LIEBERT-GP-ENVIRONMENTAL-MIB

File: LIEBERT-GP-ENVIRONMENTAL-MIB.mib (113576 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC LIEBERT-GP-REGISTRATION-MIB

Imported symbols

MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE
Unsigned32 Integer32 DisplayString
lgpEnvironmental liebertEnvironmentalModuleReg

Defined Types

LgpEnvComponentStateEntry  
SEQUENCE    
  lgpEnvComponentStateIndex Unsigned32
  lgpEnvComponentStateDescr OBJECT IDENTIFIER
  lgpEnvComponentState INTEGER

LgpEnvValveEntry  
SEQUENCE    
  lgpEnvValveIndex Unsigned32
  lgpEnvValveDescr OBJECT IDENTIFIER
  lgpEnvValveState INTEGER
  lgpEnvValvePositionTenths Unsigned32

LgpEnvOperationalTimeEntry  
SEQUENCE    
  lgpEnvOperationTimeIndex Unsigned32
  lgpEnvOperationTimePoint OBJECT IDENTIFIER
  lgpEnvOperationTimeSubID Integer32
  lgpEnvOperationTimeUnit OBJECT IDENTIFIER
  lgpEnvOperationTimeValue Integer32
  lgpEnvOperationTimeHighWarning Integer32

LgpEnvSleepIntervalTimeEntry  
SEQUENCE    
  lgpEnvSleepTimeIndex Unsigned32
  lgpEnvSleepTimeSubID Integer32
  lgpEnvSleepTimeStartHour Integer32
  lgpEnvSleepTimeStartMinute Integer32
  lgpEnvSleepTimeStopHour Integer32
  lgpEnvSleepTimeStopMinute Integer32

LgpEnvSleepDayEntry  
SEQUENCE    
  lgpEnvSleepDayIndex Unsigned32
  lgpEnvSleepDay INTEGER
  lgpEnvSleepAllDayEnabled INTEGER

LgpEnvTemperatureEntryDegF  
SEQUENCE    
  lgpEnvTemperatureIdDegF Unsigned32
  lgpEnvTemperatureDescrDegF OBJECT IDENTIFIER
  lgpEnvTemperatureMeasurementDegF Integer32
  lgpEnvTemperatureHighThresholdDegF Integer32
  lgpEnvTemperatureLowThresholdDegF Integer32
  lgpEnvTemperatureSetPointDegF Integer32
  lgpEnvTemperatureDailyHighDegF Integer32
  lgpEnvTemperatureDailyLowDegF Integer32
  lgpEnvTempDailyHighTimeHourDegF Integer32
  lgpEnvTempDailyHighTimeMinuteDegF Integer32
  lgpEnvTempDailyHighTimeSecondDegF Integer32
  lgpEnvTempDailyLowTimeHourDegF Integer32
  lgpEnvTempDailyLowTimeMinuteDegF Integer32
  lgpEnvTempDailyLowTimeSecondDegF Integer32
  lgpEnvTemperatureMeasurementTenthsDegF Integer32
  lgpEnvTemperatureHighThresholdTenthsDegF Integer32
  lgpEnvTemperatureLowThresholdTenthsDegF Integer32
  lgpEnvTemperatureSetPointTenthsDegF Integer32
  lgpEnvTemperatureDeadBandTenthsDegF Integer32
  lgpEnvTempHeatingPropBandTenthsDegF Integer32
  lgpEnvTempCoolingPropBandTenthsDegF Integer32

LgpEnvTemperatureEntryDegC  
SEQUENCE    
  lgpEnvTemperatureIdDegC Unsigned32
  lgpEnvTemperatureDescrDegC OBJECT IDENTIFIER
  lgpEnvTemperatureMeasurementDegC Integer32
  lgpEnvTemperatureHighThresholdDegC Integer32
  lgpEnvTemperatureLowThresholdDegC Integer32
  lgpEnvTemperatureSetPointDegC Integer32
  lgpEnvTemperatureDailyHighDegC Integer32
  lgpEnvTemperatureDailyLowDegC Integer32
  lgpEnvTempDailyHighTimeHourDegC Integer32
  lgpEnvTempDailyHighTimeMinuteDegC Integer32
  lgpEnvTempDailyHighTimeSecondDegC Integer32
  lgpEnvTempDailyLowTimeHourDegC Integer32
  lgpEnvTempDailyLowTimeMinuteDegC Integer32
  lgpEnvTempDailyLowTimeSecondDegC Integer32
  lgpEnvTemperatureMeasurementTenthsDegC Integer32
  lgpEnvTemperatureHighThresholdTenthsDegC Integer32
  lgpEnvTemperatureLowThresholdTenthsDegC Integer32
  lgpEnvTemperatureSetPointTenthsDegC Integer32
  lgpEnvTemperatureDeadBandTenthsDegC Integer32
  lgpEnvTempHeatingPropBandTenthsDegC Integer32
  lgpEnvTempCoolingPropBandTenthsDegC Integer32

