SOCOMECUPS-MIB

File: SOCOMECUPS-MIB.mib (80647 bytes)

Imported modules

SNMPv2-TC RFC1155-SMI RFC-1212
RFC1213-MIB RFC-1215

Imported symbols

DisplayString TimeStamp TimeInterval
TestAndIncr AutonomousType IpAddress
enterprises OBJECT-TYPE DisplayString
TRAP-TYPE

Defined Types

PositiveInteger  
INTEGER 1..2147483647    

NonNegativeInteger  
INTEGER 1..2147483647    

UpsInputEntry  
SEQUENCE    
  upsInputLineIndex INTEGER
  upsInputVoltage INTEGER
  upsInputCurrent INTEGER
  upsInputVoltageMax INTEGER
  upsInputVoltageMin INTEGER

UpsOutputEntry  
SEQUENCE    
  upsOutputLineIndex INTEGER
  upsOutputVoltage INTEGER
  upsOutputCurrent INTEGER
  upsOutputPercentLoad INTEGER
  upsOutputKva INTEGER

UpsBypassEntry  
SEQUENCE    
  upsBypassLineIndex INTEGER
  upsBypassVoltage INTEGER
  upsBypassCurrent INTEGER

UpsAlarmEntry  
SEQUENCE    
  upsAlarmId PositiveInteger
  upsAlarmDescr AutonomousType
  upsAlarmTime TimeStamp
  upsAlarmExtDes DisplayString

ShutdownParametersEntry  
SEQUENCE    
  upsControlEventDescr DisplayString
  upsControlEventStatus INTEGER
  upsControlDelay INTEGER
  upsControlFirstWarning INTEGER
  upsControlWarningInterval INTEGER
  upsControlSeverity INTEGER

UpsControlWeeklyScheduleEntry  
SEQUENCE    
  upsControlWeeklyIndex INTEGER
  upsControlWeeklyShutdownDay INTEGER
  upsControlWeeklyShutdownTime DisplayString
  upsControlWeeklyRestartDay INTEGER
  upsControlWeeklyRestartTime DisplayString

UpsControlSpecialScheduleEntry  
SEQUENCE    
  upsControlSpecialIndex INTEGER
  upsControlSpecialShutdownDay DisplayString
  upsControlSpecialShutdownTime DisplayString
  upsControlSpecialRestartDay DisplayString
  upsControlSpecialRestartTime DisplayString

UpsControlEcoModeScheduleEntry  
SEQUENCE    
  upsControlEcoModeIndex INTEGER
  upsControlEcoModeStartDay INTEGER
  upsControlEcoModeStartTime DisplayString
  upsControlEcoModeEndDay INTEGER
  upsControlEcoModeEndTime DisplayString

UpsDevicesEntry  
SEQUENCE    
  indexOfDevice INTEGER
  addrOfDevice IpAddress
  nameOfDevice DisplayString
  timeOfConnection DisplayString
  statusOfConnection INTEGER
  severityOfConnection INTEGER

UpsAgentTrapsReceiversEntry  
SEQUENCE    
  trapsIndex INTEGER
  trapsReceiverAddr DisplayString
  receiverCommunityString DisplayString
  receiverDescription DisplayString

UpsAgentAccessControlEntry  
SEQUENCE    
  accessIndex INTEGER
  accessControlAddr DisplayString
  accessCommunityString DisplayString
  accessControlMode INTEGER

