SDEVICE-MIB
File:
SDEVICE-MIB.mib (34501 bytes)
Imported modules
Imported symbols
Defined Types
ConfigurationEntry |
|
SEQUENCE |
|
|
|
|
channelIndex2 |
Integer32 |
|
|
noPhases |
Integer32 |
|
|
noOutletsTotal |
Integer32 |
|
|
noSwitchedOutlets |
Integer32 |
|
|
noMeasuredOutlets |
Integer32 |
|
|
maximumLoad |
Integer32 |
|
|
noTempSensors |
Integer32 |
|
|
noEnvSensors |
Integer32 |
|
DeciAmps |
|
Data type for reporting measurements and thresholds associated
with current sensors. If the underlying hardware sensor
indicates 1.1 amp, then the SNMP agent will report a value of
11 DeciAmps. The value is scaled in this manner as a way to
deal with floating point types that SNMP does not currently
support. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
DeciCelsius |
|
Data type for reporting sensor readings associated with
temperature sensors. If the underlying hardware sensor
indicates 20.1 degree Celsius, then the SNMP agent will report
a value of 201 tenth degrees Celsius. The value is scaled in
this manner as a way to deal with floating point types that
SNMP does not currently support. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
DeciPowerFactor |
|
Data type for reporting measurements associated with power
factor calculation. The power factor of an AC power system is
defined as the ratio of the real or active power to the
apparent power and is a number between 0 and 1. A
DeciPowerFactor value is calculated by taking this ratio and
multiplying by 1000. A power factor of 98.3% will be reported
as 983. The power factor is used to indicate how efficiently a
particular load is utilizing energy. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
DeciValue |
|
Data type for reporting generic measurements associated with
environmental sensors. If the underlying hardware sensor
indicates 21.1 degree, then the SNMP agent will report a value
of 211 DeciValue. The value is scaled in this manner as a way
to deal with floating point types that SNMP does not currently
support. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
DeciVolts |
|
Data type for reporting measurements and thresholds associated
with voltage sensors. If the underlying hardware sensor
indicates 231.1 volts, then the SNMP agent will report a value
of 2311 DeciVolts. The value is scaled in this manner as a way
to deal with floating point types that SNMP does not currently
support. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
IdentificationEntry |
|
SEQUENCE |
|
|
|
|
channelIndex1 |
Integer32 |
|
|
spdmVersion |
Integer32 |
|
|
firmwareVersion |
Integer32 |
|
|
salesOrderNumber |
DisplayString |
|
|
productId |
DisplayString |
|
|
serialNumber |
DisplayString |
|
|
hardwareAddress |
DisplayString |
|
|
unitAddress |
Integer32 |
|
|
busPosition |
Integer32 |
|
KiloWattHour |
|
Data type for reporting measurements associated with energy
accumulation sensors. If the underlying hardware sensor
indicates 1 kWh, then the SNMP agent will report a value of 1
kWh. No scaling is performed for this type. |
TEXTUAL-CONVENTION |
|
|
|
|
Integer32 |
|
|
SystemstatusEntry |
|
SEQUENCE |
|
|
|
|
channelIndex3 |
Integer32 |
|
|
deviceStatusCode |
Integer32 |
|
|
temperatureAlert |
Integer32 |
|
|
inputCurrentAlert |
Integer32 |
|
|
outputCurrentAlert |
Integer32 |
|
|
inputVoltageAlert |
Integer32 |
|
|
oCurrentDropAlert |
Integer32 |
|
|
iCurrentDropAlert |
Integer32 |
|
OutletsEntry |
|
SEQUENCE |
|
|
|
|
channelIndex4 |
Integer32 |
|
|
outletName |
DisplayString |
|
OutputmeasuresEntry |
|
SEQUENCE |
|
|
|
|
channelIndex7 |
Integer32 |
|
|
kWhTotalO |
KiloWattHour |
|
|
kWhSubtotalO |
KiloWattHour |
|
|
powerFactorO |
DeciPowerFactor |
|
|
actualCurrentO |
DeciAmps |
|
|
peakCurrentO |
DeciAmps |
|
|
actualVoltageO |
DeciVolts |
|
|
maxOutletAmps |
DeciAmps |
|
|
outputCTratio |
Integer32 |
|
SwitchedoutletsEntry |
|
SEQUENCE |
|
|
|
|
channelIndex5 |
Integer32 |
|
|
currentState |
Integer32 |
|
|
scheduled |
Integer32 |
|
|
unlock |
Integer32 |
|
|
individualOutletDelay |
Seconds |
|
SensorEntry |
|
SEQUENCE |
|
|
|
|
channelIndex8 |
Integer32 |
|
|
sensorType |
DisplayString |
|
|
sensorValue |
DeciValue |
|
|
sensorName |
DisplayString |
|
Defined Values
schleifenbauer |
1.3.6.1.4.1.31034 |
This MIB describes the functions of the Schleifenbauer device
family. |
MODULE-IDENTITY |
|
|
|
device0 |
1.3.6.1.4.1.31034.2 |
OBJECT IDENTIFIER |
|
|
|
spdmVersion |
1.3.6.1.4.1.31034.2.3.1 |
Data model version, currently 1.10 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9999 |
|
firmwareVersion |
1.3.6.1.4.1.31034.2.3.2 |
The units firmware revision number. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9999 |
|
buildNumber |
1.3.6.1.4.1.31034.2.3.3 |
