EPPC-MIB
File:
EPPC-MIB.mib (84212 bytes)
Imported modules
Imported symbols
Defined Types
UpsSystemOutputEntry |
|
SEQUENCE |
|
|
|
|
upsESystemOutputPhase |
PositiveInteger |
|
|
upsESystemOutputFrequency |
NonNegativeInteger |
|
|
upsESystemOutputVoltage |
NonNegativeInteger |
|
|
upsESystemOutputCurrent |
NonNegativeInteger |
|
|
upsESystemOutputWatts |
NonNegativeInteger |
|
|
upsESystemOutputVA |
NonNegativeInteger |
|
|
upsESystemOutputLoad |
NonNegativeInteger |
|
UpsSystemBypassEntry |
|
SEQUENCE |
|
|
|
|
upsESystemBypassPhase |
PositiveInteger |
|
|
upsESystemBypassFrequency |
NonNegativeInteger |
|
|
upsESystemBypassVoltage |
NonNegativeInteger |
|
|
upsESystemBypassCurrent |
NonNegativeInteger |
|
|
upsESystemBypassWatts |
NonNegativeInteger |
|
UpsChargerModulesEntry |
|
SEQUENCE |
|
|
|
|
chargerModulesNum |
PositiveInteger |
|
|
chargerModulesAddress |
NonNegativeInteger |
|
|
positiveChargeVotlage |
NonNegativeInteger |
|
|
negativeChargeVoltage |
NonNegativeInteger |
|
|
positiveChargeCurrent |
NonNegativeInteger |
|
|
negativeChargeCurrent |
NonNegativeInteger |
|
|
chargerModulesTemperature |
INTEGER |
|
|
chargerModulesMode |
INTEGER |
|
UpsModulesEntry |
|
SEQUENCE |
|
|
|
|
upsEModulesNum |
PositiveInteger |
|
|
upsEModuleAddress |
INTEGER |
|
|
upsEModulePositiveBusVolt |
NonNegativeInteger |
|
|
upsEModuleNegativeBusVolt |
NonNegativeInteger |
|
|
upsEModuleTemperature |
INTEGER |
|
|
upsEModuleWorkingMode |
INTEGER |
|
|
upsEModuleOutputCurrentR |
NonNegativeInteger |
|
|
upsEModuleOutputWattR |
NonNegativeInteger |
|
|
upsEModuleOutputLoadR |
INTEGER |
|
|
upsEModuleWarningCode |
DisplayString |
|
|
upsEModuleFaultCode |
DisplayString |
|
|
upsEModuleTrapState |
DisplayString |
|
|
upsEModuleConfigOutputVA |
NonNegativeInteger |
|
|
upsEModuleOutputCurrentS |
NonNegativeInteger |
|
|
upsEModuleOutputCurrentT |
NonNegativeInteger |
|
|
upsEModuleOutputWattS |
NonNegativeInteger |
|
|
upsEModuleOutputWattT |
NonNegativeInteger |
|
|
upsEModuleOutputLoadS |
INTEGER |
|
|
upsEModuleOutputLoadT |
INTEGER |
|
|
upsEModuleOutputVAR |
NonNegativeInteger |
|
|
upsEModuleOutputVAS |
NonNegativeInteger |
|
|
upsEModuleOutputVAT |
NonNegativeInteger |
|
UpsBatteryTestScheduleEntry |
|
SEQUENCE |
|
|
|
|
upsEBatteryTestScheduleIndex |
PositiveInteger |
|
|
upsEBatteryTestScheduleDay |
INTEGER |
|
|
upsEBatteryTestScheduleTime |
DisplayString |
|
|
upsEBatteryTestScheduleType |
INTEGER |
|
|
upsEBatteryTestScheduleTestWithTime |
NonNegativeInteger |
|
|
upsEBatteryTestScheduleSpecialDay |
DisplayString |
|
UpsShutdownEventsEntry |
|
SEQUENCE |
|
|
|
|
upsEShutdownEvent |
INTEGER |
|
|
upsEShutdownEventAction |
INTEGER |
|
|
upsEShutdownwarningPeriodTime |
NonNegativeInteger |
|
|
upsEShutdownWarningPeriodInterval |
NonNegativeInteger |
|
UpsControlWeeklyScheduleEntry |
|
SEQUENCE |
|
|
|
|
upsEControlWeeklyScheduleIndex |
PositiveInteger |
|
|
upsEWeeklyScheduleShutdownDay |
INTEGER |
|
|
upsEWeeklyScheduleShutdownTime |
DisplayString |
|
|
upsEWeeklyScheduleRestartDay |
INTEGER |
|
|
upsEWeeklyScheduleRestartTime |
DisplayString |
|
UpsControlSpecialDayScheduleEntry |
|
SEQUENCE |
|
|
|
|
upsEControlSpecialDayScheduleIndex |
PositiveInteger |
|
|
upsESpecialDayScheduleShutdownDay |
