.12.5
The calculated battery quality (SoH) based on the latest battery test
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryQualityMinorAlarmLevel 1.3.6.1.4.1.12148.10.10.12.6
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryQualityMajorAlarmLevel 1.3.6.1.4.1.12148.10.10.12.7
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLVBDStatus 1.3.6.1.4.1.12148.10.10.13.1
The Battery Contactor is connected, disconnected, disabled or in any other alarm condition
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryLVBDDescription 1.3.6.1.4.1.12148.10.10.13.2
A textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryLVBDTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.13.3
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryLVBDEnable 1.3.6.1.4.1.12148.10.10.13.4
This value once enabled, the alarm condition of the LVBD will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryLVBDValue 1.3.6.1.4.1.12148.10.10.13.5
The measured value of the LVBD.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryLVBDConnectVoltage 1.3.6.1.4.1.12148.10.10.13.6
The Battery Contactor's Reconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLVBDDisconnectVoltage 1.3.6.1.4.1.12148.10.10.13.7
The Battery Contactor's Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryChargeCurrentLimitEnable 1.3.6.1.4.1.12148.10.10.14.1
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryChargeCurrentLimitValue 1.3.6.1.4.1.12148.10.10.14.2
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..32767  

batteryBoostVoltage 1.3.6.1.4.1.12148.10.10.15.1
The Voltage at which the DC System boost charges the batteries.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 870..60418  

batteryBoostCommand 1.3.6.1.4.1.12148.10.10.15.2
This pushbutton will start or stop a manual battery boost if the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), startboost(1), stopboost(2)  

batteryBoostCurrentThreshold 1.3.6.1.4.1.12148.10.10.15.3
The boosting will terminate when the charge current drops below the BoostCurrentThreshold limit.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryBoostManualMaxDuration 1.3.6.1.4.1.12148.10.10.15.4
A protection against overcharging. When running manual boost, the boosting will always terminate at this point.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1440  

batteryTestVoltage 1.3.6.1.4.1.12148.10.10.16.1
This is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTestCommand 1.3.6.1.4.1.12148.10.10.16.2
This pushbutton will start or stop a manual battery test if the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), starttest(1), stoptest(2)  

batteryTestNumberOfResults 1.3.6.1.4.1.12148.10.10.16.3
This is the number of valid battery test results stored in controller.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..10  

batteryTestResultTable 1.3.6.1.4.1.12148.10.10.16.4
This table contains the battery test results stored in controller.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryTestResultEntry

batteryTestResultEntry 1.3.6.1.4.1.12148.10.10.16.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryTestResultEntry  

batteryTestResultIndex 1.3.6.1.4.1.12148.10.10.16.4.1.1
A index pointing to one of ten possible battery test results
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..10  

batteryTestResultStartDateTime 1.3.6.1.4.1.12148.10.10.16.4.1.2
This is the time and date when the test started.
Status: current Access: read-only
OBJECT-TYPE    
  DateAndTime  

batteryTestResultDuration 1.3.6.1.4.1.12148.10.10.16.4.1.3
This is the test duration in minutes.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTestResultDischarged 1.3.6.1.4.1.12148.10.10.16.4.1.4
This is the discharged Ah during test.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTestResultQuality 1.3.6.1.4.1.12148.10.10.16.4.1.5
This is the calculated battery quality (SoH)in percentage.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTempCompEnable 1.3.6.1.4.1.12148.10.10.17.1
Enable (1) or Disable (0) of Battery Temperature Compensated output regulation mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryBankNumberOfBanks 1.3.6.1.4.1.12148.10.10.18.1
Number of battery banks installed in system.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..8  

batteryBankTable 1.3.6.1.4.1.12148.10.10.18.2
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBankEntry

batteryBankEntry 1.3.6.1.4.1.12148.10.10.18.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBankEntry  

batteryBankIndex 1.3.6.1.4.1.12148.10.10.18.2.1.1
Index used for navigating the rows 1..8 of batteryBankTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

batteryBankStatus 1.3.6.1.4.1.12148.10.10.18.2.1.2
The overall status of battery bank
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryBankNumberOfTemperatures 1.3.6.1.4.1.12148.10.10.18.2.1.3
Number of temperature measurements in battery bank.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryBankNumberOfCurrents 1.3.6.1.4.1.12148.10.10.18.2.1.4
Number of current measurements in battery bank.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryBankNumberOfFuses 1.3.6.1.4.1.12148.10.10.18.2.1.5
Number of fuses installed in battery bank.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryBankTemperatureTable 1.3.6.1.4.1.12148.10.10.18.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBankTemperatureEntry

batteryBankTemperatureEntry 1.3.6.1.4.1.12148.10.10.18.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBankTemperatureEntry  

