PM-MIB

File: PM-MIB.mib (127302 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC IF-MIB

Imported symbols

enterprises OBJECT-TYPE MODULE-IDENTITY
Integer32 DisplayString InterfaceIndex
InterfaceIndexOrZero

Defined Types

PmActiveSessionsTableEntry  
SEQUENCE    
  pmActiveSessionsTableIndex InterfaceIndexOrZero
  pmActiveSessionsTableUser DisplayString
  pmActiveSessionsTableGroup DisplayString
  pmActiveSessionsTableType DisplayString
  pmActiveSessionsTableConnection DisplayString
  pmActiveSessionsTableSessionTime DisplayString
  pmActiveSessionsTableFrom DisplayString
  pmActiveSessionsTableKill INTEGER

PmPowerMgmtSerialTableEntry  
SEQUENCE    
  pmPowerMgmtSerialTableIndex InterfaceIndex
  pmPowerMgmtSerialTablePortNumber Integer32
  pmPowerMgmtSerialTableDeviceName DisplayString
  pmPowerMgmtSerialTableNumberPDUs Integer32
  pmPowerMgmtSerialTableBuzzer Integer32
  pmPowerMgmtSerialTableSyslog Integer32
  pmPowerMgmtSerialTableOverCurrent Integer32
  pmPowerMgmtSerialTableCycleInterval Integer32
  pmPowerMgmtSerialTablePollRate Integer32
  pmPowerMgmtSerialTablePassWord DisplayString
  pmPowerMgmtSerialTableSave INTEGER
  pmPowerMgmtSerialTableRestore INTEGER

PmPowerMgmtPDUTableEntry  
SEQUENCE    
  pmPowerMgmtPDUTablePortNumber InterfaceIndex
  pmPowerMgmtPDUTablePduIndex InterfaceIndexOrZero
  pmPowerMgmtPDUTablePduId DisplayString
  pmPowerMgmtPDUTablePortName DisplayString
  pmPowerMgmtPDUTableModel DisplayString
  pmPowerMgmtPDUTableVendor DisplayString
  pmPowerMgmtPDUTableFirmwareVersion DisplayString
  pmPowerMgmtPDUTableNumberOfOutlets Integer32
  pmPowerMgmtPDUTableCurrentNOS Integer32
  pmPowerMgmtPDUTableCurrent1Value Integer32
  pmPowerMgmtPDUTableCurrent1Max Integer32
  pmPowerMgmtPDUTableCurrent2Value Integer32
  pmPowerMgmtPDUTableCurrent2Max Integer32
  pmPowerMgmtPDUTableCurrent3Value Integer32
  pmPowerMgmtPDUTableCurrent3Max Integer32
  pmPowerMgmtPDUTableTemperatureNOS Integer32
  pmPowerMgmtPDUTableTemperature1Value Integer32
  pmPowerMgmtPDUTableTemperature1Max Integer32
  pmPowerMgmtPDUTableTemperature2Value Integer32
  pmPowerMgmtPDUTableTemperature2Max Integer32
  pmPowerMgmtPDUTableTemperature3Value Integer32
  pmPowerMgmtPDUTableTemperature3Max Integer32
  pmPowerMgmtPDUTableHumidityNOS Integer32
  pmPowerMgmtPDUTableHumidity1Value Integer32
  pmPowerMgmtPDUTableHumidity1Max Integer32
  pmPowerMgmtPDUTableHumidity2Value Integer32
  pmPowerMgmtPDUTableHumidity2Max Integer32
  pmPowerMgmtPDUTableHumidity3Value Integer32
  pmPowerMgmtPDUTableHumidity3Max Integer32
  pmPowerMgmtPDUTableVoltageNOS Integer32
  pmPowerMgmtPDUTableVoltage1Value Integer32
  pmPowerMgmtPDUTableVoltage1Max Integer32
  pmPowerMgmtPDUTableVoltage2Value Integer32
  pmPowerMgmtPDUTableVoltage2Max Integer32
  pmPowerMgmtPDUTableVoltage3Value Integer32
  pmPowerMgmtPDUTableVoltage3Max Integer32
  pmPowerMgmtPDUTableNumberOfPhases Integer32
  pmPowerMgmtPDUTableNumberOfBanks Integer32
  pmPowerMgmtPDUTableNumberOfSensors Integer32
  pmPowerMgmtPDUTableFactoryDefault INTEGER
  pmPowerMgmtPDUTableColdStartDelay Integer32
  pmPowerMgmtPDUTableReboot INTEGER
  pmPowerMgmtPDUTableMaxCurrent Integer32
  pmPowerMgmtPDUTableAlarm INTEGER
  pmPowerMgmtPDUTableCurrentValue Integer32
  pmPowerMgmtPDUTableCurrentMax Integer32
  pmPowerMgmtPDUTableCurrentMin Integer32
  pmPowerMgmtPDUTableCurrentAvg Integer32
  pmPowerMgmtPDUTableCurrentReset INTEGER
  pmPowerMgmtPDUTablePowerValue Integer32
  pmPowerMgmtPDUTablePowerMax Integer32
  pmPowerMgmtPDUTablePowerMin Integer32
  pmPowerMgmtPDUTablePowerAvg Integer32
  pmPowerMgmtPDUTablePowerReset INTEGER
  pmPowerMgmtPDUTablePowerType INTEGER
  pmPowerMgmtPDUTableVoltageValue Integer32
  pmPowerMgmtPDUTableVoltageMax Integer32
  pmPowerMgmtPDUTableVoltageMin Integer32
  pmPowerMgmtPDUTableVoltageAvg Integer32
  pmPowerMgmtPDUTableVoltageReset INTEGER
  pmPowerMgmtPDUTableVoltageType INTEGER
  pmPowerMgmtPDUTablePowerFactorValue Integer32
  pmPowerMgmtPDUTablePowerFactorMax Integer32
  pmPowerMgmtPDUTablePowerFactorMin Integer32
  pmPowerMgmtPDUTablePowerFactorAvg Integer32
  pmPowerMgmtPDUTablePowerFactorReset INTEGER
  pmPowerMgmtPDUTablePowerFactorType INTEGER
  pmPowerMgmtPDUTablePowerControl INTEGER
  pmPowerMgmtPDUTableResetOCP INTEGER
  pmPowerMgmtPDUTableCurrentHighCritical Integer32
  pmPowerMgmtPDUTableCurrentHighWarning Integer32
  pmPowerMgmtPDUTableCurrentLowWarning Integer32
  pmPowerMgmtPDUTableCurrentLowCritical Integer32
  pmPowerMgmtPDUTableEnergyValue Integer32
  pmPowerMgmtPDUTableEnergyStartTime DisplayString
  pmPowerMgmtPDUTableEnergyReset INTEGER