Defined Values

socomecSicon 1.3.6.1.4.1.4555
OBJECT IDENTIFIER    

software 1.3.6.1.4.1.4555.1
OBJECT IDENTIFIER    

network 1.3.6.1.4.1.4555.1.1
OBJECT IDENTIFIER    

netvision 1.3.6.1.4.1.4555.1.1.1
OBJECT IDENTIFIER    

upsObjects 1.3.6.1.4.1.4555.1.1.1.1
OBJECT IDENTIFIER    

upsTraps 1.3.6.1.4.1.4555.1.1.1.2
OBJECT IDENTIFIER    

upsIdent 1.3.6.1.4.1.4555.1.1.1.1.1
OBJECT IDENTIFIER    

upsBattery 1.3.6.1.4.1.4555.1.1.1.1.2
OBJECT IDENTIFIER    

upsInput 1.3.6.1.4.1.4555.1.1.1.1.3
OBJECT IDENTIFIER    

upsOutput 1.3.6.1.4.1.4555.1.1.1.1.4
OBJECT IDENTIFIER    

upsBypass 1.3.6.1.4.1.4555.1.1.1.1.5
OBJECT IDENTIFIER    

upsAlarm 1.3.6.1.4.1.4555.1.1.1.1.6
OBJECT IDENTIFIER    

upsTest 1.3.6.1.4.1.4555.1.1.1.1.7
OBJECT IDENTIFIER    

upsControl 1.3.6.1.4.1.4555.1.1.1.1.8
OBJECT IDENTIFIER    

upsConfig 1.3.6.1.4.1.4555.1.1.1.1.9
OBJECT IDENTIFIER    

upsAgent 1.3.6.1.4.1.4555.1.1.1.1.10
OBJECT IDENTIFIER    

emdStatus 1.3.6.1.4.1.4555.1.1.1.1.11
OBJECT IDENTIFIER    

upsIdentModel 1.3.6.1.4.1.4555.1.1.1.1.1.1
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsIdentUPSFirmwareVersion 1.3.6.1.4.1.4555.1.1.1.1.1.2
The UPS firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsIdentAgentSoftwareVersion 1.3.6.1.4.1.4555.1.1.1.1.1.3
The UPS Net Vision software version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdentUpsSerialNumber 1.3.6.1.4.1.4555.1.1.1.1.1.4
The UPS serial no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsBatteryStatus 1.3.6.1.4.1.4555.1.1.1.1.2.1
The present battery status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), upsOff(7)  

upsSecondsOnBattery 1.3.6.1.4.1.4555.1.1.1.1.2.2
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEstimatedMinutesRemaining 1.3.6.1.4.1.4555.1.1.1.1.2.3
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEstimatedChargeRemaining 1.3.6.1.4.1.4555.1.1.1.1.2.4
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryVoltage 1.3.6.1.4.1.4555.1.1.1.1.2.5
The magnitude of the present battery voltage in 0.1 Volt DC.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatteryTemperature 1.3.6.1.4.1.4555.1.1.1.1.2.6
The ambient temperature at or near the UPS Battery casing.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputNumLines 1.3.6.1.4.1.4555.1.1.1.1.3.1
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputFrequency 1.3.6.1.4.1.4555.1.1.1.1.3.2
The current input frequency to the UPS system in 0.1 HZ.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputTable 1.3.6.1.4.1.4555.1.1.1.1.3.3
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputEntry

upsInputEntry 1.3.6.1.4.1.4555.1.1.1.1.3.3.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsInputEntry  

upsInputLineIndex 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsInputVoltage 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2
The input utility line voltage in 0.1 volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputCurrent 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3
The magnitude of the present input current in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputVoltageMax 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4
The maximum utility line voltage in 0.1 VAC for last 1 minute.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInputVoltageMin 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5
The minimum utility line voltage in 0.1 VAC for last 1 minute.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputSource 1.3.6.1.4.1.4555.1.1.1.1.4.1
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), onInverter(2), onMains(3), ecoMode(4), onBypass(5), standby(6), onMaintenanceBypass(7), upsOff(8), normalMode(9)  

upsOutputFrequency 1.3.6.1.4.1.4555.1.1.1.1.4.2
The current output frequency of the UPS system in 0.1 of HZ.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputNumLines 1.3.6.1.4.1.4555.1.1.1.1.4.3
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputTable 1.3.6.1.4.1.4555.1.1.1.1.4.4
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputEntry

upsOutputEntry 1.3.6.1.4.1.4555.1.1.1.1.4.4.1
An entry containing information applicable to a particular output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsOutputEntry  

upsOutputLineIndex 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1
The output line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsOutputVoltage 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2
The output voltage of the UPS system in 0.1 volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputCurrent 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3
The output current of the UPS system in 0.1 Amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputPercentLoad 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutputKva 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5
Output KVA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassFrequency 1.3.6.1.4.1.4555.1.1.1.1.5.1
The present bypass frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassNumLines 1.3.6.1.4.1.4555.1.1.1.1.5.2
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassTable 1.3.6.1.4.1.4555.1.1.1.1.5.3
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBypassEntry

upsBypassEntry 1.3.6.1.4.1.4555.1.1.1.1.5.3.1
An entry containing information applicable to a particular bypass input.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBypassEntry  