LgpEnvHumidityEntryRel  
SEQUENCE    
  lgpEnvHumidityIdRel Unsigned32
  lgpEnvHumidityDescrRel OBJECT IDENTIFIER
  lgpEnvHumidityMeasurementRel Integer32
  lgpEnvHumidityHighThresholdRel Integer32
  lgpEnvHumidityLowThresholdRel Integer32
  lgpEnvHumiditySetPoint Integer32
  lgpEnvHumidityDailyHigh Integer32
  lgpEnvHumidityDailyLow Integer32
  lgpEnvHumidityDailyHighTimeHour Integer32
  lgpEnvHumidityDailyHighTimeMinute Integer32
  lgpEnvHumidityDailyHighTimeSecond Integer32
  lgpEnvHumidityDailyLowTimeHour Integer32
  lgpEnvHumidityDailyLowTimeMinute Integer32
  lgpEnvHumidityDailyLowTimeSecond Integer32
  lgpEnvHumidityDeadBand Integer32
  lgpEnvHumidifyPropBand Integer32
  lgpEnvDehumidifyPropBand Integer32
  lgpEnvHumidityMeasurementRelTenths Integer32
  lgpEnvHumidityHighThresholdRelTenths Integer32
  lgpEnvHumidityLowThresholdRelTenths Integer32

LgpEnvRemoteSensorEntry  
SEQUENCE    
  lgpEnvRemoteSensorIndex Unsigned32
  lgpEnvRemoteSensorId Unsigned32
  lgpEnvRemoteSensorMode Integer32
  lgpEnvRemoteSensorUsrLabel DisplayString
  lgpEnvRemoteSensorTempMeasurementDegF Integer32
  lgpEnvRemoteSensorTempMeasurementDegC Integer32

Defined Values

liebertGlobalProductsEnvironmentalModule 1.3.6.1.4.1.476.1.42.1.5.1
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY    

lgpEnvTemperature 1.3.6.1.4.1.476.1.42.3.4.1
This sub-tree is used to register Liebert temperature object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHumidity 1.3.6.1.4.1.476.1.42.3.4.2
This sub-tree is used to register Liebert humidity object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvState 1.3.6.1.4.1.476.1.42.3.4.3
This sub-tree is used to register Liebert environmental state object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvConfig 1.3.6.1.4.1.476.1.42.3.4.4
This sub-tree is used to register Liebert environmental configuration object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvControl 1.3.6.1.4.1.476.1.42.3.4.5
This sub-tree is used to register Liebert environmental control object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvStatistics 1.3.6.1.4.1.476.1.42.3.4.6
This sub-tree is used to register Liebert environmental statistic object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvPoints 1.3.6.1.4.1.476.1.42.3.4.7
This sub-tree is used to register Liebert environmental point object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvUnits 1.3.6.1.4.1.476.1.42.3.4.8
This sub-tree is used to register Liebert environmental unit object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvRemoteSensors 1.3.6.1.4.1.476.1.42.3.4.9
This sub-tree is used to register Liebert environmental remote sensor object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvTemperatureWellKnown 1.3.6.1.4.1.476.1.42.3.4.1.1
Liebert well known temperature objects are identified by OIDs that reside in this sub-tree.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvTemperatureFahrenheit 1.3.6.1.4.1.476.1.42.3.4.1.2
This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvTemperatureCelsius 1.3.6.1.4.1.476.1.42.3.4.1.3
This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvTemperatureControlMode 1.3.6.1.4.1.476.1.42.3.4.1.4
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvHumidityWellKnown 1.3.6.1.4.1.476.1.42.3.4.2.1
Liebert well known humidity objects are defined by OIDs that reside in this sub-tree.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHumidityRelative 1.3.6.1.4.1.476.1.42.3.4.2.2
This sub-tree contains OIDs that are used to control and monitor relative humidity.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvStateSystem 1.3.6.1.4.1.476.1.42.3.4.3.1
The present state of the system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), standby(3)  