PmPowerMgmtOutletsTableEntry  
SEQUENCE    
  pmPowerMgmtOutletsTablePortNumber InterfaceIndex
  pmPowerMgmtOutletsTablePduNumber InterfaceIndex
  pmPowerMgmtOutletsTableNumber InterfaceIndex
  pmPowerMgmtOutletsTableName DisplayString
  pmPowerMgmtOutletsTableStatus INTEGER
  pmPowerMgmtOutletsTablePowerControl INTEGER
  pmPowerMgmtOutletsTablePortName DisplayString
  pmPowerMgmtOutletsTablePduId DisplayString
  pmPowerMgmtOutletsTablePostOnDelay Integer32
  pmPowerMgmtOutletsTablePostOffDelay Integer32
  pmPowerMgmtOutletsTableAlarm INTEGER
  pmPowerMgmtOutletsTableCurrentValue Integer32
  pmPowerMgmtOutletsTableCurrentMax Integer32
  pmPowerMgmtOutletsTableCurrentMin Integer32
  pmPowerMgmtOutletsTableCurrentAvg Integer32
  pmPowerMgmtOutletsTableCurrentReset INTEGER
  pmPowerMgmtOutletsTablePowerValue Integer32
  pmPowerMgmtOutletsTablePowerMax Integer32
  pmPowerMgmtOutletsTablePowerMin Integer32
  pmPowerMgmtOutletsTablePowerAvg Integer32
  pmPowerMgmtOutletsTablePowerReset INTEGER
  pmPowerMgmtOutletsTablePowerType INTEGER
  pmPowerMgmtOutletsTableVoltageValue Integer32
  pmPowerMgmtOutletsTableVoltageMax Integer32
  pmPowerMgmtOutletsTableVoltageMin Integer32
  pmPowerMgmtOutletsTableVoltageAvg Integer32
  pmPowerMgmtOutletsTableVoltageReset INTEGER
  pmPowerMgmtOutletsTableVoltageType INTEGER
  pmPowerMgmtOutletsTablePowerFactorValue Integer32
  pmPowerMgmtOutletsTablePowerFactorMax Integer32
  pmPowerMgmtOutletsTablePowerFactorMin Integer32
  pmPowerMgmtOutletsTablePowerFactorAvg Integer32
  pmPowerMgmtOutletsTablePowerFactorReset INTEGER
  pmPowerMgmtOutletsTablePowerFactorType INTEGER
  pmPowerMgmtOutletsTableCurrentHighCritical Integer32
  pmPowerMgmtOutletsTableCurrentHighWarning Integer32
  pmPowerMgmtOutletsTableCurrentLowWarning Integer32
  pmPowerMgmtOutletsTableCurrentLowCritical Integer32
  pmPowerMgmtOutletsTableEnergyValue Integer32
  pmPowerMgmtOutletsTableEnergyStartTime DisplayString
  pmPowerMgmtOutletsTableEnergyReset INTEGER

PmPowerMgmtGroupTableEntry  
SEQUENCE    
  pmPowerMgmtGroupTableIndex InterfaceIndexOrZero
  pmPowerMgmtGroupTableName DisplayString
  pmPowerMgmtGroupTableStatus INTEGER
  pmPowerMgmtGroupTablePowerControl INTEGER

PmPowerMgmtPhasesTableEntry  
SEQUENCE    
  pmPowerMgmtPhasesTablePortNumber InterfaceIndex
  pmPowerMgmtPhasesTablePduNumber InterfaceIndex
  pmPowerMgmtPhasesTableNumber InterfaceIndex
  pmPowerMgmtPhasesTableName DisplayString
  pmPowerMgmtPhasesTablePortName DisplayString
  pmPowerMgmtPhasesTablePduId DisplayString
  pmPowerMgmtPhasesTableAlarm INTEGER
  pmPowerMgmtPhasesTableCurrentValue Integer32
  pmPowerMgmtPhasesTableCurrentMax Integer32
  pmPowerMgmtPhasesTableCurrentMin Integer32
  pmPowerMgmtPhasesTableCurrentAvg Integer32
  pmPowerMgmtPhasesTableCurrentReset INTEGER
  pmPowerMgmtPhasesTablePowerValue Integer32
  pmPowerMgmtPhasesTablePowerMax Integer32
  pmPowerMgmtPhasesTablePowerMin Integer32
  pmPowerMgmtPhasesTablePowerAvg Integer32
  pmPowerMgmtPhasesTablePowerReset INTEGER
  pmPowerMgmtPhasesTablePowerType INTEGER
  pmPowerMgmtPhasesTableVoltageValue Integer32
  pmPowerMgmtPhasesTableVoltageMax Integer32
  pmPowerMgmtPhasesTableVoltageMin Integer32
  pmPowerMgmtPhasesTableVoltageAvg Integer32
  pmPowerMgmtPhasesTableVoltageReset INTEGER
  pmPowerMgmtPhasesTableVoltageType INTEGER
  pmPowerMgmtPhasesTablePowerFactorValue Integer32
  pmPowerMgmtPhasesTablePowerFactorMax Integer32
  pmPowerMgmtPhasesTablePowerFactorMin Integer32
  pmPowerMgmtPhasesTablePowerFactorAvg Integer32
  pmPowerMgmtPhasesTablePowerFactorReset INTEGER
  pmPowerMgmtPhasesTablePowerFactorType INTEGER
  pmPowerMgmtPhasesTableCurrentHighCritical Integer32
  pmPowerMgmtPhasesTableCurrentHighWarning Integer32
  pmPowerMgmtPhasesTableCurrentLowWarning Integer32
  pmPowerMgmtPhasesTableCurrentLowCritical Integer32