Date and time of latest build of the firmware. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
hardwareAddress |
1.3.6.1.4.1.31034.2.3.7 |
Hardware serial number; cannot be changed. Can be used as
backup unit address. format as 3 unsigned ints separated by
dashes: int - int - int |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
macAddress |
1.3.6.1.4.1.31034.2.3.8 |
The ethernet interfaces unique hardware address. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
unitAddress |
1.3.6.1.4.1.31034.2.3.9 |
User defined address; this will be used for addressing the
unit. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..65535 |
|
deviceName |
1.3.6.1.4.1.31034.2.3.10 |
User configurable device name or identifier. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
deviceLocation |
1.3.6.1.4.1.31034.2.3.11 |
User configurable device location identifier. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
vanityTag |
1.3.6.1.4.1.31034.2.3.12 |
Characters to be displayed as vanity tekst in display. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
noPhases |
1.3.6.1.4.1.31034.2.4.1 |
Either zero, one or three for no input metering, single or
three phase system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..3 |
|
noOutletsTotal |
1.3.6.1.4.1.31034.2.4.2 |
Total number of outlets, even hardwired without switch/measure
modules. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
noSwitchedOutlets |
1.3.6.1.4.1.31034.2.4.3 |
Number of switched outlets. If outlet numbering is
non-contiguous: the highest outlet number. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..48 |
|
noMeasuredOutlets |
1.3.6.1.4.1.31034.2.4.4 |
Number of measured outlets. If outlet numbering is
non-contiguous: the highest outlet number. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..48 |
|
noSensors |
1.3.6.1.4.1.31034.2.4.5 |
The number of external, digital environmental sensors: 0 for
none, 1 to 16 depending on number of reported sensors |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
maximumLoad |
1.3.6.1.4.1.31034.2.4.6 |
Maximum rated load of device per phase, usually either 16 or
32 A. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32 |
|
deviceStatusCode |
1.3.6.1.4.1.31034.2.5.1 |
Returns an internal status or error code. 0 = OK, 16 =
watchdog timer caused reset, 128 = slave module was reset, 144
= both previous. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..255 |
|
temperatureAlert |
1.3.6.1.4.1.31034.2.5.2 |
An alert has been raised due to temperature exceeding
treshhold; 0= no alert; 1= internal unit temp, 2= external
sensor. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..2 |
|
outputCurrentAlert |
1.3.6.1.4.1.31034.2.5.4 |
An alert has been raised due to current exceeding treshhold;
0=no alert; 1-48 for outlet. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..48 |
|
oCurrentDropAlert |
1.3.6.1.4.1.31034.2.5.6 |
An alert has been raised due to the current of a measured
outlet suddenly dropping to near zero, possibly indicating a
blown fuse; 0=no alert; 1-48 for outlet. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..103 |
|
iCurrentDropAlert |
1.3.6.1.4.1.31034.2.5.7 |
An alert has been raised due to the current of a measured
input suddenly dropping to near zero, possibly indicating a
blown fuse; 0=no alert; 1-3 for phase. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..3 |
|
reset |
1.3.6.1.4.1.31034.2.6 |
OBJECT IDENTIFIER |
|
|
|
rebootDevice |
1.3.6.1.4.1.31034.2.6.1 |
Warm reboot/reset of device; note: this will have no effect on
outlet status! |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
resetAlerts |
1.3.6.1.4.1.31034.2.6.2 |
Reset all alert signals. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
zeroOutKWhSubtotal |
1.3.6.1.4.1.31034.2.6.4 |
Reset of outlet kWh subtotal counter to zero. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
resetPeakValues |
1.3.6.1.4.1.31034.2.6.5 |
Reset all peak values to zero, as well input as output
metering, voltages dips, current peaks and temperatures. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
settings |
1.3.6.1.4.1.31034.2.7 |
OBJECT IDENTIFIER |
|
|
|
general |
1.3.6.1.4.1.31034.2.7.1 |
OBJECT IDENTIFIER |
|
|
|
peakDuration |
1.3.6.1.4.1.31034.2.7.1.4 |
A current peak should last at least [stpkdr] MilliSeconds
before an alert is raised; max about a minute. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
MilliSeconds |
|
|
fixedOutletDelay |
1.3.6.1.4.1.31034.2.7.1.5 |
Minimal delay between two successive relay switches in
milliseconds. Minimal delay is 100 ms. Will always be
respected! |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
MilliSeconds |
|
|
powerSaverMode |
1.3.6.1.4.1.31034.2.7.1.6 |
Set backlight on time in seconds; 0 keeps display always on.