DisplayString |
|
|
upsESpecialDayScheduleShutdownTime |
DisplayString |
|
|
upsESpecialDayScheduleRestartDay |
DisplayString |
|
|
upsESpecialDayScheduleRestartTime |
DisplayString |
|
UpsTrapsReceiversEntry |
|
SEQUENCE |
|
|
|
|
upsETrapsReceiversIndex |
PositiveInteger |
|
|
upsETrapsReceiverAddress |
DisplayString |
|
|
upsETrapReceiverCommunityString |
DisplayString |
|
|
upsETrapType |
INTEGER |
|
|
upsETrapsSeverityLevel |
INTEGER |
|
|
upsETrapReceiverDescription |
DisplayString |
|
Defined Values
ppc |
1.3.6.1.4.1.935 |
OBJECT IDENTIFIER |
|
|
|
device |
1.3.6.1.4.1.935.10 |
OBJECT IDENTIFIER |
|
|
|
upsAgent |
1.3.6.1.4.1.935.10.1 |
OBJECT IDENTIFIER |
|
|
|
upsE |
1.3.6.1.4.1.935.10.1.1 |
OBJECT IDENTIFIER |
|
|
|
upsETraps |
1.3.6.1.4.1.935.10.1.2 |
OBJECT IDENTIFIER |
|
|
|
upsEIdentityDescription |
1.3.6.1.4.1.935.10.1.1.1.5 |
A string to identify the UPS. This object should be
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
upsEIdentityAgentSoftwareVerison |
1.3.6.1.4.1.935.10.1.1.1.6 |
The Network Management Card software/firmware version.
This variable may or may not have the same value as
upsEIdentGroupUPSSoftwareVersion in some implementations. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsEIdentityAttachedDevices |
1.3.6.1.4.1.935.10.1.1.1.7 |
A string identifying the devices attached to the output(s)
of the UPS. This object should be set by the administrator |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
upsESystemStatus |
1.3.6.1.4.1.935.10.1.1.2.1 |
The indication of UPS system status. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
power-on(1), stand-by(2), by-pass(3), line(4), battery(5), battery-test(6), fault(7), converter(8), eco(9), shutdown(10), on-booster(11), on-reducer(12), other(13) |
|
upsESystemTemperature |
1.3.6.1.4.1.935.10.1.1.2.2 |
The temperature of UPS presented in 0.1 degree. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsESystemWarningCode |
1.3.6.1.4.1.935.10.1.1.2.3 |
The warning code of UPS. Please refer the warning table
of 'Q6' for details. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsESystemFaultCode |
1.3.6.1.4.1.935.10.1.1.2.4 |
The fault code of UPS.Please refer the fault code
of 'Q6' for details. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsESystemConfigOutputVoltage |
1.3.6.1.4.1.935.10.1.1.2.7 |
The magnitude of the nominal output voltage presented in 0.1V. On those systems
which support read-write access to this object, if there is an
attempt to set this variable to a value that is not supported,
the request must be rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1, or
inconsistentValue for SNMPv2 |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsESystemConfigOutputFrequency |
1.3.6.1.4.1.935.10.1.1.2.8 |
The nominal output frequency presented in 0.1Hz. On those systems which support
read-write access to this object, if there is an attempt to set
this variable to a value that is not supported, the request must
be rejected and the agent shall respond with an appropriate error
message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsESystemOutputNumPhase |
1.3.6.1.4.1.935.10.1.1.2.17 |
The number of metered output phases, serves as the table index.