PmPowerMgmtBanksTableEntry  
SEQUENCE    
  pmPowerMgmtBanksTablePortNumber InterfaceIndex
  pmPowerMgmtBanksTablePduNumber InterfaceIndex
  pmPowerMgmtBanksTableNumber InterfaceIndex
  pmPowerMgmtBanksTableName DisplayString
  pmPowerMgmtBanksTablePortName DisplayString
  pmPowerMgmtBanksTablePduId DisplayString
  pmPowerMgmtBanksTableAlarm INTEGER
  pmPowerMgmtBanksTableCurrentValue Integer32
  pmPowerMgmtBanksTableCurrentMax Integer32
  pmPowerMgmtBanksTableCurrentMin Integer32
  pmPowerMgmtBanksTableCurrentAvg Integer32
  pmPowerMgmtBanksTableCurrentReset INTEGER
  pmPowerMgmtBanksTablePowerValue Integer32
  pmPowerMgmtBanksTablePowerMax Integer32
  pmPowerMgmtBanksTablePowerMin Integer32
  pmPowerMgmtBanksTablePowerAvg Integer32
  pmPowerMgmtBanksTablePowerReset INTEGER
  pmPowerMgmtBanksTablePowerType INTEGER
  pmPowerMgmtBanksTableVoltageValue Integer32
  pmPowerMgmtBanksTableVoltageMax Integer32
  pmPowerMgmtBanksTableVoltageMin Integer32
  pmPowerMgmtBanksTableVoltageAvg Integer32
  pmPowerMgmtBanksTableVoltageReset INTEGER
  pmPowerMgmtBanksTableVoltageType INTEGER
  pmPowerMgmtBanksTablePowerFactorValue Integer32
  pmPowerMgmtBanksTablePowerFactorMax Integer32
  pmPowerMgmtBanksTablePowerFactorMin Integer32
  pmPowerMgmtBanksTablePowerFactorAvg Integer32
  pmPowerMgmtBanksTablePowerFactorReset INTEGER
  pmPowerMgmtBanksTablePowerFactorType INTEGER
  pmPowerMgmtBanksTableCurrentHighCritical Integer32
  pmPowerMgmtBanksTableCurrentHighWarning Integer32
  pmPowerMgmtBanksTableCurrentLowWarning Integer32
  pmPowerMgmtBanksTableCurrentLowCritical Integer32
  pmPowerMgmtBanksTableEnergyValue Integer32
  pmPowerMgmtBanksTableEnergyStartTime DisplayString
  pmPowerMgmtBanksTableEnergyReset INTEGER

PmPowerMgmtSensorsTableEntry  
SEQUENCE    
  pmPowerMgmtSensorsTablePortNumber InterfaceIndex
  pmPowerMgmtSensorsTablePduNumber InterfaceIndex
  pmPowerMgmtSensorsTableNumber InterfaceIndex
  pmPowerMgmtSensorsTableName DisplayString
  pmPowerMgmtSensorsTablePortName DisplayString
  pmPowerMgmtSensorsTablePduId DisplayString
  pmPowerMgmtSensorsTableType INTEGER
  pmPowerMgmtSensorsTableStatus INTEGER
  pmPowerMgmtSensorsTableValue DisplayString
  pmPowerMgmtSensorsTableValueMax DisplayString
  pmPowerMgmtSensorsTableValueMin DisplayString
  pmPowerMgmtSensorsTableValueAvg DisplayString
  pmPowerMgmtSensorsTableValueInt Integer32
  pmPowerMgmtSensorsTableValueMaxInt Integer32
  pmPowerMgmtSensorsTableValueMinInt Integer32
  pmPowerMgmtSensorsTableValueAvgInt Integer32
  pmPowerMgmtSensorsTableValueReset INTEGER
  pmPowerMgmtSensorsTableHighCritical Integer32
  pmPowerMgmtSensorsTableHighWarning Integer32
  pmPowerMgmtSensorsTableLowWarning Integer32
  pmPowerMgmtSensorsTableLowCritical Integer32
  pmPowerMgmtSensorsTableUnit INTEGER
  pmPowerMgmtSensorsTableHighCriticalC Integer32
  pmPowerMgmtSensorsTableHighWarningC Integer32
  pmPowerMgmtSensorsTableLowWarningC Integer32
  pmPowerMgmtSensorsTableLowCriticalC Integer32
  pmPowerMgmtSensorsTableHighCriticalF Integer32
  pmPowerMgmtSensorsTableHighWarningF Integer32
  pmPowerMgmtSensorsTableLowWarningF Integer32
  pmPowerMgmtSensorsTableLowCriticalF Integer32

Defined Values

pm 1.3.6.1.4.1.10418.17
This module defines the Avocent MIB extensions to PM-PDU products.
MODULE-IDENTITY    

pmProducts 1.3.6.1.4.1.10418.17.1
OBJECT IDENTIFIER    

pmManagement 1.3.6.1.4.1.10418.17.2
OBJECT IDENTIFIER    

pm1024 1.3.6.1.4.1.10418.17.1.1
OBJECT IDENTIFIER    

pm2003 1.3.6.1.4.1.10418.17.1.2
OBJECT IDENTIFIER    

pm2006 1.3.6.1.4.1.10418.17.1.3
OBJECT IDENTIFIER    

pm2024 1.3.6.1.4.1.10418.17.1.4
OBJECT IDENTIFIER    

pm3003 1.3.6.1.4.1.10418.17.1.5
OBJECT IDENTIFIER    

pm3006 1.3.6.1.4.1.10418.17.1.6
OBJECT IDENTIFIER    

pm3024 1.3.6.1.4.1.10418.17.1.7
OBJECT IDENTIFIER    

pm1010 1.3.6.1.4.1.10418.17.1.8
OBJECT IDENTIFIER    

pm2010 1.3.6.1.4.1.10418.17.1.9
OBJECT IDENTIFIER    

pm3010 1.3.6.1.4.1.10418.17.1.10
OBJECT IDENTIFIER    

pm1020 1.3.6.1.4.1.10418.17.1.11
OBJECT IDENTIFIER    

pm2020 1.3.6.1.4.1.10418.17.1.12
OBJECT IDENTIFIER    

pm3020 1.3.6.1.4.1.10418.17.1.13
OBJECT IDENTIFIER    

pmAppliance 1.3.6.1.4.1.10418.17.2.1
OBJECT IDENTIFIER    

pmSessions 1.3.6.1.4.1.10418.17.2.2
OBJECT IDENTIFIER    

pmPowerMgmt 1.3.6.1.4.1.10418.17.2.5
OBJECT IDENTIFIER    

pmTrapObject 1.3.6.1.4.1.10418.17.2.6
OBJECT IDENTIFIER    

pmHostName 1.3.6.1.4.1.10418.17.2.1.1
The appliance name
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmProductModel 1.3.6.1.4.1.10418.17.2.1.2
The appliance product model
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

