LIEBERT-MICRO-UPS-MIB

File: LIEBERT-MICRO-UPS-MIB.mib (11799 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

enterprises TimeTicks Gauge
OBJECT-TYPE sysUpTime DisplayString
TRAP-TYPE

Defined Types

LcUpsAlarmEntry  
SEQUENCE    
  lcUpsAlarmId INTEGER
  lcUpsAlarmDescr OBJECT IDENTIFIER
  lcUpsAlarmTime TimeTicks

Defined Values

emerson 1.3.6.1.4.1.476
OBJECT IDENTIFIER    

liebertCorp 1.3.6.1.4.1.476.1
OBJECT IDENTIFIER    

liebertUps 1.3.6.1.4.1.476.1.1
OBJECT IDENTIFIER    

luExtensions 1.3.6.1.4.1.476.1.1.1
OBJECT IDENTIFIER    

luExperimental 1.3.6.1.4.1.476.1.1.2
OBJECT IDENTIFIER    

luPrivate 1.3.6.1.4.1.476.1.1.3
OBJECT IDENTIFIER    

luCore 1.3.6.1.4.1.476.1.1.1.1
OBJECT IDENTIFIER    

lcUpsIdent 1.3.6.1.4.1.476.1.1.1.1.1
OBJECT IDENTIFIER    

lcUpsIdentManufacturer 1.3.6.1.4.1.476.1.1.1.1.1.1
The UPS manufacturer.
Status: optional Access: read-only
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentModel 1.3.6.1.4.1.476.1.1.1.1.1.2
The UPS Model designation.
Status: optional Access: read-write
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentSoftwareVersion 1.3.6.1.4.1.476.1.1.1.1.1.3
The UPS SNMP Agent software version.
Status: optional Access: read-only
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentSpecific 1.3.6.1.4.1.476.1.1.1.1.1.4
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
Status: optional Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lcUpsAlarm 1.3.6.1.4.1.476.1.1.1.1.6
OBJECT IDENTIFIER    

lcUpsAlarms 1.3.6.1.4.1.476.1.1.1.1.6.1
The current number of alarm conditions.
Status: optional Access: read-only
OBJECT-TYPE    
  Gauge  

lcUpsAlarmTable 1.3.6.1.4.1.476.1.1.1.1.6.2
Tok_String
Status: optional Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LcUpsAlarmEntry

lcUpsAlarmEntry 1.3.6.1.4.1.476.1.1.1.1.6.2.1
Tok_String
Status: optional Access: not-accessible
OBJECT-TYPE    
  LcUpsAlarmEntry  

lcUpsAlarmId 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
Status: optional Access: read-only
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsAlarmDescr 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
Status: optional Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lcUpsAlarmTime 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3
The value of sysUpTime when the alarm condition occured.
Status: optional Access: read-only
OBJECT-TYPE    
  TimeTicks  

lcUpsAlarmConditions 1.3.6.1.4.1.476.1.1.1.1.6.3
OBJECT IDENTIFIER    

lcUpsAlarmLowBatteryWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.1
OBJECT IDENTIFIER    

lcUpsAlarmOnBattery 1.3.6.1.4.1.476.1.1.1.1.6.3.10
OBJECT IDENTIFIER    

lcUpsAlarmStopNoticeIssued 1.3.6.1.4.1.476.1.1.1.1.6.3.11
OBJECT IDENTIFIER    

lcUpsControl 1.3.6.1.4.1.476.1.1.1.1.8
OBJECT IDENTIFIER    

lcUpsControlUnixShutdownDelay 1.3.6.1.4.1.476.1.1.1.1.8.5
Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlUnixShutdownTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.6
When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlCancelCommands 1.3.6.1.4.1.476.1.1.1.1.8.7
Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER unknown(1), cancel(2)  

lcUpsControlRebootAgentDelay 1.3.6.1.4.1.476.1.1.1.1.8.8
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel.
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsNominal 1.3.6.1.4.1.476.1.1.1.1.9
OBJECT IDENTIFIER    

lcUpsNominalOutputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.1
The nominal output voltage. (Unit of measure: volt)
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalInputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.2
The nominal input voltage. (Unit of measure: volt)
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputVA 1.3.6.1.4.1.476.1.1.1.1.9.3
The nominal Volt-Amp rating.
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputWatts 1.3.6.1.4.1.476.1.1.1.1.9.4
The nominal power rating. (Unit of measure: watt)
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputFreq 1.3.6.1.4.1.476.1.1.1.1.9.5
The nominal output frequency. (Unit of measure: Hertz)
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalInputFreq 1.3.6.1.4.1.476.1.1.1.1.9.6
The nominal input frequency. (Unit of measure: Hertz)
Status: optional Access: read-write
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsTraps 1.3.6.1.4.1.476.1.1.1.1.11
OBJECT IDENTIFIER    

lcUpsOnBatteryTrap 3
An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power.
TRAP-TYPE    

lcUpsLowBatteryWarningTrap 4
An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state.
TRAP-TYPE    

lcUpsAlarmTrap 11
An Alarm condition has occurred and is being reported in the lcUpsAlarmTable.
TRAP-TYPE    

lcUpsUnixShutdownTrap 16
An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown.
TRAP-TYPE    

lcUpsUnixShutdownWarningTrap 17
An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay.
TRAP-TYPE    

luExternal 1.3.6.1.4.1.476.1.1.1.6
OBJECT IDENTIFIER