This value indicate the device initialized feature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..3 |
|
upsESystemOutputTable |
1.3.6.1.4.1.935.10.1.1.2.18 |
A list of output table entries. The number of entries is given
by the value of upsESystemOutputNumPhase. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsSystemOutputEntry |
|
upsESystemOutputEntry |
1.3.6.1.4.1.935.10.1.1.2.18.1 |
An entry containing information applicable to a particular line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsSystemOutputEntry |
|
|
upsESystemOutputPhase |
1.3.6.1.4.1.935.10.1.1.2.18.1.1 |
The number of the phase. Serves as index for output table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..3 |
|
upsESystemBypassNumPhase |
1.3.6.1.4.1.935.10.1.1.2.19 |
The number of bypass phases, serves as the table index.
This value indicate the device initialized feature |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..3 |
|
upsESystemBypassTable |
1.3.6.1.4.1.935.10.1.1.2.20 |
A list of bypass table entries. The number of entries is given by the
value of upsESystemBypassNumPhase. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsSystemBypassEntry |
|
upsESystemBypassEntry |
1.3.6.1.4.1.935.10.1.1.2.20.1 |
An entry containing information applicable to a particular line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsSystemBypassEntry |
|
|
upsESystemBypassPhase |
1.3.6.1.4.1.935.10.1.1.2.20.1.1 |
The number of the phase. Serves as index for bypass table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..3 |
|
upsESystemConfigBelowRemainTimeLimit |
1.3.6.1.4.1.935.10.1.1.2.22 |
The UPS batteries backup time(minute) limit for shutdown |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEBatteryStatus |
1.3.6.1.4.1.935.10.1.1.3.1 |
The status of UPS battery, a value of batteryLow indicates
that the battery-low status bit has been set from device.
A value of batteryDepleted indicates that the UPS will be
unable to sustain the present load when and if the utility
power is lost (including the possibility that the utility
power is mandatoryly absent and the UPS is unable to sustain
the output) |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6) |
|
upsESecondsOnBattery |
1.3.6.1.4.1.935.10.1.1.3.2 |
If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. 0 shall be returned
if the unit is not on battery power |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEBatteryEstimatedMinutesRemaining |
1.3.6.1.4.1.935.10.1.1.3.3 |
An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
upsEBatteryEstimatedChargeRemaining |
1.3.6.1.4.1.935.10.1.1.3.4 |
An estimate of the battery charge remaining expressed
as a percent of full charge |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..100 |
|
upsEBatteryTemperature |
1.3.6.1.4.1.935.10.1.1.3.8 |
The ambient temperature at or near the UPS Battery
casing in 0.1 degree. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEBatteryLastReplacedDate |
1.3.6.1.4.1.935.10.1.1.3.9 |
The date when the Batteries in this UPS were last replaced.
The format should be DD/MM/YYYY. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10..10) |
|
upsEBatteryABMStatus |
1.3.6.1.4.1.935.10.1.1.3.10 |
The status of ABM. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
charge(1), float(2), rest(3), discharge(4), disable(5) |
|
upsEChargerModulesNum |
1.3.6.1.4.1.935.10.1.1.3.11 |
The number of charger modules inserted to UPS systems. served
as the index of the upsEChargerModulesTable.