lgpEnvStateCooling 1.3.6.1.4.1.476.1.42.3.4.3.2
The present state of the cooling subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHeating 1.3.6.1.4.1.476.1.42.3.4.3.3
The present state of the heating subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHumidifying 1.3.6.1.4.1.476.1.42.3.4.3.4
The present state of the humidifier subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateDehumidifying 1.3.6.1.4.1.476.1.42.3.4.3.5
The present state of the dehumidifier subsystem
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateEconoCycle 1.3.6.1.4.1.476.1.42.3.4.3.6
The present state of the Econ-o-cycle subsystem.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateFan 1.3.6.1.4.1.476.1.42.3.4.3.7
The present state of the system fan.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateGeneralAlarmOutput 1.3.6.1.4.1.476.1.42.3.4.3.8
The present state of the general alarm output. This indicates if an alarm is active in the system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateCoolingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.9
The percentage of the cooling capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateHeatingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.10
The percentage of the heating capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateAudibleAlarm 1.3.6.1.4.1.476.1.42.3.4.3.11
The present state of the audible alarm output.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateCoolingUnits 1.3.6.1.4.1.476.1.42.3.4.3.12
This sub-tree contains OIDs that are used to indicate the status of cooling units.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvStateCoolingUnit1 1.3.6.1.4.1.476.1.42.3.4.3.12.2
The present state of cooling unit 1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateCoolingUnit2 1.3.6.1.4.1.476.1.42.3.4.3.12.3
The present state of cooling unit 2.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateCoolingUnit3 1.3.6.1.4.1.476.1.42.3.4.3.12.4
The present state of cooling unit 3.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateCoolingUnit4 1.3.6.1.4.1.476.1.42.3.4.3.12.5
The present state of cooling unit 4.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHeatingUnits 1.3.6.1.4.1.476.1.42.3.4.3.13
This sub-tree contains OIDs that are used to indicate the status of heating units.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvStateHeatingUnit1 1.3.6.1.4.1.476.1.42.3.4.3.13.2
The present state of heating unit 1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHeatingUnit2 1.3.6.1.4.1.476.1.42.3.4.3.13.3
The present state of heating unit 2.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHeatingUnit3 1.3.6.1.4.1.476.1.42.3.4.3.13.4
The present state of heating unit 3.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHeatingUnit4 1.3.6.1.4.1.476.1.42.3.4.3.13.5
The present state of heating unit 4.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateOperatingReason 1.3.6.1.4.1.476.1.42.3.4.3.14
The reason for the current operating state of the system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none(1), localUser(2), alarm(3), schedule(4), remoteUser(5), externalDevice(6), localDisplay(7)  

lgpEnvStateOperatingMode 1.3.6.1.4.1.476.1.42.3.4.3.15
The present operating mode of the system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

lgpEnvStateFanCapacity 1.3.6.1.4.1.476.1.42.3.4.3.16
The percentage of the fan capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateFreeCoolingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.17
The percentage of the free cooling capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateDehumidifyingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.18
The percentage of the dehumidifying capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateHumidifyingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.19
The percentage of the humidifying capacity presently in use.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStateFreeCooling 1.3.6.1.4.1.476.1.42.3.4.3.20
The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2), start(3), unavailable(4)  

lgpEnvStateElectricHeater 1.3.6.1.4.1.476.1.42.3.4.3.21
The present state of the electric heaters.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateHotWater 1.3.6.1.4.1.476.1.42.3.4.3.22
The present state of hot water system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpEnvStateOperatingEfficiency 1.3.6.1.4.1.476.1.42.3.4.3.23
The ratio of cooling energy provided to the amount of total energy being used.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvComponentStateTable 1.3.6.1.4.1.476.1.42.3.4.3.50
This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvComponentStateEntry

lgpEnvComponentStateEntry 1.3.6.1.4.1.476.1.42.3.4.3.50.1
This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvComponentStateEntry  

lgpEnvComponentStateIndex 1.3.6.1.4.1.476.1.42.3.4.3.50.1.1
This is the index indicating the nth element of the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvComponentStateDescr 1.3.6.1.4.1.476.1.42.3.4.3.50.1.2
A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvComponentState 1.3.6.1.4.1.476.1.42.3.4.3.50.1.3
not-specified The state of the component is unknown. on The component is on. off The component is off.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER not-specified(0), on(1), off(2)  