Note that keeping the backlight on may decrease luminosity over
time. Setting this to other values than 10, 60, 120 or 240 is
incompatible with the gateway! |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Seconds |
|
|
outletPowerupMode |
1.3.6.1.4.1.31034.2.7.1.7 |
Behaviour of outlet on power-up: 0=off; 1=same state as at
power down; 2=same state, but delayed by individual delay
timer. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..2 |
|
maximumTemperature |
1.3.6.1.4.1.31034.2.7.1.8 |
An alert should be generated whenever the temperature of the
first connected T sensor is above this value. Zero means
disabled. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
displayOrientation |
1.3.6.1.4.1.31034.2.7.1.9 |
0 no display; display off; 1 vertical, display on top; 2
vertical, upside down; 3 horizontal, display at left; 4
horizontal, display at right |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
localAlertReset |
1.3.6.1.4.1.31034.2.7.1.10 |
Allow alerts to be reset locally on device by pushing one of
the buttons. [replaces dipDuration] |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
currentDropDetection |
1.3.6.1.4.1.31034.2.7.1.11 |
Enables the current drop detection function. 0 = always off
(default), 1 = input (s) only, 2 = output(s) only, 3 = both
inputs and outputs. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..3 |
|
wirelessDisplayPower |
1.3.6.1.4.1.31034.2.7.1.12 |
Controls the transit power of the wireless display transciever
(if installed). Set to zero to completely disable the module. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
inputmeasuresEntry |
1.3.6.1.4.1.31034.2.8.1 |
The record containing the registers for the channel selected
by channelIndex. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
InputmeasuresEntry |
|
|
channelIndex6 |
1.3.6.1.4.1.31034.2.8.1.1 |
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..48 |
|
kWhTotalI |
1.3.6.1.4.1.31034.2.8.1.2 |
Either the only phase in a single phase measurement; or one of
the three phases in a multiphase measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
KiloWattHour |
|
|
kWhSubtotalI |
1.3.6.1.4.1.31034.2.8.1.3 |
kWh subtotal register of the only phase in a single phase
measurement; or one of three phases in a multiphase
measurement. Reset to zero with [rsimks]. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
KiloWattHour |
|
|
powerFactorI |
1.3.6.1.4.1.31034.2.8.1.4 |
The effective power factor in percent. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciPowerFactor |
|
|
actualCurrentI |
1.3.6.1.4.1.31034.2.8.1.5 |
Actual apparent, RMS current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
peakCurrentI |
1.3.6.1.4.1.31034.2.8.1.6 |
Peak apparent, RMS current; highest value since last reset of
the alerts. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
actualVoltageI |
1.3.6.1.4.1.31034.2.8.1.7 |
The actual voltage. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciVolts |
|
|
minVoltageI |
1.3.6.1.4.1.31034.2.8.1.8 |
RMS voltage dip; lowest value since reset of alerts. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciVolts |
|
|
powerVAI |
1.3.6.1.4.1.31034.2.8.1.9 |
Power value calculated, not in data model of device. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
powerWattI |
1.3.6.1.4.1.31034.2.8.1.10 |
Power value calculated by the gateway, not in data model of
device. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
maxInletAmps |
1.3.6.1.4.1.31034.2.8.1.11 |
Maximum current per input phase in A; should last at least
[stpkdr] MilliSeconds before triggering an alert. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
outletsTable |
1.3.6.1.4.1.31034.2.9 |
This table contains the customer specific settings,
determining toutlestablehe behaviour of the DEVICE. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
OutletsEntry |
|
outletsEntry |
1.3.6.1.4.1.31034.2.9.1 |
The record containing the registers forthe channel selected by
channelIndex. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
OutletsEntry |
|
|
channelIndex4 |
1.3.6.1.4.1.31034.2.9.1.1 |
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..48 |
|
outletName |
1.3.6.1.4.1.31034.2.9.1.2 |
User configurable naming of individual outlets. Useful to
distinguish outlets based on customer or device name. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
outputmeasuresTable |
1.3.6.1.4.1.31034.2.10 |
This table contains all measures related to the measured
outputs of the DEVICE. Note: up to 48 channels, depending on
number of measured outlets. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
OutputmeasuresEntry |
|
outputmeasuresEntry |
1.3.6.1.4.1.31034.2.10.1 |
The record containing the registers for the channel selected
by channelIndex. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
OutputmeasuresEntry |
|
|
channelIndex7 |
1.3.6.1.4.1.31034.2.10.1.1 |
