PDU2-MIB

File: PDU2-MIB.mib (791120 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC
INET-ADDRESS-MIB RFC1213-MIB

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises Integer32 Unsigned32
IpAddress MODULE-COMPLIANCE OBJECT-GROUP
NOTIFICATION-GROUP TEXTUAL-CONVENTION DisplayString
MacAddress TruthValue RowPointer
InetAddressType InetAddress InetPortNumber
sysContact sysName sysLocation

Defined Types

SensorTypeEnumeration  
The types a sensor can be.
TEXTUAL-CONVENTION    
  INTEGER rmsCurrent(1), peakCurrent(2), unbalancedCurrent(3), rmsVoltage(4), activePower(5), apparentPower(6), powerFactor(7), activeEnergy(8), apparentEnergy(9), temperature(10), humidity(11), airFlow(12), airPressure(13), onOff(14), trip(15), vibration(16), waterDetection(17), smokeDetection(18), binary(19), contact(20), fanSpeed(21), surgeProtectorStatus(22), frequency(23), phaseAngle(24), rmsVoltageLN(25), residualCurrent(26), rcmState(27), absoluteHumidity(28), reactivePower(29), other(30), none(31), powerQuality(32), overloadStatus(33), overheatStatus(34), displacementPowerFactor(35), fanStatus(37), inletPhaseSyncAngle(38), inletPhaseSync(39), operatingState(40), activeInlet(41), illuminance(42), doorContact(43), tamperDetection(44), motionDetection(45), i1smpsStatus(46), i2smpsStatus(47), switchStatus(48)  

SensorStateEnumeration  
The states a sensor can be in.
TEXTUAL-CONVENTION    
  INTEGER unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11), ok(12), fail(14), yes(15), no(16), standby(17), one(18), two(19), inSync(20), outOfSync(21), i1OpenFault(22), i1ShortFault(23), i2OpenFault(24), i2ShortFault(25), fault(26), warning(27), critical(28), selfTest(29), nonRedundant(30)  

PlugTypeEnumeration  
The types of inlet plug.
TEXTUAL-CONVENTION    
  INTEGER plugOTHER(-1), plugNONE(0), plug56P320(1), plug56P520(2), plug56P532(3), plugCS8365C(4), plugIEC320C14(5), plugIEC320C20(6), plugIEC603093WIRE250V16A(7), plugIEC603093WIRE250V20A(8), plugIEC603093WIRE250V30A(9), plugIEC603093WIRE250V32A(10), plugIEC603093WIRE250V60A(11), plugIEC603093WIRE250V63A(12), plugIEC603093WIRE250V100A(13), plugIEC603093WIRE250V125A(14), plugIEC603094WIRE250V20A(15), plugIEC603094WIRE250V30A(16), plugIEC603094WIRE250V60A(17), plugIEC603094WIRE250V100A(18), plugIEC603095WIRE208V20A(23), plugIEC603095WIRE208V30A(24), plugIEC603095WIRE208V60A(25), plugIEC603095WIRE208V100A(26), plugIEC603095WIRE415V16A(27), plugIEC603095WIRE415V32A(28), plugIEC603095WIRE415V63A(29), plugIEC603095WIRE415V125A(30), plugIEC603095WIRE480V20A(31), plugIEC603095WIRE480V30A(32), plugIEC603095WIRE480V60A(33), plugIEC603095WIRE480V100A(34), plugNEMA515P(35), plugNEMAL515P(36), plugNEMA520P(37), plugNEMAL520P(38), plugNEMAL530P(39), plugNEMAL615P(40), plugNEMAL620P(41), plugNEMAL630P(42), plugNEMAL1520P(43), plugNEMAL1530P(44), plugNEMAL2120P(45), plugNEMAL2130P(46), plugNEMAL2230P(47), plug56P320F(48), plug56PA320(49)  

ReceptacleTypeEnumeration  
The types of outlet receptacle.
TEXTUAL-CONVENTION    
  INTEGER receptacleOTHER(-1), receptacleNONE(0), receptacleBS1363(1), receptacle56P532(3), receptacleCS8364C(4), receptacleIEC320C13(5), receptacleIEC320C19(6), receptacleIEC603093WIRE250V16A(7), receptacleIEC603093WIRE250V20A(8), receptacleIEC603093WIRE250V30A(9), receptacleIEC603093WIRE250V32A(10), receptacleIEC603093WIRE250V60A(11), receptacleIEC603093WIRE250V63A(12), receptacleIEC603093WIRE250V100A(13), receptacleIEC603093WIRE250V125A(14), receptacleIEC603094WIRE250V20A(15), receptacleIEC603094WIRE250V30A(16), receptacleIEC603094WIRE250V60A(17), receptacleIEC603094WIRE250V100A(18), receptacleIEC603095WIRE208V20A(23), receptacleIEC603095WIRE208V30A(24), receptacleIEC603095WIRE208V60A(25), receptacleIEC603095WIRE208V100A(26), receptacleIEC603095WIRE415V16A(27), receptacleIEC603095WIRE415V32A(28), receptacleIEC603095WIRE415V63A(29), receptacleIEC603095WIRE415V125A(30), receptacleIEC603095WIRE480V20A(31), receptacleIEC603095WIRE480V30A(32), receptacleIEC603095WIRE480V60A(33), receptacleIEC603095WIRE480V100A(34), receptacleNEMA515R(35), receptacleNEMAL515R(36), receptacleNEMA520R(37), receptacleNEMAL520R(38), receptacleNEMAL530R(39), receptacleNEMAL615R(40), receptacleNEMAL620R(41), receptacleNEMAL630R(42), receptacleNEMAL1520R(43), receptacleNEMAL1530R(44), receptacleNEMAL2120RP(45), receptacleNEMAL2130R(46), receptacleSCHUKOTYPEE(47), receptacleSCHUKOTYPEF(48)  

OverCurrentProtectorTypeEnumeration  
The types of overcurrent protectors.
TEXTUAL-CONVENTION    
  INTEGER ocpBREAKER1POLE(1), ocpBREAKER2POLE(2), ocpBREAKER3POLE(3), ocpFUSE(4), ocpFUSEPAIR(5), ocpRCBO2POLE(6), ocpRCBO3POLE(7), ocpRCBO4POLE(8)  

BoardTypeEnumeration  
The types of boards.
TEXTUAL-CONVENTION    
  INTEGER mainController(1), inletController(2), outletController(3), meteringController(4)  

OutletSwitchingOperationsEnumeration  
The switching operations on an outlet.
TEXTUAL-CONVENTION    
  INTEGER off(0), on(1), cycle(2)  

SensorUnitsEnumeration  
The sensor units.
TEXTUAL-CONVENTION    
  INTEGER none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19), degrees(20), lux(21), grampercubicmeter(22), var(23)  

DaisychainMemberTypeEnumeration  
The daisy chain member type.
TEXTUAL-CONVENTION    
  INTEGER standalone(0), master(1), slave(2)  

URL  
A Uniform Resource Locator (URL), as defined in RFC1738.
TEXTUAL-CONVENTION    
  OCTET STRING Size(0..255)  

GlobalOutletStateOnStartupEnumeration  
The global outlet state on device start up; can be overridden per outlet.
TEXTUAL-CONVENTION    
  INTEGER off(0), on(1), lastKnownState(2)  

OutletStateOnStartupEnumeration  
The outlet state on device start up; this overrides the global value.
TEXTUAL-CONVENTION    
  INTEGER off(0), on(1), lastKnownState(2), globalOutletStateOnStartup(3)  

ExternalSensorsZCoordinateUnitsEnumeration  
The units of the external Sensor Z Coordinate. rackUnits implies that the Z Coordinate for all external sensors is in rack Units (U) text implies that the Z Coordinate for all external sensors is a text string (label)
TEXTUAL-CONVENTION    
  INTEGER rackUnits(0), text(1)  

HundredthsOfAPercentage  
Data type for reporting values in hundredths of percentage, i.e. 0.01 %.
TEXTUAL-CONVENTION    
  Unsigned32 0..10000  

DeviceIdentificationParameterEnumeration  
The configurable parameters.
TEXTUAL-CONVENTION    
  INTEGER pduName(0), sysContact(1), sysName(2), sysLocation(3)  

TransferSwitchTransferReasonEnumeration  
Transfer Switch Transfer Reason
TEXTUAL-CONVENTION    
  INTEGER unknown(0), startup(1), manualTransfer(2), automaticReTransfer(3), powerFailure(4), powerQuality(5), overloadAlarm(6), overheatAlarm(7), internalFailure(8)  

ProductTypeEnumeration  
The product types.
TEXTUAL-CONVENTION    
  INTEGER rackPdu(0), bcm(1), transferSwitch(2), powerMeter(3)  

RelayPowerLossBehaviorEnumeration  
The type of relay behavior on power loss.
TEXTUAL-CONVENTION    
  INTEGER nonLatching(0), latching(1)  

DeviceCascadeTypeEnumeration  
The type of configured cascading on this device.
TEXTUAL-CONVENTION    
  INTEGER bridging(0), portForwarding(1)  

PeripheralDeviceFirmwareUpdateStateEnumeration  
The state of an peripheral device firmware update.
TEXTUAL-CONVENTION    
  INTEGER started(1), successful(2), failed(3)  

PanelLayoutEnumeration  
The panel circuit position layout.
TEXTUAL-CONVENTION    
  INTEGER invalid(-1), oneColumn(1), twoColumns(2)  

PanelNumberingEnumeration  
The panel circuit position numbering scheme.
TEXTUAL-CONVENTION    
  INTEGER invalid(-1), oddEven(1), sequential(2)  

CircuitTypeEnumeration  
The panel circuit types.
TEXTUAL-CONVENTION    
  INTEGER onePhaseLL(1), onePhaseLN(2), onePhaseLLN(3), threePhase(4)  

PhaseEnumeration  
The power phase.
TEXTUAL-CONVENTION    
  INTEGER phaseA(1), phaseB(2), phaseC(3), neutral(4), earth(5)  

LineEnumeration  
The Lines: L1, L2, L3, N.
TEXTUAL-CONVENTION    
  INTEGER lineL1(1), lineL2(2), lineL3(3), lineNeutral(4)  

PowerMeterTypeEnumeration  
The power meter types
TEXTUAL-CONVENTION    
  INTEGER singlePhase(1), splitPhase(2), threePhase(3)  

NetworkInterfaceTypeEnumeration  
The type of network interface.
TEXTUAL-CONVENTION    
  INTEGER wired(0), wireless(1)  

AddressSourceEnumeration  
How was the address obtained?
TEXTUAL-CONVENTION    
  INTEGER static(1), dhcp(2), dhcpv6(3)  

NameplateEntryStruct  
SEQUENCE    
  pduId Integer32
  pduManufacturer DisplayString
  pduModel DisplayString
  pduSerialNumber DisplayString
  pduRatedVoltage DisplayString
  pduRatedCurrent DisplayString
  pduRatedFrequency DisplayString
  pduRatedVA DisplayString
  pduImage URL

UnitConfigurationEntryStruct  
SEQUENCE    
  inletCount Integer32
  overCurrentProtectorCount Integer32
  outletCount Integer32
  inletControllerCount Integer32
  outletControllerCount Integer32
  externalSensorCount Integer32
  pxIPAddress IpAddress
  netmask IpAddress
  gateway IpAddress
  pxMACAddress MacAddress
  utcOffset DisplayString
  pduName DisplayString
  networkInterfaceType NetworkInterfaceTypeEnumeration
  externalSensorsZCoordinateUnits ExternalSensorsZCoordinateUnitsEnumeration
  unitDeviceCapabilities BITS
  outletSequencingDelay Unsigned32
  globalOutletPowerCyclingPowerOffPeriod Unsigned32
  globalOutletStateOnStartup GlobalOutletStateOnStartupEnumeration
  outletPowerupSequence DisplayString
  pduPowerCyclingPowerOffPeriod Unsigned32
  pduDaisychainMemberType DaisychainMemberTypeEnumeration
  managedExternalSensorCount Integer32
  pxInetAddressType InetAddressType
  pxInetIPAddress InetAddress
  pxInetNetmask InetAddress
  pxInetGateway InetAddress
  loadShedding TruthValue
  serverCount Integer32
  inrushGuardDelay Unsigned32
  cascadedDeviceConnected TruthValue
  synchronizeWithNTPServer TruthValue
  useDHCPProvidedNTPServer TruthValue
  firstNTPServerAddressType InetAddressType
  firstNTPServerAddress InetAddress
  secondNTPServerAddressType InetAddressType
  secondNTPServerAddress InetAddress
  wireCount Integer32
  transferSwitchCount Integer32
  productType ProductTypeEnumeration
  meteringControllerCount Integer32
  relayBehaviorOnPowerLoss RelayPowerLossBehaviorEnumeration
  deviceCascadeType DeviceCascadeTypeEnumeration
  deviceCascadePosition Integer32
  peripheralDevicesAutoManagement TruthValue
  frontPanelOutletSwitching TruthValue
  frontPanelRCMSelfTest TruthValue
  frontPanelActuatorControl TruthValue
  circuitCount Integer32
  activeDNSServerCount Integer32

ActiveDNSServerEntryStruct  
SEQUENCE    
  activeDNSServerIndex Integer32
  activeDNSServerAddressType InetAddressType
  activeDNSServerAddress InetAddress
  activeDNSServerAddressSource AddressSourceEnumeration

ControllerConfigurationEntryStruct  
SEQUENCE    
  boardType BoardTypeEnumeration
  boardIndex Integer32
  boardVersion DisplayString
  boardFirmwareVersion DisplayString
  boardFirmwareTimeStamp Unsigned32

LogConfigurationEntryStruct  
SEQUENCE    
  dataLogging TruthValue
  measurementPeriod Integer32
  measurementsPerLogEntry Integer32
  logSize Integer32
  dataLoggingEnableForAllSensors TruthValue

TrapInformationEntryStruct  
SEQUENCE    
  userName DisplayString
  targetUser DisplayString
  imageVersion DisplayString
  roleName DisplayString
  smtpMessageRecipients DisplayString
  smtpServer DisplayString

UnitSensorConfigurationEntryStruct  
SEQUENCE    
  sensorType SensorTypeEnumeration
  unitSensorLogAvailable TruthValue
  unitSensorUnits SensorUnitsEnumeration
  unitSensorDecimalDigits Unsigned32
  unitSensorAccuracy HundredthsOfAPercentage
  unitSensorResolution Unsigned32
  unitSensorTolerance Unsigned32
  unitSensorMaximum Unsigned32
  unitSensorMinimum Unsigned32
  unitSensorHysteresis Unsigned32
  unitSensorStateChangeDelay Unsigned32
  unitSensorLowerCriticalThreshold Unsigned32
  unitSensorLowerWarningThreshold Unsigned32
  unitSensorUpperCriticalThreshold Unsigned32
  unitSensorUpperWarningThreshold Unsigned32
  unitSensorEnabledThresholds BITS
  unitSensorSignedMaximum Integer32
  unitSensorSignedMinimum Integer32
  unitSensorSignedLowerCriticalThreshold Integer32
  unitSensorSignedLowerWarningThreshold Integer32
  unitSensorSignedUpperCriticalThreshold Integer32
  unitSensorSignedUpperWarningThreshold Integer32

InletConfigurationEntryStruct  
SEQUENCE    
  inletId Integer32
  inletLabel DisplayString
  inletName DisplayString
  inletPlug PlugTypeEnumeration
  inletPoleCount Integer32
  inletRatedVoltage DisplayString
  inletRatedCurrent DisplayString
  inletRatedFrequency DisplayString
  inletRatedVA DisplayString
  inletDeviceCapabilities BITS
  inletPoleCapabilities BITS
  inletPlugDescriptor DisplayString
  inletEnableState TruthValue
  inletRCMResidualOperatingCurrent Unsigned32

InletPoleConfigurationEntryStruct  
SEQUENCE    
  inletPoleLine LineEnumeration
  inletPoleNode Integer32

InletSensorConfigurationEntryStruct  
SEQUENCE    
  inletSensorLogAvailable TruthValue
  inletSensorUnits SensorUnitsEnumeration
  inletSensorDecimalDigits Unsigned32
  inletSensorAccuracy HundredthsOfAPercentage
  inletSensorResolution Unsigned32
  inletSensorTolerance Unsigned32
  inletSensorMaximum Unsigned32
  inletSensorMinimum Unsigned32
  inletSensorHysteresis Unsigned32
  inletSensorStateChangeDelay Unsigned32
  inletSensorLowerCriticalThreshold Unsigned32
  inletSensorLowerWarningThreshold Unsigned32
  inletSensorUpperCriticalThreshold Unsigned32
  inletSensorUpperWarningThreshold Unsigned32
  inletSensorEnabledThresholds BITS
  inletSensorSignedMaximum Integer32
  inletSensorSignedMinimum Integer32
  inletSensorSignedLowerCriticalThreshold Integer32
  inletSensorSignedLowerWarningThreshold Integer32
  inletSensorSignedUpperCriticalThreshold Integer32
  inletSensorSignedUpperWarningThreshold Integer32

InletPoleSensorConfigurationEntryStruct  
SEQUENCE    
  inletPoleIndex Integer32
  inletPoleSensorLogAvailable TruthValue
  inletPoleSensorUnits SensorUnitsEnumeration
  inletPoleSensorDecimalDigits Unsigned32
  inletPoleSensorAccuracy HundredthsOfAPercentage
  inletPoleSensorResolution Unsigned32
  inletPoleSensorTolerance Unsigned32
  inletPoleSensorMaximum Unsigned32
  inletPoleSensorMinimum Unsigned32
  inletPoleSensorHysteresis Unsigned32
  inletPoleSensorStateChangeDelay Unsigned32
  inletPoleSensorLowerCriticalThreshold Unsigned32
  inletPoleSensorLowerWarningThreshold Unsigned32
  inletPoleSensorUpperCriticalThreshold Unsigned32
  inletPoleSensorUpperWarningThreshold Unsigned32
  inletPoleSensorEnabledThresholds BITS
  inletPoleSensorSignedMaximum Integer32
  inletPoleSensorSignedMinimum Integer32
  inletPoleSensorSignedLowerCriticalThreshold Integer32
  inletPoleSensorSignedLowerWarningThreshold Integer32
  inletPoleSensorSignedUpperCriticalThreshold Integer32
  inletPoleSensorSignedUpperWarningThreshold Integer32

OverCurrentProtectorConfigurationEntryStruct  
SEQUENCE    
  overCurrentProtectorIndex Integer32
  overCurrentProtectorLabel DisplayString
  overCurrentProtectorName DisplayString
  overCurrentProtectorType OverCurrentProtectorTypeEnumeration
  overCurrentProtectorRatedCurrent DisplayString
  overCurrentProtectorPoleCount Integer32
  overCurrentProtectorCapabilities BITS
  overCurrentProtectorPowerSource RowPointer

OverCurrentProtectorPoleConfigurationEntryStruct  
SEQUENCE    
  overCurrentProtectorPoleIndex Integer32
  overCurrentProtectorPoleLine LineEnumeration
  overCurrentProtectorPoleInNode Integer32
  overCurrentProtectorPoleOutNode Integer32