batteryTemperatureIndex 1.3.6.1.4.1.12148.10.10.18.3.1.1
This index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryTemperatureStatus 1.3.6.1.4.1.12148.10.10.18.3.1.2
The status of battery temperature monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryTemperatureDescription 1.3.6.1.4.1.12148.10.10.18.3.1.3
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryTemperatureTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.18.3.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryTemperatureAlarmEnable 1.3.6.1.4.1.12148.10.10.18.3.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryTemperatureValue 1.3.6.1.4.1.12148.10.10.18.3.1.6
The measured battery temperature.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTemperatureMajorHighLevel 1.3.6.1.4.1.12148.10.10.18.3.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperatureMinorHighLevel 1.3.6.1.4.1.12148.10.10.18.3.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperatureMinorLowLevel 1.3.6.1.4.1.12148.10.10.18.3.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryTemperatureMajorLowLevel 1.3.6.1.4.1.12148.10.10.18.3.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryBankCurrentTable 1.3.6.1.4.1.12148.10.10.18.4
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBankCurrentEntry

batteryBankCurrentEntry 1.3.6.1.4.1.12148.10.10.18.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBankCurrentEntry  

batteryCurrentIndex 1.3.6.1.4.1.12148.10.10.18.4.1.1
This index denotes which row in the current input table. The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryCurrentStatus 1.3.6.1.4.1.12148.10.10.18.4.1.2
The status of battery current monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryCurrentDescription 1.3.6.1.4.1.12148.10.10.18.4.1.3
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.18.4.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryCurrentAlarmEnable 1.3.6.1.4.1.12148.10.10.18.4.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryCurrentValue 1.3.6.1.4.1.12148.10.10.18.4.1.6
The measured battery current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCurrentMajorHighLevel 1.3.6.1.4.1.12148.10.10.18.4.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentMinorHighLevel 1.3.6.1.4.1.12148.10.10.18.4.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentMinorLowLevel 1.3.6.1.4.1.12148.10.10.18.4.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryCurrentMajorLowLevel 1.3.6.1.4.1.12148.10.10.18.4.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryBankFuseTable 1.3.6.1.4.1.12148.10.10.18.5
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBankFuseEntry

batteryBankFuseEntry 1.3.6.1.4.1.12148.10.10.18.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBankFuseEntry  

batteryFuseIndex 1.3.6.1.4.1.12148.10.10.18.5.1.1
This index denotes which row in the fuse table. The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryFuseStatus 1.3.6.1.4.1.12148.10.10.18.5.1.2
The status of battery fuse monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryFuseDescription 1.3.6.1.4.1.12148.10.10.18.5.1.3
A textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryFuseTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.18.5.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryFuseAlarmEnable 1.3.6.1.4.1.12148.10.10.18.5.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryFuseValue 1.3.6.1.4.1.12148.10.10.18.5.1.6
The measured value of battery fuse input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorsNumberOfUnits 1.3.6.1.4.1.12148.10.10.19.1
The number of battery monitor installed in system.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorsTable 1.3.6.1.4.1.12148.10.10.19.2
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMonitorsEntry

batteryMonitorsEntry 1.3.6.1.4.1.12148.10.10.19.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMonitorsEntry  

batteryMonitorIndex 1.3.6.1.4.1.12148.10.10.19.2.1.1
Index used for navigating the rows 1..8 of batteryMonitorsTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

batteryMonitorNumberOfTemperatures 1.3.6.1.4.1.12148.10.10.19.2.1.2
The number of temperature measurements in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryMonitorNumberOfCurrents 1.3.6.1.4.1.12148.10.10.19.2.1.3
The number of current measurements in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryMonitorNumberOfFuses 1.3.6.1.4.1.12148.10.10.19.2.1.4
The number of fuse measurements in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryMonitorNumberOfSymmetries 1.3.6.1.4.1.12148.10.10.19.2.1.5
The number of symmetry measurements in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

batteryMonitorTemperatureTable 1.3.6.1.4.1.12148.10.10.19.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMonitorTemperatureEntry

batteryMonitorTemperatureEntry 1.3.6.1.4.1.12148.10.10.19.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMonitorTemperatureEntry  

batteryMonitorTemperatureIndex 1.3.6.1.4.1.12148.10.10.19.3.1.1
This index denotes which row in the temperature input table. The size of the table is defined by the batteryMonitorNumberOfTemperatures
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryMonitorTemperatureStatus 1.3.6.1.4.1.12148.10.10.19.3.1.2
The status of battery temperature monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryMonitorTemperatureDescription 1.3.6.1.4.1.12148.10.10.19.3.1.3
A textual description of the battery monitor temperature. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryMonitorTemperatureTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.19.3.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryMonitorTemperatureAlarmEnable 1.3.6.1.4.1.12148.10.10.19.3.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryMonitorTemperatureValue 1.3.6.1.4.1.12148.10.10.19.3.1.6
The measured battery temperature in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorTemperatureMajorHighLevel 1.3.6.1.4.1.12148.10.10.19.3.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorTemperatureMinorHighLevel 1.3.6.1.4.1.12148.10.10.19.3.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorTemperatureMinorLowLevel 1.3.6.1.4.1.12148.10.10.19.3.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorTemperatureMajorLowLevel 1.3.6.1.4.1.12148.10.10.19.3.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentTable 1.3.6.1.4.1.12148.10.10.19.4
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMonitorCurrentEntry

batteryMonitorCurrentEntry 1.3.6.1.4.1.12148.10.10.19.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMonitorCurrentEntry  

batteryMonitorCurrentIndex 1.3.6.1.4.1.12148.10.10.19.4.1.1
This index denotes which row in the current input table. The size of the table is defined by the batteryMonitorNumberOfCurrents
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryMonitorCurrentStatus 1.3.6.1.4.1.12148.10.10.19.4.1.2
The status of battery current monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryMonitorCurrentDescription 1.3.6.1.4.1.12148.10.10.19.4.1.3
A textual description of the battery monitor current. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryMonitorCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.19.4.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryMonitorCurrentAlarmEnable 1.3.6.1.4.1.12148.10.10.19.4.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryMonitorCurrentValue 1.3.6.1.4.1.12148.10.10.19.4.1.6
The measured battery current in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentMajorHighLevel 1.3.6.1.4.1.12148.10.10.19.4.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentMinorHighLevel 1.3.6.1.4.1.12148.10.10.19.4.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentMinorLowLevel 1.3.6.1.4.1.12148.10.10.19.4.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentMajorLowLevel 1.3.6.1.4.1.12148.10.10.19.4.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorFuseTable 1.3.6.1.4.1.12148.10.10.19.5
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMonitorFuseEntry

batteryMonitorFuseEntry 1.3.6.1.4.1.12148.10.10.19.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMonitorFuseEntry  

batteryMonitorFuseIndex 1.3.6.1.4.1.12148.10.10.19.5.1.1
This index denotes which row in the fuse table. The size of the table is defined by the batteryMonitorNumberOfFuses
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

batteryMonitorFuseStatus 1.3.6.1.4.1.12148.10.10.19.5.1.2
The status of battery fuse monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryMonitorFuseDescription 1.3.6.1.4.1.12148.10.10.19.5.1.3
A textual description of the battery monitor fuse. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryMonitorFuseTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.19.5.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryMonitorFuseAlarmEnable 1.3.6.1.4.1.12148.10.10.19.5.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryMonitorFuseValue 1.3.6.1.4.1.12148.10.10.19.5.1.6
The measured value of battery fuse in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetryTable 1.3.6.1.4.1.12148.10.10.19.6
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMonitorSymmetryEntry

batteryMonitorSymmetryEntry 1.3.6.1.4.1.12148.10.10.19.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMonitorSymmetryEntry  

batteryMonitorSymmetryIndex 1.3.6.1.4.1.12148.10.10.19.6.1.1
This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

batteryMonitorSymmetryStatus 1.3.6.1.4.1.12148.10.10.19.6.1.2
The status of battery symmetry monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

batteryMonitorSymmetryDescription 1.3.6.1.4.1.12148.10.10.19.6.1.3
A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryMonitorSymmetryTrapRepeatCounter 1.3.6.1.4.1.12148.10.10.19.6.1.4
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

batteryMonitorSymmetryAlarmEnable 1.3.6.1.4.1.12148.10.10.19.6.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

batteryMonitorSymmetryMeasureValue 1.3.6.1.4.1.12148.10.10.19.6.1.6
The measured battery symmetry voltage in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetryDeltaValue 1.3.6.1.4.1.12148.10.10.19.6.1.7
The measured battery symmetry delta voltage in battery monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetryMajorAlarmLevel 1.3.6.1.4.1.12148.10.10.19.6.1.8
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetryMinorAlarmLevel 1.3.6.1.4.1.12148.10.10.19.6.1.9
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryEnergyLogAccumulated 1.3.6.1.4.1.12148.10.10.20.1
This is the accumulated energy delivered to/from battery.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.10.20.2
This is the maximal number of entries stored in battery hourly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.10.20.3
This table contains hourly energy log of battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryEnergyLogLastHoursEntry

batteryEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.10.20.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryEnergyLogLastHoursEntry  

batteryEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.10.20.3.1.1
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.10.20.3.1.2
Energy value logged every hour.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.10.20.4
This is the maximal number of entries stored in battery daily energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.10.20.5
This table contains daily energy log of battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryEnergyLogLastDaysEntry

batteryEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.10.20.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryEnergyLogLastDaysEntry  

batteryEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.10.20.5.1.1
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.10.20.5.1.2
Energy value logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.10.20.6
This is the maximal number of entries stored in battery weekly energy log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.10.20.7
This table contains weekly energy log of battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryEnergyLogLastWeeksEntry

batteryEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.10.20.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryEnergyLogLastWeeksEntry  

batteryEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.10.20.7.1.1
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.10.20.7.1.2
Energy value logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCycleLogTotalCycles 1.3.6.1.4.1.12148.10.10.21.1
This is the total number of battery discharge cycles.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCycleLogDaysNumberOfEntries 1.3.6.1.4.1.12148.10.10.21.2
This is the maximal number of entries stored in daily battery discharge cycle log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryCycleLogDaysTable 1.3.6.1.4.1.12148.10.10.21.3
This table contains daily battery discharge cycle log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryCycleLogDaysEntry

batteryCycleLogDaysEntry 1.3.6.1.4.1.12148.10.10.21.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryCycleLogDaysEntry  

batteryCycleLogDaysIndex 1.3.6.1.4.1.12148.10.10.21.3.1.1
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryCycleLogDaysValue 1.3.6.1.4.1.12148.10.10.21.3.1.2
Number of discharge cycles logged every day.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCycleLogWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.10.21.4
This is the maximal number of entries stored in weeky battery discharge cycle log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryCycleLogWeeksTable 1.3.6.1.4.1.12148.10.10.21.5
This table contains weekly battery discharge cycle log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryCycleLogWeeksEntry

batteryCycleLogWeeksEntry 1.3.6.1.4.1.12148.10.10.21.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryCycleLogWeeksEntry  

batteryCycleLogWeeksIndex 1.3.6.1.4.1.12148.10.10.21.5.1.1
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryCycleLogWeeksValue 1.3.6.1.4.1.12148.10.10.21.5.1.2
Number of discharge cycles logged every week.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCycleLogMonthsNumberOfEntries 1.3.6.1.4.1.12148.10.10.21.6
This is the maximal number of entries stored in monthly battery discharge cycle log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

batteryCycleLogMonthsTable 1.3.6.1.4.1.12148.10.10.21.7
This table contains monthly battery discharge cycle log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryCycleLogMonthsEntry

batteryCycleLogMonthsEntry 1.3.6.1.4.1.12148.10.10.21.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryCycleLogMonthsEntry  

batteryCycleLogMonthsIndex 1.3.6.1.4.1.12148.10.10.21.7.1.1
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

batteryCycleLogMonthsValue 1.3.6.1.4.1.12148.10.10.21.7.1.2
Number of discharge cycles logged every month.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inputControlUnitsTable 1.3.6.1.4.1.12148.10.11.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InputControlUnitsEntry

inputControlUnitsEntry 1.3.6.1.4.1.12148.10.11.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  InputControlUnitsEntry  

inputControlUnitIndex 1.3.6.1.4.1.12148.10.11.1.1.1
Index used for navigating the rows of inputControlUnitTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

inputControlUnitNumberOfInputs 1.3.6.1.4.1.12148.10.11.1.1.2
Number of programmable inputs available in controller.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

inputControlUnitInputTable 1.3.6.1.4.1.12148.10.11.2
This table contains the status of the programmable inputs for Control Units.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InputControlUnitInputEntry

inputControlUnitInputEntry 1.3.6.1.4.1.12148.10.11.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  InputControlUnitInputEntry  

inputControlUnitInputIndex 1.3.6.1.4.1.12148.10.11.2.1.1
Index used for navigating the rows of inputControlUnitInputTable The size of the table is defined by the inputControlUnitNumberOfInputs
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

inputControlUnitInputStatus 1.3.6.1.4.1.12148.10.11.2.1.2
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

inputControlUnitInputDescription 1.3.6.1.4.1.12148.10.11.2.1.3
A textual description of the programmable input. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

inputControlUnitInputTrapRepeatCounter 1.3.6.1.4.1.12148.10.11.2.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

inputControlUnitInputAlarmEnable 1.3.6.1.4.1.12148.10.11.2.1.5
This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

inputControlUnitInputValue 1.3.6.1.4.1.12148.10.11.2.1.6
The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value. Note: This value can only be set for virtual input on SP2 master or Smartpack S. When this value is set to '0', the input is deactivated; When this value is set to '1', the input is activated; if set to any other value, an Inconsistent Value error will be generated.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inputControlUnitInputConfiguration 1.3.6.1.4.1.12148.10.11.2.1.7
Configuration of the input type. Configurations available for different controllers are as follows: SP2 Master(clock, virtual), SP2 Basic(normally open, normally close),Compack(normally open, normallly close, diode matrix, voltage, clock)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4), clock(5), virtual(6)  