upsBypassLineIndex 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1
The bypass line identifier.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsBypassVoltage 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2
The present bypass voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBypassCurrent 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3
The present bypass current.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmsPresent 1.3.6.1.4.1.4555.1.1.1.1.6.1
The present number of active alarm conditions.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmTable 1.3.6.1.4.1.4555.1.1.1.1.6.2
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAlarmEntry

upsAlarmEntry 1.3.6.1.4.1.4555.1.1.1.1.6.2.1
An entry containing information applicable to a particular alarm.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAlarmEntry  

upsAlarmId 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1
A unique identifier for an alarm condition. This value must remain constant.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsAlarmDescr 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
Status: mandatory Access: read-only
OBJECT-TYPE    
  AutonomousType  

upsAlarmTime 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

upsAlarmExtDes 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4
Extra description.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsWellKnownAlarms 1.3.6.1.4.1.4555.1.1.1.1.6.3
OBJECT IDENTIFIER    

upsAlarmBatteryBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.1
One or more batteries have been determined to require replacement.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOnBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.2
The UPS is drawing power from the batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmLowBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.3
The remaining battery run-time is less than or equal to upsConfigLowBattTime.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDepletedBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.4
The UPS will be unable to sustain the present load when and if the utility power is lost.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmTempBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.5
A temperature is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.6
An input condition is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.7
An output condition (other than OutputOverload) is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.8
The output load exceeds the UPS output capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOnBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.9
The Bypass is presently engaged on the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.10
The Bypass is out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.11
The UPS has shutdown as requested, i.e., the output is off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.12
The entire UPS has shutdown as commanded.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmChargerFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.13
An uncorrected problem has been detected within the UPS charger subsystem.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsOutputOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.14
The output of the UPS is in the off state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmUpsSystemOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.15
The UPS system is in the off state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmFanFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.16
The failure of one or more fans in the UPS has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmFuseFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.17
The failure of one or more fuses has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmGeneralFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.18
A general fault in the UPS has been detected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDiagnosticTestFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.19
The result of the last diagnostic test indicates a failure.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmCommunicationLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.20
A problem has been encountered in the communications between the agent and the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAwaitingPower 1.3.6.1.4.1.4555.1.1.1.1.6.3.21
The UPS output is off and the UPS is awaiting the return of input power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShutdownPending 1.3.6.1.4.1.4555.1.1.1.1.6.3.22
A upsShutdownAfterDelay countdown is underway.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShutdownImminent 1.3.6.1.4.1.4555.1.1.1.1.6.3.23
The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmTestInProgress 1.3.6.1.4.1.4555.1.1.1.1.6.3.24
A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPowerSupplyFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.25
Digital power supply fault.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAuxMainFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.26
Auxiliary mains out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmManualBypassClose 1.3.6.1.4.1.4555.1.1.1.1.6.3.27
Manual By-pass closed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmShortCircuit 1.3.6.1.4.1.4555.1.1.1.1.6.3.28
Short Circuit on UPS output.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryChargerFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.29
Battery charger failure.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInverterOverCurrent 1.3.6.1.4.1.4555.1.1.1.1.6.3.30
Inverter Over-current.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInverterDistorsion 1.3.6.1.4.1.4555.1.1.1.1.6.3.31
Excessive Inverter Distorsion.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPrechargeVoltageFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.32
Precharge voltage out of tolerance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBoostTooLow 1.3.6.1.4.1.4555.1.1.1.1.6.3.33
Boost output voltage too low.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBoostTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.34
Boost output voltage too high.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.35
Battery voltage too high.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmImproperCondition 1.3.6.1.4.1.4555.1.1.1.1.6.3.36
Improper condition of use
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOverloadTimeout 1.3.6.1.4.1.4555.1.1.1.1.6.3.37
Overload timeout blocking Inverter.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmControlSystemFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.38
Microprocessor control system failure
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmDataCorrupted 1.3.6.1.4.1.4555.1.1.1.1.6.3.39
Configuration data map corrupted.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPllFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.40
Pll fault.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInputGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.41
Input mains general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmRectifierGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.42
Rectifier general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBoostGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.43
Boost general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInverterGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.44
Inverter general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.45
Bettery charger general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputOver 1.3.6.1.4.1.4555.1.1.1.1.6.3.46
Output voltage over limit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOutputUnder 1.3.6.1.4.1.4555.1.1.1.1.6.3.47
Output voltage under limit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBypassGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.48
Bypass charger general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmStopForOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.49
Stop for overload.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmImminentStop 1.3.6.1.4.1.4555.1.1.1.1.6.3.50
UPS imminent stop
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule1Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.51
Module 1 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule2Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.52
Module 2 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule3Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.53
Module 3 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule4Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.54
Module 4 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule5Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.55
Module 5 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmModule6Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.56
Module 6 in parallel general alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmExternalAlarm1 1.3.6.1.4.1.4555.1.1.1.1.6.3.57
External Alarm 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmExternalAlarm2 1.3.6.1.4.1.4555.1.1.1.1.6.3.58
External Alarm 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmExternalAlarm3 1.3.6.1.4.1.4555.1.1.1.1.6.3.59
External Alarm 3.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmExternalAlarm4 1.3.6.1.4.1.4555.1.1.1.1.6.3.60
External Alarm 4.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEService 1.3.6.1.4.1.4555.1.1.1.1.6.3.61
E-Service General Alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmRedundancyLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.62
Redundancy lost
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPeriodicServiceCheck 1.3.6.1.4.1.4555.1.1.1.1.6.3.63
Periodic service check up.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAllTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.64
Automatic and manual transfer disabled
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmAutoTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.65
Automatic transfer disabled
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryRoom 1.3.6.1.4.1.4555.1.1.1.1.6.3.66
Battery room alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmManualBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.67
Manual bypass alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryDischarged 1.3.6.1.4.1.4555.1.1.1.1.6.3.68
Battery Discharged
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInsufficientResources 1.3.6.1.4.1.4555.1.1.1.1.6.3.69
Insufficient resources
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmOptionalBoards 1.3.6.1.4.1.4555.1.1.1.1.6.3.70
Optional boards general alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmRectifierFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.71
Rectifier fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBoostFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.72
Boost fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmInverterFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.73
Inverter fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmParallelModuleFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.74
Parallel module fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmGenSetGeneral 1.3.6.1.4.1.4555.1.1.1.1.6.3.75
Gen-set general alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmGenSetFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.76
Gen-set fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmEmergencyStopActive 1.3.6.1.4.1.4555.1.1.1.1.6.3.77
Emergency stop active
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmBatteryCircuitOpen 1.3.6.1.4.1.4555.1.1.1.1.6.3.78
Battery circuit open
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmFansFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.79
Fans failure
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmPhaseRotationFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.80
Phase rotation fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmA62 1.3.6.1.4.1.4555.1.1.1.1.6.3.81
A62.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAlarmA63 1.3.6.1.4.1.4555.1.1.1.1.6.3.82
A63.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestId 1.3.6.1.4.1.4555.1.1.1.1.7.1
The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. Tests in progress may be aborted by setting this variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has bee run, in which case the well known value upsTestNoTestsInitiated is returned.
Status: mandatory Access: read-write
OBJECT-TYPE    
  OBJECT IDENTIFIER  

