ELTEK-GENERIC-MIB
File:
ELTEK-GENERIC-MIB.mib (46686 bytes)
Imported modules
Imported symbols
Defined Types
BatteryMidpointControlEntry |
|
SEQUENCE |
|
|
|
|
midpointEnableID |
Integer32 |
|
|
midpointEnable |
INTEGER |
|
BatteryMidpointStatusEntry |
|
SEQUENCE |
|
|
|
|
midpointStatusID |
Integer32 |
|
|
midpointStatus |
INTEGER |
|
|
midpointDeltaVoltage |
Integer32 |
|
RectifierStatusEntry |
|
SEQUENCE |
|
|
|
|
rectifierStatusID |
Integer32 |
|
|
rectifierStatusStatus |
INTEGER |
|
|
rectifierStatusOutputCurrent |
Integer32 |
|
|
rectifierStatusOutputVoltage |
Integer32 |
|
|
rectifierStatusTemp |
Integer32 |
|
|
rectifierStatusType |
DisplayString |
|
|
rectifierStatusSKU |
DisplayString |
|
|
rectifierStatusSerialNo |
DisplayString |
|
|
rectifierStatusRevisionLevel |
DisplayString |
|
Defined Values
systemTime |
1.3.6.1.4.1.12148.7.1.1 |
OBJECT IDENTIFIER |
|
|
|
dcSystem |
1.3.6.1.4.1.12148.7.2 |
OBJECT IDENTIFIER |
|
|
|
dcPlant |
1.3.6.1.4.1.12148.7.2.1 |
OBJECT IDENTIFIER |
|
|
|
battery |
1.3.6.1.4.1.12148.7.3 |
OBJECT IDENTIFIER |
|
|
|
batteryLVD |
1.3.6.1.4.1.12148.7.3.17 |
OBJECT IDENTIFIER |
|
|
|
rectifier |
1.3.6.1.4.1.12148.7.5 |
OBJECT IDENTIFIER |
|
|
|
alarmGroup |
1.3.6.1.4.1.12148.7.7 |
OBJECT IDENTIFIER |
|
|
|
systemTimeTime |
1.3.6.1.4.1.12148.7.1.1.1 |
The system date and time. Used for event timestamps and logging |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
systemInfoRefresh |
1.3.6.1.4.1.12148.7.1.2 |
This object will re-initialize the agent, updating MIB data values. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
pushbutton(0), refreshdata(1) |
|
systemTrapRepeatRate |
1.3.6.1.4.1.12148.7.1.3 |
This object sets the repeat rate of any active traps, in seconds.
Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..10 |
|
systemSendOffTrap |
1.3.6.1.4.1.12148.7.1.4 |
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1.
Entering 0 (zero) will prevent OFF traps from being transmitted. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
systemSiteInfoCustomer |
1.3.6.1.4.1.12148.7.2.1.3.1 |
The Customer name (as stored in the Smartpack Control Unit) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
systemSiteInfoLocation |
1.3.6.1.4.1.12148.7.2.1.3.2 |
The system/site Location details (as stored in the Smartpack Control Unit). |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
systemSiteInfoMessage1 |
1.3.6.1.4.1.12148.7.2.1.3.3 |
The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
systemSiteInfoMessage2 |
1.3.6.1.4.1.12148.7.2.1.3.4 |
The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
systemSiteInfoInstalledDate |
1.3.6.1.4.1.12148.7.2.1.3.5 |
The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
systemSiteInfoControllerType |
1.3.6.1.4.1.12148.7.2.1.3.6 |
The system Controller Module currently connected.
AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
al175(0), al4000(1), al6000(2), enexus(3) |
|
systemNominalVoltage |
1.3.6.1.4.1.12148.7.2.1.4 |
The nominal voltage rating. 12V/24V/48V/60V systems
0=48V
1=24V
2=12V
3=26V
4=60V |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
prs48v(0), prs24v(1), prs12v(2), prs26v(3), prs60v(4) |
|
systemOperationalStatus |
1.3.6.1.4.1.12148.7.2.2 |
A summary status showing if the system is testing, boosting, floating etc.