inputIoUnitsTable 1.3.6.1.4.1.12148.10.11.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InputIoUnitsEntry

inputIoUnitsEntry 1.3.6.1.4.1.12148.10.11.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  InputIoUnitsEntry  

inputIoUnitIndex 1.3.6.1.4.1.12148.10.11.3.1.1
Index used for navigating the rows of inputIoUnitsTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

inputIoUnitNumberOfInputs 1.3.6.1.4.1.12148.10.11.3.1.2
Number of programmable inputs available in IO unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

inputIoUnitProgInputTable 1.3.6.1.4.1.12148.10.11.4
This table contains the status of the programmable inputs for I/O monitor units. .
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InputIoUnitProgInputEntry

inputIoUnitProgInputEntry 1.3.6.1.4.1.12148.10.11.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  InputIoUnitProgInputEntry  

inputIoUnitProgInputIndex 1.3.6.1.4.1.12148.10.11.4.1.1
The Index to the Input of the selected I/O monitor unit. Or the input number if you like.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..6  

inputIoUnitProgInputStatus 1.3.6.1.4.1.12148.10.11.4.1.2
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

inputIoUnitProgInputDescription 1.3.6.1.4.1.12148.10.11.4.1.3
A textual description of the programmable input in IO unit. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

inputIoUnitProgInputTrapRepeatCounter 1.3.6.1.4.1.12148.10.11.4.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

inputIoUnitProgInputAlarmEnable 1.3.6.1.4.1.12148.10.11.4.1.5
This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

inputIoUnitProgInputValue 1.3.6.1.4.1.12148.10.11.4.1.6
The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inputIoUnitProgInputConfiguration 1.3.6.1.4.1.12148.10.11.4.1.7
Configuration of the input type. Configurations available for IO unit are normally open, normally closed, diode matrix, voltage.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4)  

outputControlUnitTable 1.3.6.1.4.1.12148.10.12.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputControlUnitEntry

outputControlUnitEntry 1.3.6.1.4.1.12148.10.12.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  OutputControlUnitEntry  

outputControlUnitIndex 1.3.6.1.4.1.12148.10.12.1.1.1
Index used for navigating the rows of outputControlUnitTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

outputControlUnitNumberOfOutputs 1.3.6.1.4.1.12148.10.12.1.1.2
Number of outputs available in controller.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

outputControlUnitOutputTable 1.3.6.1.4.1.12148.10.12.2
This table contains the status of the outputs for Control Units.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputControlUnitOutputEntry

outputControlUnitOutputEntry 1.3.6.1.4.1.12148.10.12.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  OutputControlUnitOutputEntry  

outputControlUnitOutputIndex 1.3.6.1.4.1.12148.10.12.2.1.1
Index used for navigating the rows of outputControlUnitoutputTable The size of the table is defined by the outputControlUnitNumberOfOutputs
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

outputControlUnitOutputStatus 1.3.6.1.4.1.12148.10.12.2.1.2
General output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have values 'disconnected' or 'connected'
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notenergized(0), energized(1), disconnected(2), connected(3)  

outputControlUnitOutputDescription 1.3.6.1.4.1.12148.10.12.2.1.3
A textual description of the output. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

outputIoUnitTable 1.3.6.1.4.1.12148.10.12.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputIoUnitEntry

outputIoUnitEntry 1.3.6.1.4.1.12148.10.12.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  OutputIoUnitEntry  

outputIoUnitIndex 1.3.6.1.4.1.12148.10.12.3.1.1
Index used for navigating the rows of outputIoUnitTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

outputIoUnitNumberOfOutputs 1.3.6.1.4.1.12148.10.12.3.1.2
Number of outputs available in IO unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

outputIoUnitOutputTable 1.3.6.1.4.1.12148.10.12.4
This table contains the status of the outputs for IO Units.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputIoUnitOutputEntry

outputIoUnitOutputEntry 1.3.6.1.4.1.12148.10.12.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  OutputIoUnitOutputEntry  

outputIoUnitOutputIndex 1.3.6.1.4.1.12148.10.12.4.1.1
Index used for navigating the rows of outputIOUnitOutputTable The size of the table is defined by the outputIOUnitNumberOfOutputs
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

outputIoUnitOutputStatus 1.3.6.1.4.1.12148.10.12.4.1.2
General output relays may be 'energized' or 'not energized'. Latched contactors may have values 'disconnected' or 'connected'
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notenergized(0), energized(1), disconnected(2), connected(3)  

outputIoUnitOutputDescription 1.3.6.1.4.1.12148.10.12.4.1.3
A textual description of the output in IO unit. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

controlSystemStatus 1.3.6.1.4.1.12148.10.13.1
The overall status of control system subsystem
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