lgpEnvValveTable 1.3.6.1.4.1.476.1.42.3.4.3.70
This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvValveEntry

lgpEnvValveEntry 1.3.6.1.4.1.476.1.42.3.4.3.70.1
This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvValveEntry  

lgpEnvValveIndex 1.3.6.1.4.1.476.1.42.3.4.3.70.1.1
This is the index indicating the nth element of the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvValveDescr 1.3.6.1.4.1.476.1.42.3.4.3.70.1.2
A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvValveState 1.3.6.1.4.1.476.1.42.3.4.3.70.1.3
not-specified The state of the component is unknown. open The valve is open. off The valve is closed.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER not-specified(0), open(1), closed(2)  

lgpEnvValvePositionTenths 1.3.6.1.4.1.476.1.42.3.4.3.70.1.20
This gives a value describing the position of the valve.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigReheatLockout 1.3.6.1.4.1.476.1.42.3.4.4.1
If locked-out the reheats will not operate even if controller calls for its operation.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER lockedOut(1), notLockedOut(2)  

lgpEnvConfigHumLockout 1.3.6.1.4.1.476.1.42.3.4.4.2
If locked-out the humidifier will not operate even if controller calls for its operation.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER lockedOut(1), notLockedOut(2)  

lgpEnvConfigRestartDelay 1.3.6.1.4.1.476.1.42.3.4.4.4
When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigRemoteShutdown 1.3.6.1.4.1.476.1.42.3.4.4.7
When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigCoolingServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.8
The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigHumidifierServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.9
The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigFilterServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.10
The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigSleepModeDeadbandRangeDegC 1.3.6.1.4.1.476.1.42.3.4.4.11
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigSleepModeDeadbandRangeDegF 1.3.6.1.4.1.476.1.42.3.4.4.12
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigSupplyTempLowLimitDegF 1.3.6.1.4.1.476.1.42.3.4.4.13
The minimum allowable supply temperature.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigSupplyTempLowLimitDegC 1.3.6.1.4.1.476.1.42.3.4.4.14
The minimum allowable supply temperature.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigTemperatureIntegTime 1.3.6.1.4.1.476.1.42.3.4.4.15
The value used as the integration factor in the proportional integral derivative (PID) temperature calculation.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigLocalTemperatureUnit 1.3.6.1.4.1.476.1.42.3.4.4.16
The local temperature unit of the system.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER degC(1), degF(2)  

lgpEnvConfigSleepMode 1.3.6.1.4.1.476.1.42.3.4.4.17
The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2), auto(3)  

lgpEnvConfigHumidityIntegTime 1.3.6.1.4.1.476.1.42.3.4.4.18
The value used as the integration factor in the proportional integral derivative (PID) humidity calculation.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigFreecoolingDeltaDegF 1.3.6.1.4.1.476.1.42.3.4.4.19
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigFreecoolingDeltaDegC 1.3.6.1.4.1.476.1.42.3.4.4.20
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigSupplyTempLowLimit 1.3.6.1.4.1.476.1.42.3.4.4.21
The system configuration parameter to enable or disable the supply air low temperature limit.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigSensorEventsStandard 1.3.6.1.4.1.476.1.42.3.4.4.22
The system configuration parameter to enable or disable the standard sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigSensorEvents1 1.3.6.1.4.1.476.1.42.3.4.4.23
The system configuration parameter to enable or disable sensor 1 events.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigSleepModeDeadbandRange 1.3.6.1.4.1.476.1.42.3.4.4.24
The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigAutoConfiguration 1.3.6.1.4.1.476.1.42.3.4.4.25
The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigDeltaGlycolType 1.3.6.1.4.1.476.1.42.3.4.4.26
The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), contact(2), value(3)  

lgpEnvConfigChillWaterControl 1.3.6.1.4.1.476.1.42.3.4.4.27
The system configuration parameter to enable or disable the minimum chill water temperature control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

lgpEnvConfigInfaredFlushRate 1.3.6.1.4.1.476.1.42.3.4.4.28
The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigHumidityControl 1.3.6.1.4.1.476.1.42.3.4.4.29
The present configured state of the automatic humidity compensation algorithm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER relative(1), compensated(2), predictive(3)  

lgpEnvConfigCompressorLockout 1.3.6.1.4.1.476.1.42.3.4.4.30
The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER lockedOut(1), notLockedOut(2)  

lgpEnvConfigReheatAndHumidifierLockout 1.3.6.1.4.1.476.1.42.3.4.4.31
The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER lockedOut(1), notLockedOut(2)  