The default value 0 indicate that the UPS system don't have
separate charger module. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
0..32 |
|
upsEChargerModulesTable |
1.3.6.1.4.1.935.10.1.1.3.12 |
A list of charger modules entries. The number of entries is given
by the value of upsEchargerModulesNum. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsChargerModulesEntry |
|
upsEChargerModulesEntry |
1.3.6.1.4.1.935.10.1.1.3.12.1 |
An entry containing information applicable to a particular charger module. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsChargerModulesEntry |
|
|
chargerModulesNum |
1.3.6.1.4.1.935.10.1.1.3.12.1.1 |
The number of charger modules. Serves as index for charger module table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..32 |
|
positiveChargeCurrent |
1.3.6.1.4.1.935.10.1.1.3.12.1.5 |
The measured positive charger mandatory from the UPS meters in in 0.1 amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
negativeChargeCurrent |
1.3.6.1.4.1.935.10.1.1.3.12.1.6 |
The measured nepositive charger mandatory from the UPS meters in 0.1 amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
chargerModulesTemperature |
1.3.6.1.4.1.935.10.1.1.3.12.1.7 |
The measured charger temperature from the UPS meters in 0.1 degree. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
chargerModulesMode |
1.3.6.1.4.1.935.10.1.1.3.12.1.8 |
The working mode of charger modules. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
powerOn(1), standyby(2), fault(3), shutdown(4), running(5), suicide(6), unknown(7) |
|
upsEUPSModulesNum |
1.3.6.1.4.1.935.10.1.1.4.1 |
The number of UPS modules inserted to UPS systems.
served as the index of the upsEModulesTable.
the default value 0 indicate that the UPS system do not
have separate UPS module. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
0..32 |
|
upsEModulesTable |
1.3.6.1.4.1.935.10.1.1.4.2 |
A list of UPS modules entries. The number of entries is
given by the value of upsEModulesNum. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsModulesEntry |
|
upsEModulesEntry |
1.3.6.1.4.1.935.10.1.1.4.2.1 |
An entry containing information applicable to a particular upsE module. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsModulesEntry |
|
|
upsEModulesNum |
1.3.6.1.4.1.935.10.1.1.4.2.1.1 |
The number of UPS modules. Serves as index for UPS module table |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
1..32 |
|
upsEModuleAddress |
1.3.6.1.4.1.935.10.1.1.4.2.1.2 |
the address of UPS modules. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEModuleTemperature |
1.3.6.1.4.1.935.10.1.1.4.2.1.5 |
The measured upsE module temperature from the UPS meters in 0.1 degree. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEModuleWorkingMode |
1.3.6.1.4.1.935.10.1.1.4.2.1.6 |
The working mode of UPS modules. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
power-on(1), stand-by(2), by-pass(3), line(4), battery(5), battery-test(6), fault(7), converter(8), eco(9), shutdown(10), on-booster(11), on-reducer(12), other(13) |
|
upsEModuleOutputLoadR |
1.3.6.1.4.1.935.10.1.1.4.2.1.9 |
The output load of UPS modules in %. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEModuleWarningCode |
1.3.6.1.4.1.935.10.1.1.4.2.1.10 |
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsEModuleFaultCode |
1.3.6.1.4.1.935.10.1.1.4.2.1.11 |
The fault code of ups modules.Please refer command 'QU,XX' for details. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsEModuleTrapState |
1.3.6.1.4.1.935.10.1.1.4.2.1.12 |
the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'.