0=Float, voltage regulated
1=Float, temperature comp. regulated;
2=equalize
3=battery test |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
floatvoltreg(0), floattempcomp(1), batteryboost(2), batterytest(3) |
|
batteryName |
1.3.6.1.4.1.12148.7.3.1 |
A descriptive name of the battery installed in the system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
batteryVoltage |
1.3.6.1.4.1.12148.7.3.2 |
The measured battery voltage. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7500 |
|
batteryCurrent |
1.3.6.1.4.1.12148.7.3.3 |
The measured battery current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
batteryTemp |
1.3.6.1.4.1.12148.7.3.4 |
The battery temperature |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9999 |
|
batteryBreakerStatus |
1.3.6.1.4.1.12148.7.3.5 |
The state of the battery fuse/breaker can be either closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
closed(0), open(1) |
|
batteryChargeCurrentLimitCtrl |
1.3.6.1.4.1.12148.7.3.6 |
Control field for the battery charge limitation feature; 0=inactive, 1=active. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
deactivate(0), activate(1) |
|
batteryTempCompEnable |
1.3.6.1.4.1.12148.7.3.8 |
Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
batteryFloatVoltConfig |
1.3.6.1.4.1.12148.7.3.9 |
The Voltage at which the DC System float charges. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
4300..6000 |
|
batteryEqualizeVoltConfig |
1.3.6.1.4.1.12148.7.3.10 |
The Voltage at which the DC System boost charges the batteries. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
4300..6000 |
|
batteryStartManualTest |
1.3.6.1.4.1.12148.7.3.15 |
This pushbutton will start a manual battery test if otherwise the system allows it. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
pushbutton(0), starttest(1), stoptest(2) |
|
batteryStartManualBoost |
1.3.6.1.4.1.12148.7.3.16 |
This pushbutton will start a manual battery boost if otherwise the system allows it. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
pushbutton(0), startboost(1), stopboost(2) |
|
batteryLVDStatus |
1.3.6.1.4.1.12148.7.3.17.1 |
Contactor is closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
connect(0), disconnect(1), disable(2) |
|
batteryMidpointDeltaLimitVoltage |
1.3.6.1.4.1.12148.7.3.18.1 |
The allowable deviation of the midpoint battery voltage from the theoretical.
Exceeding this value in either direction (+/-) causes an alarm state |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
batteryMidpointIndex |
1.3.6.1.4.1.12148.7.3.18.2 |
An index of Battery Strings, for the batteryMidpointControlTable
and batteryMidpointStatusTable arrays |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..8 |
|
batteryMidpointControlEntry |
1.3.6.1.4.1.12148.7.3.18.3.1 |
Settings related to Battery Symmetry (midpoint) Monitoring, corresponding
to the batteryMidpointIndex value |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
BatteryMidpointControlEntry |
|
|
midpointEnableID |
1.3.6.1.4.1.12148.7.3.18.3.1.1 |
The rectifier ID number of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..8 |
|
midpointEnable |
1.3.6.1.4.1.12148.7.3.18.3.1.2 |
Enable (1) or Disable (0) the Battery Monitor channel which corresponds
to the batteryMidpointIndex value |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
batteryMidpointStatusEntry |
1.3.6.1.4.1.12148.7.3.18.4.1 |
Values related to Battery Symmetry (midpoint) Monitoring, corresponding
to the batteryMidpointIndex value |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
BatteryMidpointStatusEntry |
|
|
midpointStatusID |
1.3.6.1.4.1.12148.7.3.18.4.1.1 |
The rectifier ID number of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..8 |
|
midpointStatus |
1.3.6.1.4.1.12148.7.3.18.4.1.2 |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds
to the batteryMidpointIndex value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(0), alarm(1), disable(2) |
|
midpointDeltaVoltage |
1.3.6.1.4.1.12148.7.3.18.4.1.3 |
The measured battery voltage deviation from midpoint of the Battery Monitor channel
which corresponds to the batteryMidpointIndex value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
loadDistributionBreakerStatus |
1.3.6.1.4.1.12148.7.4.2 |
The state of the load fuse/breaker can be either closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
closed(0), open(1) |
|
loadLVD1EnableStatus |
1.3.6.1.4.1.12148.7.4.3.1 |
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
loadLVD1Status |
1.3.6.1.4.1.12148.7.4.3.2 |
The A Bus (primary loads) Contactor is closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
connect(0), disconnect(1), disable(2) |
|
loadLVD1ConnectVoltage |
1.3.6.1.4.1.12148.7.4.3.3 |
The A Bus (primary loads) Contactor Connect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
loadLVD1DisconnectVoltage |
1.3.6.1.4.1.12148.7.4.3.4 |
The A Bus (primary loads) Contactor Disconnect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
loadLVD2EnableStatus |
1.3.6.1.4.1.12148.7.4.3.5 |
The status of contactors configuration. 'enabled' means that the contactor is i n use.