pmPartNumber 1.3.6.1.4.1.10418.17.2.1.3
The part number of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmSerialNumber 1.3.6.1.4.1.10418.17.2.1.4
The serial number of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmEIDNumber 1.3.6.1.4.1.10418.17.2.1.5
The electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmBootcodeVersion 1.3.6.1.4.1.10418.17.2.1.6
The version of the bootcode of this appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmFirmwareVersion 1.3.6.1.4.1.10418.17.2.1.7
The version of the firmware of this appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmReboot 1.3.6.1.4.1.10418.17.2.1.9
A set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately reboots.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reboot(2)  

pmActiveSessionsNumberOfSession 1.3.6.1.4.1.10418.17.2.2.1
Number of active sessions.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmActiveSessionsTable 1.3.6.1.4.1.10418.17.2.2.2
This table contains the list of active sessions.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmActiveSessionsTableEntry

pmActiveSessionsTableEntry 1.3.6.1.4.1.10418.17.2.2.2.1
each entry has the information about the active session
Status: current Access: not-accessible
OBJECT-TYPE    
  PmActiveSessionsTableEntry  

pmActiveSessionsTableIndex 1.3.6.1.4.1.10418.17.2.2.2.1.1
A unique index representing an entry in this table.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

pmActiveSessionsTableUser 1.3.6.1.4.1.10418.17.2.2.2.1.2
The name of the user that opens this session.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableGroup 1.3.6.1.4.1.10418.17.2.2.2.1.3
The name of the group that the user belongs to.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableType 1.3.6.1.4.1.10418.17.2.2.2.1.4
The session type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableConnection 1.3.6.1.4.1.10418.17.2.2.2.1.5
Connection type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableSessionTime 1.3.6.1.4.1.10418.17.2.2.2.1.6
Time of the session
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableFrom 1.3.6.1.4.1.10418.17.2.2.2.1.7
The source IP address of the session.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

pmActiveSessionsTableKill 1.3.6.1.4.1.10418.17.2.2.2.1.8
A set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immediately kills the session.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), killSession(2)  

pmPowerMgmtNumSerialPorts 1.3.6.1.4.1.10418.17.2.5.1
The number of Serial Ports that has PDU connected on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTable 1.3.6.1.4.1.10418.17.2.5.2
Information about each serial port thas has PDU connect.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtSerialTableEntry

pmPowerMgmtSerialTableEntry 1.3.6.1.4.1.10418.17.2.5.2.1
Information about each serial port thas has PDU connect.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtSerialTableEntry  

pmPowerMgmtSerialTableIndex 1.3.6.1.4.1.10418.17.2.5.2.1.1
The index of the register.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtSerialTablePortNumber 1.3.6.1.4.1.10418.17.2.5.2.1.2
The number of the serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTableDeviceName 1.3.6.1.4.1.10418.17.2.5.2.1.3
The device name of this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSerialTableNumberPDUs 1.3.6.1.4.1.10418.17.2.5.2.1.4
Total number of units connected in this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTableBuzzer 1.3.6.1.4.1.10418.17.2.5.2.1.10
set/get buzzer(s) on or off for the chain. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTableSyslog 1.3.6.1.4.1.10418.17.2.5.2.1.11
set/get syslog on or off for the chain. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTableOverCurrent 1.3.6.1.4.1.10418.17.2.5.2.1.12
set/get over current proctection on or off for the chain. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTableCycleInterval 1.3.6.1.4.1.10418.17.2.5.2.1.13
set/get cycle interval for the chain in whole seconds. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTablePollRate 1.3.6.1.4.1.10418.17.2.5.2.1.14
set/get the poll rate for the chain in whole seconds. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSerialTablePassWord 1.3.6.1.4.1.10418.17.2.5.2.1.15
set the global password for admin user
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSerialTableSave 1.3.6.1.4.1.10418.17.2.5.2.1.20
noAction(1) = always returned in a GET. Does nothing if SET. save(2) = when SET the save command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), save(2)  

pmPowerMgmtSerialTableRestore 1.3.6.1.4.1.10418.17.2.5.2.1.21
noAction(1) = always returned in a GET. Does nothing if SET. restore(2) = when SET the restore command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), restore(2)  

pmPowerMgmtPDUTable 1.3.6.1.4.1.10418.17.2.5.3
This table contains the list of detected PDUs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtPDUTableEntry

pmPowerMgmtPDUTableEntry 1.3.6.1.4.1.10418.17.2.5.3.1
each entry has the information about the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtPDUTableEntry  

pmPowerMgmtPDUTablePortNumber 1.3.6.1.4.1.10418.17.2.5.3.1.1
Number of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtPDUTablePduIndex 1.3.6.1.4.1.10418.17.2.5.3.1.2
A PDU position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