lgpEnvOperationalTimeTable 1.3.6.1.4.1.476.1.42.3.4.4.32
A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvOperationalTimeEntry

lgpEnvOperationalTimeEntry 1.3.6.1.4.1.476.1.42.3.4.4.32.1
This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvOperationalTimeEntry  

lgpEnvOperationTimeIndex 1.3.6.1.4.1.476.1.42.3.4.4.32.1.1
This is the index indicating the nth element of the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvOperationTimePoint 1.3.6.1.4.1.476.1.42.3.4.4.32.1.2
An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvOperationTimeSubID 1.3.6.1.4.1.476.1.42.3.4.4.32.1.3
This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvOperationTimeUnit 1.3.6.1.4.1.476.1.42.3.4.4.32.1.4
An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvOperationTimeValue 1.3.6.1.4.1.476.1.42.3.4.4.32.1.5
The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvOperationTimeHighWarning 1.3.6.1.4.1.476.1.42.3.4.4.32.1.6
The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigTempControlAlgorithm 1.3.6.1.4.1.476.1.42.3.4.4.33
Selects the algorithm for controlling temperature.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pi(1), pid(2), intelligent(3), proportional(4)  

lgpEnvConfigFanSpeedMode 1.3.6.1.4.1.476.1.42.3.4.4.34
Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER manual(1), auto(2)  

lgpEnvConfigFanSpeedCapacity 1.3.6.1.4.1.476.1.42.3.4.4.35
Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigBmsResetTimer 1.3.6.1.4.1.476.1.42.3.4.4.36
The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigDisableSensorOffsetDegC 1.3.6.1.4.1.476.1.42.3.4.4.37
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigDisableSensorOffsetDegF 1.3.6.1.4.1.476.1.42.3.4.4.38
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigCabinetSensorAlarms 1.3.6.1.4.1.476.1.42.3.4.4.39
Enable or Disable Cabinet Sensor Alarms.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

lgpEnvConfigAirTemperatureControlSensor 1.3.6.1.4.1.476.1.42.3.4.4.42
Sensor from which air temperature measurements will be used for cooling and heating control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER supply(1), remote(2), return(3)  

lgpEnvConfigFanSpeedControlSensor 1.3.6.1.4.1.476.1.42.3.4.4.43
Sensor from which air temperature measurements will be used for fan speed control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER supply(1), remote(2), return(3)  

lgpEnvConfigMinFanSpeed 1.3.6.1.4.1.476.1.42.3.4.4.44
Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigMaxFanSpeed 1.3.6.1.4.1.476.1.42.3.4.4.45
Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpEnvConfigFanSpeedPropBandDegC 1.3.6.1.4.1.476.1.42.3.4.4.46
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvConfigFanSpeedPropBandDegF 1.3.6.1.4.1.476.1.42.3.4.4.47
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvControlShutdownAfterDelay 1.3.6.1.4.1.476.1.42.3.4.5.1
Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -1..2147483647  

lgpEnvControlStartupAfterDelay 1.3.6.1.4.1.476.1.42.3.4.5.2
Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -1..2147483647  

lgpEnvSleepIntervalTimeTable 1.3.6.1.4.1.476.1.42.3.4.5.3
A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvSleepIntervalTimeEntry

lgpEnvSleepIntervalTimeEntry 1.3.6.1.4.1.476.1.42.3.4.5.3.1
This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvSleepIntervalTimeEntry  

lgpEnvSleepTimeIndex 1.3.6.1.4.1.476.1.42.3.4.5.3.1.1
This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvSleepTimeSubID 1.3.6.1.4.1.476.1.42.3.4.5.3.1.2
This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvSleepTimeStartHour 1.3.6.1.4.1.476.1.42.3.4.5.3.1.3
This is the hours digit of the time when the system will be put online.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvSleepTimeStartMinute 1.3.6.1.4.1.476.1.42.3.4.5.3.1.4
This is the minutes digit of the time when the system will be put online.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvSleepTimeStopHour 1.3.6.1.4.1.476.1.42.3.4.5.3.1.5
This is the hours digit containing the time when the system will be taken offline.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvSleepTimeStopMinute 1.3.6.1.4.1.476.1.42.3.4.5.3.1.6
This is the minutes digit containing the time when the system will be taken offline.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvSleepDayTable 1.3.6.1.4.1.476.1.42.3.4.5.4
A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvSleepDayEntry

lgpEnvSleepDayEntry 1.3.6.1.4.1.476.1.42.3.4.5.4.1
This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvSleepDayEntry  

lgpEnvSleepDayIndex 1.3.6.1.4.1.476.1.42.3.4.5.4.1.1
This is the index indicating the row of the table 'lgpEnvSleepDayTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvSleepDay 1.3.6.1.4.1.476.1.42.3.4.5.4.1.2
This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)  

lgpEnvSleepAllDayEnabled 1.3.6.1.4.1.476.1.42.3.4.5.4.1.3
The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpEnvStatisticsComp1RunHr 1.3.6.1.4.1.476.1.42.3.4.6.1
Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsComp2RunHr 1.3.6.1.4.1.476.1.42.3.4.6.2
Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsFanRunHr 1.3.6.1.4.1.476.1.42.3.4.6.3
Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsHumRunHr 1.3.6.1.4.1.476.1.42.3.4.6.4
Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsReheat1RunHr 1.3.6.1.4.1.476.1.42.3.4.6.7
Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsReheat2RunHr 1.3.6.1.4.1.476.1.42.3.4.6.8
Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsReheat3RunHr 1.3.6.1.4.1.476.1.42.3.4.6.9
Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsCoolingModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.10
Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsHeatingModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.11
Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsHumidifyModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.12
Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsDehumidifyModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.13
Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsHotGasRunHr 1.3.6.1.4.1.476.1.42.3.4.6.14
Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsHotWaterRunHr 1.3.6.1.4.1.476.1.42.3.4.6.15
Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsFreeCoolRunHr 1.3.6.1.4.1.476.1.42.3.4.6.16
Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsComp3RunHr 1.3.6.1.4.1.476.1.42.3.4.6.17
Accumulated run hours of compressor 3.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvStatisticsComp4RunHr 1.3.6.1.4.1.476.1.42.3.4.6.18
Accumulated run hours of compressor 4.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvWellKnownPoints 1.3.6.1.4.1.476.1.42.3.4.7.1
This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvFanPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.1
This identifier represents a well known fan measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressorPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.2
This identifier represents a well known compressor measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvElectricHeaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.3
This identifier represents a well known electric heater measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvChilledWaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.4
This identifier represents a well known chilled water measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHumidifierPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.5
This identifier represents a well known humidifier measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvDehumidifierPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.6
This identifier represents a well known dehumidifier measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvFreeCoolingPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.7
This identifier represents a well known free-cooling measurement process.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHotWaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.8
This identifier represents a well known hot water measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHotGasPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.9
This identifier represents a well known hot gas measurement point.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvBatteryCabinetPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.10
This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvPumpPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.11
This sub-tree identifies well-known pumps in the system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvPump1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.11.1
This identifier represents pump 1.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvPump2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.11.2
This identifier represents pump 2.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressorPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.12
This sub-tree identifies well-known compressors in the system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1
This identifier represents compressor 1.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor1APoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1
This identifier represents compressor 1A.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor1BPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2
This identifier represents compressor 1B.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2
This identifier represents compressor 2.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor2APoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1
This identifier represents compressor 2A.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvCompressor2BPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2
This identifier represents compressor 2B.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvValvePoints 1.3.6.1.4.1.476.1.42.3.4.7.1.13
This sub-tree identifies well-known valves in the system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHotGasValve1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.13.1
This identifier represents hot gas valve 1.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHotGasValve2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.13.2
This identifier represents hot gas valve 2.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvRemoteSensorStatisticPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.14
This sub-tree identifies well-known remote sensor statistics in the system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvRemoteSensorMinimumPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.1
This identifier represents the minimum value for remote sensor readings.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvRemoteSensorMaximumPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.2
This identifier represents the maximum value for remote sensor readings.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvRemoteSensorAveragePoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.3