'disabled' means that the contactor is disconfigured and not in use. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
loadLVD2Status |
1.3.6.1.4.1.12148.7.4.3.6 |
The B Bus (secondary loads) Contactor is closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
connect(0), disconnect(1), disable(2) |
|
loadLVD2ConnectVoltage |
1.3.6.1.4.1.12148.7.4.3.7 |
The B Bus (secondary loads) Contactor Connect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
loadLVD2DisconnectVoltage |
1.3.6.1.4.1.12148.7.4.3.8 |
The B Bus (secondary loads) Contactor Disconnect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
loadLVD3EnableStatus |
1.3.6.1.4.1.12148.7.4.3.9 |
The status of contactors configuration. 'enabled' means that the contactor is i n use.
'disabled' means that the contactor is disconfigured and not in use. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1) |
|
loadLVD3Status |
1.3.6.1.4.1.12148.7.4.3.10 |
The C Bus (critical loads) Contactor is closed(0) or open(1) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
connect(0), disconnect(1), disable(2) |
|
loadLVD3ConnectVoltage |
1.3.6.1.4.1.12148.7.4.3.11 |
The C Bus (critical loads) Contactor Connect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
loadLVD3DisconnectVoltage |
1.3.6.1.4.1.12148.7.4.3.12 |
The C Bus (critical loads) Contactor Disconnect Voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..7200 |
|
rectifierRectifiersActive |
1.3.6.1.4.1.12148.7.5.2 |
The actual number of active rectifiers in this DC Power System. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..101 |
|
rectifierUtilization |
1.3.6.1.4.1.12148.7.5.4 |
Utilization in % of available rectifier capacity |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..100 |
|
rectifierStatusNoIndex |
1.3.6.1.4.1.12148.7.5.5.1 |
A starting index for the rectifierStatusTable array |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..20 |
|
rectifierStatusTable |
1.3.6.1.4.1.12148.7.5.5.2 |
A table listing up to sixteen sequential recifiers, starting
from the rectifier number specified by rectifierStatusNoIndex |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
RectifierStatusEntry |
|
rectifierStatusEntry |
1.3.6.1.4.1.12148.7.5.5.2.1 |
A row of rectifier status data corresponding to the rectifierStatusNoIndex value |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
RectifierStatusEntry |
|
|
rectifierStatusID |
1.3.6.1.4.1.12148.7.5.5.2.1.1 |
The rectifier ID number of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..100 |
|
rectifierStatusStatus |
1.3.6.1.4.1.12148.7.5.5.2.1.2 |
The operational status of the rectifier record.