pmPowerMgmtPDUTablePduId 1.3.6.1.4.1.10418.17.2.5.3.1.3
PDU identification.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTablePortName 1.3.6.1.4.1.10418.17.2.5.3.1.4
Name of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTableModel 1.3.6.1.4.1.10418.17.2.5.3.1.5
Model of the PDU. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTableVendor 1.3.6.1.4.1.10418.17.2.5.3.1.6
Vendor of the PDU. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTableFirmwareVersion 1.3.6.1.4.1.10418.17.2.5.3.1.7
Version of the PDU firmware. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTableNumberOfOutlets 1.3.6.1.4.1.10418.17.2.5.3.1.8
Number of outlets of the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentNOS 1.3.6.1.4.1.10418.17.2.5.3.1.9
Number of current sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent1Value 1.3.6.1.4.1.10418.17.2.5.3.1.10
Current of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.). This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent1Max 1.3.6.1.4.1.10418.17.2.5.3.1.11
Maximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent2Value 1.3.6.1.4.1.10418.17.2.5.3.1.12
Current of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.). This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent2Max 1.3.6.1.4.1.10418.17.2.5.3.1.13
Maximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent3Value 1.3.6.1.4.1.10418.17.2.5.3.1.14
Current of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrent3Max 1.3.6.1.4.1.10418.17.2.5.3.1.15
Maximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperatureNOS 1.3.6.1.4.1.10418.17.2.5.3.1.16
Number of temperature sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature1Value 1.3.6.1.4.1.10418.17.2.5.3.1.17
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature1Max 1.3.6.1.4.1.10418.17.2.5.3.1.18
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature2Value 1.3.6.1.4.1.10418.17.2.5.3.1.19
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature2Max 1.3.6.1.4.1.10418.17.2.5.3.1.20
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature3Value 1.3.6.1.4.1.10418.17.2.5.3.1.21
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableTemperature3Max 1.3.6.1.4.1.10418.17.2.5.3.1.22
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidityNOS 1.3.6.1.4.1.10418.17.2.5.3.1.23
Number of humidity sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity1Value 1.3.6.1.4.1.10418.17.2.5.3.1.24
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity1Max 1.3.6.1.4.1.10418.17.2.5.3.1.25
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity2Value 1.3.6.1.4.1.10418.17.2.5.3.1.26
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity2Max 1.3.6.1.4.1.10418.17.2.5.3.1.27
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity3Value 1.3.6.1.4.1.10418.17.2.5.3.1.28
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableHumidity3Max 1.3.6.1.4.1.10418.17.2.5.3.1.29
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltageNOS 1.3.6.1.4.1.10418.17.2.5.3.1.30
Number of voltage sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage1Value 1.3.6.1.4.1.10418.17.2.5.3.1.31
Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage1Max 1.3.6.1.4.1.10418.17.2.5.3.1.32
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage2Value 1.3.6.1.4.1.10418.17.2.5.3.1.33
Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage2Max 1.3.6.1.4.1.10418.17.2.5.3.1.34
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage3Value 1.3.6.1.4.1.10418.17.2.5.3.1.35
Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltage3Max 1.3.6.1.4.1.10418.17.2.5.3.1.36
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableNumberOfPhases 1.3.6.1.4.1.10418.17.2.5.3.1.37
Number of phases of the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableNumberOfBanks 1.3.6.1.4.1.10418.17.2.5.3.1.38
Number of banks in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableNumberOfSensors 1.3.6.1.4.1.10418.17.2.5.3.1.40
Number of sensors in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableFactoryDefault 1.3.6.1.4.1.10418.17.2.5.3.1.41
A set value of 2 will set the PDU to factory default settings. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the factory default command is sent to the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTableColdStartDelay 1.3.6.1.4.1.10418.17.2.5.3.1.42
PDUs cold start delay in whole seconds (0-60). Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableReboot 1.3.6.1.4.1.10418.17.2.5.3.1.43
A set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the reboot command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reboot(2)  

pmPowerMgmtPDUTableMaxCurrent 1.3.6.1.4.1.10418.17.2.5.3.1.44
Maximum value of current allowed in the PDU (A x 10).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableAlarm 1.3.6.1.4.1.10418.17.2.5.3.1.45
Show the PDU alarm status. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

pmPowerMgmtPDUTableCurrentValue 1.3.6.1.4.1.10418.17.2.5.3.1.50
Actual value of current in the PDU (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentMax 1.3.6.1.4.1.10418.17.2.5.3.1.51
Maximum value of current in the PDU (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentMin 1.3.6.1.4.1.10418.17.2.5.3.1.52
Minimum value of current in the PDU (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentAvg 1.3.6.1.4.1.10418.17.2.5.3.1.53
Average value of current in the PDU (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentReset 1.3.6.1.4.1.10418.17.2.5.3.1.54
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTablePowerValue 1.3.6.1.4.1.10418.17.2.5.3.1.60
Actual value of power in the PDU (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerMax 1.3.6.1.4.1.10418.17.2.5.3.1.61
Maximum value of power in the PDU (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerMin 1.3.6.1.4.1.10418.17.2.5.3.1.62
Minimum value of power in the PDU (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerAvg 1.3.6.1.4.1.10418.17.2.5.3.1.63
Average value of power in the PDU (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerReset 1.3.6.1.4.1.10418.17.2.5.3.1.64
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTablePowerType 1.3.6.1.4.1.10418.17.2.5.3.1.65
Type of power values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPDUTableVoltageValue 1.3.6.1.4.1.10418.17.2.5.3.1.70
Actual value of voltage in the PDU (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltageMax 1.3.6.1.4.1.10418.17.2.5.3.1.71
Maximum value of voltage in the PDU (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltageMin 1.3.6.1.4.1.10418.17.2.5.3.1.72
Minimum value of voltage in the PDU (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltageAvg 1.3.6.1.4.1.10418.17.2.5.3.1.73
Average value of voltage in the PDU (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableVoltageReset 1.3.6.1.4.1.10418.17.2.5.3.1.74
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTableVoltageType 1.3.6.1.4.1.10418.17.2.5.3.1.75
Type of voltage values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPDUTablePowerFactorValue 1.3.6.1.4.1.10418.17.2.5.3.1.80
Actual value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerFactorMax 1.3.6.1.4.1.10418.17.2.5.3.1.81
Maximum value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerFactorMin 1.3.6.1.4.1.10418.17.2.5.3.1.82
Minimum value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerFactorAvg 1.3.6.1.4.1.10418.17.2.5.3.1.83
Average value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTablePowerFactorReset 1.3.6.1.4.1.10418.17.2.5.3.1.84
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTablePowerFactorType 1.3.6.1.4.1.10418.17.2.5.3.1.85
Type of power values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPDUTablePowerControl 1.3.6.1.4.1.10418.17.2.5.3.1.90
A set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4)  

pmPowerMgmtPDUTableResetOCP 1.3.6.1.4.1.10418.17.2.5.3.1.91
A set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPDUTableCurrentHighCritical 1.3.6.1.4.1.10418.17.2.5.3.1.100
outlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentHighWarning 1.3.6.1.4.1.10418.17.2.5.3.1.101
outlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentLowWarning 1.3.6.1.4.1.10418.17.2.5.3.1.102
outlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableCurrentLowCritical 1.3.6.1.4.1.10418.17.2.5.3.1.103
outlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableEnergyValue 1.3.6.1.4.1.10418.17.2.5.3.1.105
pdu energy value (Wh). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPDUTableEnergyStartTime 1.3.6.1.4.1.10418.17.2.5.3.1.106
time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPDUTableEnergyReset 1.3.6.1.4.1.10418.17.2.5.3.1.107
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtTotalNumberOfOutlets 1.3.6.1.4.1.10418.17.2.5.4
Number of outlets managed by the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTable 1.3.6.1.4.1.10418.17.2.5.5
This table contains the information about outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtOutletsTableEntry

pmPowerMgmtOutletsTableEntry 1.3.6.1.4.1.10418.17.2.5.5.1
each entry has the information about the outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtOutletsTableEntry  