controlSystemClock 1.3.6.1.4.1.12148.10.13.2
This is the system time.
Status: current Access: read-write
OBJECT-TYPE    
  DateAndTime Size(8..11)  

controlSystemNumberOfControlUnits 1.3.6.1.4.1.12148.10.13.3
Total number of controllers (SP2 Basic, Compack, Smartpack S, Smartpack)
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..14  

snmpSendOffTraps 1.3.6.1.4.1.12148.10.13.4.1
When this is enabled, a trap is sent when a alarm condition goes off .
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

snmpTrapRepeatRate 1.3.6.1.4.1.12148.10.13.4.2
The time between every repeated trap when an alarm condition is on. To turn repetetive traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1440  

snmpHeartBeatTrapRepeatRate 1.3.6.1.4.1.12148.10.13.4.3
The time between every heartbeat trap when an alarm condition is on. To turn heartbeat traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1440  

snmpInhibitTraps 1.3.6.1.4.1.12148.10.13.4.4
When this is enabled, no trap is sent regardless of alarm conditions.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

controlSystemResetManualAlarms 1.3.6.1.4.1.12148.10.13.5
Reset manual alarms and put buzzer into silence.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), resetalarm(1)  

controlSystemResetNumberOfModules 1.3.6.1.4.1.12148.10.13.6
If set to '1', the number of modules (rectifier, solar charger, wind charger, control units, etc.) will be reset, and only those modules communicating are counted.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), resetnumber(1)  

controlSystemIoUnitsNumberOfUnits 1.3.6.1.4.1.12148.10.13.7.1
This is the number of IO units installed in the system.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..14  

controlSystemIoUnitsTable 1.3.6.1.4.1.12148.10.13.7.2
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ControlSystemIoUnitsEntry

controlSystemIoUnitsEntry 1.3.6.1.4.1.12148.10.13.7.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  ControlSystemIoUnitsEntry  

controlSystemIoUnitIndex 1.3.6.1.4.1.12148.10.13.7.2.1.1
Index used for navigating the rows of controlSystemIoUnitTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

controlSystemIoUnitNumberOfTemperatures 1.3.6.1.4.1.12148.10.13.7.2.1.2
Number of temperature measurements available in IO unit
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

controlSystemIoUnitNumberOfFans 1.3.6.1.4.1.12148.10.13.7.2.1.3
Number of fan measurements available in IO unit
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

controlSystemIoUnitTemperatureTable 1.3.6.1.4.1.12148.10.13.7.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ControlSystemIoUnitTemperatureEntry

controlSystemIoUnitTemperatureEntry 1.3.6.1.4.1.12148.10.13.7.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  ControlSystemIoUnitTemperatureEntry  

controlSystemIoUnitTemperatureIndex 1.3.6.1.4.1.12148.10.13.7.3.1.1
Index used for navigating the rows of controlSystemIoUnitTemperatureTable The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..2  

controlSystemIoUnitTemperatureStatus 1.3.6.1.4.1.12148.10.13.7.3.1.2
The status of temperature monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

controlSystemIoUnitTemperatureDescription 1.3.6.1.4.1.12148.10.13.7.3.1.3
A textual description of the temperature monitor in control system. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

controlSystemIoUnitTemperatureTrapRepeatCounter 1.3.6.1.4.1.12148.10.13.7.3.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

controlSystemIoUnitTemperatureAlarmEnable 1.3.6.1.4.1.12148.10.13.7.3.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

controlSystemIoUnitTemperatureValue 1.3.6.1.4.1.12148.10.13.7.3.1.6
The measured temperature value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitTemperatureMajorHighLevel 1.3.6.1.4.1.12148.10.13.7.3.1.7
The major high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitTemperatureMinorHighLevel 1.3.6.1.4.1.12148.10.13.7.3.1.8
The minor high alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitTemperatureMinorLowLevel 1.3.6.1.4.1.12148.10.13.7.3.1.9
The minor low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitTemperatureMajorLowLevel 1.3.6.1.4.1.12148.10.13.7.3.1.10
The major low alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitFanTable 1.3.6.1.4.1.12148.10.13.7.4
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ControlSystemIoUnitFanEntry

controlSystemIoUnitFanEntry 1.3.6.1.4.1.12148.10.13.7.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  ControlSystemIoUnitFanEntry  

controlSystemIoUnitFanIndex 1.3.6.1.4.1.12148.10.13.7.4.1.1
Index used for navigating the rows 1..2 of ioUnitFan Table
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..2  

controlSystemIoUnitFanSpeedValue 1.3.6.1.4.1.12148.10.13.7.4.1.2
The measured fan speed
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitFanSpeedDeviation 1.3.6.1.4.1.12148.10.13.7.4.1.3
The measured fan speed deviation
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

controlSystemIoUnitFanControl 1.3.6.1.4.1.12148.10.13.7.4.1.4
Fan speed control value in percentage
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