upsTestSpinLock 1.3.6.1.4.1.4555.1.1.1.1.7.2
A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  TestAndIncr  

upsTestResultsSummary 1.3.6.1.4.1.4555.1.1.1.1.7.3
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notActive(1), inProgress(2), byPass(3), failed(4)  

upsTestResultsDetail 1.3.6.1.4.1.4555.1.1.1.1.7.4
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsTestStartTime 1.3.6.1.4.1.4555.1.1.1.1.7.5
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

upsTestElapsedTime 1.3.6.1.4.1.4555.1.1.1.1.7.6
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeInterval  

upsWellKnownTests 1.3.6.1.4.1.4555.1.1.1.1.7.7
OBJECT IDENTIFIER    

upsTestNoTestsInitiated 1.3.6.1.4.1.4555.1.1.1.1.7.7.1
No tests have been initiated and no test is in progress.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestAbortTestInProgress 1.3.6.1.4.1.4555.1.1.1.1.7.7.2
The test in progress is to be aborted / the test in progress was aborted.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestGeneralSystemsTest 1.3.6.1.4.1.4555.1.1.1.1.7.7.3
The manufacturer's standard test of UPS device systems.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTestQuickBatteryTest 1.3.6.1.4.1.4555.1.1.1.1.7.7.4
A test that is sufficient to determine if the battery needs replacement.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDeepBatteryCalibration 1.3.6.1.4.1.4555.1.1.1.1.7.7.5
The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsControlStatusControl 1.3.6.1.4.1.4555.1.1.1.1.8.1
This object Control UPS status
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER upsStandbyOn(1), upsStandbyOff(2), upsEcoMode(3), upsNormalMode(4), upsAlarmReset(5), upsCommandReset(6), upsBuzzerOff(7), upsOnBypass(8), upsOnInverter(9)  