OverCurrentProtectorSensorConfigurationEntryStruct  
SEQUENCE    
  overCurrentProtectorSensorLogAvailable TruthValue
  overCurrentProtectorSensorUnits SensorUnitsEnumeration
  overCurrentProtectorSensorDecimalDigits Unsigned32
  overCurrentProtectorSensorAccuracy HundredthsOfAPercentage
  overCurrentProtectorSensorResolution Unsigned32
  overCurrentProtectorSensorTolerance Unsigned32
  overCurrentProtectorSensorMaximum Unsigned32
  overCurrentProtectorSensorMinimum Unsigned32
  overCurrentProtectorSensorHysteresis Unsigned32
  overCurrentProtectorSensorStateChangeDelay Unsigned32
  overCurrentProtectorSensorLowerCriticalThreshold Unsigned32
  overCurrentProtectorSensorLowerWarningThreshold Unsigned32
  overCurrentProtectorSensorUpperCriticalThreshold Unsigned32
  overCurrentProtectorSensorUpperWarningThreshold Unsigned32
  overCurrentProtectorSensorEnabledThresholds BITS
  overCurrentProtectorSensorSignedMaximum Integer32
  overCurrentProtectorSensorSignedMinimum Integer32
  overCurrentProtectorSensorSignedLowerCriticalThreshold Integer32
  overCurrentProtectorSensorSignedLowerWarningThreshold Integer32
  overCurrentProtectorSensorSignedUpperCriticalThreshold Integer32
  overCurrentProtectorSensorSignedUpperWarningThreshold Integer32

OutletConfigurationEntryStruct  
SEQUENCE    
  outletId Integer32
  outletLabel DisplayString
  outletName DisplayString
  outletReceptacle ReceptacleTypeEnumeration
  outletPoleCount Integer32
  outletRatedVoltage DisplayString
  outletRatedCurrent DisplayString
  outletRatedVA DisplayString
  outletDeviceCapabilities BITS
  outletPoleCapabilities BITS
  outletPowerCyclingPowerOffPeriod Unsigned32
  outletStateOnStartup OutletStateOnStartupEnumeration
  outletUseGlobalPowerCyclingPowerOffPeriod TruthValue
  outletSwitchable TruthValue
  outletReceptacleDescriptor DisplayString
  outletNonCritical TruthValue
  outletSequenceDelay Unsigned32
  outletPowerSource RowPointer

OutletPoleConfigurationEntryStruct  
SEQUENCE    
  outletPoleLine LineEnumeration
  outletPoleNode Integer32

OutletSensorConfigurationEntryStruct  
SEQUENCE    
  outletSensorLogAvailable TruthValue
  outletSensorUnits SensorUnitsEnumeration
  outletSensorDecimalDigits Unsigned32
  outletSensorAccuracy HundredthsOfAPercentage
  outletSensorResolution Unsigned32
  outletSensorTolerance Unsigned32
  outletSensorMaximum Unsigned32
  outletSensorMinimum Unsigned32
  outletSensorHysteresis Unsigned32
  outletSensorStateChangeDelay Unsigned32
  outletSensorLowerCriticalThreshold Unsigned32
  outletSensorLowerWarningThreshold Unsigned32
  outletSensorUpperCriticalThreshold Unsigned32
  outletSensorUpperWarningThreshold Unsigned32
  outletSensorEnabledThresholds BITS
  outletSensorSignedMaximum Integer32
  outletSensorSignedMinimum Integer32
  outletSensorSignedLowerCriticalThreshold Integer32
  outletSensorSignedLowerWarningThreshold Integer32
  outletSensorSignedUpperCriticalThreshold Integer32
  outletSensorSignedUpperWarningThreshold Integer32

OutletPoleSensorConfigurationEntryStruct  
SEQUENCE    
  outletPoleIndex Integer32
  outletPoleSensorLogAvailable TruthValue
  outletPoleSensorUnits SensorUnitsEnumeration
  outletPoleSensorDecimalDigits Unsigned32
  outletPoleSensorAccuracy HundredthsOfAPercentage
  outletPoleSensorResolution Unsigned32
  outletPoleSensorTolerance Unsigned32
  outletPoleSensorMaximum Unsigned32
  outletPoleSensorMinimum Unsigned32
  outletPoleSensorHysteresis Unsigned32
  outletPoleSensorStateChangeDelay Unsigned32
  outletPoleSensorLowerCriticalThreshold Unsigned32
  outletPoleSensorLowerWarningThreshold Unsigned32
  outletPoleSensorUpperCriticalThreshold Unsigned32
  outletPoleSensorUpperWarningThreshold Unsigned32
  outletPoleSensorEnabledThresholds BITS
  outletPoleSensorSignedMaximum Integer32
  outletPoleSensorSignedMinimum Integer32
  outletPoleSensorSignedLowerCriticalThreshold Integer32
  outletPoleSensorSignedLowerWarningThreshold Integer32
  outletPoleSensorSignedUpperCriticalThreshold Integer32
  outletPoleSensorSignedUpperWarningThreshold Integer32

ExternalSensorConfigurationEntryStruct  
SEQUENCE    
  sensorID Integer32
  externalSensorType SensorTypeEnumeration
  externalSensorSerialNumber DisplayString
  externalSensorName DisplayString
  externalSensorDescription DisplayString
  externalSensorXCoordinate DisplayString
  externalSensorYCoordinate DisplayString
  externalSensorZCoordinate DisplayString
  externalSensorChannelNumber Integer32
  externalOnOffSensorSubtype SensorTypeEnumeration
  externalSensorLogAvailable TruthValue
  externalSensorUnits SensorUnitsEnumeration
  externalSensorDecimalDigits Unsigned32
  externalSensorAccuracy HundredthsOfAPercentage
  externalSensorResolution Unsigned32
  externalSensorTolerance Unsigned32
  externalSensorMaximum Integer32
  externalSensorMinimum Integer32
  externalSensorHysteresis Unsigned32
  externalSensorStateChangeDelay Unsigned32
  externalSensorLowerCriticalThreshold Integer32
  externalSensorLowerWarningThreshold Integer32
  externalSensorUpperCriticalThreshold Integer32
  externalSensorUpperWarningThreshold Integer32
  externalSensorEnabledThresholds BITS
  externalSensorIsActuator TruthValue
  externalSensorPosition DisplayString
  externalSensorUseDefaultThresholds TruthValue
  externalSensorAlarmedToNormalDelay Integer32

ExternalSensorTypeDefaultThresholdsEntryStruct  
SEQUENCE    
  externalSensorTypeDefaultHysteresis Unsigned32
  externalSensorTypeDefaultStateChangeDelay Unsigned32
  externalSensorTypeDefaultLowerCriticalThreshold Integer32
  externalSensorTypeDefaultLowerWarningThreshold Integer32
  externalSensorTypeDefaultUpperCriticalThreshold Integer32
  externalSensorTypeDefaultUpperWarningThreshold Integer32
  externalSensorTypeDefaultEnabledThresholds BITS

ServerReachabilityEntryStruct  
SEQUENCE    
  serverID Integer32
  serverIPAddress DisplayString
  serverPingEnabled TruthValue

WireConfigurationEntryStruct  
SEQUENCE    
  wireId Integer32
  wireLabel DisplayString
  wireCapabilities BITS
  wirePowerSource RowPointer

WireSensorConfigurationEntryStruct  
SEQUENCE    
  wireSensorLogAvailable TruthValue
  wireSensorUnits SensorUnitsEnumeration
  wireSensorDecimalDigits Unsigned32
  wireSensorAccuracy HundredthsOfAPercentage
  wireSensorResolution Unsigned32
  wireSensorTolerance Unsigned32
  wireSensorMaximum Unsigned32
  wireSensorMinimum Unsigned32
  wireSensorHysteresis Unsigned32
  wireSensorStateChangeDelay Unsigned32
  wireSensorLowerCriticalThreshold Unsigned32
  wireSensorLowerWarningThreshold Unsigned32
  wireSensorUpperCriticalThreshold Unsigned32
  wireSensorUpperWarningThreshold Unsigned32
  wireSensorEnabledThresholds BITS

TransferSwitchConfigurationEntryStruct  
SEQUENCE    
  transferSwitchId Integer32
  transferSwitchLabel DisplayString
  transferSwitchName DisplayString
  transferSwitchPreferredInlet Integer32
  transferSwitchPoleCount Integer32
  transferSwitchAutoReTransferEnabled TruthValue
  transferSwitchAutoReTransferWaitTime Unsigned32
  transferSwitchAutoReTransferRequiresPhaseSync TruthValue
  transferSwitchFrontPanelManualTransferButtonEnabled TruthValue
  transferSwitchCapabilities BITS
  transferSwitchPowerSource1 RowPointer
  transferSwitchPowerSource2 RowPointer

TransferSwitchPoleConfigurationEntryStruct  
SEQUENCE    
  transferSwitchPoleIndex Integer32
  transferSwitchPoleLine LineEnumeration
  transferSwitchPoleIn1Node Integer32
  transferSwitchPoleIn2Node Integer32
  transferSwitchPoleOutNode Integer32

TransferSwitchSensorConfigurationEntryStruct  
SEQUENCE    
  transferSwitchSensorLogAvailable TruthValue
  transferSwitchSensorUnits SensorUnitsEnumeration
  transferSwitchSensorDecimalDigits Unsigned32
  transferSwitchSensorAccuracy HundredthsOfAPercentage
  transferSwitchSensorResolution Unsigned32
  transferSwitchSensorTolerance Unsigned32
  transferSwitchSensorMaximum Unsigned32
  transferSwitchSensorMinimum Unsigned32
  transferSwitchSensorHysteresis Unsigned32
  transferSwitchSensorStateChangeDelay Unsigned32
  transferSwitchSensorLowerCriticalThreshold Unsigned32
  transferSwitchSensorLowerWarningThreshold Unsigned32
  transferSwitchSensorUpperCriticalThreshold Unsigned32
  transferSwitchSensorUpperWarningThreshold Unsigned32
  transferSwitchSensorEnabledThresholds BITS
  transferSwitchSensorSignedMaximum Integer32
  transferSwitchSensorSignedMinimum Integer32
  transferSwitchSensorSignedLowerCriticalThreshold Integer32
  transferSwitchSensorSignedLowerWarningThreshold Integer32
  transferSwitchSensorSignedUpperCriticalThreshold Integer32
  transferSwitchSensorSignedUpperWarningThreshold Integer32

PowerMeterConfigurationEntryStruct  
SEQUENCE    
  powerMeterPhaseCTRating Unsigned32
  powerMeterNeutralCTRating Unsigned32
  powerMeterEarthCTRating Unsigned32
  powerMeterBranchCount Unsigned32
  powerMeterPanelPositions Integer32
  powerMeterPanelLayout PanelLayoutEnumeration
  powerMeterPanelNumbering PanelNumberingEnumeration
  powerMeterType PowerMeterTypeEnumeration

CircuitConfigurationEntryStruct  
SEQUENCE    
  circuitId Integer32
  circuitPoleCount Integer32
  circuitName DisplayString
  circuitType CircuitTypeEnumeration
  circuitRatedCurrent Unsigned32
  circuitCTRating Unsigned32
  circuitCapabilities BITS
  circuitPoleCapabilities BITS
  circuitPowerSource RowPointer

CircuitPoleConfigurationEntryStruct  
SEQUENCE    
  circuitPoleId Integer32
  circuitPolePanelPosition Integer32
  circuitPoleCTNumber Integer32
  circuitPolePhase PhaseEnumeration

CircuitSensorConfigurationEntryStruct  
SEQUENCE    
  circuitSensorLogAvailable TruthValue
  circuitSensorUnits SensorUnitsEnumeration
  circuitSensorDecimalDigits Unsigned32
  circuitSensorResolution Unsigned32
  circuitSensorMaximum Unsigned32
  circuitSensorMinimum Unsigned32
  circuitSensorHysteresis Unsigned32
  circuitSensorStateChangeDelay Unsigned32
  circuitSensorLowerCriticalThreshold Unsigned32
  circuitSensorLowerWarningThreshold Unsigned32
  circuitSensorUpperCriticalThreshold Unsigned32
  circuitSensorUpperWarningThreshold Unsigned32
  circuitSensorEnabledThresholds BITS
  circuitSensorSignedMaximum Integer32
  circuitSensorSignedMinimum Integer32
  circuitSensorSignedLowerCriticalThreshold Integer32
  circuitSensorSignedLowerWarningThreshold Integer32
  circuitSensorSignedUpperCriticalThreshold Integer32
  circuitSensorSignedUpperWarningThreshold Integer32

CircuitPoleSensorConfigurationEntryStruct  
SEQUENCE    
  circuitPoleSensorLogAvailable TruthValue
  circuitPoleSensorUnits SensorUnitsEnumeration
  circuitPoleSensorDecimalDigits Unsigned32
  circuitPoleSensorResolution Unsigned32
  circuitPoleSensorMaximum Unsigned32
  circuitPoleSensorMinimum Unsigned32
  circuitPoleSensorHysteresis Unsigned32
  circuitPoleSensorStateChangeDelay Unsigned32
  circuitPoleSensorLowerCriticalThreshold Unsigned32
  circuitPoleSensorLowerWarningThreshold Unsigned32
  circuitPoleSensorUpperCriticalThreshold Unsigned32
  circuitPoleSensorUpperWarningThreshold Unsigned32
  circuitPoleSensorEnabledThresholds BITS
  circuitPoleSensorSignedMaximum Integer32
  circuitPoleSensorSignedMinimum Integer32
  circuitPoleSensorSignedLowerCriticalThreshold Integer32
  circuitPoleSensorSignedLowerWarningThreshold Integer32
  circuitPoleSensorSignedUpperCriticalThreshold Integer32
  circuitPoleSensorSignedUpperWarningThreshold Integer32

PeripheralDevicePackageEntryStruct  
SEQUENCE    
  peripheralDevicePackageId Integer32
  peripheralDevicePackageSerialNumber DisplayString
  peripheralDevicePackageModel DisplayString
  peripheralDevicePackageFirmwareVersion DisplayString
  peripheralDevicePackageMinFirmwareVersion DisplayString
  peripheralDevicePackageFirmwareTimeStamp Unsigned32
  peripheralDevicePackagePosition DisplayString
  peripheralDevicePackageState DisplayString

LogIndexEntryStruct  
SEQUENCE    
  oldestLogID Integer32
  newestLogID Integer32

LogTimeStampEntryStruct  
SEQUENCE    
  logIndex Integer32
  logTimeStamp Unsigned32

UnitSensorLogEntryStruct  
SEQUENCE    
  logUnitSensorDataAvailable TruthValue
  logUnitSensorState SensorStateEnumeration
  logUnitSensorAvgValue Unsigned32
  logUnitSensorMaxValue Unsigned32
  logUnitSensorMinValue Unsigned32
  logUnitSensorSignedAvgValue Integer32
  logUnitSensorSignedMaxValue Integer32
  logUnitSensorSignedMinValue Integer32

InletSensorLogEntryStruct  
SEQUENCE    
  logInletSensorDataAvailable TruthValue
  logInletSensorState SensorStateEnumeration
  logInletSensorAvgValue Unsigned32
  logInletSensorMaxValue Unsigned32
  logInletSensorMinValue Unsigned32
  logInletSensorSignedAvgValue Integer32
  logInletSensorSignedMaxValue Integer32
  logInletSensorSignedMinValue Integer32

InletPoleSensorLogEntryStruct  
SEQUENCE    
  logInletPoleSensorDataAvailable TruthValue
  logInletPoleSensorState SensorStateEnumeration
  logInletPoleSensorAvgValue Unsigned32
  logInletPoleSensorMaxValue Unsigned32
  logInletPoleSensorMinValue Unsigned32
  logInletPoleSensorSignedAvgValue Integer32
  logInletPoleSensorSignedMaxValue Integer32
  logInletPoleSensorSignedMinValue Integer32

OutletSensorLogEntryStruct  
SEQUENCE    
  logOutletSensorDataAvailable TruthValue
  logOutletSensorState SensorStateEnumeration
  logOutletSensorAvgValue Unsigned32
  logOutletSensorMaxValue Unsigned32
  logOutletSensorMinValue Unsigned32
  logOutletSensorSignedAvgValue Integer32
  logOutletSensorSignedMaxValue Integer32
  logOutletSensorSignedMinValue Integer32

OutletPoleSensorLogEntryStruct  
SEQUENCE    
  logOutletPoleSensorDataAvailable TruthValue
  logOutletPoleSensorState SensorStateEnumeration
  logOutletPoleSensorAvgValue Unsigned32
  logOutletPoleSensorMaxValue Unsigned32
  logOutletPoleSensorMinValue Unsigned32
  logOutletPoleSensorSignedAvgValue Integer32
  logOutletPoleSensorSignedMaxValue Integer32
  logOutletPoleSensorSignedMinValue Integer32

OverCurrentProtectorSensorLogEntryStruct  
SEQUENCE    
  logOverCurrentProtectorSensorDataAvailable TruthValue
  logOverCurrentProtectorSensorState SensorStateEnumeration
  logOverCurrentProtectorSensorAvgValue Unsigned32
  logOverCurrentProtectorSensorMaxValue Unsigned32
  logOverCurrentProtectorSensorMinValue Unsigned32
  logOverCurrentProtectorSensorSignedAvgValue Integer32
  logOverCurrentProtectorSensorSignedMaxValue Integer32
  logOverCurrentProtectorSensorSignedMinValue Integer32

ExternalSensorLogEntryStruct  
SEQUENCE    
  logExternalSensorDataAvailable TruthValue
  logExternalSensorState SensorStateEnumeration
  logExternalSensorAvgValue Integer32
  logExternalSensorMaxValue Integer32
  logExternalSensorMinValue Integer32

WireSensorLogEntryStruct  
SEQUENCE    
  logWireSensorDataAvailable TruthValue
  logWireSensorState SensorStateEnumeration
  logWireSensorAvgValue Unsigned32
  logWireSensorMaxValue Unsigned32
  logWireSensorMinValue Unsigned32

TransferSwitchSensorLogEntryStruct  
SEQUENCE    
  logTransferSwitchSensorDataAvailable TruthValue
  logTransferSwitchSensorState SensorStateEnumeration
  logTransferSwitchSensorAvgValue Unsigned32
  logTransferSwitchSensorMaxValue Unsigned32
  logTransferSwitchSensorMinValue Unsigned32
  logTransferSwitchSensorSignedAvgValue Integer32
  logTransferSwitchSensorSignedMaxValue Integer32
  logTransferSwitchSensorSignedMinValue Integer32

CircuitSensorLogEntryStruct  
SEQUENCE    
  logCircuitSensorDataAvailable TruthValue
  logCircuitSensorState SensorStateEnumeration
  logCircuitSensorAvgValue Unsigned32
  logCircuitSensorMaxValue Unsigned32
  logCircuitSensorMinValue Unsigned32
  logCircuitSensorSignedAvgValue Integer32
  logCircuitSensorSignedMaxValue Integer32
  logCircuitSensorSignedMinValue Integer32

CircuitPoleSensorLogEntryStruct  
SEQUENCE    
  logCircuitPoleSensorDataAvailable TruthValue
  logCircuitPoleSensorState SensorStateEnumeration
  logCircuitPoleSensorAvgValue Unsigned32
  logCircuitPoleSensorMaxValue Unsigned32
  logCircuitPoleSensorMinValue Unsigned32
  logCircuitPoleSensorSignedAvgValue Integer32
  logCircuitPoleSensorSignedMaxValue Integer32
  logCircuitPoleSensorSignedMinValue Integer32

UnitSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsUnitSensorIsAvailable TruthValue
  measurementsUnitSensorState SensorStateEnumeration
  measurementsUnitSensorValue Unsigned32
  measurementsUnitSensorTimeStamp Unsigned32
  measurementsUnitSensorSignedValue Integer32

InletSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsInletSensorIsAvailable TruthValue
  measurementsInletSensorState SensorStateEnumeration
  measurementsInletSensorValue Unsigned32
  measurementsInletSensorTimeStamp Unsigned32
  measurementsInletSensorSignedValue Integer32

InletPoleSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsInletPoleSensorIsAvailable TruthValue
  measurementsInletPoleSensorState SensorStateEnumeration
  measurementsInletPoleSensorValue Unsigned32
  measurementsInletPoleSensorTimeStamp Unsigned32
  measurementsInletPoleSensorSignedValue Integer32

OutletSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsOutletSensorIsAvailable TruthValue
  measurementsOutletSensorState SensorStateEnumeration
  measurementsOutletSensorValue Unsigned32
  measurementsOutletSensorTimeStamp Unsigned32
  measurementsOutletSensorSignedValue Integer32

OutletPoleSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsOutletPoleSensorIsAvailable TruthValue
  measurementsOutletPoleSensorState SensorStateEnumeration
  measurementsOutletPoleSensorValue Unsigned32
  measurementsOutletPoleSensorTimeStamp Unsigned32
  measurementsOutletPoleSensorSignedValue Integer32

OverCurrentProtectorSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsOverCurrentProtectorSensorIsAvailable TruthValue
  measurementsOverCurrentProtectorSensorState SensorStateEnumeration
  measurementsOverCurrentProtectorSensorValue Unsigned32
  measurementsOverCurrentProtectorSensorTimeStamp Unsigned32
  measurementsOverCurrentProtectorSensorSignedValue Integer32

ExternalSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsExternalSensorIsAvailable TruthValue
  measurementsExternalSensorState SensorStateEnumeration
  measurementsExternalSensorValue Integer32
  measurementsExternalSensorTimeStamp Unsigned32

WireSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsWireSensorIsAvailable TruthValue
  measurementsWireSensorState SensorStateEnumeration
  measurementsWireSensorValue Unsigned32
  measurementsWireSensorTimeStamp Unsigned32

TransferSwitchSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsTransferSwitchSensorIsAvailable TruthValue
  measurementsTransferSwitchSensorState SensorStateEnumeration
  measurementsTransferSwitchSensorValue Unsigned32
  measurementsTransferSwitchSensorTimeStamp Unsigned32
  measurementsTransferSwitchSensorSignedValue Integer32

CircuitSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsCircuitSensorIsAvailable TruthValue
  measurementsCircuitSensorState SensorStateEnumeration
  measurementsCircuitSensorValue Unsigned32
  measurementsCircuitSensorTimeStamp Unsigned32
  measurementsCircuitSensorSignedValue Integer32

CircuitPoleSensorMeasurementsEntryStruct  
SEQUENCE    
  measurementsCircuitPoleSensorIsAvailable TruthValue
  measurementsCircuitPoleSensorState SensorStateEnumeration
  measurementsCircuitPoleSensorValue Unsigned32
  measurementsCircuitPoleSensorTimeStamp Unsigned32
  measurementsCircuitPoleSensorSignedValue Integer32

OutletSwitchControlEntryStruct  
SEQUENCE    
  switchingOperation OutletSwitchingOperationsEnumeration
  outletSwitchingState SensorStateEnumeration
  outletSwitchingTimeStamp Unsigned32

TransferSwitchControlEntryStruct  
SEQUENCE    
  transferSwitchActiveInlet Integer32
  transferSwitchTransferToInlet Integer32
  transferSwitchAlarmOverride TruthValue
  transferSwitchLastTransferReason TransferSwitchTransferReasonEnumeration

ActuatorControlEntryStruct  
SEQUENCE    
  actuatorState SensorStateEnumeration

RcmSelfTestEntryStruct  
SEQUENCE    
  rcmState SensorStateEnumeration

InletSensorControlEntryStruct  
SEQUENCE    
  inletSensorResetValue Integer32

OutletSensorControlEntryStruct  
SEQUENCE    
  outletSensorResetValue Integer32

UnitSensorControlEntryStruct  
SEQUENCE    
  unitSensorResetValue Integer32

CircuitSensorControlEntryStruct  
SEQUENCE    
  circuitSensorResetValue Integer32

ReliabilityDataEntryStruct  
SEQUENCE    
  reliabilityIndex Integer32
  reliabilityId DisplayString
  reliabilityDataValue Unsigned32
  reliabilityDataMaxPossible Unsigned32
  reliabilityDataWorstValue Unsigned32
  reliabilityDataThreshold Unsigned32
  reliabilityDataRawUpperBytes Unsigned32
  reliabilityDataRawLowerBytes Unsigned32
  reliabilityDataFlags BITS

ReliabilityErrorLogEntryStruct  
SEQUENCE    
  reliabilityErrorLogIndex Integer32
  reliabilityErrorLogId DisplayString
  reliabilityErrorLogValue Unsigned32
  reliabilityErrorLogThreshold Unsigned32
  reliabilityErrorLogRawUpperBytes Unsigned32
  reliabilityErrorLogRawLowerBytes Unsigned32
  reliabilityErrorLogPOH Unsigned32
  reliabilityErrorLogTime Unsigned32

Defined Values

raritan 1.3.6.1.4.1.13742
This MIB describes the SNMP functions of the Dominion PX G2 Power Distribution Unit by Raritan Computer.
MODULE-IDENTITY    

pdu2 1.3.6.1.4.1.13742.6
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.13742.6.0
OBJECT IDENTIFIER    

trapInformation 1.3.6.1.4.1.13742.6.0.0
OBJECT IDENTIFIER    

board 1.3.6.1.4.1.13742.6.1
OBJECT IDENTIFIER    

environmental 1.3.6.1.4.1.13742.6.2
OBJECT IDENTIFIER    

configuration 1.3.6.1.4.1.13742.6.3
OBJECT IDENTIFIER    

control 1.3.6.1.4.1.13742.6.4
OBJECT IDENTIFIER    

measurements 1.3.6.1.4.1.13742.6.5
OBJECT IDENTIFIER    

log 1.3.6.1.4.1.13742.6.6
OBJECT IDENTIFIER    

conformance 1.3.6.1.4.1.13742.6.9
OBJECT IDENTIFIER    

reliability 1.3.6.1.4.1.13742.6.10
OBJECT IDENTIFIER    

unit 1.3.6.1.4.1.13742.6.3.2
OBJECT IDENTIFIER    

inlets 1.3.6.1.4.1.13742.6.3.3
OBJECT IDENTIFIER    

overCurrentProtector 1.3.6.1.4.1.13742.6.3.4
OBJECT IDENTIFIER    

outlets 1.3.6.1.4.1.13742.6.3.5
OBJECT IDENTIFIER    

externalSensors 1.3.6.1.4.1.13742.6.3.6
OBJECT IDENTIFIER    

serverReachability 1.3.6.1.4.1.13742.6.3.7
OBJECT IDENTIFIER    

wires 1.3.6.1.4.1.13742.6.3.8
OBJECT IDENTIFIER    

transferSwitch 1.3.6.1.4.1.13742.6.3.9
OBJECT IDENTIFIER    

powerMeter 1.3.6.1.4.1.13742.6.3.10
OBJECT IDENTIFIER    

circuit 1.3.6.1.4.1.13742.6.3.11
OBJECT IDENTIFIER    

outletControl 1.3.6.1.4.1.13742.6.4.1
OBJECT IDENTIFIER    

externalSensorControl 1.3.6.1.4.1.13742.6.4.2
OBJECT IDENTIFIER    

transferSwitchControl 1.3.6.1.4.1.13742.6.4.3
OBJECT IDENTIFIER    

actuatorControl 1.3.6.1.4.1.13742.6.4.4
OBJECT IDENTIFIER    

rcmControl 1.3.6.1.4.1.13742.6.4.5
OBJECT IDENTIFIER    

inletSensorControl 1.3.6.1.4.1.13742.6.4.6
OBJECT IDENTIFIER    

outletSensorControl 1.3.6.1.4.1.13742.6.4.7
OBJECT IDENTIFIER    

unitSensorControl 1.3.6.1.4.1.13742.6.4.8
OBJECT IDENTIFIER    

circuitSensorControl 1.3.6.1.4.1.13742.6.4.9
OBJECT IDENTIFIER    

measurementsUnit 1.3.6.1.4.1.13742.6.5.1
OBJECT IDENTIFIER    

measurementsInlet 1.3.6.1.4.1.13742.6.5.2
OBJECT IDENTIFIER    

measurementsOverCurrentProtector 1.3.6.1.4.1.13742.6.5.3
OBJECT IDENTIFIER    

measurementsOutlet 1.3.6.1.4.1.13742.6.5.4
OBJECT IDENTIFIER    

measurementsExternalSensor 1.3.6.1.4.1.13742.6.5.5
OBJECT IDENTIFIER    

measurementsWire 1.3.6.1.4.1.13742.6.5.6
OBJECT IDENTIFIER    

measurementsTransferSwitch 1.3.6.1.4.1.13742.6.5.7
OBJECT IDENTIFIER    

measurementsCircuit 1.3.6.1.4.1.13742.6.5.8
OBJECT IDENTIFIER    

logUnit 1.3.6.1.4.1.13742.6.6.1
OBJECT IDENTIFIER    

logInlet 1.3.6.1.4.1.13742.6.6.2
OBJECT IDENTIFIER    

logOverCurrentProtector 1.3.6.1.4.1.13742.6.6.3
OBJECT IDENTIFIER    

logOutlet 1.3.6.1.4.1.13742.6.6.4
OBJECT IDENTIFIER    

logExternalSensor 1.3.6.1.4.1.13742.6.6.5
OBJECT IDENTIFIER    

logWire 1.3.6.1.4.1.13742.6.6.6
OBJECT IDENTIFIER    

logTransferSwitch 1.3.6.1.4.1.13742.6.6.7
OBJECT IDENTIFIER    

logCircuit 1.3.6.1.4.1.13742.6.6.8
OBJECT IDENTIFIER    

reliabilityData 1.3.6.1.4.1.13742.6.10.1
OBJECT IDENTIFIER    

reliabilityErrorLog 1.3.6.1.4.1.13742.6.10.2
OBJECT IDENTIFIER    

compliances 1.3.6.1.4.1.13742.6.9.1
OBJECT IDENTIFIER    

groups 1.3.6.1.4.1.13742.6.9.2
OBJECT IDENTIFIER    

complianceRev2 1.3.6.1.4.1.13742.6.9.1.2
The requirements for conformance to the PDU2-MIB.
Status: current Access: read-only
MODULE-COMPLIANCE    

complianceRev1 1.3.6.1.4.1.13742.6.9.1.1
The requirements for conformance to the PDU2-MIB.
Status: deprecated Access: read-only
MODULE-COMPLIANCE    

configGroup 1.3.6.1.4.1.13742.6.9.2.1
A collection of objects representing configuration data.
Status: current Access: read-only
OBJECT-GROUP    

ipAddressGroup 1.3.6.1.4.1.13742.6.9.2.12
A collection of objects representing configuration data.
Status: deprecated Access: read-only
OBJECT-GROUP    

oldConfigGroup 1.3.6.1.4.1.13742.6.9.2.13
A collection of objects representing old (deprecated) configuration data.
Status: deprecated Access: read-only
OBJECT-GROUP    

logGroup 1.3.6.1.4.1.13742.6.9.2.2
A collection of objects providing logging (history of readings) capabilities about the PDU.
Status: current Access: read-only
OBJECT-GROUP    

oldLogGroup 1.3.6.1.4.1.13742.6.9.2.14
A collection of objects representing old (deprecated) logging data.
Status: deprecated Access: read-only
OBJECT-GROUP    

measurementsGroup 1.3.6.1.4.1.13742.6.9.2.3
A collection of objects providing measurements (most recent data) capabilities. about the PDU.
Status: current Access: read-only
OBJECT-GROUP    

oldMeasurementsGroup 1.3.6.1.4.1.13742.6.9.2.15
A collection of objects representing old (deprecated) measurement data.
Status: deprecated Access: read-only
OBJECT-GROUP    

controlGroup 1.3.6.1.4.1.13742.6.9.2.4
A collection of objects providing the ability to control various components of a PDU.
Status: current Access: read-only
OBJECT-GROUP    

trapInformationGroup 1.3.6.1.4.1.13742.6.9.2.5
A collection of objects providing information in the traps.
Status: current Access: read-only
OBJECT-GROUP    

trapsGroup 1.3.6.1.4.1.13742.6.9.2.9
A collection of traps.
Status: current Access: read-only
NOTIFICATION-GROUP    

oldTrapsGroup 1.3.6.1.4.1.13742.6.9.2.16
A collection of objects representing old (deprecated) traps.
Status: deprecated Access: read-only
NOTIFICATION-GROUP    

reliabilityGroup 1.3.6.1.4.1.13742.6.9.2.10
A collection of objects providing reliability data.
Status: current Access: read-only
OBJECT-GROUP    

pduCount 1.3.6.1.4.1.13742.6.3.1
For a PX2/3 and transfer switch, pduCount = 1 For a BCM2, pduCount = number of power meters + 1 (for the main controller)
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

nameplateTable 1.3.6.1.4.1.13742.6.3.2.1
A list of PDU nameplate entries. The number of entries is given by the value of pduCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    NameplateEntryStruct

nameplateEntry 1.3.6.1.4.1.13742.6.3.2.1.1
An entry providing PDU nameplate information.
Status: current Access: not-accessible
OBJECT-TYPE    
  NameplateEntryStruct  

pduId 1.3.6.1.4.1.13742.6.3.2.1.1.1
A unique value for each PDU/Power meter. PX2/3 and transfer switch: pduiId = 1 BCM2: main controller: pduId = 0 power meter: pduId = rotary switch setting for the power meter It is the same as the MeterID in the GUI Example: a power meter, rotary switch setting = 5, pduId = 5 a panel (power meter + branch metering), rotary switch setting = 23, pduId = 23
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..256  

pduManufacturer 1.3.6.1.4.1.13742.6.3.2.1.1.2
The PDU manaufacturer.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduModel 1.3.6.1.4.1.13742.6.3.2.1.1.3
The PDU model.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduSerialNumber 1.3.6.1.4.1.13742.6.3.2.1.1.4
The PDU serial Number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduRatedVoltage 1.3.6.1.4.1.13742.6.3.2.1.1.5
The PDU voltage rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduRatedCurrent 1.3.6.1.4.1.13742.6.3.2.1.1.6
The PDU current rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduRatedFrequency 1.3.6.1.4.1.13742.6.3.2.1.1.7
The PDU frequency rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduRatedVA 1.3.6.1.4.1.13742.6.3.2.1.1.8
The PDU VA (VoltAmps) rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduImage 1.3.6.1.4.1.13742.6.3.2.1.1.9
The URL of the wiring diagram for this PDU.
Status: current Access: read-only
OBJECT-TYPE    
  URL  

unitConfigurationTable 1.3.6.1.4.1.13742.6.3.2.2
A list of PDU configuration entries. The number of entries is given by the value of pduCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UnitConfigurationEntryStruct

unitConfigurationEntry 1.3.6.1.4.1.13742.6.3.2.2.1
An entry containing configuration objects for a particular PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  UnitConfigurationEntryStruct  

inletCount 1.3.6.1.4.1.13742.6.3.2.2.1.2
The number of inlets.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

overCurrentProtectorCount 1.3.6.1.4.1.13742.6.3.2.2.1.3
The number of overcurrent protectors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

outletCount 1.3.6.1.4.1.13742.6.3.2.2.1.4
The number of outlets.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

inletControllerCount 1.3.6.1.4.1.13742.6.3.2.2.1.5
The number of inlet controllers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

outletControllerCount 1.3.6.1.4.1.13742.6.3.2.2.1.6
The number of outlet controllers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

externalSensorCount 1.3.6.1.4.1.13742.6.3.2.2.1.7
The number of external sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pxIPAddress 1.3.6.1.4.1.13742.6.3.2.2.1.8
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
Status: deprecated Access: read-only
OBJECT-TYPE    
  IpAddress  

netmask 1.3.6.1.4.1.13742.6.3.2.2.1.9
The current netmask. A value of 0.0.0.0 indicates an error or an unset option.
Status: deprecated Access: read-only
OBJECT-TYPE    
  IpAddress  

gateway 1.3.6.1.4.1.13742.6.3.2.2.1.10
The current gateway. A value of 0.0.0.0 indicates an error or an unset option.
Status: deprecated Access: read-only
OBJECT-TYPE    
  IpAddress  

pxMACAddress 1.3.6.1.4.1.13742.6.3.2.2.1.11
The current MAC address.
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

utcOffset 1.3.6.1.4.1.13742.6.3.2.2.1.12
The current UTC offset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduName 1.3.6.1.4.1.13742.6.3.2.2.1.13
The user-defined name for the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

networkInterfaceType 1.3.6.1.4.1.13742.6.3.2.2.1.14
The network interface type: wired or wireless.
Status: current Access: read-only
OBJECT-TYPE    
  NetworkInterfaceTypeEnumeration  

externalSensorsZCoordinateUnits 1.3.6.1.4.1.13742.6.3.2.2.1.34
External Sensor Z Coordinate units: Freeform Text or Rack Units (U) Default is U.
Status: current Access: read-write
OBJECT-TYPE    
  ExternalSensorsZCoordinateUnitsEnumeration  

unitDeviceCapabilities 1.3.6.1.4.1.13742.6.3.2.2.1.35
A bit string which indicates which unit sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS i1smpsStatus(45), i2smpsStatus(46)  

outletSequencingDelay 1.3.6.1.4.1.13742.6.3.2.2.1.36
It is deprecated. This is an alias for inrushGuardDelay
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

globalOutletPowerCyclingPowerOffPeriod 1.3.6.1.4.1.13742.6.3.2.2.1.37
The power-off period when an outlet is cycled; applies to all outlets unless overridden at the outlet level; specified in seconds; 0 <= value <= 3600 seconds.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

globalOutletStateOnStartup 1.3.6.1.4.1.13742.6.3.2.2.1.38
The outlet state on device startup; applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
Status: current Access: read-write
OBJECT-TYPE    
  GlobalOutletStateOnStartupEnumeration  

outletPowerupSequence 1.3.6.1.4.1.13742.6.3.2.2.1.39
The sequence in which will the outlets will be switched on under the following conditions. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled String must consist of a comma separated sequence of the outlet numbers and all outlet numbers must be included. The numbers entered must be a permutation of the numbers 1,2,3,-outletnumber. Example for a 12 outlet PDU: 1,12,3,5,6,7,10,2,4,11,9,8. The per outlet sequence delays are defined as outletSequenceDelay in the outletConfigurationTable
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduPowerCyclingPowerOffPeriod 1.3.6.1.4.1.13742.6.3.2.2.1.40
When power to the PX is cycled (either manually or because of a temporary power loss), this number determines how many seconds the PX will wait before it provides power to the outlets. specified in seconds: 0 <= value <= 3600 seconds. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduDaisychainMemberType 1.3.6.1.4.1.13742.6.3.2.2.1.41
The daisy chain member type.
Status: current Access: read-only
OBJECT-TYPE    
  DaisychainMemberTypeEnumeration  