And then the AC restore, the value of upsEModuleTrapState
should change to empty. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..127) |
|
upsEModuleOutputLoadS |
1.3.6.1.4.1.935.10.1.1.4.2.1.18 |
The output load of UPS modules in %. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEModuleOutputLoadT |
1.3.6.1.4.1.935.10.1.1.4.2.1.19 |
The output load of UPS modules in %. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment1OffDelay |
1.3.6.1.4.1.935.10.1.1.5.1 |
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment1OnDelay |
1.3.6.1.4.1.935.10.1.1.5.2 |
Setting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment1AutoOffTimer |
1.3.6.1.4.1.935.10.1.1.5.3 |
The load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment1AutoOnTimer |
1.3.6.1.4.1.935.10.1.1.5.4 |
The load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment1State |
1.3.6.1.4.1.935.10.1.1.5.5 |
Load segment output state. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(1), on(2), off-pending(3), on-pending(4), not-support(5) |
|
upsELoadSegment2OffDelay |
1.3.6.1.4.1.935.10.1.1.5.6 |
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment2OnDelay |
1.3.6.1.4.1.935.10.1.1.5.7 |
Setting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment2AutoOffTimer |
1.3.6.1.4.1.935.10.1.1.5.8 |
The load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment2AutoOnTimer |
1.3.6.1.4.1.935.10.1.1.5.9 |
The load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsELoadSegment2State |
1.3.6.1.4.1.935.10.1.1.5.10 |
Load segment output state. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(1), on(2), off-pending(3), on-pending(4), not-support(5) |
|
upsEEnvironmentCurrentTemperature |
1.3.6.1.4.1.935.10.1.1.6.1.1 |
The measurement of temperature sensor, in 0.1 degree |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentTemperatureHighSetPoint |
1.3.6.1.4.1.935.10.1.1.6.1.2 |
The set point for high temperature warning, in 0.1 degrees.
This value must be greater than upsEEnvironmentTemperatureLowSetPoint,
and the least significant digit must be zero. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentTemperatureHighStatus |
1.3.6.1.4.1.935.10.1.1.6.1.3 |
To enable/disable high set point check with sensor temperature. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsEEnvironmentTemperatureLowSetPoint |
1.3.6.1.4.1.935.10.1.1.6.1.4 |
The set point for low temperature warning, in 0.1 degrees.
This value must be less than upsEEnvironmentTemperatureHighSetPoint,
and the least significant digit must be zero. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentTemperatureLowStatus |
1.3.6.1.4.1.935.10.1.1.6.1.5 |
To enable/disable low set point check with sensor temperature. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsEEnvironmentTemperatureOffset |
1.3.6.1.4.1.935.10.1.1.6.1.6 |
The offset to calibrate temperature of EMD, in 0.1 degrees |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentCurrentHumidity |
1.3.6.1.4.1.935.10.1.1.6.2.1 |
The measurement of sensor humidity present in %. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentHumidityHighSetPoint |
1.3.6.1.4.1.935.10.1.1.6.2.2 |
The set point for high humidity warning, in %.
This value must be greater than upsEEnvironmentHumidityLowSetPoint. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentHumidityHighStatus |
1.3.6.1.4.1.935.10.1.1.6.2.3 |
To enable/disable high set point check with emd humidity. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsEEnvironmentHumidityLowSetPoint |
1.3.6.1.4.1.935.10.1.1.6.2.4 |
The set point for low humidity warning, in %.
This value must be less than upsEEnvironmentHumidityHighSetPoint. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEEnvironmentHumidityLowStatus |
1.3.6.1.4.1.935.10.1.1.6.2.5 |
To enable/disable high set point check with emd humidity. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
upsEEnvironmentHumidityOffset |
1.3.6.1.4.1.935.10.1.1.6.2.6 |
The offset to calibrate humidity of EMD, in %. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsEBatteryTestStart |
1.3.6.1.4.1.935.10.1.1.7.1 |
This object specify the battery test type and initiate battery test.