pmPowerMgmtOutletsTablePortNumber 1.3.6.1.4.1.10418.17.2.5.5.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtOutletsTablePduNumber 1.3.6.1.4.1.10418.17.2.5.5.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtOutletsTableNumber 1.3.6.1.4.1.10418.17.2.5.5.1.3
Number of the outlet in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtOutletsTableName 1.3.6.1.4.1.10418.17.2.5.5.1.4
Name of the outlet.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtOutletsTableStatus 1.3.6.1.4.1.10418.17.2.5.5.1.5
Status of the outlet. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2), offLocked(3), onLocked(4), offCycle(5), onPendingOff(6), offPendingOn(7), onPendingCycle(8), notSet(9), onFixed(10), offShutdown(11), tripped(12)  

pmPowerMgmtOutletsTablePowerControl 1.3.6.1.4.1.10418.17.2.5.5.1.6
A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. powerLock(5)= when SET the power lock command is sent to PDU. powerUnlock(6)=when SET the power unlock command is sent to PDU. The powerLock and powerUnlock are valid only for Cyclades-PM PDUs
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4), powerLock(5), powerUnlock(6)  

pmPowerMgmtOutletsTablePortName 1.3.6.1.4.1.10418.17.2.5.5.1.7
Serial Port Name where the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtOutletsTablePduId 1.3.6.1.4.1.10418.17.2.5.5.1.8
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtOutletsTablePostOnDelay 1.3.6.1.4.1.10418.17.2.5.5.1.9
post on delay for the outlet (seconds x 10) Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePostOffDelay 1.3.6.1.4.1.10418.17.2.5.5.1.10
post off delay for the outlet (seconds x 10) Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableAlarm 1.3.6.1.4.1.10418.17.2.5.5.1.45
Show the outlet alarm status. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

pmPowerMgmtOutletsTableCurrentValue 1.3.6.1.4.1.10418.17.2.5.5.1.50
Actual value of current in the outlet (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentMax 1.3.6.1.4.1.10418.17.2.5.5.1.51
Maximum value of current in the outlet (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentMin 1.3.6.1.4.1.10418.17.2.5.5.1.52
Minimum value of current in the outlet (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentAvg 1.3.6.1.4.1.10418.17.2.5.5.1.53
Average value of current in the outlet (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentReset 1.3.6.1.4.1.10418.17.2.5.5.1.54
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtOutletsTablePowerValue 1.3.6.1.4.1.10418.17.2.5.5.1.60
Actual value of power in the outlet (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerMax 1.3.6.1.4.1.10418.17.2.5.5.1.61
Maximum value of power in the outlet (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerMin 1.3.6.1.4.1.10418.17.2.5.5.1.62
Minimum value of power in the outlet (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerAvg 1.3.6.1.4.1.10418.17.2.5.5.1.63
Average value of power in the outlet (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerReset 1.3.6.1.4.1.10418.17.2.5.5.1.64
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtOutletsTablePowerType 1.3.6.1.4.1.10418.17.2.5.5.1.65
Type of power values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtOutletsTableVoltageValue 1.3.6.1.4.1.10418.17.2.5.5.1.70
Actual value of voltage in the outlet (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableVoltageMax 1.3.6.1.4.1.10418.17.2.5.5.1.71
Maximum value of voltage in the outlet (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableVoltageMin 1.3.6.1.4.1.10418.17.2.5.5.1.72
Minimum value of voltage in the outlet (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableVoltageAvg 1.3.6.1.4.1.10418.17.2.5.5.1.73
Average value of voltage in the outlet (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableVoltageReset 1.3.6.1.4.1.10418.17.2.5.5.1.74
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtOutletsTableVoltageType 1.3.6.1.4.1.10418.17.2.5.5.1.75
Type of voltage values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtOutletsTablePowerFactorValue 1.3.6.1.4.1.10418.17.2.5.5.1.80
Actual value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerFactorMax 1.3.6.1.4.1.10418.17.2.5.5.1.81
Maximum value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerFactorMin 1.3.6.1.4.1.10418.17.2.5.5.1.82
Minimum value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerFactorAvg 1.3.6.1.4.1.10418.17.2.5.5.1.83
Average value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTablePowerFactorReset 1.3.6.1.4.1.10418.17.2.5.5.1.84
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtOutletsTablePowerFactorType 1.3.6.1.4.1.10418.17.2.5.5.1.85
Type of power factor values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtOutletsTableCurrentHighCritical 1.3.6.1.4.1.10418.17.2.5.5.1.100
outlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentHighWarning 1.3.6.1.4.1.10418.17.2.5.5.1.101
outlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentLowWarning 1.3.6.1.4.1.10418.17.2.5.5.1.102
outlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableCurrentLowCritical 1.3.6.1.4.1.10418.17.2.5.5.1.103
outlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableEnergyValue 1.3.6.1.4.1.10418.17.2.5.5.1.105
outlet energy value (Wh). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtOutletsTableEnergyStartTime 1.3.6.1.4.1.10418.17.2.5.5.1.106
time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtOutletsTableEnergyReset 1.3.6.1.4.1.10418.17.2.5.5.1.107
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtNumberOfOutletGroup 1.3.6.1.4.1.10418.17.2.5.6
Number of configured group of outlets.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtGroupTable 1.3.6.1.4.1.10418.17.2.5.7
This table contains the information about group of outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtGroupTableEntry

pmPowerMgmtGroupTableEntry 1.3.6.1.4.1.10418.17.2.5.7.1
each entry has the information about group of outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtGroupTableEntry  

pmPowerMgmtGroupTableIndex 1.3.6.1.4.1.10418.17.2.5.7.1.1
Index of the group.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

pmPowerMgmtGroupTableName 1.3.6.1.4.1.10418.17.2.5.7.1.2
Name of the group of outlets.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtGroupTableStatus 1.3.6.1.4.1.10418.17.2.5.7.1.3
Status of the group of outlet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

pmPowerMgmtGroupTablePowerControl 1.3.6.1.4.1.10418.17.2.5.7.1.4
A set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4)  

pmPowerMgmtTotalNumberOfPhases 1.3.6.1.4.1.10418.17.2.5.8
Number of phases managed by the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTable 1.3.6.1.4.1.10418.17.2.5.9
This table contains the information about phases.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtPhasesTableEntry

pmPowerMgmtPhasesTableEntry 1.3.6.1.4.1.10418.17.2.5.9.1
each entry has the information about the phases.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtPhasesTableEntry  