This identifier represents the average value for remote sensor readings.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvWellKnownUnits 1.3.6.1.4.1.476.1.42.3.4.8.1
This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvHours 1.3.6.1.4.1.476.1.42.3.4.8.1.1
This identifier represents well known time unit of hours.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvControlTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.1
Temperature measurement used as control feedback.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvReturnAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.2
Temperature measurement of return air.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvSupplyAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.3
Temperature measurement of supply air.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpAmbientTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.4
Ambient temperature measurement.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpInverterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.5
Temperature measurement of the inverter.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpBatteryTempterature 1.3.6.1.4.1.476.1.42.3.4.1.1.6
Temperature measurement of the battery.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpAcDcConverterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.7
Temperature measurement of the AC-to-DC Converter.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpPfcTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.8
Temperature measurement of the power factor correction circuitry.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpTransformerTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.9
Temperature measurement of the transformer.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpLocalTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10
Temperature measurement of local temperature sensor.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpLocal1Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.1
Temperature and humidity measurements of Local Sensor 1.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpLocal2Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.2
Temperature and humidity measurements of Local Sensor 2.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpLocal3Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.3
Temperature and humidity measurements of Local Sensor 3.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpDigitalScrollCompressorTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11
Temperature and humidity measurements of a digital Scroll Compressor.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpDigitalScrollCompressor1Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11.1
Temperature and humidity measurements of a digital Scroll Compressor 1.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpDigitalScrollCompressor2Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11.2
Temperature and humidity measurements of a digital Scroll Compressor 2.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpChillWaterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.12
Temperature measurements of a chill water system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpCoolantTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.13
Temperature measurements of an environmental system's coolant.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperatureSensors 1.3.6.1.4.1.476.1.42.3.4.1.1.14
Enclosure temperature sensors
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperatureSensor1 1.3.6.1.4.1.476.1.42.3.4.1.1.14.1
Enclosure temperature sensor 1
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperatureSensor2 1.3.6.1.4.1.476.1.42.3.4.1.1.14.2
Enclosure temperature sensor 2
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperatureSensor3 1.3.6.1.4.1.476.1.42.3.4.1.1.14.3
Enclosure temperature sensor 3
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperatureSensor4 1.3.6.1.4.1.476.1.42.3.4.1.1.14.4
Enclosure temperature sensor 4
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvValueAmbientRoomTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.15
Temperature outside enclosure.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvDewPointTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.16
The calculated temperature outside of the enclosure at which condensation is likely to occur.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvEnclosureTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.17
Temperature inside of enclosure.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvAdjustedTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.18
The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvExternalSensors 1.3.6.1.4.1.476.1.42.3.4.1.1.19
External sensors to monitor environmental variables such as temperature and humidity
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvExternalAirSensorA 1.3.6.1.4.1.476.1.42.3.4.1.1.19.1
Temperature and humidity measurements from external air sensor A.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvExternalAirSensorADewPoint 1.3.6.1.4.1.476.1.42.3.4.1.1.19.2
Dewpoint temperature for External Air Sensor A.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvExternalAirSensorB 1.3.6.1.4.1.476.1.42.3.4.1.1.19.3
Temperature and humidity measurements from external air sensor B.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvExternalAirSensorBDewPoint 1.3.6.1.4.1.476.1.42.3.4.1.1.19.4
Dewpoint temperature for External Air Sensor B.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvSupplyFluidTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.20
The current temperature of the fluid being supplied.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvSupplyRefrigerantTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.21
The current temperature of the refrigerant being supplied.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvMinDesiredRoomAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.22
The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvDewPointTemperatures 1.3.6.1.4.1.476.1.42.3.4.1.1.23
This sub-tree identifies well-known dew point temperatures in the system.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvInletDewPointTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.23.1
Dew point temperature measured at the inlet of the unit.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpEnvTemperatureSettingDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.1
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureToleranceDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.2
The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureTableDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvTemperatureEntryDegF

lgpEnvTemperatureDeadbandRangeDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.4
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureEntryDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvTemperatureEntryDegF  

lgpEnvTemperatureIdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvTemperatureDescrDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvTemperatureMeasurementDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3
The measured temperature value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureHighThresholdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureLowThresholdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureSetPointDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDailyHighDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7
The daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDailyLowDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8
The daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTempDailyHighTimeHourDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9
The hours digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvTempDailyHighTimeMinuteDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10
The minutes digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyHighTimeSecondDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11
The seconds digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyLowTimeHourDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12
The hours digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvTempDailyLowTimeMinuteDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13
The minutes digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyLowTimeSecondDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14
The seconds digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTemperatureMeasurementTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50
The measured temperature value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureHighThresholdTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureLowThresholdTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureSetPointTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDeadBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTempHeatingPropBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTempCoolingPropBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureSettingDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.1
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureToleranceDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.2
The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureTableDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvTemperatureEntryDegC

lgpEnvTemperatureDeadbandRangeDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.4
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureEntryDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvTemperatureEntryDegC  

lgpEnvTemperatureIdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvTemperatureDescrDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvTemperatureMeasurementDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3
The measured temperature value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureHighThresholdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureLowThresholdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureSetPointDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDailyHighDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7
The daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDailyLowDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8
The daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTempDailyHighTimeHourDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9
The hours digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvTempDailyHighTimeMinuteDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10
The minutes digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyHighTimeSecondDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11
The seconds digit of the time corresponding to the daily high temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyLowTimeHourDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12
The hours digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvTempDailyLowTimeMinuteDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13
The minutes digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTempDailyLowTimeSecondDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14
The seconds digit of the time corresponding to the daily low temperature measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvTemperatureMeasurementTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50
The measured temperature value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureHighThresholdTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureLowThresholdTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureSetPointTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTemperatureDeadBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTempHeatingPropBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvTempCoolingPropBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvControlHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.1
Humidity measurement used as control feedback.
Status: current Access: read-write
OBJECT-IDENTITY    

lgpEnvReturnAirHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.2
Humidity measurement of return air.
Status: current Access: read-write
OBJECT-IDENTITY    

lgpEnvSupplyAirHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.3
Humidity measurement of supply air.
Status: current Access: read-write
OBJECT-IDENTITY    

lgpEnvValueAmbientHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.4
Humidity outside enclosure.
Status: current Access: read-write
OBJECT-IDENTITY    

lgpEnvHumiditySettingRel 1.3.6.1.4.1.476.1.42.3.4.2.2.1
The humidity setting used to control the well known humidity point.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityToleranceRel 1.3.6.1.4.1.476.1.42.3.4.2.2.2
Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityTableRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3
A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvHumidityEntryRel

lgpEnvHumidityDeadbandRange 1.3.6.1.4.1.476.1.42.3.4.2.2.4
The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityEntryRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1
This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvHumidityEntryRel  

lgpEnvHumidityIdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1
This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvHumidityDescrRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2
A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpEnvHumidityMeasurementRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3
The measured humidity value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityHighThresholdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityLowThresholdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumiditySetPoint 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6
The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityDailyHigh 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7
The daily high relative humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityDailyLow 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8
The daily low relative humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityDailyHighTimeHour 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9
The hours digit of the time corresponding to the daily high humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvHumidityDailyHighTimeMinute 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10
The minutes digit of the time corresponding to the daily high humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvHumidityDailyHighTimeSecond 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11
The seconds digit of the time corresponding to the daily high humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvHumidityDailyLowTimeHour 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12
The hours digit of the time corresponding to the daily low humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..23  

lgpEnvHumidityDailyLowTimeMinute 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13
The minutes digit of the time corresponding to the daily low humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvHumidityDailyLowTimeSecond 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14
The seconds digit of the time corresponding to the daily low humidity measurement.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..59  

lgpEnvHumidityDeadBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15
The deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidifyPropBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16
The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvDehumidifyPropBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17
The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityMeasurementRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50
The measured humidity value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityHighThresholdRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvHumidityLowThresholdRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpEnvRemoteSensorCalc 1.3.6.1.4.1.476.1.42.3.4.9.1
Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER average(1), maximum(2)  

lgpEnvRemoteSensorTable 1.3.6.1.4.1.476.1.42.3.4.9.10
This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpEnvRemoteSensorEntry

lgpEnvRemoteSensorEntry 1.3.6.1.4.1.476.1.42.3.4.9.10.1
This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpEnvRemoteSensorEntry  

lgpEnvRemoteSensorIndex 1.3.6.1.4.1.476.1.42.3.4.9.10.1.1
This is the index indicating the nth element of the table.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpEnvRemoteSensorId 1.3.6.1.4.1.476.1.42.3.4.9.10.1.2
This is the sensor number identifying the sensor.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpEnvRemoteSensorMode 1.3.6.1.4.1.476.1.42.3.4.9.10.1.3
Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), reference(1), control(2)  

lgpEnvRemoteSensorUsrLabel 1.3.6.1.4.1.476.1.42.3.4.9.10.1.4
User assigned remote sensor label.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

lgpEnvRemoteSensorTempMeasurementDegF 1.3.6.1.4.1.476.1.42.3.4.9.10.1.5
Temperature measured at the temperature sensor reported in degrees Fahrenheit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

lgpEnvRemoteSensorTempMeasurementDegC 1.3.6.1.4.1.476.1.42.3.4.9.10.1.6
Temperature measured at the temperature sensor reported in degrees Celsius.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32