controlUnitNumberOfUnits 1.3.6.1.4.1.12148.10.13.8.1
Total number of control units installed in system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..254  

controlUnitTable 1.3.6.1.4.1.12148.10.13.8.2
A table containing an inventory listing. Each row represent one of the system hardware unit that is connected to the can bus. These units are system controllers, battery monitors, I/O units, AC Mains Monitor boxes and load monitors. Due to the system architechture the tables index are not contiguous. Each unit type har its own address range on the can bus. All unit types except the system controller may contain from 0 to 14 units. The system controlller can never be zero. Then there is no powersystem.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ControlUnitEntry

controlUnitEntry 1.3.6.1.4.1.12148.10.13.8.2.1
One row in the table containing all hardware units connected to the canbus.
Status: current Access: not-accessible
OBJECT-TYPE    
  ControlUnitEntry  

controlUnitIndex 1.3.6.1.4.1.12148.10.13.8.2.1.1
Index used for navigating the rows of controlUnitTable The size of the table is defined by the controlUnitNumberOfUnits
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..254  

controlUnitDescription 1.3.6.1.4.1.12148.10.13.8.2.1.2
A textual description of the control unit
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

controlUnitStatus 1.3.6.1.4.1.12148.10.13.8.2.1.3
The overall status of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

controlUnitSerialNumber 1.3.6.1.4.1.12148.10.13.8.2.1.4
Serial number of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

controlUnitHwPartNumber 1.3.6.1.4.1.12148.10.13.8.2.1.5
Hardware part number of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

controlUnitHwVersion 1.3.6.1.4.1.12148.10.13.8.2.1.6
Hardware version of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..20)  

controlUnitSwPartNumber 1.3.6.1.4.1.12148.10.13.8.2.1.7
Software part number of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..12)  

controlUnitSwVersion 1.3.6.1.4.1.12148.10.13.8.2.1.8
Software version of the control unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..20)  

currentMonitorsNumberOfUnits 1.3.6.1.4.1.12148.10.13.9.1
This is the number of current monitors installed in the system.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..14  

currentMonitorsTable 1.3.6.1.4.1.12148.10.13.9.2
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorsEntry

currentMonitorsEntry 1.3.6.1.4.1.12148.10.13.9.2.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorsEntry  

currentMonitorIndex 1.3.6.1.4.1.12148.10.13.9.2.1.1
Index used for navigating the rows of currentMonitorsTable The size of the table is defined by the system
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..14  

currentMonitorType 1.3.6.1.4.1.12148.10.13.9.2.1.2
This shows if the current monitor is configured as standard load monitor (1), load current monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5), wind current monitor (6) or fuel cell current monitor (7).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER stdLoadMonitor(1), loadCurrMonitor(2), rectCurrMonitor(3), dcdcCurrMonitor(4), solarCurrMonitor(5), windCurrMonitor(6), fuelcellCurrMonitor(7)  

currentMonitorId 1.3.6.1.4.1.12148.10.13.9.2.1.3
This is the unit index for each current monitor type.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorNumberOfFuses 1.3.6.1.4.1.12148.10.13.9.2.1.4
Number of fuse measurements in current monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

currentMonitorNumberOfCurrents 1.3.6.1.4.1.12148.10.13.9.2.1.5
Number of current measurements in current monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

currentMonitorFuseTable 1.3.6.1.4.1.12148.10.13.9.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorFuseEntry

currentMonitorFuseEntry 1.3.6.1.4.1.12148.10.13.9.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorFuseEntry  

currentMonitorFuseIndex 1.3.6.1.4.1.12148.10.13.9.3.1.1
Index used for navigating the rows of currentMonitorFuseTable The size of the table is defined by the currentMonitorNumberOfFuses
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

currentMonitorFuseStatus 1.3.6.1.4.1.12148.10.13.9.3.1.2
The status of fuse in current monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

currentMonitorFuseDescription 1.3.6.1.4.1.12148.10.13.9.3.1.3
A textual description of the fuse monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..16)  

currentMonitorFuseTrapRepeatCounter 1.3.6.1.4.1.12148.10.13.9.3.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

currentMonitorFuseAlarmEnable 1.3.6.1.4.1.12148.10.13.9.3.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

currentMonitorFuseValue 1.3.6.1.4.1.12148.10.13.9.3.1.6
The measured fuse value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorCurrentTable 1.3.6.1.4.1.12148.10.13.9.4
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorCurrentEntry

currentMonitorCurrentEntry 1.3.6.1.4.1.12148.10.13.9.4.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorCurrentEntry  

currentMonitorCurrentIndex 1.3.6.1.4.1.12148.10.13.9.4.1.1
Index used for navigating the rows of currentMonitorCurrentTable The size of the table is defined by the currentMonitorNumberOfCurrents
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..8  