absent (0),
active (1),
failed (2),
walkin (3),
disabledbycommand (4)
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
absent(0), active(1), failed(2), walkin(3), disabledbycommand(4) |
|
rectifierStatusTemp |
1.3.6.1.4.1.12148.7.5.5.2.1.5 |
The heatsink temperature of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..65535 |
|
rectifierStatusType |
1.3.6.1.4.1.12148.7.5.5.2.1.6 |
The rectifier article number string of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
rectifierStatusSKU |
1.3.6.1.4.1.12148.7.5.5.2.1.7 |
The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
rectifierStatusSerialNo |
1.3.6.1.4.1.12148.7.5.5.2.1.8 |
The rectifier serial number string of the rectifier record. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..16) |
|
acVoltage1 |
1.3.6.1.4.1.12148.7.6.1 |
The AC Voltage of phase 1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
acVoltage2 |
1.3.6.1.4.1.12148.7.6.2 |
The AC Voltage of phase 2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
acVoltage3 |
1.3.6.1.4.1.12148.7.6.3 |
The AC Voltage of phase 3 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
alarmMajorHighBattVolt |
1.3.6.1.4.1.12148.7.7.1.1 |
The Very High Battery Voltage Alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMinorHighBattVolt |
1.3.6.1.4.1.12148.7.7.1.2 |
The High Battery Voltage alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMajorLowBattVolt |
1.3.6.1.4.1.12148.7.7.1.3 |
The Very Low Battery Voltage Alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMinorLowBattVolt |
1.3.6.1.4.1.12148.7.7.1.4 |
The Low Battery Voltage Alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMajorBatteryHighTemp |
1.3.6.1.4.1.12148.7.7.1.5 |
Temperature much too high alarm, or temperature compensation circuit / probe failure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMinorBatteryHighTemp |
1.3.6.1.4.1.12148.7.7.1.6 |
Temperature much too high alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmBatteryDisconnectOpen |
1.3.6.1.4.1.12148.7.7.1.7 |
The Battery Disconnect Contactor alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmLVD1open |
1.3.6.1.4.1.12148.7.7.1.8 |
The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been
reached and the contactor will release. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmLVD2open |
1.3.6.1.4.1.12148.7.7.1.9 |
The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been
reached and the contactor will release. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmLVD3open |
1.3.6.1.4.1.12148.7.7.1.10 |
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been
reached and the contactor will release.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmACmains |
1.3.6.1.4.1.12148.7.7.1.11 |
The AC voltage has dropped below critical level,
or one or more AC input phases was lost. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmBatteryBreakerOpen |
1.3.6.1.4.1.12148.7.7.1.12 |
Battery string disconnect breaker/fuse alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmDistributionBreakerOpen |
1.3.6.1.4.1.12148.7.7.1.13 |
The Load Distribution breaker/fuse alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMajorRectifier |
1.3.6.1.4.1.12148.7.7.1.14 |
This is a 'multiple rectifiers have failed' alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMinorRectifier |
1.3.6.1.4.1.12148.7.7.1.15 |
This is a 'one rectifier has failed' alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMajorBatteryMidpoint |
1.3.6.1.4.1.12148.7.7.1.16 |
Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmMinorBatteryMidpoint |
1.3.6.1.4.1.12148.7.7.1.17 |
Battery Symmetry (midpoint) Delta Voltage out of limits alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmBatteryLifeEnded |
1.3.6.1.4.1.12148.7.7.1.18 |
The battery capacity has dropped below critical level.
A battery test has measured the fully charged capacity to be too low,
and thus probably the battery lifecycle to be near expired. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmBatteryTestmodeEntered |
1.3.6.1.4.1.12148.7.7.1.19 |
The system has lowered the battery charge voltage in order to discharge the batteries
to a predefinend level. When the criteria for stopping the battery testing is reached, the
charge voltage is increased to commence normal charging. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmBatteryBoostmodeEntered |
1.3.6.1.4.1.12148.7.7.1.20 |
The system has increased the battery charge voltage in order to equalize the
battery cells charging. When the criteria for stopping the battery equalizing is reached,
the charge voltage is lowered to commence normal charging. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable1 |
1.3.6.1.4.1.12148.7.7.1.21 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable2 |
1.3.6.1.4.1.12148.7.7.1.22 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable3 |
1.3.6.1.4.1.12148.7.7.1.23 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable4 |
1.3.6.1.4.1.12148.7.7.1.24 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable5 |
1.3.6.1.4.1.12148.7.7.1.25 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable6 |
1.3.6.1.4.1.12148.7.7.1.26 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable7 |
1.3.6.1.4.1.12148.7.7.1.27 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable8 |
1.3.6.1.4.1.12148.7.7.1.28 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable9 |
1.3.6.1.4.1.12148.7.7.1.29 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable10 |
1.3.6.1.4.1.12148.7.7.1.30 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable11 |
1.3.6.1.4.1.12148.7.7.1.31 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable12 |
1.3.6.1.4.1.12148.7.7.1.32 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable13 |
1.3.6.1.4.1.12148.7.7.1.33 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
alarmUserConfigurable14 |
1.3.6.1.4.1.12148.7.7.1.34 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), alarm(1) |
|
dcSystemTraps |
1.3.6.1.4.1.12148.7.8 |
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs.