If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), batteryTest10Sec(2), batteryTestUntilLow(3), batteryTestWithTime(4), cancelBatteryTest(5), clearBatteryInfo(6) |
|
upsEBatteryTestResult |
1.3.6.1.4.1.935.10.1.1.7.3 |
This object indicate the test result of battery. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
idle(1), processing(2), noFailure(3), failureOrWarning(4), notPossible(5), testCancel(6) |
|
upsEBatteryTestStartTime |
1.3.6.1.4.1.935.10.1.1.7.4 |
The value of the time the test in progress was initiated,
or, if no test is in progress, the time the previous test
was initiated. If the value of upsETestBatteryTestResult
is noTestsInitiated(6), upsETestStartTime has the value
01/01/1970 00:00:00. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(19..19) |
|
upsEBatteryTestElapsedTime |
1.3.6.1.4.1.935.10.1.1.7.5 |
The amount of time in format hh:mm:ss, since the test in progress
was initiated, or, if no test is in progress, the previous
test took to complete. If the value of upsTestResultsSummary
is idle(1), upsTestElapsedTime has the value 00:00:00. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(11..11) |
|
upsEBatteryTestScheduleEntry |
1.3.6.1.4.1.935.10.1.1.7.6.1 |
An entry containing information applicable to schedule test. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsBatteryTestScheduleEntry |
|
|
upsEBatteryTestScheduleDay |
1.3.6.1.4.1.935.10.1.1.7.6.1.2 |
The weekday or specaial day on which the UPS should start battery test. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
monday(1), tuesday(2), wednsday(3), thusday(4), friday(5), saturday(6), sunday(7), specialday(8), none(9) |
|
upsEBatteryTestScheduleType |
1.3.6.1.4.1.935.10.1.1.7.6.1.5 |
The type of battery test. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), batteryTest10sec(2), batteryTestUntilLow(3), batteryTestWithTime(4) |
|
upsEControlOutputOffDelay |
1.3.6.1.4.1.935.10.1.1.8.1 |
Setting this value to other than zero will cause the UPS
output to turn off after the number of seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEControlOutputOnDelay |
1.3.6.1.4.1.935.10.1.1.8.2 |
Setting this value to other than zero will cause the
UPS output to turn on after the number of seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEControlOutputOnOffControl |
1.3.6.1.4.1.935.10.1.1.8.3 |
upsEOutputOff ( 1 ) indicates the shutdown sequence,
upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence,
upsESleep( 3 ) indicates shutdown UPS first, then switch on. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
upsEOutputOff(1), upsEOutputOffCancel(2), upsESleep(3), none(4) |
|
upsEShutdownEventsEntry |
1.3.6.1.4.1.935.10.1.1.8.4.1 |
An entry containing information applicable to a particular shutdown
event line |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsShutdownEventsEntry |
|
|
upsEShutdownEvent |
1.3.6.1.4.1.935.10.1.1.8.4.1.1 |
The shutdown event identification |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
acFail(1), batteryLow(2), upsEOverLoad(3), upsEOverTemperature(4), upsEWeeklySchedule(5), upsESpecialSchedule(6), environmentTemperatureOverThreshold(7), environmentHumidityOverThreshold(8), environmentContact1Alarm(9), environmentContact2Alarm(10), belowCapacityLimit(11), belowRemainTimeLimit(12) |
|
upsEShutdownEventAction |
1.3.6.1.4.1.935.10.1.1.8.4.1.2 |
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occured. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(1), warning(2), shutdownClient(3), shutdownUPS(4) |
|
upsEShutdownwarningPeriodTime |
1.3.6.1.4.1.935.10.1.1.8.4.1.3 |
The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEShutdownWarningPeriodInterval |
1.3.6.1.4.1.935.10.1.1.8.4.1.4 |
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs.