managedExternalSensorCount 1.3.6.1.4.1.13742.6.3.2.2.1.42
The number of managed external sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pxInetAddressType 1.3.6.1.4.1.13742.6.3.2.2.1.50
The type of address format This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
Status: deprecated Access: read-only
OBJECT-TYPE    
  InetAddressType  

pxInetIPAddress 1.3.6.1.4.1.13742.6.3.2.2.1.51
The current IP address. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
Status: deprecated Access: read-only
OBJECT-TYPE    
  InetAddress  

pxInetNetmask 1.3.6.1.4.1.13742.6.3.2.2.1.52
The current netmask. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
Status: deprecated Access: read-only
OBJECT-TYPE    
  InetAddress  

pxInetGateway 1.3.6.1.4.1.13742.6.3.2.2.1.53
The current gateway. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
Status: deprecated Access: read-only
OBJECT-TYPE    
  InetAddress  

loadShedding 1.3.6.1.4.1.13742.6.3.2.2.1.55
Enter/Exit Load Shedding Mode
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

serverCount 1.3.6.1.4.1.13742.6.3.2.2.1.56
The number of servers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

inrushGuardDelay 1.3.6.1.4.1.13742.6.3.2.2.1.57
The time interval between switching on two outlets; specified in milliseconds; 100 <= value <= 100000 milliseconds.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

cascadedDeviceConnected 1.3.6.1.4.1.13742.6.3.2.2.1.58
Indicates whether another PX2 is connected using an USB cable to the USB-A port of this PX2 in a cascaded configuration. true: Connected false: Not Connected
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

synchronizeWithNTPServer 1.3.6.1.4.1.13742.6.3.2.2.1.59
Will time be obtained using NTP? true: time will be obtained using NTP servers false: time will not be obtained using NTP servers Deafault is false.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

useDHCPProvidedNTPServer 1.3.6.1.4.1.13742.6.3.2.2.1.60
Will the NTP server addresses be provided by DHCP/BOOTP? This is used only if synchronizeWithNTPServer is enabled Default is enabled, i.e. DHCP provided NTP servers will be used
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

firstNTPServerAddressType 1.3.6.1.4.1.13742.6.3.2.2.1.61
Represents the type of the corresponding instance of firstNTPServerAddress object.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddressType  

firstNTPServerAddress 1.3.6.1.4.1.13742.6.3.2.2.1.62
The address of the primary ntp server.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddress  

secondNTPServerAddressType 1.3.6.1.4.1.13742.6.3.2.2.1.63
Represents the type of the corresponding instance of secondNTPServerAddress object. Default is ipv4
Status: current Access: read-write
OBJECT-TYPE    
  InetAddressType  

secondNTPServerAddress 1.3.6.1.4.1.13742.6.3.2.2.1.64
The address of the second ntp server.
Status: current Access: read-write
OBJECT-TYPE    
  InetAddress  

wireCount 1.3.6.1.4.1.13742.6.3.2.2.1.65
The number of wires.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

transferSwitchCount 1.3.6.1.4.1.13742.6.3.2.2.1.66
The number of transfer switches.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

productType 1.3.6.1.4.1.13742.6.3.2.2.1.67
The product type. Is this product a PDU, STS, BCM,...?
Status: current Access: read-only
OBJECT-TYPE    
  ProductTypeEnumeration  

meteringControllerCount 1.3.6.1.4.1.13742.6.3.2.2.1.68
The number of metering controllers.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

relayBehaviorOnPowerLoss 1.3.6.1.4.1.13742.6.3.2.2.1.69
The relay behavior on power loss.
Status: current Access: read-write
OBJECT-TYPE    
  RelayPowerLossBehaviorEnumeration  

deviceCascadeType 1.3.6.1.4.1.13742.6.3.2.2.1.70
The configured type of cascading: default is bridging. This can be set only if the unit is the master.
Status: current Access: read-write
OBJECT-TYPE    
  DeviceCascadeTypeEnumeration  

deviceCascadePosition 1.3.6.1.4.1.13742.6.3.2.2.1.71
The position of the device in the cascaded chain. 0: master >= 1: slaves
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..99  

peripheralDevicesAutoManagement 1.3.6.1.4.1.13742.6.3.2.2.1.72
Auto-management enabled state for peripheral devices.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

frontPanelOutletSwitching 1.3.6.1.4.1.13742.6.3.2.2.1.73
Enables/disables switching of outlets using the PDU front panel.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

frontPanelRCMSelfTest 1.3.6.1.4.1.13742.6.3.2.2.1.74
Enables/disables front panel RCM self-test.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

frontPanelActuatorControl 1.3.6.1.4.1.13742.6.3.2.2.1.75
Enables/disables front panel peripheral actuator control.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

circuitCount 1.3.6.1.4.1.13742.6.3.2.2.1.76
The number of user configured circuits in the panel.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

activeDNSServerCount 1.3.6.1.4.1.13742.6.3.2.2.1.77
The number of active DNS Servers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..16  

activeDNSServerTable 1.3.6.1.4.1.13742.6.3.2.6
A list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount (from unitConfigurationTable). If activeDNSServerCount = 0, then the table is empty.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ActiveDNSServerEntryStruct

activeDNSServerEntry 1.3.6.1.4.1.13742.6.3.2.6.1
An entry containing the active DNS servers for a particular PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  ActiveDNSServerEntryStruct  

activeDNSServerIndex 1.3.6.1.4.1.13742.6.3.2.6.1.2
A unique value for a dns Server. Its value ranges between 1 and activeDNSServerCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..16  

activeDNSServerAddressType 1.3.6.1.4.1.13742.6.3.2.6.1.3
Represents the type of the corresponding instance of activeDNSServerAddress object.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddressType  

activeDNSServerAddress 1.3.6.1.4.1.13742.6.3.2.6.1.4
The address of the dns server.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

activeDNSServerAddressSource 1.3.6.1.4.1.13742.6.3.2.6.1.5
How was the address obtained: static, dhcp, dhcpv6?
Status: current Access: read-only
OBJECT-TYPE    
  AddressSourceEnumeration  

controllerConfigurationTable 1.3.6.1.4.1.13742.6.3.2.3
A list of entries for the boards in each PDU. The number of entries is given by the value of inletControllerCount + outletControllerCount + 1 (for main controller board).
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ControllerConfigurationEntryStruct

controllerConfigurationEntry 1.3.6.1.4.1.13742.6.3.2.3.1
An entry containing objects for a controller.
Status: current Access: not-accessible
OBJECT-TYPE    
  ControllerConfigurationEntryStruct  

boardType 1.3.6.1.4.1.13742.6.3.2.3.1.1
The type of board.
Status: current Access: not-accessible
OBJECT-TYPE    
  BoardTypeEnumeration  

boardIndex 1.3.6.1.4.1.13742.6.3.2.3.1.2
A unique value for each controller. Its value ranges between 1 and the value of inletControllerCount + outletControllerCount + 1.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

boardVersion 1.3.6.1.4.1.13742.6.3.2.3.1.4
The board hardware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

boardFirmwareVersion 1.3.6.1.4.1.13742.6.3.2.3.1.6
The firmware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

boardFirmwareTimeStamp 1.3.6.1.4.1.13742.6.3.2.3.1.8
The time when the board firmware was updated in UNIX(epoch)time. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logConfigurationTable 1.3.6.1.4.1.13742.6.3.2.4
A table of parameters for the data logging feature. The number of entries is given by the value of pduCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LogConfigurationEntryStruct

logConfigurationEntry 1.3.6.1.4.1.13742.6.3.2.4.1
An entry containing data logging parameters for a particular PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  LogConfigurationEntryStruct  

dataLogging 1.3.6.1.4.1.13742.6.3.2.4.1.1
Data Retrieval: enabled/disabled.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

measurementPeriod 1.3.6.1.4.1.13742.6.3.2.4.1.2
Data Collection periodicity. This is the periodicity of the data collected by the PX. This value is fixed at 1 second.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

measurementsPerLogEntry 1.3.6.1.4.1.13742.6.3.2.4.1.3
The number of measurements used for each entry in the log.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

logSize 1.3.6.1.4.1.13742.6.3.2.4.1.4
The number of entries in the log.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

dataLoggingEnableForAllSensors 1.3.6.1.4.1.13742.6.3.2.4.1.5
Operation to control data logging for all sensors. If this OID is set to true, then all xxxSensorLogAvailable are set to true If this OID is set to false, then all xxxSensorLogAvailable are set to false
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

trapInformationTable 1.3.6.1.4.1.13742.6.0.0.1
A list of Trap Information entries. The number of entries is given by the value of pduCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TrapInformationEntryStruct

trapInformationEntry 1.3.6.1.4.1.13742.6.0.0.1.1
An entry containing objects used in traps.
Status: current Access: not-accessible
OBJECT-TYPE    
  TrapInformationEntryStruct  

userName 1.3.6.1.4.1.13742.6.0.0.1.1.2
The user currently logged in.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

targetUser 1.3.6.1.4.1.13742.6.0.0.1.1.3
The user added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

imageVersion 1.3.6.1.4.1.13742.6.0.0.1.1.5
The version of the upgrade image.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

roleName 1.3.6.1.4.1.13742.6.0.0.1.1.6
The role added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpMessageRecipients 1.3.6.1.4.1.13742.6.0.0.1.1.7
Comma separated list of SMTP Message recipients
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpServer 1.3.6.1.4.1.13742.6.0.0.1.1.8
The IP address/host name of the SMTP server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

oldSensorState 1.3.6.1.4.1.13742.6.0.0.2
The old sensor state used in Sensor State Transition traps.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  SensorStateEnumeration  

pduNumber 1.3.6.1.4.1.13742.6.0.0.3
A unique value for each PDU. Its value ranges between 1 and the value of pduCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

inletPoleNumber 1.3.6.1.4.1.13742.6.0.0.5
A unique value for each inlet Pole. Its value ranges between 1 and the value of inletPoleCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

outletPoleNumber 1.3.6.1.4.1.13742.6.0.0.7
A unique value for each outlet Pole. Its value ranges between 1 and the value of outletPoleCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

externalSensorNumber 1.3.6.1.4.1.13742.6.0.0.8
A unique value for each external sensor. Its value ranges between 1 and the value of externalSensorCount.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

typeOfSensor 1.3.6.1.4.1.13742.6.0.0.10
The type of sensor.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  SensorTypeEnumeration  

errorDescription 1.3.6.1.4.1.13742.6.0.0.11
Description of the Error
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

deviceChangedParameter 1.3.6.1.4.1.13742.6.0.0.12
Description of the parameter(s) that changed.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DeviceIdentificationParameterEnumeration  

changedParameterNewValue 1.3.6.1.4.1.13742.6.0.0.13
The new value of the changed parameter
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

lhxSupportEnabled 1.3.6.1.4.1.13742.6.0.0.14
The new enabled state for Schroff LHX Support.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  TruthValue  

webcamModel 1.3.6.1.4.1.13742.6.0.0.15
The model of the Webcam
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

webcamConnectionPort 1.3.6.1.4.1.13742.6.0.0.16
The port to which the Webcam is connected
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

agentInetPortNumber 1.3.6.1.4.1.13742.6.0.0.18
The UDP port number used for accessing the SNMP agent on the device. Examples: If deviceCascadeType is portForwarding, then master: 50500 slave 1:50501 slave 2: 50502 ...... If cascading mode is not portForwarding and default (Standard) ports are being used, then port: 161
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  InetPortNumber  

peripheralDeviceRomcode 1.3.6.1.4.1.13742.6.0.0.19
The Romcode of an peripheral device
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

peripheralDeviceFirmwareUpdateState 1.3.6.1.4.1.13742.6.0.0.20
The firmware update state of an peripheral device
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  PeripheralDeviceFirmwareUpdateStateEnumeration  

circuitNumber 1.3.6.1.4.1.13742.6.0.0.21
A unique value for each circuit. circuitId is defined as follows. circuitID = 1000*(panelId) + circuitPosition Examples: 1045 is the the circuit on panel 1 with lowest circuit position equal to 45 4067 is the the circuit on panel 4 with lowest circuit position equal to 67.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..33000  

circuitPoleNumber 1.3.6.1.4.1.13742.6.0.0.22
A unique value for each circuit Pole.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..256  

phoneNumber 1.3.6.1.4.1.13742.6.0.0.23
The phone number of e.g. an SMS receiver.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

unitSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.2.5
A list of unit level sensors for a PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UnitSensorConfigurationEntryStruct

unitSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.2.5.1
An entry containing unit sensor parameters.
Status: current Access: not-accessible
OBJECT-TYPE    
  UnitSensorConfigurationEntryStruct  

sensorType 1.3.6.1.4.1.13742.6.3.2.5.1.1
The type of sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SensorTypeEnumeration  

unitSensorLogAvailable 1.3.6.1.4.1.13742.6.3.2.5.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

unitSensorUnits 1.3.6.1.4.1.13742.6.3.2.5.1.6
The units in which the sensor data is reported.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

unitSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.2.5.1.7
The number of digits displayed to the right of the decimal point.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorAccuracy 1.3.6.1.4.1.13742.6.3.2.5.1.8
The accuracy: how close (in percent) the measurement is to the actual value.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

unitSensorResolution 1.3.6.1.4.1.13742.6.3.2.5.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorTolerance 1.3.6.1.4.1.13742.6.3.2.5.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1). For example, if the value is 50 and unitSensorDecimalDigits is 2, then actual value is 0.05.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorMaximum 1.3.6.1.4.1.13742.6.3.2.5.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorMinimum 1.3.6.1.4.1.13742.6.3.2.5.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorHysteresis 1.3.6.1.4.1.13742.6.3.2.5.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.2.5.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

unitSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.2.5.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

unitSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.2.5.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.2.5.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

unitSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

unitSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

unitSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.2.5.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletConfigurationTable 1.3.6.1.4.1.13742.6.3.3.3
A list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletConfigurationEntryStruct

inletConfigurationEntry 1.3.6.1.4.1.13742.6.3.3.3.1
An entry containing parametersfor a particular inlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletConfigurationEntryStruct  

inletId 1.3.6.1.4.1.13742.6.3.3.3.1.1
A unique value for each inlet. Its value ranges between 1 and the value of inletCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

inletLabel 1.3.6.1.4.1.13742.6.3.3.3.1.2
The label on the PDU identifying the inlet.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inletName 1.3.6.1.4.1.13742.6.3.3.3.1.3
The user-defined name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

inletPlug 1.3.6.1.4.1.13742.6.3.3.3.1.4
The type of plug/receptacle wired to the inlet.
Status: current Access: read-only
OBJECT-TYPE    
  PlugTypeEnumeration  

inletPoleCount 1.3.6.1.4.1.13742.6.3.3.3.1.5
The number of poles. PDU: 2 for 1-phase circuits 3 for 3-phase DELTA wired models; 4 for 3-phase WYE wired models; Pole 4 is neutral; Note that sensors are not supported for neutral poles; Power Meter: 5: Pole 1 is Phase A Pole 2 is Phase B Pole 3 is Phase C Pole 4 is Neutral Pole 5 is Earth
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 2..5  

inletRatedVoltage 1.3.6.1.4.1.13742.6.3.3.3.1.6
The inlet voltage rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inletRatedCurrent 1.3.6.1.4.1.13742.6.3.3.3.1.7
The inlet current rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inletRatedFrequency 1.3.6.1.4.1.13742.6.3.3.3.1.8
The inlet frequency rating. Deprecated: use pduRatedFrequency for unit nameplate information.
Status: deprecated Access: read-only
OBJECT-TYPE    
  DisplayString  

inletRatedVA 1.3.6.1.4.1.13742.6.3.3.3.1.9
The inlet VA (VoltAmps) rating. Deprecated: use pduRatedVA for unit nameplate information.
Status: deprecated Access: read-only
OBJECT-TYPE    
  DisplayString  

inletDeviceCapabilities 1.3.6.1.4.1.13742.6.3.3.3.1.10
A bit string which indicates which inlet sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), surgeProtectorStatus(21), frequency(22), phaseAngle(23), residualCurrent(25), rcmState(26), reactivePower(28), powerQuality(31)  

inletPoleCapabilities 1.3.6.1.4.1.13742.6.3.3.3.1.11
A bit string which indicates which inletpole sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), phaseAngle(23), rmsVoltageLN(24), reactivePower(28), displacementPowerFactor(34)  

inletPlugDescriptor 1.3.6.1.4.1.13742.6.3.3.3.1.12
Description of the Plug
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inletEnableState 1.3.6.1.4.1.13742.6.3.3.3.1.13
Is this PDU operation is enabled for this inlet? When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet switching is no longer allowed. This is only meaningful for multi-inlet units if one inlet is temporarily expected to be powered down. Disabling the inlet of a single-inlet unit is forbidden and any attempt to do so will result in an error.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

inletRCMResidualOperatingCurrent 1.3.6.1.4.1.13742.6.3.3.3.1.14
The Residual Operating Current (Threshold) for the RCM State sensor. For inlets without an RCM, any attempt to access this OID will return NoSuchInstance error. The value of this OID is in milliamps.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleConfigurationTable 1.3.6.1.4.1.13742.6.3.3.5
A list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletPoleConfigurationEntryStruct

inletPoleConfigurationEntry 1.3.6.1.4.1.13742.6.3.3.5.1
An entry containing parametersfor a particular inlet pole.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletPoleConfigurationEntryStruct  

inletPoleLine 1.3.6.1.4.1.13742.6.3.3.5.1.1
The Phase for this inlet Pole.
Status: current Access: read-only
OBJECT-TYPE    
  LineEnumeration  

inletPoleNode 1.3.6.1.4.1.13742.6.3.3.5.1.2
The node to which this inlet pole is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.3.4
A list of configuration entries for an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletSensorConfigurationEntryStruct

inletSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.3.4.1
An entry containing objects for configuring an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletSensorConfigurationEntryStruct  

inletSensorLogAvailable 1.3.6.1.4.1.13742.6.3.3.4.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

inletSensorUnits 1.3.6.1.4.1.13742.6.3.3.4.1.6
The base units. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

inletSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.3.4.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletSensorAccuracy 1.3.6.1.4.1.13742.6.3.3.4.1.8
The accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

inletSensorResolution 1.3.6.1.4.1.13742.6.3.3.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletSensorTolerance 1.3.6.1.4.1.13742.6.3.3.4.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (inletSensorDecimalDigits + 1). For example, if the value is 50 and inletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletSensorMaximum 1.3.6.1.4.1.13742.6.3.3.4.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletSensorMinimum 1.3.6.1.4.1.13742.6.3.3.4.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletSensorHysteresis 1.3.6.1.4.1.13742.6.3.3.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.3.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.3.4.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

inletSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.3.4.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.3.4.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.3.4.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletPoleSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.3.6
A list of configuration entries for an inlet pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletPoleSensorConfigurationEntryStruct

inletPoleSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.3.6.1
An entry containing objects for configuring an inlet pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletPoleSensorConfigurationEntryStruct  

inletPoleIndex 1.3.6.1.4.1.13742.6.3.3.6.1.1
A unique value for each inlet Pole. Its value ranges between 1 and the value of inletPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

inletPoleSensorLogAvailable 1.3.6.1.4.1.13742.6.3.3.6.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

inletPoleSensorUnits 1.3.6.1.4.1.13742.6.3.3.6.1.6
The base units. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

inletPoleSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.3.6.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorAccuracy 1.3.6.1.4.1.13742.6.3.3.6.1.8
The accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