currentMonitorCurrentStatus 1.3.6.1.4.1.12148.10.13.9.4.1.2
The status of current in current monitor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)  

currentMonitorCurrentDescription 1.3.6.1.4.1.12148.10.13.9.4.1.3
A textual description of the current monitor. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

currentMonitorCurrentTrapRepeatCounter 1.3.6.1.4.1.12148.10.13.9.4.1.4
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

currentMonitorCurrentAlarmEnable 1.3.6.1.4.1.12148.10.13.9.4.1.5
This value once enabled, the alarm condition of the monitor will be reported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

currentMonitorCurrentValue 1.3.6.1.4.1.12148.10.13.9.4.1.6
The measured current value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorCurrentMajorAlarmLevel 1.3.6.1.4.1.12148.10.13.9.4.1.7
The major alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

currentMonitorCurrentMinorAlarmLevel 1.3.6.1.4.1.12148.10.13.9.4.1.8
The minor alarm limit
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

currentMonitorEnergyLogAccumulatedTable 1.3.6.1.4.1.12148.10.13.9.5
This table contains the accumulated energy consumption measured in current monitor
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorEnergyLogAccumulatedEntry

currentMonitorEnergyLogAccumulatedEntry 1.3.6.1.4.1.12148.10.13.9.5.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorEnergyLogAccumulatedEntry  

currentMonitorEnergyLogAccumulated 1.3.6.1.4.1.12148.10.13.9.5.1.1
The accumulated energy consumption value
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorEnergyLogLastHoursNumberOfEntries 1.3.6.1.4.1.12148.10.13.9.6
This is the maximal number of entries stored in hourly energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

currentMonitorEnergyLogLastHoursTable 1.3.6.1.4.1.12148.10.13.9.7
This table contains energy consumption values logged every hour in current monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorEnergyLogLastHoursEntry

currentMonitorEnergyLogLastHoursEntry 1.3.6.1.4.1.12148.10.13.9.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorEnergyLogLastHoursEntry  

currentMonitorEnergyLogLastHoursIndex 1.3.6.1.4.1.12148.10.13.9.7.1.1
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

currentMonitorEnergyLogLastHoursValue 1.3.6.1.4.1.12148.10.13.9.7.1.2
Energy consumption value logged every hour in current monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorEnergyLogLastDaysNumberOfEntries 1.3.6.1.4.1.12148.10.13.9.8
This is the maximal number of entries stored in daily energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

currentMonitorEnergyLogLastDaysTable 1.3.6.1.4.1.12148.10.13.9.9
This table contains energy consumption values logged every day in current monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorEnergyLogLastDaysEntry

currentMonitorEnergyLogLastDaysEntry 1.3.6.1.4.1.12148.10.13.9.9.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorEnergyLogLastDaysEntry  

currentMonitorEnergyLogLastDaysIndex 1.3.6.1.4.1.12148.10.13.9.9.1.1
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

currentMonitorEnergyLogLastDaysValue 1.3.6.1.4.1.12148.10.13.9.9.1.2
Energy consumption value logged every day in current monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

currentMonitorEnergyLogLastWeeksNumberOfEntries 1.3.6.1.4.1.12148.10.13.9.10
This is the maximal number of entries stored in weekly energy log
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..52  

currentMonitorEnergyLogLastWeeksTable 1.3.6.1.4.1.12148.10.13.9.11
This table contains energy consumption values logged every week in current monitor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CurrentMonitorEnergyLogLastWeeksEntry

currentMonitorEnergyLogLastWeeksEntry 1.3.6.1.4.1.12148.10.13.9.11.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  CurrentMonitorEnergyLogLastWeeksEntry  

currentMonitorEnergyLogLastWeeksIndex 1.3.6.1.4.1.12148.10.13.9.11.1.1
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..52  

currentMonitorEnergyLogLastWeeksValue 1.3.6.1.4.1.12148.10.13.9.11.1.2
Energy consumption value logged every week in current monitor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

alarmGroupTable 1.3.6.1.4.1.12148.10.14.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AlarmGroupEntry

alarmGroupEntry 1.3.6.1.4.1.12148.10.14.1.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  AlarmGroupEntry  

alarmGroupIndex 1.3.6.1.4.1.12148.10.14.1.1.1
Index used for navigating the rows 1..49 of alarmGroupTable
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..49  

alarmGroupStatus 1.3.6.1.4.1.12148.10.14.1.1.2
The status of alarm group
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmGroupDescription 1.3.6.1.4.1.12148.10.14.1.1.3
A textual description of the alarm group. This is stored in the system controller and can be changed by the user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..16)  

powerSystemTrapsGroup 1.3.6.1.4.1.12148.10.1.3
The powerSystem Trap goup. Entry point for the trap list.
Status: current Access: read-write
NOTIFICATION-GROUP