upsShutdownDelay 1.3.6.1.4.1.4555.1.1.1.1.8.2
This object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsTurnOffAfterShutdown 1.3.6.1.4.1.4555.1.1.1.1.8.3
This object enable/disable UPS turn off function after shutdown process complete
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsControlShutdownParametersTable 1.3.6.1.4.1.4555.1.1.1.1.8.4
Table which describes the parametes for shutdown process when shutdown event occurs
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ShutdownParametersEntry

shutdownParametersEntry 1.3.6.1.4.1.4555.1.1.1.1.8.4.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  ShutdownParametersEntry  

upsControlEventDescr 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1
The shutdown event identification
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

upsControlEventStatus 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsControlDelay 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3
The Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when Net Vision will start sending the warning message to the connected clients. The value is in units of minutes.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32767  

upsControlFirstWarning 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4
The delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32767  

upsControlWarningInterval 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32767  

upsControlSeverity 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.6
Shutdown daemon severity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..2  

upsControlWeeklyScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.5
The table to schedule shutting down the ups by weekly.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlWeeklyScheduleEntry

upsControlWeeklyScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.5.1
The entries for each day.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlWeeklyScheduleEntry  

upsControlWeeklyIndex 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1
The index of scheduled events.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..7  

upsControlWeeklyShutdownDay 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2
The weekday on which the UPS should shut down.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlWeeklyShutdownTime 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlWeeklyRestartDay 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4
The weekday on which the UPS should restart
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlWeeklyRestartTime 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5
The time the UPS will restart in hh:mm:ss format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlSpecialScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.6
The table to schedule shutting down the ups.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlSpecialScheduleEntry

upsControlSpecialScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.6.1
The entries for each day.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlSpecialScheduleEntry  

upsControlSpecialIndex 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1
The index of scheduled events.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

upsControlSpecialShutdownDay 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2
The date on which the UPS should shut down in dd/mm/yyyy format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsControlSpecialShutdownTime 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlSpecialRestartDay 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4
The date on which the UPS should restart in dd/mm/yyyy format
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsControlSpecialRestartTime 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5
The time the UPS will restart in hh:mm:ss format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlEcoModeScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.7
The table to schedule enable/disable ups eco/mode by weekly.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlEcoModeScheduleEntry

upsControlEcoModeScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.7.1
The entries for each day.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlEcoModeScheduleEntry  

upsControlEcoModeIndex 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1
The index of scheduled events.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..7  

upsControlEcoModeStartDay 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2
The weekday on which the UPS Eco/Mode should enable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlEcoModeStartTime 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3
The time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsControlEcoModeEndDay 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4
The weekday on which the UPS Eco/Mode should disable
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)  

upsControlEcoModeEndTime 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5
The time the UPS Eco/Mode will disabled, in hh:mm:ss format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsConfigInputVoltage 1.3.6.1.4.1.4555.1.1.1.1.9.1
The magnitude of the nominal input voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigInputFreq 1.3.6.1.4.1.4555.1.1.1.1.9.2
The nominal input frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigOutputVoltage 1.3.6.1.4.1.4555.1.1.1.1.9.3
The magnitude of the nominal output voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsConfigOutputFreq 1.3.6.1.4.1.4555.1.1.1.1.9.4
The nominal output frequency.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsDevicesTable 1.3.6.1.4.1.4555.1.1.1.1.9.5
The devices powered by UPS and registered to Net Vision
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsDevicesEntry

upsDevicesEntry 1.3.6.1.4.1.4555.1.1.1.1.9.5.1
The devices protected by Net Vision
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsDevicesEntry  

indexOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1
The index of the device that is plugged into the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..255  

addrOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2
The ip address of the device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

nameOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3
The name/description of the device plugged into the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

timeOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4
The that device registered to Net Vision
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

statusOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5
status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

severityOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6
severity
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAgentIpaddress 1.3.6.1.4.1.4555.1.1.1.1.10.1
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentGateway 1.3.6.1.4.1.4555.1.1.1.1.10.2
The default gateway that allow device managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentSubnetMask 1.3.6.1.4.1.4555.1.1.1.1.10.3
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

upsAgentDate 1.3.6.1.4.1.4555.1.1.1.1.10.4
The date in agent, format is (dd/mm/yyyy)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsAgentTime 1.3.6.1.4.1.4555.1.1.1.1.10.5
The time in agent, format is (hh:mm:ss)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

upsAgentNtpTimeServer 1.3.6.1.4.1.4555.1.1.1.1.10.6
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

upsAgentNtpTimeZone 1.3.6.1.4.1.4555.1.1.1.1.10.7
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER gmt1200dateLineWest(1), gmt1200kwajalein(2), gmt1100samoa(3), gmt1000hawaii(4), gmt0900alaska(5), gmt0800tijuana(6), gmt0700arizona(7), gmt0700chihuahua(8), gmt0700mountain(9), gmt0600camerica(10), gmt0600ctime(11), gmt0600guadalajara(12), gmt0600saskatchewan(13), gmt0500quito(14), gmt0500etime(15), gmt0500indiana(16), gmt0400atime(17), gmt0400caracas(18), gmt0400santiago(19), gmt0300newfoundland(20), gmt0300brasilia(21), gmt0300georgetown(22), gmt0300greenland(23), gmt0200atlantic(24), gmt0100azores(25), gmt0100cvi(26), gmt0000monrovia(27), gmt0000london(28), gmt0100vienna(29), gmt0100prague(30), gmt0100paris(31), gmt0100zagreb(32), gmt0100wcafrica(33), gmt0200minsk(34), gmt0200bucharest(35), gmt0200cairo(36), gmt0200pretoria(37), gmt0200vilnius(38), gmt0200jerusalem(39), gmt0300maghdad(40), gmt0300riyadh(41), gmt0300volgograd(42), gmt0300nairobi(43), gmt0300tehran(44), gmt0400muscat(45), gmt0400yerevan(46), gmt0400kabul(47), gmt0500ekaterinburg(48), gmt0500tashkent(49), gmt0500calcutta(50), gmt0500mumbai(51), gmt0500kathmandu(52), gmt0600novosibirsk(53), gmt0600dhaka(54), gmt0600jayawardenepura(55), gmt0600rangoon(56), gmt0700bangkok(57), gmt0700krasnoyarsk(58), gmt0800beijing(59), gmt0800irkutsk(60), gmt0800singapore(61), gmt0800perth(62), gmt0800taipei(63), gmt0900tokyo(64), gmt0900seoul(65), gmt0900yakutsk(66), gmt0900adelaide(67), gmt0900darwin(68), gmt1000brisbane(69), gmt1000canberra(70), gmt1000guam(71), gmt1000hobart(72), gmt1000vladivostok(73), gmt1100magadan(74), gmt1200auckland(75), gmt1200fiji(76), gmt1300alofa(77)  

upsAgentHistoryLogFrequency 1.3.6.1.4.1.4555.1.1.1.1.10.8
The frequency of the updation of the history log. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 5..21600  

upsAgentExtHistoryLogFrequency 1.3.6.1.4.1.4555.1.1.1.1.10.9
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10080  

upsAgentPollRate 1.3.6.1.4.1.4555.1.1.1.1.10.10
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 3..60  

upsAgentBaudRate 1.3.6.1.4.1.4555.1.1.1.1.10.11
The serial port communication speed (2400/9600 allowed).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER br2400(1), br9600(2), br19200(3)  

upsAgentDhcpStatus 1.3.6.1.4.1.4555.1.1.1.1.10.12
Enable or disable DHCP-BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

upsAgentTelnetStatus 1.3.6.1.4.1.4555.1.1.1.1.10.13
Enable or disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

upsAgentTftpStatus 1.3.6.1.4.1.4555.1.1.1.1.10.14
Enable or disable network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

upsAgentResetToDefault 1.3.6.1.4.1.4555.1.1.1.1.10.15
Reset all parameters of Net Vision to default value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER reset(1), nothing(2)  

upsAgentRestart 1.3.6.1.4.1.4555.1.1.1.1.10.16
Restart Net Vision
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restart(1), nothing(2)  

upsAgentClearAgentLog 1.3.6.1.4.1.4555.1.1.1.1.10.17
Clear agent log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