inletPoleSensorResolution 1.3.6.1.4.1.13742.6.3.3.6.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorTolerance 1.3.6.1.4.1.13742.6.3.3.6.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (inletPoleSensorDecimalDigits + 1). For example, if the value is 50 and inletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorMaximum 1.3.6.1.4.1.13742.6.3.3.6.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorMinimum 1.3.6.1.4.1.13742.6.3.3.6.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorHysteresis 1.3.6.1.4.1.13742.6.3.3.6.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.3.6.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

inletPoleSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.3.6.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

inletPoleSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.3.6.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletPoleSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.3.6.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletPoleSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletPoleSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletPoleSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

inletPoleSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.3.6.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

overCurrentProtectorConfigurationTable 1.3.6.1.4.1.13742.6.3.4.3
A list of overCurrentProtector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OverCurrentProtectorConfigurationEntryStruct

overCurrentProtectorConfigurationEntry 1.3.6.1.4.1.13742.6.3.4.3.1
An entry containing objects for a particular overCurrentProtector.
Status: current Access: not-accessible
OBJECT-TYPE    
  OverCurrentProtectorConfigurationEntryStruct  

overCurrentProtectorIndex 1.3.6.1.4.1.13742.6.3.4.3.1.1
A unique value for each overcurrent protector. Its value ranges between 1 and the value of overCurrentProtectorCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

overCurrentProtectorLabel 1.3.6.1.4.1.13742.6.3.4.3.1.2
The label on the PDU identifying the overcurrent protector.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

overCurrentProtectorName 1.3.6.1.4.1.13742.6.3.4.3.1.3
The user-defined name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

overCurrentProtectorType 1.3.6.1.4.1.13742.6.3.4.3.1.4
The type of overcurrent protector.
Status: current Access: read-only
OBJECT-TYPE    
  OverCurrentProtectorTypeEnumeration  

overCurrentProtectorRatedCurrent 1.3.6.1.4.1.13742.6.3.4.3.1.5
The current rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

overCurrentProtectorPoleCount 1.3.6.1.4.1.13742.6.3.4.3.1.6
The number of overCurrentProtector poles.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..3  

overCurrentProtectorCapabilities 1.3.6.1.4.1.13742.6.3.4.3.1.9
A bit string which indicates which overcurrent protector sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), trip(14)  

overCurrentProtectorPowerSource 1.3.6.1.4.1.13742.6.3.4.3.1.10
This object allows discovery of how the PDU is wired. It indicates the overCurrentProtector's power source which can one of the following: overCurrentProtector transfer switch inlet If the power source is an OverCurrentProtector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The index of the OID can then be used to reference other objects in the overCurrentProtectorConfigurationTable. If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable. If the power source is a transferSwitch, it contains the OID of a transferSwitchLabel in the transferSwitchConfiguration Table. The index of the OID can then be used to reference other objects in the transferSwitchConfigurationTable.
Status: current Access: read-only
OBJECT-TYPE    
  RowPointer  

overCurrentProtectorPoleConfigurationTable 1.3.6.1.4.1.13742.6.3.4.5
A list of overCurrentProtector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OverCurrentProtectorPoleConfigurationEntryStruct

overCurrentProtectorPoleConfigurationEntry 1.3.6.1.4.1.13742.6.3.4.5.1
An entry containing parametersfor a particular overCurrentProtector pole.
Status: current Access: not-accessible
OBJECT-TYPE    
  OverCurrentProtectorPoleConfigurationEntryStruct  

overCurrentProtectorPoleIndex 1.3.6.1.4.1.13742.6.3.4.5.1.1
A unique value for each overCurrentProtector Pole. Its value ranges between 1 and the value of overCurrentProtectorPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

overCurrentProtectorPoleLine 1.3.6.1.4.1.13742.6.3.4.5.1.2
The Phase for this overCurrentProtector Pole.
Status: current Access: read-only
OBJECT-TYPE    
  LineEnumeration  

overCurrentProtectorPoleInNode 1.3.6.1.4.1.13742.6.3.4.5.1.3
The node to which this overCurrentProtector pole input is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorPoleOutNode 1.3.6.1.4.1.13742.6.3.4.5.1.4
The node to which this overCurrentProtector pole output is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.4.4
A list of overCurrentProtectorSensor configuration entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OverCurrentProtectorSensorConfigurationEntryStruct

overCurrentProtectorSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.4.4.1
An overCurrentProtectorSensor entry containing objects for a particular overCurrentProtector Sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OverCurrentProtectorSensorConfigurationEntryStruct  

overCurrentProtectorSensorLogAvailable 1.3.6.1.4.1.13742.6.3.4.4.1.4
Is logging available for this sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

overCurrentProtectorSensorUnits 1.3.6.1.4.1.13742.6.3.4.4.1.6
The base units This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

overCurrentProtectorSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.4.4.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorAccuracy 1.3.6.1.4.1.13742.6.3.4.4.1.8
The accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

overCurrentProtectorSensorResolution 1.3.6.1.4.1.13742.6.3.4.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorTolerance 1.3.6.1.4.1.13742.6.3.4.4.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (overCurrentProtectorSensorDecimalDigits + 1). For example, if the value is 50 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorMaximum 1.3.6.1.4.1.13742.6.3.4.4.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorMinimum 1.3.6.1.4.1.13742.6.3.4.4.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorHysteresis 1.3.6.1.4.1.13742.6.3.4.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.4.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

overCurrentProtectorSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.4.4.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

overCurrentProtectorSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.4.4.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.4.4.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.4.4.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletConfigurationTable 1.3.6.1.4.1.13742.6.3.5.3
A list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletConfigurationEntryStruct

outletConfigurationEntry 1.3.6.1.4.1.13742.6.3.5.3.1
An outlet entry containing parameters for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletConfigurationEntryStruct  

outletId 1.3.6.1.4.1.13742.6.3.5.3.1.1
A unique value for each outlet. Its value ranges between 1 and the value of outletCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

outletLabel 1.3.6.1.4.1.13742.6.3.5.3.1.2
The label on the PDU identifying the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

outletName 1.3.6.1.4.1.13742.6.3.5.3.1.3
The user-defined name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

outletReceptacle 1.3.6.1.4.1.13742.6.3.5.3.1.4
The plug.
Status: current Access: read-only
OBJECT-TYPE    
  ReceptacleTypeEnumeration  

outletPoleCount 1.3.6.1.4.1.13742.6.3.5.3.1.5
The number of poles.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 2..4  

outletRatedVoltage 1.3.6.1.4.1.13742.6.3.5.3.1.6
The outlet voltage rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

outletRatedCurrent 1.3.6.1.4.1.13742.6.3.5.3.1.7
The outlet current rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

outletRatedVA 1.3.6.1.4.1.13742.6.3.5.3.1.8
The outlet VA (VoltAmps) rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

outletDeviceCapabilities 1.3.6.1.4.1.13742.6.3.5.3.1.10
A bit string which indicates which outlet sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), onOff(13), frequency(22), phaseAngle(23)  

outletPoleCapabilities 1.3.6.1.4.1.13742.6.3.5.3.1.11
A bit string which indicates which outlet pole sensors are available.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), rmsVoltageLN(24)  

outletPowerCyclingPowerOffPeriod 1.3.6.1.4.1.13742.6.3.5.3.1.12
The power-off period when an outlet is cycled; overrides the global value; specified in seconds; 0 <= value <= 3600 seconds.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletStateOnStartup 1.3.6.1.4.1.13742.6.3.5.3.1.13
The outlet state on device startup; overrides the global value. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
Status: current Access: read-write
OBJECT-TYPE    
  OutletStateOnStartupEnumeration  

outletUseGlobalPowerCyclingPowerOffPeriod 1.3.6.1.4.1.13742.6.3.5.3.1.14
If this true, then use globalOutletPowerCyclingPowerOffPeriod.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

outletSwitchable 1.3.6.1.4.1.13742.6.3.5.3.1.28
Is this outlet switchable?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

outletReceptacleDescriptor 1.3.6.1.4.1.13742.6.3.5.3.1.29
Description of the Receptacle
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

outletNonCritical 1.3.6.1.4.1.13742.6.3.5.3.1.30
Is this outlet non-critical?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

outletSequenceDelay 1.3.6.1.4.1.13742.6.3.5.3.1.32
The time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycledThis applies only when all outlets are being switched on or cycled. It is specified in seconds; 1 <= value <= 3600 seconds. The actual time interval used can never be less than the inrushGuardDelay defined in the unitConfigurationTable. Examples: 1) inrush Guard Delay is 2 seconds and outletSequenceDelay is 5 seconds. The time interval will be 5 seconds 2) inrush Guard Delay is 5 seconds and outletSequenceDelay is 2 seconds. The time interval will be 5 seconds
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPowerSource 1.3.6.1.4.1.13742.6.3.5.3.1.33
This object allows discovery of how the PDU is wired. It indicates the outlet's power source which can one of the following: overCurrentProtector transfer switch inlet If the power source is an OverCurrentProtector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The index of the OID can then be used to reference other objects in the overCurrentProtectorConfigurationTable. If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable. If the power source is a transferSwitch, it contains the OID of a transferSwitchLabel in the transferSwitchConfiguration Table. The index of the OID can then be used to reference other objects in the transferSwitchConfigurationTable.
Status: current Access: read-only
OBJECT-TYPE    
  RowPointer  

outletPoleConfigurationTable 1.3.6.1.4.1.13742.6.3.5.5
A list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletPoleConfigurationEntryStruct

outletPoleConfigurationEntry 1.3.6.1.4.1.13742.6.3.5.5.1
An entry containing parametersfor a particular outlet pole.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletPoleConfigurationEntryStruct  

outletPoleLine 1.3.6.1.4.1.13742.6.3.5.5.1.1
The Phase for this inlet Pole.
Status: current Access: read-only
OBJECT-TYPE    
  LineEnumeration  

outletPoleNode 1.3.6.1.4.1.13742.6.3.5.5.1.2
The node to which this outlet pole is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.5.4
A list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletSensorConfigurationEntryStruct

outletSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.5.4.1
An entry containing parameters for an outlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletSensorConfigurationEntryStruct  

outletSensorLogAvailable 1.3.6.1.4.1.13742.6.3.5.4.1.4
Is logging available for this sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

outletSensorUnits 1.3.6.1.4.1.13742.6.3.5.4.1.6
The base units. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

outletSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.5.4.1.7
The number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletSensorAccuracy 1.3.6.1.4.1.13742.6.3.5.4.1.8
The accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

outletSensorResolution 1.3.6.1.4.1.13742.6.3.5.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletSensorTolerance 1.3.6.1.4.1.13742.6.3.5.4.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (outletSensorDecimalDigits + 1). For example, if the value is 50 and outletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletSensorMaximum 1.3.6.1.4.1.13742.6.3.5.4.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletSensorMinimum 1.3.6.1.4.1.13742.6.3.5.4.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletSensorHysteresis 1.3.6.1.4.1.13742.6.3.5.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.5.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.5.4.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

outletSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.5.4.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.5.4.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.5.4.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletPoleSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.5.6
A list of outlet pole sensor configuration entries. The number of entries is given by the value of outletPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletPoleSensorConfigurationEntryStruct

outletPoleSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.5.6.1
An entry containing objects for configuring an outlet pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletPoleSensorConfigurationEntryStruct  

outletPoleIndex 1.3.6.1.4.1.13742.6.3.5.6.1.1
A unique value for each outlet Pole. Its value ranges between 1 and the value of outletPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

outletPoleSensorLogAvailable 1.3.6.1.4.1.13742.6.3.5.6.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

outletPoleSensorUnits 1.3.6.1.4.1.13742.6.3.5.6.1.6
The base units. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

outletPoleSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.5.6.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorAccuracy 1.3.6.1.4.1.13742.6.3.5.6.1.8
The accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

outletPoleSensorResolution 1.3.6.1.4.1.13742.6.3.5.6.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorTolerance 1.3.6.1.4.1.13742.6.3.5.6.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (outletPoleSensorDecimalDigits + 1). For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorMaximum 1.3.6.1.4.1.13742.6.3.5.6.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorMinimum 1.3.6.1.4.1.13742.6.3.5.6.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorHysteresis 1.3.6.1.4.1.13742.6.3.5.6.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.5.6.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

outletPoleSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.5.6.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

outletPoleSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.5.6.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletPoleSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.5.6.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletPoleSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletPoleSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletPoleSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletPoleSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.5.6.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.6.3
A list of externalSensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorConfigurationEntryStruct

externalSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.6.3.1
An entry containing parameters for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorConfigurationEntryStruct  

sensorID 1.3.6.1.4.1.13742.6.3.6.3.1.1
A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

externalSensorType 1.3.6.1.4.1.13742.6.3.6.3.1.2
The type of sensor.
Status: current Access: read-only
OBJECT-TYPE    
  SensorTypeEnumeration  

externalSensorSerialNumber 1.3.6.1.4.1.13742.6.3.6.3.1.3
The sensor serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

externalSensorName 1.3.6.1.4.1.13742.6.3.6.3.1.4
The user-defined name.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorDescription 1.3.6.1.4.1.13742.6.3.6.3.1.5
The user-defined description.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorXCoordinate 1.3.6.1.4.1.13742.6.3.6.3.1.6
The X coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorYCoordinate 1.3.6.1.4.1.13742.6.3.6.3.1.7
The Y coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorZCoordinate 1.3.6.1.4.1.13742.6.3.6.3.1.8
The Z coordinate.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

externalSensorChannelNumber 1.3.6.1.4.1.13742.6.3.6.3.1.9
The channel number, applies only to contact sensors; -1 for other sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalOnOffSensorSubtype 1.3.6.1.4.1.13742.6.3.6.3.1.10
The subtype of the binary sensor
Status: current Access: read-write
OBJECT-TYPE    
  SensorTypeEnumeration  

externalSensorLogAvailable 1.3.6.1.4.1.13742.6.3.6.3.1.14
Is logging available for this sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

externalSensorUnits 1.3.6.1.4.1.13742.6.3.6.3.1.16
The base units This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

externalSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.6.3.1.17
The number of digits displayed to the right of the decimal point This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorAccuracy 1.3.6.1.4.1.13742.6.3.6.3.1.18
The accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

externalSensorResolution 1.3.6.1.4.1.13742.6.3.6.3.1.19
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorTolerance 1.3.6.1.4.1.13742.6.3.6.3.1.20
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1). For example, if the value is 50 and externalSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

externalSensorMaximum 1.3.6.1.4.1.13742.6.3.6.3.1.21
The largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorMinimum 1.3.6.1.4.1.13742.6.3.6.3.1.22
The smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorHysteresis 1.3.6.1.4.1.13742.6.3.6.3.1.23
The hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.6.3.1.24
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. At present, this value cannot be written (set)
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.6.3.1.31
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.6.3.1.32
The lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.6.3.1.33
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.6.3.1.34
The upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.6.3.1.35
A bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

externalSensorIsActuator 1.3.6.1.4.1.13742.6.3.6.3.1.36
Is this an actuator? True: It is an actuator False: It is not an actuator
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

externalSensorPosition 1.3.6.1.4.1.13742.6.3.6.3.1.37
The position of the sensor. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples 1) Onboard Sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old style sensor connected to end of new style sensor chain DEVICE-1WIREPORT:2;
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

externalSensorUseDefaultThresholds 1.3.6.1.4.1.13742.6.3.6.3.1.38
Use default thresholds for this sensor? True: Use Default thresholds for this sensor False: Do not Use Default thresholds for this sensor
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

externalSensorAlarmedToNormalDelay 1.3.6.1.4.1.13742.6.3.6.3.1.39
The delay in seconds for transitions from the alarmed state to the normal state. If the sensor type is motionDetection, then it can set to a value greater >= 0 For all other sensor types, the value is 0 and cannot be set to any other value.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultThresholdsTable 1.3.6.1.4.1.13742.6.3.6.4
A list of entries listing the default thresholds for each sensor type.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorTypeDefaultThresholdsEntryStruct

externalSensorTypeDefaultThresholdsEntry 1.3.6.1.4.1.13742.6.3.6.4.1
An entry containing default thresholds for a sensor type.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorTypeDefaultThresholdsEntryStruct  

externalSensorTypeDefaultHysteresis 1.3.6.1.4.1.13742.6.3.6.4.1.3
The hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorTypeDefaultStateChangeDelay 1.3.6.1.4.1.13742.6.3.6.4.1.4
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. At present, this value cannot be written (set)
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

externalSensorTypeDefaultLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.6.4.1.5
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.6.4.1.6
The lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.6.4.1.7
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.6.4.1.8
The upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

externalSensorTypeDefaultEnabledThresholds 1.3.6.1.4.1.13742.6.3.6.4.1.9
A bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

serverReachabilityTable 1.3.6.1.4.1.13742.6.3.7.3
A list of server entries. The number of entries is given by the value of serverCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ServerReachabilityEntryStruct

serverReachabilityEntry 1.3.6.1.4.1.13742.6.3.7.3.1
An entry containing parameters for a server.
Status: current Access: not-accessible
OBJECT-TYPE    
  ServerReachabilityEntryStruct  

serverID 1.3.6.1.4.1.13742.6.3.7.3.1.1
A unique value for each server. Its value ranges between 1 and the value of serverCount for that PDU
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

serverIPAddress 1.3.6.1.4.1.13742.6.3.7.3.1.3
The IP Address/host name of the server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

serverPingEnabled 1.3.6.1.4.1.13742.6.3.7.3.1.4
Is ping enabled for this server?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

wireConfigurationTable 1.3.6.1.4.1.13742.6.3.8.3
A list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WireConfigurationEntryStruct

wireConfigurationEntry 1.3.6.1.4.1.13742.6.3.8.3.1
An entry containing objects for a particular wire.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  WireConfigurationEntryStruct  

wireId 1.3.6.1.4.1.13742.6.3.8.3.1.1
A unique value for each wire. Its value ranges between 1 and the value of wireCount.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

wireLabel 1.3.6.1.4.1.13742.6.3.8.3.1.2
The label on the PDU identifying the wire.
Status: deprecated Access: read-only
OBJECT-TYPE    
  DisplayString  

wireCapabilities 1.3.6.1.4.1.13742.6.3.8.3.1.3
A bit string which indicates which wire sensors are available.
Status: deprecated Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8)  

wirePowerSource 1.3.6.1.4.1.13742.6.3.8.3.1.4
This object allows discovery of how the PDU is wired. It indicates the wire's power source which can one of the following: overCurrentProtector transfer switch inlet If the power source is an OverCurrentProtector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The index of the OID can then be used to reference other objects in the overCurrentProtectorConfigurationTable. If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable. If the power source is a transferSwitch, it contains the OID of a transferSwitchLabel in the transferSwitchConfiguration Table. The index of the OID can then be used to reference other objects in the transferSwitchConfigurationTable.
Status: deprecated Access: read-only
OBJECT-TYPE    
  RowPointer  

wireSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.8.4
A list of wireSensor configuration entries.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WireSensorConfigurationEntryStruct

wireSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.8.4.1
An wireSensor entry containing objects for a particular wire Sensor.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  WireSensorConfigurationEntryStruct  

wireSensorLogAvailable 1.3.6.1.4.1.13742.6.3.8.4.1.4
Is logging available for this sensor?
Status: deprecated Access: read-write
OBJECT-TYPE    
  TruthValue  