The value is in units of seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEControlWeeklyScheduleEntry |
1.3.6.1.4.1.935.10.1.1.8.5.1 |
An entry containing information applicable to a particular line |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsControlWeeklyScheduleEntry |
|
|
upsEWeeklyScheduleShutdownDay |
1.3.6.1.4.1.935.10.1.1.8.5.1.2 |
the weekday on which upsE shoud shutdown |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6), sunday(7), none(8) |
|
upsEWeeklyScheduleShutdownTime |
1.3.6.1.4.1.935.10.1.1.8.5.1.3 |
The time that the process of shutting down the UPS will be initiated
in hh:mm format. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(5) |
|
upsEWeeklyScheduleRestartDay |
1.3.6.1.4.1.935.10.1.1.8.5.1.4 |
the weekday on which the UPS should restart. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6), sunday(7), none(8) |
|
upsEControlSpecialDayScheduleEntry |
1.3.6.1.4.1.935.10.1.1.8.6.1 |
An entry containing information applicable to a particular line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsControlSpecialDayScheduleEntry |
|
|
upsESystemMasterOffDelay |
1.3.6.1.4.1.935.10.1.1.8.7 |
The UPS output will shutdown after the indicated number of seconds, -1 indicate no action. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsESystemMasterOnDelay |
1.3.6.1.4.1.935.10.1.1.8.8 |
The UPS output will start on after the indicated number of seconds, -1 indicate no action. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsETrapsReceiversEntry |
1.3.6.1.4.1.935.10.1.1.9.1.1 |
An entry containing information applicable to a particular input line. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsTrapsReceiversEntry |
|
|
upsETrapType |
1.3.6.1.4.1.935.10.1.1.9.1.1.4 |
The type of trap to be received by the manager. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), rfc1628Trap(2), eppcTrap(3) |
|
upsETrapsSeverityLevel |
1.3.6.1.4.1.935.10.1.1.9.1.1.5 |
The severity level of traps to be received by this manager. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
informational(1), warning(2), severe(3) |
|
upsETrapState |
1.3.6.1.4.1.935.10.1.1.9.2 |
the values indicate the unrestored traps.
For example, after AC fail, the agent send
the trap 1(AC Fail) and trap 7(battery on) to
NMS. so the value of upsETrapState should be '1,7'.
And then the AC restore, the value of upsETrapState
should change to empty. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..127) |
|
upsELowBattery |
3 |
SEVERE: The UPS batteries are low and will soon be exhausted. |
TRAP-TYPE |
|
|
|
upsEFailed |
5 |
SEVERE: The UPS is not working fine. |
TRAP-TYPE |
|
|
|
upsEOk |
6 |
INFORMATION: The UPS is working fine. |
TRAP-TYPE |
|
|
|
upsEOnBattery |
7 |
WARNING: The UPS has switched to battery backup power. |
TRAP-TYPE |
|
|
|
upsETestOver |
10 |
INFORMATION: The testing of UPS is completed. |
TRAP-TYPE |
|
|
|
upsEBypassOn |
11 |
INFORMATION: The UPS has enabled bypass. |
TRAP-TYPE |
|
|
|
upsEOnline |
12 |
INFORMATION: The UPS is not on Bypass and return to normal status. |
TRAP-TYPE |
|
|
|
upsESleeping |
21 |
INFORMATION: UPS has entered sleep mode and power to load has been cut off. |
TRAP-TYPE |
|
|
|
upsEWokeUp |
22 |
INFORMATION: The UPS woke up from sleep mode and power to load has been restored. |
TRAP-TYPE |
|
|
|
upsEOverLoad |
25 |
WARNING: The UPS load is over the setting limit. |
TRAP-TYPE |
|
|
|
upsENotOverLoad |
26 |
INFORMATION: The UPS load is not over the setting limit. |
TRAP-TYPE |
|
|
|
upsEMain1Neutralloss |
47 |
WARNING: Main 1 Neutral loss. |
TRAP-TYPE |
|
|
|
upsEReturnFromMain1Neutralloss |
48 |
INFORMATION: Return from Main 1 Neutral loss. |
TRAP-TYPE |
|
|
|
upsEMain1phaseerror |
49 |
WARNING: Main 1 phase error. |
TRAP-TYPE |
|
|
|
upsEReturnFromMain1phaseerror |
50 |
INFORMATION: Return from Main 1 phase error. |
TRAP-TYPE |
|
|
|
upsEMaintaincoverisopen |
69 |
WARNING: Maintain cover is open. |
TRAP-TYPE |
|
|
|
upsEReturnFromMaintaincoverisopen |
70 |
INFORMATION: Return from Maintain cover is open. |
TRAP-TYPE |
|
|
|
upsEBelowRemainTimeLimit |
125 |
SEVERE: The UPS batteries backup time is below the setting limit. |
TRAP-TYPE |
|
|
|
upsENotBelowRemainTimeLimit |
126 |
INFORMATION: The UPS batteries backup time is not below the setting limit. |
TRAP-TYPE |
|
|
|