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..48 |
|
kWhTotalO |
1.3.6.1.4.1.31034.2.10.1.2 |
Total kWh of selected output. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
KiloWattHour |
|
|
kWhSubtotalO |
1.3.6.1.4.1.31034.2.10.1.3 |
kWh subtotal register of selected output. Reset to zero with
[rsomks]. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
KiloWattHour |
|
|
actualCurrentO |
1.3.6.1.4.1.31034.2.10.1.5 |
Actual apparent, RMS current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
peakCurrentO |
1.3.6.1.4.1.31034.2.10.1.6 |
Peak apparent, RMS current; highest value since last reset of
alerts. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
actualVoltageO |
1.3.6.1.4.1.31034.2.10.1.7 |
Actual voltage on output. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciVolts |
|
|
maxOutletAmps |
1.3.6.1.4.1.31034.2.10.1.8 |
Maximum current per outlet in A; should last at least [stpkdr]
MilliSeconds before triggering an alert. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DeciAmps |
|
|
outputCTratio |
1.3.6.1.4.1.31034.2.10.1.9 |
The multiplier to use in case of use of /5 current
transformers. Defaults to 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
switchedoutletsEntry |
1.3.6.1.4.1.31034.2.11.1 |
The record containing the registers for the channel selected
by channelIndex. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SwitchedoutletsEntry |
|
|
channelIndex5 |
1.3.6.1.4.1.31034.2.11.1.1 |
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..48 |
|
currentState |
1.3.6.1.4.1.31034.2.11.1.2 |
The actual state of the outlet relays. The hardware will
contain max 48 outlets. Writing is only effective after setting
[swounl]. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
scheduled |
1.3.6.1.4.1.31034.2.11.1.3 |
A one indicates pending activity; the switch delay has not yet
expired. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
unlock |
1.3.6.1.4.1.31034.2.11.1.4 |
Setting the value to one will release the safety for this
outlet for a couple seconds; switching and rebooting are then
temporarily enabled. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
individualOutletDelay |
1.3.6.1.4.1.31034.2.11.1.5 |
Delay before an individual outlet switches on at power-up in
Seconds. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Seconds |
|
|
sensorTable |
1.3.6.1.4.1.31034.2.12 |
This table contains the environmental measurements. As well
internal temperature as external temperature probes. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
SensorEntry |
|
sensorEntry |
1.3.6.1.4.1.31034.2.12.1 |
The record containing the registers for the channel selected
by channelIndex. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SensorEntry |
|
|
channelIndex8 |
1.3.6.1.4.1.31034.2.12.1.1 |
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..48 |
|
sensorType |
1.3.6.1.4.1.31034.2.12.1.2 |
Type of connected sensor, either T, H or I for respectively
Temperature (C), Humidity (%) or dry switch contact |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
sensorValue |
1.3.6.1.4.1.31034.2.12.1.3 |
Value of connected sensor |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DeciValue |
|
|
sensorName |
1.3.6.1.4.1.31034.2.12.1.4 |
User definable name for sensors. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
compliance |
1.3.6.1.4.1.31034.99.1.1 |
The requirements for conformance to the SPGW-MIB. |
Status: current |
Access: read-write |
MODULE-COMPLIANCE |
|
|
|
groups |
1.3.6.1.4.1.31034.99.2 |
OBJECT IDENTIFIER |
|
|
|
identificationGroup |
1.3.6.1.4.1.31034.99.2.1 |
A collection of objects providing identification information
about the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
configurationGroup |
1.3.6.1.4.1.31034.99.2.2 |
A collection of objects providing configuration information
about the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
systemStatusGroup |
1.3.6.1.4.1.31034.99.2.3 |
A collection of objects providing status information about the
device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
resetGroup |
1.3.6.1.4.1.31034.99.2.4 |
Groups resettable attributes op the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
settingsGroup |
1.3.6.1.4.1.31034.99.2.5 |
A collection of objects providing the actual settings about
the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
switchedOutletsGroup |
1.3.6.1.4.1.31034.99.2.6 |
A collection of objects providing the actual outlet status of
the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
outputMeasuresGroup |
1.3.6.1.4.1.31034.99.2.8 |
A collection of objects providing the actual output
measurements of the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|
sensorsGroup |
1.3.6.1.4.1.31034.99.2.9 |
A collection of objects providing the actual environmental
measurements of the device. |
Status: current |
Access: read-write |
OBJECT-GROUP |
|
|
|