wireSensorUnits 1.3.6.1.4.1.13742.6.3.8.4.1.6
The base units
Status: deprecated Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

wireSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.8.4.1.7
The number of digits displayed to the right of the decimal point.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorAccuracy 1.3.6.1.4.1.13742.6.3.8.4.1.8
The accuracy: how close (in percent) the measurement is to the actual value
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

wireSensorResolution 1.3.6.1.4.1.13742.6.3.8.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorTolerance 1.3.6.1.4.1.13742.6.3.8.4.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1). For example, if the value is 50 and wireSensorDecimalDigits is 2, then actual value is 0.05.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorMaximum 1.3.6.1.4.1.13742.6.3.8.4.1.11
The largest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorMinimum 1.3.6.1.4.1.13742.6.3.8.4.1.12
The smallest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorHysteresis 1.3.6.1.4.1.13742.6.3.8.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.8.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. At present, this value cannot be written (set)
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.8.4.1.21
The lower critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.8.4.1.22
The lower non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.8.4.1.23
The upper critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.8.4.1.24
The upper non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.
Status: deprecated Access: read-write
OBJECT-TYPE    
  Unsigned32  

wireSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.8.4.1.25
A bit string which indicates which thresholds are enabled.
Status: deprecated Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

transferSwitchConfigurationTable 1.3.6.1.4.1.13742.6.3.9.3
A list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchConfigurationEntryStruct

transferSwitchConfigurationEntry 1.3.6.1.4.1.13742.6.3.9.3.1
An entry containing objects for a particular transferSwitch.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchConfigurationEntryStruct  

transferSwitchId 1.3.6.1.4.1.13742.6.3.9.3.1.1
A unique value for each transfer switch. Its value ranges between 1 and the value of transferSwitchCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

transferSwitchLabel 1.3.6.1.4.1.13742.6.3.9.3.1.2
The label on the PDU identifying the TS.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

transferSwitchName 1.3.6.1.4.1.13742.6.3.9.3.1.3
The user-defined name of the transferSwitch.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

transferSwitchPreferredInlet 1.3.6.1.4.1.13742.6.3.9.3.1.4
The preferred Inlet. The TS powers the outlet from the preferred inlet when acceptable power is available from the preferred inlet.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..64  

transferSwitchPoleCount 1.3.6.1.4.1.13742.6.3.9.3.1.5
The number of poles.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 2..4  

transferSwitchAutoReTransferEnabled 1.3.6.1.4.1.13742.6.3.9.3.1.20
The TS can be configured to automatically retransfer back to the preferred inlet when power is restored. Re-transfer only occurs if this variable is true.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

transferSwitchAutoReTransferWaitTime 1.3.6.1.4.1.13742.6.3.9.3.1.21
The Auto Re-Transfer Wait Time. Re-transfer occurs this many seconds after the condition causing the original transfer has been corrected.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchAutoReTransferRequiresPhaseSync 1.3.6.1.4.1.13742.6.3.9.3.1.22
If this parameter is False, then do not retransfer if there is a PHASE_SYNC_FAULT in effect. A PHASE_SYNC_FAULT occurs when the phase difference between the inlets is too high.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

transferSwitchFrontPanelManualTransferButtonEnabled 1.3.6.1.4.1.13742.6.3.9.3.1.23
If this parameter is false, then manual transfers caused by pressing the front panel switch are disabled.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

transferSwitchCapabilities 1.3.6.1.4.1.13742.6.3.9.3.1.24
A bit string which indicates which sensors are available for the transfer switch.
Status: current Access: read-only
OBJECT-TYPE    
  BITS overloadStatus(32), inletPhaseSyncAngle(37), inletPhaseSync(38), operatingState(39), activeInlet(40), switchStatus(47)  

transferSwitchPowerSource1 1.3.6.1.4.1.13742.6.3.9.3.1.31
This object allows discovery of how the PDU is wired. It indicates the transferSwitch's first power source which can one of the following: overCurrentProtector transfer switch inlet If the power source is an OverCurrentProtector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The index of the OID can then be used to reference other objects in the overCurrentProtectorConfigurationTable. If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable. If the power source is a transferSwitch, it contains the OID of a transferSwitchLabel in the transferSwitchConfiguration Table. The index of the OID can then be used to reference other objects in the transferSwitchConfigurationTable.
Status: current Access: read-only
OBJECT-TYPE    
  RowPointer  

transferSwitchPowerSource2 1.3.6.1.4.1.13742.6.3.9.3.1.32
This object allows discovery of how the PDU is wired. It indicates the transferSwitch's second power source which can one of the following: overCurrentProtector transfer switch inlet If the power source is an OverCurrentProtector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The index of the OID can then be used to reference other objects in the overCurrentProtectorConfigurationTable. If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable. If the power source is a transferSwitch, it contains the OID of a transferSwitchLabel in the transferSwitchConfiguration Table. The index of the OID can then be used to reference other objects in the transferSwitchConfigurationTable
Status: current Access: read-only
OBJECT-TYPE    
  RowPointer  

transferSwitchPoleConfigurationTable 1.3.6.1.4.1.13742.6.3.9.5
A list of transferSwitch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchPoleConfigurationEntryStruct

transferSwitchPoleConfigurationEntry 1.3.6.1.4.1.13742.6.3.9.5.1
An entry containing parametersfor a particular outlet pole.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchPoleConfigurationEntryStruct  

transferSwitchPoleIndex 1.3.6.1.4.1.13742.6.3.9.5.1.1
A unique value for each transferSwitch Pole. Its value ranges between 1 and the value of transferSwitchPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

transferSwitchPoleLine 1.3.6.1.4.1.13742.6.3.9.5.1.2
The Phase for this transferSwitch Pole.
Status: current Access: read-only
OBJECT-TYPE    
  LineEnumeration  

transferSwitchPoleIn1Node 1.3.6.1.4.1.13742.6.3.9.5.1.3
The node to which this transferSwitch pole Input 1 is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

transferSwitchPoleIn2Node 1.3.6.1.4.1.13742.6.3.9.5.1.4
The node to which this transferSwitch pole Input 2 is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

transferSwitchPoleOutNode 1.3.6.1.4.1.13742.6.3.9.5.1.5
The node to which this transferSwitch pole Output is connected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

transferSwitchSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.9.4
A list of transfer switch sensor configuration entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchSensorConfigurationEntryStruct

transferSwitchSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.9.4.1
An entry containing parameters for a transfer switch sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchSensorConfigurationEntryStruct  

transferSwitchSensorLogAvailable 1.3.6.1.4.1.13742.6.3.9.4.1.4
Is logging available for this sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

transferSwitchSensorUnits 1.3.6.1.4.1.13742.6.3.9.4.1.6
The base units. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

transferSwitchSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.9.4.1.7
The number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorAccuracy 1.3.6.1.4.1.13742.6.3.9.4.1.8
The accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  HundredthsOfAPercentage  

transferSwitchSensorResolution 1.3.6.1.4.1.13742.6.3.9.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorTolerance 1.3.6.1.4.1.13742.6.3.9.4.1.10
The resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (transferSwitchSensorDecimalDigits + 1). For example, if the value is 50 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorMaximum 1.3.6.1.4.1.13742.6.3.9.4.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorMinimum 1.3.6.1.4.1.13742.6.3.9.4.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorHysteresis 1.3.6.1.4.1.13742.6.3.9.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.9.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.9.4.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

transferSwitchSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.9.4.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

transferSwitchSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.9.4.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

transferSwitchSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

transferSwitchSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

transferSwitchSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

transferSwitchSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.9.4.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

powerMeterConfigurationTable 1.3.6.1.4.1.13742.6.3.10.2
A list of power meter and panel configuration entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PowerMeterConfigurationEntryStruct

powerMeterConfigurationEntry 1.3.6.1.4.1.13742.6.3.10.2.1
An entry containing configuration objects for power meters and panels.
Status: current Access: not-accessible
OBJECT-TYPE    
  PowerMeterConfigurationEntryStruct  

powerMeterPhaseCTRating 1.3.6.1.4.1.13742.6.3.10.2.1.2
The rating of the Phase CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

powerMeterNeutralCTRating 1.3.6.1.4.1.13742.6.3.10.2.1.3
The rating of the Neutral CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

powerMeterEarthCTRating 1.3.6.1.4.1.13742.6.3.10.2.1.4
The rating of the Earth CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

powerMeterBranchCount 1.3.6.1.4.1.13742.6.3.10.2.1.5
The maximum number of circuits supported by the panel. (The number of user configured circuits is in unitConfigurationTable(pduId).circuitCount.) It can be used to distinguish between power meters and panels. If value > 0, then panel (BCM) else power meter
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

powerMeterPanelPositions 1.3.6.1.4.1.13742.6.3.10.2.1.6
The number of circuit positions in the panel. Its value is specified by the user when configuring a panel
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

powerMeterPanelLayout 1.3.6.1.4.1.13742.6.3.10.2.1.7
valid only for panels (powerMeterCircuitPositionCount > 0); invalid for power meters (powerMeterCircuitPositionCount = 0): value returned is invalid(-1). The panel circuit position layout: single column, two columns.
Status: current Access: read-only
OBJECT-TYPE    
  PanelLayoutEnumeration  

powerMeterPanelNumbering 1.3.6.1.4.1.13742.6.3.10.2.1.8
valid only for panels (powerMeterCircuitPositionCount > 0); invalid for power meters (powerMeterCircuitPositionCount = 0): value returned is invalid(-1). The panel circuit position numbering scheme: odd/even, sequential.
Status: current Access: read-only
OBJECT-TYPE    
  PanelNumberingEnumeration  

powerMeterType 1.3.6.1.4.1.13742.6.3.10.2.1.9
The power meter type: 3-phase, single-phase, split-phase.
Status: current Access: read-only
OBJECT-TYPE    
  PowerMeterTypeEnumeration  

circuitConfigurationTable 1.3.6.1.4.1.13742.6.3.11.2
A list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitConfigurationEntryStruct

circuitConfigurationEntry 1.3.6.1.4.1.13742.6.3.11.2.1
An entry containing configuration objects for the circuit.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitConfigurationEntryStruct  

circuitId 1.3.6.1.4.1.13742.6.3.11.2.1.1
A unique value for each circuit. circuitId is defined as follows. It is the circuit position in the panel
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..1024  

circuitPoleCount 1.3.6.1.4.1.13742.6.3.11.2.1.2
The number of circuit positions (poles) in the circuit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

circuitName 1.3.6.1.4.1.13742.6.3.11.2.1.3
The user-defined name for the circuit. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

circuitType 1.3.6.1.4.1.13742.6.3.11.2.1.4
The type of circuit: singlePhaseL_L, singlePhaseL_N, twoPhase,threePhase
Status: current Access: read-only
OBJECT-TYPE    
  CircuitTypeEnumeration  

circuitRatedCurrent 1.3.6.1.4.1.13742.6.3.11.2.1.5
The rating of the breaker for the circuit in A. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitCTRating 1.3.6.1.4.1.13742.6.3.11.2.1.6
The rating of the CTs metering this circuit in A. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitCapabilities 1.3.6.1.4.1.13742.6.3.11.2.1.7
A bit string which indicates which sensors are available for the circuit.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), surgeProtectorStatus(21), frequency(22), phaseAngle(23), residualCurrent(25), rcmState(26), reactivePower(28), powerQuality(31), displacementPowerFactor(34)  

circuitPoleCapabilities 1.3.6.1.4.1.13742.6.3.11.2.1.8
A bit string which indicates which sensors are available for the circuit pole.
Status: current Access: read-only
OBJECT-TYPE    
  BITS rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), phaseAngle(23), rmsVoltageLN(24), reactivePower(28), displacementPowerFactor(34)  

circuitPowerSource 1.3.6.1.4.1.13742.6.3.11.2.1.9
This object allows discovery of how the circuit is wired. It indicates the circuit's power source which can one of the following: Inlet It contains the OID of an inletLabel in the inletConfigurationTable. The index of the OID can then be used to reference other objects in the inletConfigurationTable.
Status: current Access: read-only
OBJECT-TYPE    
  RowPointer  

circuitPoleConfigurationTable 1.3.6.1.4.1.13742.6.3.11.3
A list of Panel Circuit Pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitPoleConfigurationEntryStruct

circuitPoleConfigurationEntry 1.3.6.1.4.1.13742.6.3.11.3.1
An entry containing configuration objects for the circuit poles.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitPoleConfigurationEntryStruct  

circuitPoleId 1.3.6.1.4.1.13742.6.3.11.3.1.1
A unique value for each circuit Pole. Its value ranges between 1 and the value of circuitPoleCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

circuitPolePanelPosition 1.3.6.1.4.1.13742.6.3.11.3.1.2
The circuit position for this pole.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

circuitPoleCTNumber 1.3.6.1.4.1.13742.6.3.11.3.1.3
The CT Number for this circuit Pole, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..256  

circuitPolePhase 1.3.6.1.4.1.13742.6.3.11.3.1.4
The Phase for this circuit Pole. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
Status: current Access: read-write
OBJECT-TYPE    
  PhaseEnumeration  

circuitSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.11.4
A list of configuration entries for an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitSensorConfigurationEntryStruct

circuitSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.11.4.1
An entry containing objects for configuring an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitSensorConfigurationEntryStruct  

circuitSensorLogAvailable 1.3.6.1.4.1.13742.6.3.11.4.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

circuitSensorUnits 1.3.6.1.4.1.13742.6.3.11.4.1.6
The base units. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

circuitSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.11.4.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitSensorResolution 1.3.6.1.4.1.13742.6.3.11.4.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitSensorMaximum 1.3.6.1.4.1.13742.6.3.11.4.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitSensorMinimum 1.3.6.1.4.1.13742.6.3.11.4.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitSensorHysteresis 1.3.6.1.4.1.13742.6.3.11.4.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.11.4.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.11.4.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

circuitSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.11.4.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.11.4.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.11.4.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitPoleSensorConfigurationTable 1.3.6.1.4.1.13742.6.3.11.6
A list of configuration entries for a circuit's pole sensors.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitPoleSensorConfigurationEntryStruct

circuitPoleSensorConfigurationEntry 1.3.6.1.4.1.13742.6.3.11.6.1
An entry containing objects for configuring an inlet pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitPoleSensorConfigurationEntryStruct  

circuitPoleSensorLogAvailable 1.3.6.1.4.1.13742.6.3.11.6.1.4
Is logging enabled for the sensor?
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

circuitPoleSensorUnits 1.3.6.1.4.1.13742.6.3.11.6.1.6
The base units. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  SensorUnitsEnumeration  

circuitPoleSensorDecimalDigits 1.3.6.1.4.1.13742.6.3.11.6.1.7
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorResolution 1.3.6.1.4.1.13742.6.3.11.6.1.9
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorMaximum 1.3.6.1.4.1.13742.6.3.11.6.1.11
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorMinimum 1.3.6.1.4.1.13742.6.3.11.6.1.12
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorHysteresis 1.3.6.1.4.1.13742.6.3.11.6.1.13
The hysteresis used for deassertions The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorStateChangeDelay 1.3.6.1.4.1.13742.6.3.11.6.1.14
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.21
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.22
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.23
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.24
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

circuitPoleSensorEnabledThresholds 1.3.6.1.4.1.13742.6.3.11.6.1.25
A bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

circuitPoleSensorSignedMaximum 1.3.6.1.4.1.13742.6.3.11.6.1.26
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitPoleSensorSignedMinimum 1.3.6.1.4.1.13742.6.3.11.6.1.27
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitPoleSensorSignedLowerCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.28
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitPoleSensorSignedLowerWarningThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.29
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitPoleSensorSignedUpperCriticalThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.30
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitPoleSensorSignedUpperWarningThreshold 1.3.6.1.4.1.13742.6.3.11.6.1.31
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

peripheralDevicePackageTable 1.3.6.1.4.1.13742.6.3.6.5
A list of entries for the peripheral Device Packages connected to each PDU. The number of entries is given by the value of peripheralDevicePackagesCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PeripheralDevicePackageEntryStruct

peripheralDevicePackageEntry 1.3.6.1.4.1.13742.6.3.6.5.1
An entry containing objects for a controller.
Status: current Access: not-accessible
OBJECT-TYPE    
  PeripheralDevicePackageEntryStruct  

peripheralDevicePackageId 1.3.6.1.4.1.13742.6.3.6.5.1.1
A unique value for each peripheral device package.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

peripheralDevicePackageSerialNumber 1.3.6.1.4.1.13742.6.3.6.5.1.3
The peripheral device package serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageModel 1.3.6.1.4.1.13742.6.3.6.5.1.4
The peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageFirmwareVersion 1.3.6.1.4.1.13742.6.3.6.5.1.5
The peripheral device package firmware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageMinFirmwareVersion 1.3.6.1.4.1.13742.6.3.6.5.1.6
The peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral device firmware to a version < minimum firmware version number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageFirmwareTimeStamp 1.3.6.1.4.1.13742.6.3.6.5.1.7
The time when the peripheralDevicePackage firmware was updated in UNIX(epoch)time. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

peripheralDevicePackagePosition 1.3.6.1.4.1.13742.6.3.6.5.1.8
The position of the package. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples 1) Onboard Sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old style sensor connected to end of new style sensor chain DEVICE-1WIREPORT:2;
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

peripheralDevicePackageState 1.3.6.1.4.1.13742.6.3.6.5.1.9
The state of the package.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

logIndexTable 1.3.6.1.4.1.13742.6.6.1.1
A table of log entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LogIndexEntryStruct

logIndexEntry 1.3.6.1.4.1.13742.6.6.1.1.1
An entry in the log containing sensor data.
Status: current Access: not-accessible
OBJECT-TYPE    
  LogIndexEntryStruct  

oldestLogID 1.3.6.1.4.1.13742.6.6.1.1.1.2
The index of the oldest data in the buffer for this PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

newestLogID 1.3.6.1.4.1.13742.6.6.1.1.1.3
The index of the newest data in the buffer for this PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logTimeStampTable 1.3.6.1.4.1.13742.6.6.1.2
A list of entries containing the timestamps of the entries in the log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LogTimeStampEntryStruct

logTimeStampEntry 1.3.6.1.4.1.13742.6.6.1.2.1
An entry containing the timestamp for log entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  LogTimeStampEntryStruct  

logIndex 1.3.6.1.4.1.13742.6.6.1.2.1.1
A unique value for each entry in the log. Its value ranges between 1 and the value of logSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

logTimeStamp 1.3.6.1.4.1.13742.6.6.1.2.1.2
The time when the data was collected. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

unitSensorLogTable 1.3.6.1.4.1.13742.6.6.1.3
A list of unit sensor entries in the log.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UnitSensorLogEntryStruct

unitSensorLogEntry 1.3.6.1.4.1.13742.6.6.1.3.1
An entry containing log objects for an unit sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  UnitSensorLogEntryStruct  

logUnitSensorDataAvailable 1.3.6.1.4.1.13742.6.6.1.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logUnitSensorState 1.3.6.1.4.1.13742.6.6.1.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logUnitSensorAvgValue 1.3.6.1.4.1.13742.6.6.1.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logUnitSensorMaxValue 1.3.6.1.4.1.13742.6.6.1.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logUnitSensorMinValue 1.3.6.1.4.1.13742.6.6.1.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logUnitSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.1.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logUnitSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.1.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logUnitSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.1.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletSensorLogTable 1.3.6.1.4.1.13742.6.6.2.3
A list of inlet sensor entries. The number of entries is given by the value of inletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletSensorLogEntryStruct

inletSensorLogEntry 1.3.6.1.4.1.13742.6.6.2.3.1
An entry containing log objects for an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletSensorLogEntryStruct  

logInletSensorDataAvailable 1.3.6.1.4.1.13742.6.6.2.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logInletSensorState 1.3.6.1.4.1.13742.6.6.2.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logInletSensorAvgValue 1.3.6.1.4.1.13742.6.6.2.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletSensorMaxValue 1.3.6.1.4.1.13742.6.6.2.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletSensorMinValue 1.3.6.1.4.1.13742.6.6.2.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.2.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logInletSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.2.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logInletSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.2.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletPoleSensorLogTable 1.3.6.1.4.1.13742.6.6.2.4
A list of inletPole sensor entries. The number of entries is given by the value of inletPoleCount for the inlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletPoleSensorLogEntryStruct

inletPoleSensorLogEntry 1.3.6.1.4.1.13742.6.6.2.4.1
An entry containing log objects for an inletPole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletPoleSensorLogEntryStruct  

logInletPoleSensorDataAvailable 1.3.6.1.4.1.13742.6.6.2.4.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logInletPoleSensorState 1.3.6.1.4.1.13742.6.6.2.4.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logInletPoleSensorAvgValue 1.3.6.1.4.1.13742.6.6.2.4.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletPoleSensorMaxValue 1.3.6.1.4.1.13742.6.6.2.4.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletPoleSensorMinValue 1.3.6.1.4.1.13742.6.6.2.4.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logInletPoleSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.2.4.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logInletPoleSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.2.4.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logInletPoleSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.2.4.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSensorLogTable 1.3.6.1.4.1.13742.6.6.4.3
A list of outlet sensor entries. The number of entries is given by the value of outletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletSensorLogEntryStruct

outletSensorLogEntry 1.3.6.1.4.1.13742.6.6.4.3.1
An entry containing log objects for an outlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletSensorLogEntryStruct  

logOutletSensorDataAvailable 1.3.6.1.4.1.13742.6.6.4.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logOutletSensorState 1.3.6.1.4.1.13742.6.6.4.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logOutletSensorAvgValue 1.3.6.1.4.1.13742.6.6.4.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletSensorMaxValue 1.3.6.1.4.1.13742.6.6.4.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletSensorMinValue 1.3.6.1.4.1.13742.6.6.4.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.4.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOutletSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.4.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOutletSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.4.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletPoleSensorLogTable 1.3.6.1.4.1.13742.6.6.4.4
A list of outletPole sensor entries. The number of entries is given by the value of outletPoleCount for the outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletPoleSensorLogEntryStruct

outletPoleSensorLogEntry 1.3.6.1.4.1.13742.6.6.4.4.1
An entry containing log objects for an outletPole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletPoleSensorLogEntryStruct  

logOutletPoleSensorDataAvailable 1.3.6.1.4.1.13742.6.6.4.4.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logOutletPoleSensorState 1.3.6.1.4.1.13742.6.6.4.4.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logOutletPoleSensorAvgValue 1.3.6.1.4.1.13742.6.6.4.4.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletPoleSensorMaxValue 1.3.6.1.4.1.13742.6.6.4.4.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletPoleSensorMinValue 1.3.6.1.4.1.13742.6.6.4.4.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOutletPoleSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.4.4.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOutletPoleSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.4.4.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOutletPoleSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.4.4.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorLogTable 1.3.6.1.4.1.13742.6.6.3.3
A list of overCurrentProtector sensor entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OverCurrentProtectorSensorLogEntryStruct

overCurrentProtectorSensorLogEntry 1.3.6.1.4.1.13742.6.6.3.3.1
An entry containing log objects for an overCurrentProtector sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OverCurrentProtectorSensorLogEntryStruct  

logOverCurrentProtectorSensorDataAvailable 1.3.6.1.4.1.13742.6.6.3.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logOverCurrentProtectorSensorState 1.3.6.1.4.1.13742.6.6.3.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logOverCurrentProtectorSensorAvgValue 1.3.6.1.4.1.13742.6.6.3.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOverCurrentProtectorSensorMaxValue 1.3.6.1.4.1.13742.6.6.3.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOverCurrentProtectorSensorMinValue 1.3.6.1.4.1.13742.6.6.3.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logOverCurrentProtectorSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.3.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOverCurrentProtectorSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.3.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logOverCurrentProtectorSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.3.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorLogTable 1.3.6.1.4.1.13742.6.6.5.3
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorLogEntryStruct

externalSensorLogEntry 1.3.6.1.4.1.13742.6.6.5.3.1
An entry containing log objects for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorLogEntryStruct  

logExternalSensorDataAvailable 1.3.6.1.4.1.13742.6.6.5.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logExternalSensorState 1.3.6.1.4.1.13742.6.6.5.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logExternalSensorAvgValue 1.3.6.1.4.1.13742.6.6.5.3.1.4
The sensor reading average value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logExternalSensorMaxValue 1.3.6.1.4.1.13742.6.6.5.3.1.5
The sensor reading maximum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logExternalSensorMinValue 1.3.6.1.4.1.13742.6.6.5.3.1.6
The sensor reading minimum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

wireSensorLogTable 1.3.6.1.4.1.13742.6.6.6.3
A list of wire sensor entries. The number of entries is given by the value of wireCount for the PDU.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WireSensorLogEntryStruct

wireSensorLogEntry 1.3.6.1.4.1.13742.6.6.6.3.1
An entry containing log objects for a wire sensor.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  WireSensorLogEntryStruct  

logWireSensorDataAvailable 1.3.6.1.4.1.13742.6.6.6.3.1.2
Is data available for this sensor during this measurement period?
Status: deprecated Access: read-only
OBJECT-TYPE    
  TruthValue  

logWireSensorState 1.3.6.1.4.1.13742.6.6.6.3.1.3
The sensor state.
Status: deprecated Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logWireSensorAvgValue 1.3.6.1.4.1.13742.6.6.6.3.1.4
The sensor reading average value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

logWireSensorMaxValue 1.3.6.1.4.1.13742.6.6.6.3.1.5
The sensor reading maximum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

logWireSensorMinValue 1.3.6.1.4.1.13742.6.6.6.3.1.6
The sensor reading minimum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorLogTable 1.3.6.1.4.1.13742.6.6.7.3
A list of Transfer Switch sensor entries. The number of entries is given by the value of transferSwitchCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchSensorLogEntryStruct

transferSwitchSensorLogEntry 1.3.6.1.4.1.13742.6.6.7.3.1
An entry containing log objects for a transfer switch sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchSensorLogEntryStruct  

logTransferSwitchSensorDataAvailable 1.3.6.1.4.1.13742.6.6.7.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logTransferSwitchSensorState 1.3.6.1.4.1.13742.6.6.7.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logTransferSwitchSensorAvgValue 1.3.6.1.4.1.13742.6.6.7.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logTransferSwitchSensorMaxValue 1.3.6.1.4.1.13742.6.6.7.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logTransferSwitchSensorMinValue 1.3.6.1.4.1.13742.6.6.7.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logTransferSwitchSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.7.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logTransferSwitchSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.7.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logTransferSwitchSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.7.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitSensorLogTable 1.3.6.1.4.1.13742.6.6.8.3
A list of Circuit sensor log entries. The number of entries is given by the value of panelinletCount for the Floor PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitSensorLogEntryStruct

circuitSensorLogEntry 1.3.6.1.4.1.13742.6.6.8.3.1
An entry containing log objects for a circuit sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitSensorLogEntryStruct  

logCircuitSensorDataAvailable 1.3.6.1.4.1.13742.6.6.8.3.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logCircuitSensorState 1.3.6.1.4.1.13742.6.6.8.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logCircuitSensorAvgValue 1.3.6.1.4.1.13742.6.6.8.3.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitSensorMaxValue 1.3.6.1.4.1.13742.6.6.8.3.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitSensorMinValue 1.3.6.1.4.1.13742.6.6.8.3.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.8.3.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logCircuitSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.8.3.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logCircuitSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.8.3.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitPoleSensorLogTable 1.3.6.1.4.1.13742.6.6.8.5
A list of circuit pole sensor log entries. The number of entries is given by the value of panelCircuitPoleCount for the circut.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitPoleSensorLogEntryStruct

circuitPoleSensorLogEntry 1.3.6.1.4.1.13742.6.6.8.5.1
An entry containing log objects for a circuit pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitPoleSensorLogEntryStruct  

logCircuitPoleSensorDataAvailable 1.3.6.1.4.1.13742.6.6.8.5.1.2
Is data available for this sensor during this measurement period?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

logCircuitPoleSensorState 1.3.6.1.4.1.13742.6.6.8.5.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

logCircuitPoleSensorAvgValue 1.3.6.1.4.1.13742.6.6.8.5.1.4
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitPoleSensorMaxValue 1.3.6.1.4.1.13742.6.6.8.5.1.5
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitPoleSensorMinValue 1.3.6.1.4.1.13742.6.6.8.5.1.6
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

logCircuitPoleSensorSignedAvgValue 1.3.6.1.4.1.13742.6.6.8.5.1.7
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logCircuitPoleSensorSignedMaxValue 1.3.6.1.4.1.13742.6.6.8.5.1.8
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

logCircuitPoleSensorSignedMinValue 1.3.6.1.4.1.13742.6.6.8.5.1.9
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.1.3
A list of unit sensor entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UnitSensorMeasurementsEntryStruct

unitSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.1.3.1
An entry containing measurement objects for an unit sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  UnitSensorMeasurementsEntryStruct  

measurementsUnitSensorIsAvailable 1.3.6.1.4.1.13742.6.5.1.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsUnitSensorState 1.3.6.1.4.1.13742.6.5.1.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsUnitSensorValue 1.3.6.1.4.1.13742.6.5.1.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. power supply status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsUnitSensorTimeStamp 1.3.6.1.4.1.13742.6.5.1.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsUnitSensorSignedValue 1.3.6.1.4.1.13742.6.5.1.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. power supply status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.2.3
A list of inlet sensor entries. The number of entries is given by the value of inletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletSensorMeasurementsEntryStruct

inletSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.2.3.1
An entry containing measurement objects for an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletSensorMeasurementsEntryStruct  

measurementsInletSensorIsAvailable 1.3.6.1.4.1.13742.6.5.2.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsInletSensorState 1.3.6.1.4.1.13742.6.5.2.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsInletSensorValue 1.3.6.1.4.1.13742.6.5.2.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsInletSensorTimeStamp 1.3.6.1.4.1.13742.6.5.2.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsInletSensorSignedValue 1.3.6.1.4.1.13742.6.5.2.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inletPoleSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.2.4
A list of inletPole sensor entries. The number of entries is given by the value of inletPoleCount for the inlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletPoleSensorMeasurementsEntryStruct

inletPoleSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.2.4.1
An entry containing measurement objects for an inletPole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletPoleSensorMeasurementsEntryStruct  

measurementsInletPoleSensorIsAvailable 1.3.6.1.4.1.13742.6.5.2.4.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsInletPoleSensorState 1.3.6.1.4.1.13742.6.5.2.4.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsInletPoleSensorValue 1.3.6.1.4.1.13742.6.5.2.4.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsInletPoleSensorTimeStamp 1.3.6.1.4.1.13742.6.5.2.4.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsInletPoleSensorSignedValue 1.3.6.1.4.1.13742.6.5.2.4.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.4.3
A list of outlet sensor entries. The number of entries is given by the value of outletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletSensorMeasurementsEntryStruct

outletSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.4.3.1
An entry containing measurement objects for an outlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletSensorMeasurementsEntryStruct  

measurementsOutletSensorIsAvailable 1.3.6.1.4.1.13742.6.5.4.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsOutletSensorState 1.3.6.1.4.1.13742.6.5.4.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsOutletSensorValue 1.3.6.1.4.1.13742.6.5.4.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOutletSensorTimeStamp 1.3.6.1.4.1.13742.6.5.4.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOutletSensorSignedValue 1.3.6.1.4.1.13742.6.5.4.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletPoleSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.4.4
A list of outletPole sensor entries. The number of entries is given by the value of outletPoletCount for the outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletPoleSensorMeasurementsEntryStruct

outletPoleSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.4.4.1
An entry containing measurement objects for an outletPole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletPoleSensorMeasurementsEntryStruct  

measurementsOutletPoleSensorIsAvailable 1.3.6.1.4.1.13742.6.5.4.4.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsOutletPoleSensorState 1.3.6.1.4.1.13742.6.5.4.4.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsOutletPoleSensorValue 1.3.6.1.4.1.13742.6.5.4.4.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOutletPoleSensorTimeStamp 1.3.6.1.4.1.13742.6.5.4.4.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOutletPoleSensorSignedValue 1.3.6.1.4.1.13742.6.5.4.4.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

overCurrentProtectorSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.3.3
A list of overCurrentProtector sensor entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OverCurrentProtectorSensorMeasurementsEntryStruct

overCurrentProtectorSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.3.3.1
An entry containing measurement objects for an overCurrentProtector.
Status: current Access: not-accessible
OBJECT-TYPE    
  OverCurrentProtectorSensorMeasurementsEntryStruct  

measurementsOverCurrentProtectorSensorIsAvailable 1.3.6.1.4.1.13742.6.5.3.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsOverCurrentProtectorSensorState 1.3.6.1.4.1.13742.6.5.3.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsOverCurrentProtectorSensorValue 1.3.6.1.4.1.13742.6.5.3.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOverCurrentProtectorSensorTimeStamp 1.3.6.1.4.1.13742.6.5.3.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsOverCurrentProtectorSensorSignedValue 1.3.6.1.4.1.13742.6.5.3.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

externalSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.5.3
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExternalSensorMeasurementsEntryStruct

externalSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.5.3.1
An entry containing measurement objects for an external sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  ExternalSensorMeasurementsEntryStruct  

measurementsExternalSensorIsAvailable 1.3.6.1.4.1.13742.6.5.5.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsExternalSensorState 1.3.6.1.4.1.13742.6.5.5.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsExternalSensorValue 1.3.6.1.4.1.13742.6.5.5.3.1.4
The sensor reading as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading, e.g. contact closure or smoke detection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

measurementsExternalSensorTimeStamp 1.3.6.1.4.1.13742.6.5.5.3.1.5
The sensor reading timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

wireSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.6.3
A list of wire sensor entries. The number of entries is given by the value of wireCount for the PDU.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    WireSensorMeasurementsEntryStruct

wireSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.6.3.1
An entry containing measurement objects for a wire.
Status: deprecated Access: not-accessible
OBJECT-TYPE    
  WireSensorMeasurementsEntryStruct  

measurementsWireSensorIsAvailable 1.3.6.1.4.1.13742.6.5.6.3.1.2
Is the sensor available?
Status: deprecated Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsWireSensorState 1.3.6.1.4.1.13742.6.5.6.3.1.3
The sensor state.
Status: deprecated Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsWireSensorValue 1.3.6.1.4.1.13742.6.5.6.3.1.4
The sensor value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295 This parameter does not apply to sensors without numerical reading.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsWireSensorTimeStamp 1.3.6.1.4.1.13742.6.5.6.3.1.5
The timestamp.
Status: deprecated Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.7.3
A list of transfer switch sensor entries. The number of entries is given by the value of transferSwitchCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchSensorMeasurementsEntryStruct

transferSwitchSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.7.3.1
An entry containing measurement objects for a transfer switch.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchSensorMeasurementsEntryStruct  

measurementsTransferSwitchSensorIsAvailable 1.3.6.1.4.1.13742.6.5.7.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsTransferSwitchSensorState 1.3.6.1.4.1.13742.6.5.7.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsTransferSwitchSensorValue 1.3.6.1.4.1.13742.6.5.7.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsTransferSwitchSensorTimeStamp 1.3.6.1.4.1.13742.6.5.7.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsTransferSwitchSensorSignedValue 1.3.6.1.4.1.13742.6.5.7.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.8.3
A list of circuit sensor entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitSensorMeasurementsEntryStruct

circuitSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.8.3.1
An entry containing measurement objects for circuit sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitSensorMeasurementsEntryStruct  

measurementsCircuitSensorIsAvailable 1.3.6.1.4.1.13742.6.5.8.3.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsCircuitSensorState 1.3.6.1.4.1.13742.6.5.8.3.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsCircuitSensorValue 1.3.6.1.4.1.13742.6.5.8.3.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsCircuitSensorTimeStamp 1.3.6.1.4.1.13742.6.5.8.3.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsCircuitSensorSignedValue 1.3.6.1.4.1.13742.6.5.8.3.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

circuitPoleSensorMeasurementsTable 1.3.6.1.4.1.13742.6.5.8.4
A list of panel circuit pole sensor entries. The number of entries is given by the value of inletCount for the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitPoleSensorMeasurementsEntryStruct

circuitPoleSensorMeasurementsEntry 1.3.6.1.4.1.13742.6.5.8.4.1
An entry containing measurement objects for a circuit pole sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitPoleSensorMeasurementsEntryStruct  

measurementsCircuitPoleSensorIsAvailable 1.3.6.1.4.1.13742.6.5.8.4.1.2
Is the sensor available?
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

measurementsCircuitPoleSensorState 1.3.6.1.4.1.13742.6.5.8.4.1.3
The sensor state.
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

measurementsCircuitPoleSensorValue 1.3.6.1.4.1.13742.6.5.8.4.1.4
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsCircuitPoleSensorTimeStamp 1.3.6.1.4.1.13742.6.5.8.4.1.5
The timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

measurementsCircuitPoleSensorSignedValue 1.3.6.1.4.1.13742.6.5.8.4.1.6
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

outletSwitchControlTable 1.3.6.1.4.1.13742.6.4.1.2
A list of outlets for a PDU. The number of entries is given by the value of outletCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletSwitchControlEntryStruct

outletSwitchControlEntry 1.3.6.1.4.1.13742.6.4.1.2.1
An entry for implementing switching operations on an outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletSwitchControlEntryStruct  

switchingOperation 1.3.6.1.4.1.13742.6.4.1.2.1.2
The switching operation.
Status: current Access: read-write
OBJECT-TYPE    
  OutletSwitchingOperationsEnumeration  

outletSwitchingState 1.3.6.1.4.1.13742.6.4.1.2.1.3
The outlet state at present
Status: current Access: read-only
OBJECT-TYPE    
  SensorStateEnumeration  

outletSwitchingTimeStamp 1.3.6.1.4.1.13742.6.4.1.2.1.4
The timestamp indicating when the outlet was last switched
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

transferSwitchControlTable 1.3.6.1.4.1.13742.6.4.3.1
A list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TransferSwitchControlEntryStruct

transferSwitchControlEntry 1.3.6.1.4.1.13742.6.4.3.1.1
An entry for implementing switching operations on a transfer switch.
Status: current Access: not-accessible
OBJECT-TYPE    
  TransferSwitchControlEntryStruct  

transferSwitchActiveInlet 1.3.6.1.4.1.13742.6.4.3.1.1.1
The index of the currently active inlet.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..64  

transferSwitchTransferToInlet 1.3.6.1.4.1.13742.6.4.3.1.1.2
Select the active inlet. If the new inlet is available, it will become both active and preferred, otherwise an inconsistentValue error will be returned. By default the switching operation will fail if the phase difference between the inlets is too large. In this case the switch can be forced by writing transferSwitchAlarmOverride as True in the same request. This variable will always read as 0.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..64  