pmPowerMgmtPhasesTablePortNumber 1.3.6.1.4.1.10418.17.2.5.9.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtPhasesTablePduNumber 1.3.6.1.4.1.10418.17.2.5.9.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtPhasesTableNumber 1.3.6.1.4.1.10418.17.2.5.9.1.3
Number of the phase in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtPhasesTableName 1.3.6.1.4.1.10418.17.2.5.9.1.4
Name of the phase. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPhasesTablePortName 1.3.6.1.4.1.10418.17.2.5.9.1.5
Serial Port Name where the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPhasesTablePduId 1.3.6.1.4.1.10418.17.2.5.9.1.6
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtPhasesTableAlarm 1.3.6.1.4.1.10418.17.2.5.9.1.45
Show the phase alarm status. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

pmPowerMgmtPhasesTableCurrentValue 1.3.6.1.4.1.10418.17.2.5.9.1.50
Actual value of current in the phase (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentMax 1.3.6.1.4.1.10418.17.2.5.9.1.51
Maximum value of current in the phase (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentMin 1.3.6.1.4.1.10418.17.2.5.9.1.52
Minimum value of current in the phase (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentAvg 1.3.6.1.4.1.10418.17.2.5.9.1.53
Average value of current in the phase (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentReset 1.3.6.1.4.1.10418.17.2.5.9.1.54
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPhasesTablePowerValue 1.3.6.1.4.1.10418.17.2.5.9.1.60
Actual value of power in the phase (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerMax 1.3.6.1.4.1.10418.17.2.5.9.1.61
Maximum value of power in the phase (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerMin 1.3.6.1.4.1.10418.17.2.5.9.1.62
Minimum value of power in the phase (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerAvg 1.3.6.1.4.1.10418.17.2.5.9.1.63
Average value of power in the phase (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerReset 1.3.6.1.4.1.10418.17.2.5.9.1.64
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPhasesTablePowerType 1.3.6.1.4.1.10418.17.2.5.9.1.65
Type of power values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPhasesTableVoltageValue 1.3.6.1.4.1.10418.17.2.5.9.1.70
Actual value of voltage in the phase (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableVoltageMax 1.3.6.1.4.1.10418.17.2.5.9.1.71
Maximum value of voltage in the phase (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableVoltageMin 1.3.6.1.4.1.10418.17.2.5.9.1.72
Minimum value of voltage in the phase (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableVoltageAvg 1.3.6.1.4.1.10418.17.2.5.9.1.73
Average value of voltage in the phase (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableVoltageReset 1.3.6.1.4.1.10418.17.2.5.9.1.74
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPhasesTableVoltageType 1.3.6.1.4.1.10418.17.2.5.9.1.75
Type of voltage values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPhasesTablePowerFactorValue 1.3.6.1.4.1.10418.17.2.5.9.1.80
Actual value of power factor in the phase (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerFactorMax 1.3.6.1.4.1.10418.17.2.5.9.1.81
Maximum value of power factor in the phase (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerFactorMin 1.3.6.1.4.1.10418.17.2.5.9.1.82
Minimum value of power factor in the phase (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerFactorAvg 1.3.6.1.4.1.10418.17.2.5.9.1.83
Average value of power factor in the phase (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTablePowerFactorReset 1.3.6.1.4.1.10418.17.2.5.9.1.84
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtPhasesTablePowerFactorType 1.3.6.1.4.1.10418.17.2.5.9.1.85
Type of power factor values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtPhasesTableCurrentHighCritical 1.3.6.1.4.1.10418.17.2.5.9.1.100
phase high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentHighWarning 1.3.6.1.4.1.10418.17.2.5.9.1.101
phase high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentLowWarning 1.3.6.1.4.1.10418.17.2.5.9.1.102
phase low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtPhasesTableCurrentLowCritical 1.3.6.1.4.1.10418.17.2.5.9.1.103
phase low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtTotalNumberOfBanks 1.3.6.1.4.1.10418.17.2.5.10
Number of banks managed by the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTable 1.3.6.1.4.1.10418.17.2.5.11
This table contains the information about banks.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtBanksTableEntry

pmPowerMgmtBanksTableEntry 1.3.6.1.4.1.10418.17.2.5.11.1
each entry has the information about the banks.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtBanksTableEntry  

pmPowerMgmtBanksTablePortNumber 1.3.6.1.4.1.10418.17.2.5.11.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtBanksTablePduNumber 1.3.6.1.4.1.10418.17.2.5.11.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtBanksTableNumber 1.3.6.1.4.1.10418.17.2.5.11.1.3
Number of the bank in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtBanksTableName 1.3.6.1.4.1.10418.17.2.5.11.1.4
Name of the bank.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtBanksTablePortName 1.3.6.1.4.1.10418.17.2.5.11.1.5
Serial Port Name where the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtBanksTablePduId 1.3.6.1.4.1.10418.17.2.5.11.1.6
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtBanksTableAlarm 1.3.6.1.4.1.10418.17.2.5.11.1.45
Show the bank alarm status. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

pmPowerMgmtBanksTableCurrentValue 1.3.6.1.4.1.10418.17.2.5.11.1.50
Actual value of current in the bank (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentMax 1.3.6.1.4.1.10418.17.2.5.11.1.51
Maximum value of current in the bank (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentMin 1.3.6.1.4.1.10418.17.2.5.11.1.52
Minimum value of current in the bank (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentAvg 1.3.6.1.4.1.10418.17.2.5.11.1.53
Average value of current in the bank (A x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentReset 1.3.6.1.4.1.10418.17.2.5.11.1.54
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtBanksTablePowerValue 1.3.6.1.4.1.10418.17.2.5.11.1.60
Actual value of power in the bank (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerMax 1.3.6.1.4.1.10418.17.2.5.11.1.61
Maximum value of power in the bank (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerMin 1.3.6.1.4.1.10418.17.2.5.11.1.62
Minimum value of power in the bank (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerAvg 1.3.6.1.4.1.10418.17.2.5.11.1.63
Average value of power in the bank (W x 10). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerReset 1.3.6.1.4.1.10418.17.2.5.11.1.64
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtBanksTablePowerType 1.3.6.1.4.1.10418.17.2.5.11.1.65
Type of power values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtBanksTableVoltageValue 1.3.6.1.4.1.10418.17.2.5.11.1.70
Actual value of voltage in the bank (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableVoltageMax 1.3.6.1.4.1.10418.17.2.5.11.1.71
Maximum value of voltage in the bank (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableVoltageMin 1.3.6.1.4.1.10418.17.2.5.11.1.72
Minimum value of voltage in the bank (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableVoltageAvg 1.3.6.1.4.1.10418.17.2.5.11.1.73
Average value of voltage in the bank (V). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableVoltageReset 1.3.6.1.4.1.10418.17.2.5.11.1.74
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtBanksTableVoltageType 1.3.6.1.4.1.10418.17.2.5.11.1.75
Type of voltage values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtBanksTablePowerFactorValue 1.3.6.1.4.1.10418.17.2.5.11.1.80
Actual value of power factor in the bank (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerFactorMax 1.3.6.1.4.1.10418.17.2.5.11.1.81
Maximum value of power factor in the bank (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerFactorMin 1.3.6.1.4.1.10418.17.2.5.11.1.82
Minimum value of power factor in the bank (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerFactorAvg 1.3.6.1.4.1.10418.17.2.5.11.1.83
Average value of power factor in the bank (Pf x 100). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTablePowerFactorReset 1.3.6.1.4.1.10418.17.2.5.11.1.84
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtBanksTablePowerFactorType 1.3.6.1.4.1.10418.17.2.5.11.1.85
Type of power factor values. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), measured(2)  