upsAgentClearEventLog 1.3.6.1.4.1.4555.1.1.1.1.10.18
Clear event log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

upsAgentClearExtHistoryLog 1.3.6.1.4.1.4555.1.1.1.1.10.19
Clear extented history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

upsAgentClearHistoryLog 1.3.6.1.4.1.4555.1.1.1.1.10.20
Clear history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

upsAgentTrapsReceiversTable 1.3.6.1.4.1.4555.1.1.1.1.10.21
A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAgentTrapsReceiversEntry

upsAgentTrapsReceiversEntry 1.3.6.1.4.1.4555.1.1.1.1.10.21.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAgentTrapsReceiversEntry  

trapsIndex 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

trapsReceiverAddr 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

receiverCommunityString 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

receiverDescription 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsAgentAccessControlTable 1.3.6.1.4.1.4555.1.1.1.1.10.22
A list of managers which can access Net Vision with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsAgentAccessControlEntry

upsAgentAccessControlEntry 1.3.6.1.4.1.4555.1.1.1.1.10.22.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsAgentAccessControlEntry  

accessIndex 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

accessControlAddr 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2
The IP address of the manager to access Net Vision
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

accessCommunityString 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3
The community name to use in the manager when access Net Vision
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

accessControlMode 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4
Access type, only read-Write access type can change parameter of Net Vision
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), readWrite(2), notAccess(3)  

upsAgentMibVersion 1.3.6.1.4.1.4555.1.1.1.1.10.23
The version of MIB spec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsAgentTrapString 1.3.6.1.4.1.4555.1.1.1.1.10.50
This OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

emdSatatusTemperature 1.3.6.1.4.1.4555.1.1.1.1.11.1
The measurement of EMD temperature, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

emdSatatusHumidity 1.3.6.1.4.1.4555.1.1.1.1.11.2
The measurement of EMD humidity, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTrapOnBattery 1
The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
TRAP-TYPE    

upsTrapTestCompleted 2
This trap is sent upon completion of a UPS diagnostic test.
TRAP-TYPE    

upsTrapAlarmEntryAdded 3
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress.
TRAP-TYPE    

upsTrapAlarmEntryRemoved 4
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
TRAP-TYPE    

upsTrapUpsNormal 5
INFORMATION: The UPS status is normal.
TRAP-TYPE    

upsTrapUpsBattTestFailed 6
SEVERE: UPS failed the last test of battery.
TRAP-TYPE    

upsTrapOnBatteryPower 7
WARNING: The UPS has switched to battery backup power.
TRAP-TYPE    

upsTrapBatteryLow 8
SEVERE: Battery is near to be discharged.
TRAP-TYPE    

upsTrapPowerRestored 9
INFORMATION: Input power has been restored.
TRAP-TYPE    

upsTrapImminentStop 10
SEVERE: The UPS is near to switch off the output power.
TRAP-TYPE    

upsTrapTurnedOff 11
WARNING: The UPS has been turned off by the management station.
TRAP-TYPE    

upsTrapOverTemperature 12
SEVERE: The UPS has sensed a temperature greater than its limit.
TRAP-TYPE    

upsTrapOverload 13
SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
TRAP-TYPE    

upsTrapOnMains 14
SEVERE: The UPS output is on mains.
TRAP-TYPE    

upsTrapRedoundancyLost 15
SEVERE: Redoundancy is lost.
TRAP-TYPE    

upsTrapEmdTempLow 16
SEVERE: EMD Sensor detected low temperature.
TRAP-TYPE    

upsTrapEmdTempHigh 17
SEVERE: EMD Sensor detected high temperature.
TRAP-TYPE    

upsTrapEmdHumidityLow 18
SEVERE: EMD Sensor detected low humidity.
TRAP-TYPE    

upsTrapEmdHumidityHigh 19
SEVERE: EMD Sensor detected high humidity.
TRAP-TYPE    

upsTrapEmdFirstInputActive 20
SEVERE: The input is active.
TRAP-TYPE    

upsTrapEmdFirstInputRestored 21
INFORMATION: The input is restored.
TRAP-TYPE    

upsTrapEmdSecondInputActive 22
SEVERE: The input is active.
TRAP-TYPE    

upsTrapEmdSecondInputRestored 23
INFORMATION: The input is restored.
TRAP-TYPE