Each alarm condition is represented by a Alarm Condition Trap and an associated OFF
Trap, which is optionally transmitted according to the state of OID systemSendOffTrap |
Status: current |
Access: read-only |
NOTIFICATION-GROUP |
|
|
|
alarmMajorHighBattVoltTrap |
1.3.6.1.4.1.12148.7.8.1 |
The Very High Battery Voltage alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMinorHighBattVoltTrap |
1.3.6.1.4.1.12148.7.8.2 |
The High Battery Voltage alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMajorLowBattVoltTrap |
1.3.6.1.4.1.12148.7.8.3 |
The Very Low Battery Voltage Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMinorLowBattVoltTrap |
1.3.6.1.4.1.12148.7.8.4 |
The Low Battery Voltage Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMajorBatteryHighTempTrap |
1.3.6.1.4.1.12148.7.8.5 |
High Battery temperature alarm or
Temperature Compensation circuit / probe failure alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmLVD1openTrap |
1.3.6.1.4.1.12148.7.8.8 |
The A Bus (primary loads) Contactor is open alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmLVD2openTrap |
1.3.6.1.4.1.12148.7.8.9 |
The B Bus (secondary loads) Contactor is open alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmLVD3openTrap |
1.3.6.1.4.1.12148.7.8.10 |
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been
reached and the contactor is released.
|
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmACmainsTrap |
1.3.6.1.4.1.12148.7.8.11 |
The AC voltage has dropped below critical level,
or one or more AC input phases was lost. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmBatteryBreakerOpenTrap |
1.3.6.1.4.1.12148.7.8.12 |
Battery string disconnect breaker/fuse alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMajorRectifierTrap |
1.3.6.1.4.1.12148.7.8.14 |
This is a 'multiple rectifiers have failed' alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMinorRectifierTrap |
1.3.6.1.4.1.12148.7.8.15 |
This is a 'one rectifier has failed' alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMajorBatteryMidpointTrap |
1.3.6.1.4.1.12148.7.8.16 |
Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmMinorBatteryMidpointTrap |
1.3.6.1.4.1.12148.7.8.17 |
Battery Symmetry (midpoint) Delta Voltage out of limits alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmBatteryLifeEndedTrap |
1.3.6.1.4.1.12148.7.8.18 |
The battery capacity has dropped below critical level.
A battery test has measured the fully charged capacity to be too low,
and thus probably the battery lifecycle to be near expired. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmBatteryTestmodeEnteredTrap |
1.3.6.1.4.1.12148.7.8.19 |
The system has lowered the battery charge voltage in order to discharge the batteries
to a predefinend level. When the criteria for stopping the battery testing is reached, the
charge voltage is increased to commence normal charging. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmBatteryBoostmodeEnteredTrap |
1.3.6.1.4.1.12148.7.8.20 |
The system has increased the battery charge voltage in order to equalize the
battery cells charging. When the criteria for stopping the battery equalizing is reached,
the charge voltage is lowered to commence normal charging. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable1Trap |
1.3.6.1.4.1.12148.7.8.21 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable2Trap |
1.3.6.1.4.1.12148.7.8.22 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable3Trap |
1.3.6.1.4.1.12148.7.8.23 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable4Trap |
1.3.6.1.4.1.12148.7.8.24 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable5Trap |
1.3.6.1.4.1.12148.7.8.25 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable6Trap |
1.3.6.1.4.1.12148.7.8.26 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable7Trap |
1.3.6.1.4.1.12148.7.8.27 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable8Trap |
1.3.6.1.4.1.12148.7.8.28 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable9Trap |
1.3.6.1.4.1.12148.7.8.29 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable10Trap |
1.3.6.1.4.1.12148.7.8.30 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable11Trap |
1.3.6.1.4.1.12148.7.8.31 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable12Trap |
1.3.6.1.4.1.12148.7.8.32 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable13Trap |
1.3.6.1.4.1.12148.7.8.33 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
alarmUserConfigurable14Trap |
1.3.6.1.4.1.12148.7.8.34 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB.
User configurable alarms will on some systems have text attached to the traps
that explains the purpose of the alarm. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|