pmPowerMgmtBanksTableCurrentHighCritical 1.3.6.1.4.1.10418.17.2.5.11.1.100
bank high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentHighWarning 1.3.6.1.4.1.10418.17.2.5.11.1.101
bank high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentLowWarning 1.3.6.1.4.1.10418.17.2.5.11.1.102
bank low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableCurrentLowCritical 1.3.6.1.4.1.10418.17.2.5.11.1.103
bank low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableEnergyValue 1.3.6.1.4.1.10418.17.2.5.11.1.105
bank energy value (Wh). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtBanksTableEnergyStartTime 1.3.6.1.4.1.10418.17.2.5.11.1.106
time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtBanksTableEnergyReset 1.3.6.1.4.1.10418.17.2.5.11.1.107
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtTotalNumberOfSensors 1.3.6.1.4.1.10418.17.2.5.12
Number of Sensors managed by the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTable 1.3.6.1.4.1.10418.17.2.5.13
This table contains the information about sensors.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PmPowerMgmtSensorsTableEntry

pmPowerMgmtSensorsTableEntry 1.3.6.1.4.1.10418.17.2.5.13.1
each entry has the information about the sensors.
Status: current Access: not-accessible
OBJECT-TYPE    
  PmPowerMgmtSensorsTableEntry  

pmPowerMgmtSensorsTablePortNumber 1.3.6.1.4.1.10418.17.2.5.13.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtSensorsTablePduNumber 1.3.6.1.4.1.10418.17.2.5.13.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtSensorsTableNumber 1.3.6.1.4.1.10418.17.2.5.13.1.3
Number of the sensor in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

pmPowerMgmtSensorsTableName 1.3.6.1.4.1.10418.17.2.5.13.1.4
Name of the sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTablePortName 1.3.6.1.4.1.10418.17.2.5.13.1.5
Serial Port Name where the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTablePduId 1.3.6.1.4.1.10418.17.2.5.13.1.6
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTableType 1.3.6.1.4.1.10418.17.2.5.13.1.7
The type of environmental monitor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER temp-internal(1), temperature(2), humidity(3), air-flow(4), smoke(5), dry-concact(6), water-level(7), motion(8), unplugged(9), unknown(10)  

pmPowerMgmtSensorsTableStatus 1.3.6.1.4.1.10418.17.2.5.13.1.8
Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), triggered(2), not-applicable(3), opened(4), closed(5)  

pmPowerMgmtSensorsTableValue 1.3.6.1.4.1.10418.17.2.5.13.1.20
Actual value of the sensor. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTableValueMax 1.3.6.1.4.1.10418.17.2.5.13.1.21
Maximum value of the sensor. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTableValueMin 1.3.6.1.4.1.10418.17.2.5.13.1.22
Minimum value of the sensor. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTableValueAvg 1.3.6.1.4.1.10418.17.2.5.13.1.23
Average value of the sensor. Returns N/A if not applicable.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pmPowerMgmtSensorsTableValueInt 1.3.6.1.4.1.10418.17.2.5.13.1.25
Actual value of the sensor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableValueMaxInt 1.3.6.1.4.1.10418.17.2.5.13.1.26
Maximum value of the sensor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableValueMinInt 1.3.6.1.4.1.10418.17.2.5.13.1.27
Minimum value of the sensor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableValueAvgInt 1.3.6.1.4.1.10418.17.2.5.13.1.28
Average value of the sensor. Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableValueReset 1.3.6.1.4.1.10418.17.2.5.13.1.30
noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to sensor.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

pmPowerMgmtSensorsTableHighCritical 1.3.6.1.4.1.10418.17.2.5.13.1.40
sensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableHighWarning 1.3.6.1.4.1.10418.17.2.5.13.1.41
sensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighCritical or lower than LowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowWarning 1.3.6.1.4.1.10418.17.2.5.13.1.42
sensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighWarning or lower than LowCritical. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowCritical 1.3.6.1.4.1.10418.17.2.5.13.1.43
sensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than LowWarning. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableUnit 1.3.6.1.4.1.10418.17.2.5.13.1.45
sensor unit. Returns 0 if not supported.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER undefined(1), fahrenheit(2), celsius(3), percent(4), afu(5)  

pmPowerMgmtSensorsTableHighCriticalC 1.3.6.1.4.1.10418.17.2.5.13.1.50
sensor high critical (alarm) threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableHighWarningC 1.3.6.1.4.1.10418.17.2.5.13.1.51
sensor high warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowWarningC 1.3.6.1.4.1.10418.17.2.5.13.1.52
sensor low warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowCriticalC 1.3.6.1.4.1.10418.17.2.5.13.1.53
sensor low critical threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableHighCriticalF 1.3.6.1.4.1.10418.17.2.5.13.1.60
sensor high critical (alarm) threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableHighWarningF 1.3.6.1.4.1.10418.17.2.5.13.1.61
sensor high warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowWarningF 1.3.6.1.4.1.10418.17.2.5.13.1.62
sensor low warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pmPowerMgmtSensorsTableLowCriticalF 1.3.6.1.4.1.10418.17.2.5.13.1.63
sensor low critical threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32