transferSwitchAlarmOverride 1.3.6.1.4.1.13742.6.4.3.1.1.3
Force transfer even if the phase difference between the inlets is too large. This may only be written together with transferSwitchTransferToInlet, otherwise an inconsistentValue error will be returned. Always reads as false.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

transferSwitchLastTransferReason 1.3.6.1.4.1.13742.6.4.3.1.1.4
The reason for the most recent transfer
Status: current Access: read-only
OBJECT-TYPE    
  TransferSwitchTransferReasonEnumeration  

actuatorControlTable 1.3.6.1.4.1.13742.6.4.4.2
A list of actuators for a PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ActuatorControlEntryStruct

actuatorControlEntry 1.3.6.1.4.1.13742.6.4.4.2.1
An entry for implementing user-initiated state changes for an actuator.
Status: current Access: not-accessible
OBJECT-TYPE    
  ActuatorControlEntryStruct  

actuatorState 1.3.6.1.4.1.13742.6.4.4.2.1.2
The actuator state. A Get operation retrieves the state of the actuator. A Set operation changes the stae of the sensor. The valid states for set operations are on and Off. Attempting to set the state to any other value will generate an error.
Status: current Access: read-write
OBJECT-TYPE    
  SensorStateEnumeration  

rcmSelfTestTable 1.3.6.1.4.1.13742.6.4.5.2
A list of RCMs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RcmSelfTestEntryStruct

rcmSelfTestEntry 1.3.6.1.4.1.13742.6.4.5.2.1
An entry for implementing self test of an RCM.
Status: current Access: not-accessible
OBJECT-TYPE    
  RcmSelfTestEntryStruct  

rcmState 1.3.6.1.4.1.13742.6.4.5.2.1.2
The rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The valid state for set operations is selfTest. When rcmState is set to selfTest, self test of the RCM starts. Attempting to set the state to any other value will generate an error. If the current state is selfTest, then an attempt to set the value to selfTest will be ignored.
Status: current Access: read-write
OBJECT-TYPE    
  SensorStateEnumeration  

inletSensorControlTable 1.3.6.1.4.1.13742.6.4.6.1
A list of control entries for the inlet sensors of a PDU. The set of valid indexes is defined by the value of inletCount and the inletDeviceCapabilities entry for the selected inlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InletSensorControlEntryStruct

inletSensorControlEntry 1.3.6.1.4.1.13742.6.4.6.1.1
An entry used for controlling an inlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  InletSensorControlEntryStruct  

inletSensorResetValue 1.3.6.1.4.1.13742.6.4.6.1.1.1
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

outletSensorControlTable 1.3.6.1.4.1.13742.6.4.7.1
A list of control entries for the outlet sensors of a PDU. The set of valid indexes is defined by the value of outletCount and the outletDeviceCapabilities entry for the selected outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutletSensorControlEntryStruct

outletSensorControlEntry 1.3.6.1.4.1.13742.6.4.7.1.1
An entry used for controlling an outlet sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  OutletSensorControlEntryStruct  

outletSensorResetValue 1.3.6.1.4.1.13742.6.4.7.1.1.1
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

unitSensorControlTable 1.3.6.1.4.1.13742.6.4.8.1
A list of control entries for the global sensors of a PDU. The set of valid indexes is defined by the value of pduCount and the pduDeviceCapabilities entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UnitSensorControlEntryStruct

unitSensorControlEntry 1.3.6.1.4.1.13742.6.4.8.1.1
An entry used for controlling an global sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  UnitSensorControlEntryStruct  

unitSensorResetValue 1.3.6.1.4.1.13742.6.4.8.1.1.1
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. This object applies only to multi-inlet PDUs.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

circuitSensorControlTable 1.3.6.1.4.1.13742.6.4.9.1
A list of control entries for the circuit sensors of a BCM2. The maximum number of entries is given by the value of panelCircuitPositionCount.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CircuitSensorControlEntryStruct

circuitSensorControlEntry 1.3.6.1.4.1.13742.6.4.9.1.1
An entry used for controlling an circuit sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  CircuitSensorControlEntryStruct  

circuitSensorResetValue 1.3.6.1.4.1.13742.6.4.9.1.1.1
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

reliabilityDataTableSequenceNumber 1.3.6.1.4.1.13742.6.10.1.1
The sequence number for updates to the reliability data table
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..2147483647  

reliabilityDataTable 1.3.6.1.4.1.13742.6.10.1.2
A list of PDU reliability data entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ReliabilityDataEntryStruct

reliabilityDataEntry 1.3.6.1.4.1.13742.6.10.1.2.1
An entry containing reliability data for a particular PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  ReliabilityDataEntryStruct  

reliabilityIndex 1.3.6.1.4.1.13742.6.10.1.2.1.1
Index of the entry in the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4096  

reliabilityId 1.3.6.1.4.1.13742.6.10.1.2.1.2
Unique ID of the entry. POH Power on hours. CB.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

reliabilityDataValue 1.3.6.1.4.1.13742.6.10.1.2.1.3
The normalized value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataMaxPossible 1.3.6.1.4.1.13742.6.10.1.2.1.4
The maximum possible normalized value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataWorstValue 1.3.6.1.4.1.13742.6.10.1.2.1.5
The worst normalized value seen so far
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataThreshold 1.3.6.1.4.1.13742.6.10.1.2.1.6
The normalized Threshold value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataRawUpperBytes 1.3.6.1.4.1.13742.6.10.1.2.1.7
The Upper 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataRawLowerBytes 1.3.6.1.4.1.13742.6.10.1.2.1.8
The lower 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityDataFlags 1.3.6.1.4.1.13742.6.10.1.2.1.9
Flags
Status: current Access: read-only
OBJECT-TYPE    
  BITS invalidFlag(0), oldValue(1), criticalEntry(2)  

reliabilityErrorLogTable 1.3.6.1.4.1.13742.6.10.2.2
A list of PDU reliability ErrorLog entries.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ReliabilityErrorLogEntryStruct

reliabilityErrorLogEntry 1.3.6.1.4.1.13742.6.10.2.2.1
An entry containing reliability ErrorLog data for a particular PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  ReliabilityErrorLogEntryStruct  

reliabilityErrorLogIndex 1.3.6.1.4.1.13742.6.10.2.2.1.1
Index of the entry in the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..2147483647  

reliabilityErrorLogId 1.3.6.1.4.1.13742.6.10.2.2.1.2
Unique ID of the entry. POH Power on hours. CB.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

reliabilityErrorLogValue 1.3.6.1.4.1.13742.6.10.2.2.1.3
The normalized value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityErrorLogThreshold 1.3.6.1.4.1.13742.6.10.2.2.1.6
The normalized Threshold value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityErrorLogRawUpperBytes 1.3.6.1.4.1.13742.6.10.2.2.1.7
The Upper 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityErrorLogRawLowerBytes 1.3.6.1.4.1.13742.6.10.2.2.1.8
The lower 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityErrorLogPOH 1.3.6.1.4.1.13742.6.10.2.2.1.9
The time of occurrence of the event measured from the last time the PDU was powered on
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

reliabilityErrorLogTime 1.3.6.1.4.1.13742.6.10.2.2.1.10
The UTC time of occurrence of the event
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

systemStarted 1.3.6.1.4.1.13742.6.0.1
The system has started.
Status: current Access: read-only
NOTIFICATION-TYPE    

systemReset 1.3.6.1.4.1.13742.6.0.2
The system was reset. The conditions under which this trap is sent include, but are not limited to, the following. using the GUI - Maintenance->Reset Unit using the CLI - reset pdu unit
Status: current Access: read-only
NOTIFICATION-TYPE    

userLogin 1.3.6.1.4.1.13742.6.0.3
A user logged in.
Status: current Access: read-only
NOTIFICATION-TYPE    

userLogout 1.3.6.1.4.1.13742.6.0.4
A user logged out.
Status: current Access: read-only
NOTIFICATION-TYPE    

userAuthenticationFailure 1.3.6.1.4.1.13742.6.0.5
A user authentication attempt failed.
Status: current Access: read-only
NOTIFICATION-TYPE    

userSessionTimeout 1.3.6.1.4.1.13742.6.0.8
A user session timed out.
Status: current Access: read-only
NOTIFICATION-TYPE    

userAdded 1.3.6.1.4.1.13742.6.0.11
A user was added to the system.
Status: current Access: read-only
NOTIFICATION-TYPE    

userModified 1.3.6.1.4.1.13742.6.0.12
A user was modified.
Status: current Access: read-only
NOTIFICATION-TYPE    

userDeleted 1.3.6.1.4.1.13742.6.0.13
A user was deleted from the system.
Status: current Access: read-only
NOTIFICATION-TYPE    

roleAdded 1.3.6.1.4.1.13742.6.0.14
A role was added to the system.
Status: current Access: read-only
NOTIFICATION-TYPE    

roleModified 1.3.6.1.4.1.13742.6.0.15
A role was modified.
Status: current Access: read-only
NOTIFICATION-TYPE    

roleDeleted 1.3.6.1.4.1.13742.6.0.16
A role was deleted from the system.
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceUpdateStarted 1.3.6.1.4.1.13742.6.0.20
The device update has started.
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceUpdateCompleted 1.3.6.1.4.1.13742.6.0.21
The device update has completed.
Status: current Access: read-only
NOTIFICATION-TYPE    

userBlocked 1.3.6.1.4.1.13742.6.0.22
A blocked user tried to log in.
Status: current Access: read-only
NOTIFICATION-TYPE    

powerControl 1.3.6.1.4.1.13742.6.0.23
An outlet switching operation has been performed. Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. This may be different from the final state of the outlet. For instance, if the outlet is cycled and the outlet cycle delay is 20 seconds, this variable will indicate OFF although the final state of the outlet will be ON. The final state of the outlet will be indicated in the outletSensorStateChange trap for the outlet onOff sensor.
Status: current Access: read-only
NOTIFICATION-TYPE    

userPasswordChanged 1.3.6.1.4.1.13742.6.0.24
User password was changed.
Status: current Access: read-only
NOTIFICATION-TYPE    

passwordSettingsChanged 1.3.6.1.4.1.13742.6.0.28
Strong password settings changed.
Status: current Access: read-only
NOTIFICATION-TYPE    

firmwareValidationFailed 1.3.6.1.4.1.13742.6.0.38
Firmware validation failed.
Status: current Access: read-only
NOTIFICATION-TYPE    

logFileCleared 1.3.6.1.4.1.13742.6.0.41
The log file has been cleared.
Status: current Access: read-only
NOTIFICATION-TYPE    

bulkConfigurationSaved 1.3.6.1.4.1.13742.6.0.53
Bulk Configuration saved.
Status: current Access: read-only
NOTIFICATION-TYPE    

bulkConfigurationCopied 1.3.6.1.4.1.13742.6.0.54
Bulk Configuration copied to the device.
Status: current Access: read-only
NOTIFICATION-TYPE    

pduSensorStateChange 1.3.6.1.4.1.13742.6.0.60
PDU Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: deprecated Access: read-only
NOTIFICATION-TYPE    

inletSensorStateChange 1.3.6.1.4.1.13742.6.0.61
Inlet Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsInletSensorValue is undefined for sensors which can have negative readings, measurementsInletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state i.e. if typeOfSensor = rcmState and measurementsInletSensorState = fail, then measurementsInletSensorValue = the residual current just before the sensor transitioned to the fail state
Status: current Access: read-only
NOTIFICATION-TYPE    

inletPoleSensorStateChange 1.3.6.1.4.1.13742.6.0.62
Inlet Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsInletPoleSensorValue is undefined for sensors which can have negative readings, measurementsInletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

outletSensorStateChange 1.3.6.1.4.1.13742.6.0.63
Outlet Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can have negative readings, measurementsOutletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

outletPoleSensorStateChange 1.3.6.1.4.1.13742.6.0.64
Outlet Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors which can have negative readings, measurementsOutletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

overCurrentProtectorSensorStateChange 1.3.6.1.4.1.13742.6.0.65
Overcurrent Protector Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

externalSensorStateChange 1.3.6.1.4.1.13742.6.0.66
External Sensor State Change.
Status: current Access: read-only
NOTIFICATION-TYPE    

smtpMessageTransmissionFailure 1.3.6.1.4.1.13742.6.0.67
SMTP message transmission failure
Status: current Access: read-only
NOTIFICATION-TYPE    

ldapError 1.3.6.1.4.1.13742.6.0.68
LDAP Error occurred; errorDescription describes the error
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceUpdateFailed 1.3.6.1.4.1.13742.6.0.70
The device update has failed.
Status: current Access: read-only
NOTIFICATION-TYPE    

loadSheddingModeEntered 1.3.6.1.4.1.13742.6.0.71
The PX has enetered Load Shedding Mode
Status: current Access: read-only
NOTIFICATION-TYPE    

loadSheddingModeExited 1.3.6.1.4.1.13742.6.0.72
The PX has exited Load Shedding Mode
Status: current Access: read-only
NOTIFICATION-TYPE    

pingServerEnabled 1.3.6.1.4.1.13742.6.0.73
The ping feature has been enabled
Status: current Access: read-only
NOTIFICATION-TYPE    

pingServerDisabled 1.3.6.1.4.1.13742.6.0.74
The ping feature has been disabled
Status: current Access: read-only
NOTIFICATION-TYPE    

serverNotReachable 1.3.6.1.4.1.13742.6.0.75
The server is not reachable
Status: current Access: read-only
NOTIFICATION-TYPE    

serverReachable 1.3.6.1.4.1.13742.6.0.76
The server is reachable
Status: current Access: read-only
NOTIFICATION-TYPE    

rfCodeTagConnected 1.3.6.1.4.1.13742.6.0.77
The RF Code Tag is Connected
Status: current Access: read-only
NOTIFICATION-TYPE    

rfCodeTagDisconnected 1.3.6.1.4.1.13742.6.0.78
The RF Code Tag is Disconnected
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceIdentificationChanged 1.3.6.1.4.1.13742.6.0.79
Device identification has changed
Status: current Access: read-only
NOTIFICATION-TYPE    

usbSlaveConnected 1.3.6.1.4.1.13742.6.0.80
USB Connectivity to slave has been established
Status: current Access: read-only
NOTIFICATION-TYPE    

usbSlaveDisconnected 1.3.6.1.4.1.13742.6.0.81
USB Connectivity to slave has been lost
Status: current Access: read-only
NOTIFICATION-TYPE    

lhxSupportChanged 1.3.6.1.4.1.13742.6.0.82
The Schroff LHX Support has been either enabled or disabled.
Status: current Access: read-only
NOTIFICATION-TYPE    

userAcceptedRestrictedServiceAgreement 1.3.6.1.4.1.13742.6.0.83
The user accepted the Restricted Service Agreement.
Status: current Access: read-only
NOTIFICATION-TYPE    

userDeclinedRestrictedServiceAgreement 1.3.6.1.4.1.13742.6.0.84
The user declined the Restricted Service Agreement.
Status: current Access: read-only
NOTIFICATION-TYPE    

wireSensorStateChange 1.3.6.1.4.1.13742.6.0.85
Wire Sensor State Change.
Status: deprecated Access: read-only
NOTIFICATION-TYPE    

transferSwitchSensorStateChange 1.3.6.1.4.1.13742.6.0.86
Transfer Switch Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsTransferSwitchSensorValue is undefined for sensors which can have negative readings, measurementsTransferSwitchSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceSettingsSaved 1.3.6.1.4.1.13742.6.0.88
Device Settings have been saved.
Status: current Access: read-only
NOTIFICATION-TYPE    

deviceSettingsRestored 1.3.6.1.4.1.13742.6.0.89
Device Settings have been restored.
Status: current Access: read-only
NOTIFICATION-TYPE    

webcamInserted 1.3.6.1.4.1.13742.6.0.90
A webcam has been inserted
Status: current Access: read-only
NOTIFICATION-TYPE    

webcamRemoved 1.3.6.1.4.1.13742.6.0.91
A webcam has been removed
Status: current Access: read-only
NOTIFICATION-TYPE    

inletEnabled 1.3.6.1.4.1.13742.6.0.92
PDU operation has been enabled for an inlet
Status: current Access: read-only
NOTIFICATION-TYPE    

inletDisabled 1.3.6.1.4.1.13742.6.0.93
PDU operation has been disabled for an inlet
Status: current Access: read-only
NOTIFICATION-TYPE    

serverConnectivityUnrecoverable 1.3.6.1.4.1.13742.6.0.94
The connection to the server could not be recovered
Status: current Access: read-only
NOTIFICATION-TYPE    

radiusError 1.3.6.1.4.1.13742.6.0.95
LDAP Error occurred; errorDescription describes the error
Status: current Access: read-only
NOTIFICATION-TYPE    

serverReachabilityError 1.3.6.1.4.1.13742.6.0.96
Server Reachability Error occurred; errorDescription describes the error. This trap is sent when the Error state is entered. Reasons for transitioning to the Error state include the following: Unable to resolve the server hostname.
Status: current Access: read-only
NOTIFICATION-TYPE    

inletSensorReset 1.3.6.1.4.1.13742.6.0.97
An inlet sensor was reset.
Status: current Access: read-only
NOTIFICATION-TYPE    

outletSensorReset 1.3.6.1.4.1.13742.6.0.98
An outlet sensor was reset.
Status: current Access: read-only
NOTIFICATION-TYPE    

unknownPeripheralDeviceAttached 1.3.6.1.4.1.13742.6.0.99
An unknown peripheral device was attached.
Status: current Access: read-only
NOTIFICATION-TYPE    

peripheralDeviceFirmwareUpdate 1.3.6.1.4.1.13742.6.0.100
The firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion.
Status: current Access: read-only
NOTIFICATION-TYPE    

unitSensorReset 1.3.6.1.4.1.13742.6.0.101
A global sensor was reset.
Status: current Access: read-only
NOTIFICATION-TYPE    

unitSensorStateChange 1.3.6.1.4.1.13742.6.0.102
Unit Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitSensorStateChange 1.3.6.1.4.1.13742.6.0.103
circuit Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can have negative readings, measurementsCircuitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitPoleSensorStateChange 1.3.6.1.4.1.13742.6.0.104
Circuit Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors which can have negative readings, measurementsCircuitPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitAdded 1.3.6.1.4.1.13742.6.0.105
A Circuit has been added
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitDeleted 1.3.6.1.4.1.13742.6.0.106
A Circuit has been deleted
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitModified 1.3.6.1.4.1.13742.6.0.107
A Circuit has been modified
Status: current Access: read-only
NOTIFICATION-TYPE    

circuitSensorReset 1.3.6.1.4.1.13742.6.0.108
An ciruit sensor was reset.
Status: current Access: read-only
NOTIFICATION-TYPE    

powerMeterAdded 1.3.6.1.4.1.13742.6.0.109
A Power Meter has been added
Status: current Access: read-only
NOTIFICATION-TYPE    

powerMeterDeleted 1.3.6.1.4.1.13742.6.0.110
A Power Meter has been deleted
Status: current Access: read-only
NOTIFICATION-TYPE    

powerMeterModified 1.3.6.1.4.1.13742.6.0.111
A Power Meter has been modified
Status: current Access: read-only
NOTIFICATION-TYPE    

smsMessageTransmissionFailure 1.3.6.1.4.1.13742.6.0.112
Sending an SMS message failed.
Status: current Access: read-only
NOTIFICATION-TYPE