RIELLOMDU-MIB

File: RIELLOMDU-MIB.mib (10798 bytes)

Imported modules

RFC1213-MIB RFC-1212 RFC-1215
RIELLO-MIB

Imported symbols

DisplayString OBJECT-TYPE TRAP-TYPE
rielloMIB

Defined Types

MduOutputSockets  
SEQUENCE    
  mduOutputLineIndex INTEGER
  mduOutputCurrent INTEGER
  mduOutputDisabled INTEGER
  mduOutputOverload INTEGER
  mduOutputStatus INTEGER

Defined Values

mduMIB 1.3.6.1.4.1.5491.11
OBJECT IDENTIFIER    

mduIdent 1.3.6.1.4.1.5491.11.1
OBJECT IDENTIFIER    

mduIdentManufacturer 1.3.6.1.4.1.5491.11.1.1
The name of the mdu manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

mduIdentModel 1.3.6.1.4.1.5491.11.1.2
The mdu Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

mduIdentSoftwareVersion 1.3.6.1.4.1.5491.11.1.3
The mdu Software version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

mduIdentIOConfiguration 1.3.6.1.4.1.5491.11.1.4
The mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduIdentInputSockets 1.3.6.1.4.1.5491.11.1.5
The number of mdu input sockets.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduIdentOutputSockets 1.3.6.1.4.1.5491.11.1.6
The number of mdu output sockets.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduIdentNominalCurrent 1.3.6.1.4.1.5491.11.1.7
The mdu nominal current (A).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduIdentNominalVoltage 1.3.6.1.4.1.5491.11.1.8
The mdu nominal voltage (V).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduIdentNominalFrequency 1.3.6.1.4.1.5491.11.1.9
The mdu nominal frequency (0.1 Hz).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduStatus 1.3.6.1.4.1.5491.11.2
OBJECT IDENTIFIER    

mduLineAFrequency 1.3.6.1.4.1.5491.11.2.1
The frequency of source A (0.1 Hz).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduLineAVoltage 1.3.6.1.4.1.5491.11.2.2
The voltage of source 1 (V).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduLineACurrent 1.3.6.1.4.1.5491.11.2.3
The current of line A (0.1 A).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduOutput 1.3.6.1.4.1.5491.11.2.4
A list of output table entries.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    MduOutputSockets

mduOutputSockets 1.3.6.1.4.1.5491.11.2.4.1
An entry containing information applicable to a particular output line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  MduOutputSockets  

mduOutputLineIndex 1.3.6.1.4.1.5491.11.2.4.1.1
The line identifier.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  INTEGER 1..2147483647  

mduOutputCurrent 1.3.6.1.4.1.5491.11.2.4.1.2
Output current (0.1 A)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduOutputDisabled 1.3.6.1.4.1.5491.11.2.4.1.3
1->line active, 2->line deactivated
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER no(1), yes(2)  

mduOutputOverload 1.3.6.1.4.1.5491.11.2.4.1.4
1->line ok, 2->line deactivated for overload
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduOutputStatus 1.3.6.1.4.1.5491.11.2.4.1.5
0=OFF 1=ON 2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the 'Imminent time' is not reached) 3= Shutdown imminent (S01 to S08 code) 4= Restore active (when after that a CR command is received and the shutdown has been acted but the restore delay time is not expired) 5= Overload alarm (F01 to F08 code) 6= Locked: OFF for overload (L01 to L08 code)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1), shutdownActive(2), shutdownImminent(3), restoreActive(4), overload(5), locked(6)  

mduLowInputVoltage 1.3.6.1.4.1.5491.11.2.5
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduHighInputVoltage 1.3.6.1.4.1.5491.11.2.6
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduLowInputCurrent 1.3.6.1.4.1.5491.11.2.7
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduHighInputCurrent 1.3.6.1.4.1.5491.11.2.8
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduPowerFailAux1 1.3.6.1.4.1.5491.11.2.9
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduPowerFailAux2 1.3.6.1.4.1.5491.11.2.10
1= yes, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduManualBypass 1.3.6.1.4.1.5491.11.2.11
1= on manual bypass, 0= no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduTemperature 1.3.6.1.4.1.5491.11.2.12
The temperature (oC).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduCommand 1.3.6.1.4.1.5491.11.3
OBJECT IDENTIFIER    

mduCommandCode 1.3.6.1.4.1.5491.11.3.1
This object determines the nature of the action to be taken at the time when the countdown of the mduShutdownDelay and mduRestoreDelay objects reaches zero. Setting this object to shutdown(1) indicates that the specified sockets mduOutputSocketApplyCommand will yurn off. Setting this object to restore(2) indicates that the specified output sockets will turn on. command delete(3) will delete the applied command, test panel will perform a test of LCD panel and audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER shutdown(1), restore(2), commandDelete(3), testPanel(22)  

mduShutdownDelay 1.3.6.1.4.1.5491.11.3.2
Setting this object will shutdown (i.e., turn off) either the MDU output socket by the value of mduCommandCode at the time of shutdown after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

mduRestoreDelay 1.3.6.1.4.1.5491.11.3.3
The restore delay.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

mduOutputSocketApplyCommand 1.3.6.1.4.1.5491.11.3.4
Specify the socket to apply the command, the value 0 apply to all sockets.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

mduCommandResult 1.3.6.1.4.1.5491.11.3.5
The command result, refer to the follow codes: 0+mduCommandCode Command in progress 256+mduCommandCode Wrong Command code 512+mduCommandCode Command is not handled 768+mduCommandCode Parameter out of range 3584+mduCommandCode Command sent to MDU 3840+mduCommandCode Command executed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

mduTraps 1.3.6.1.4.1.5491.11.4
OBJECT IDENTIFIER    

mduNormal 1
This trap is sent when MDU is on normal status
TRAP-TYPE    

mduAnomaly 2
This trap is sent when MDU is has some anomaly and is resent every minute
TRAP-TYPE    

mduFault 3
This trap is sent when MDU is has some fault and is resent every minute
TRAP-TYPE    

mduLock 4
This trap is sent when MDU is locked and is resent every minute
TRAP-TYPE    

mduManualBypassEnabled 5
This trap is sent when MDU is on manual bypass and is resent every minute
TRAP-TYPE