DELL-SNMP-UPS-MIB
File:
DELL-SNMP-UPS-MIB.mib (46883 bytes)
Imported modules
Imported symbols
Defined Types
Defined Values
dell |
1.3.6.1.4.1.674 |
OBJECT IDENTIFIER |
|
|
|
upsdell |
1.3.6.1.4.1.674.10902 |
OBJECT IDENTIFIER |
|
|
|
hardware |
1.3.6.1.4.1.674.10902.2 |
OBJECT IDENTIFIER |
|
|
|
productID |
1.3.6.1.4.1.674.10902.2.100 |
OBJECT IDENTIFIER |
|
|
|
physical |
1.3.6.1.4.1.674.10902.2.120 |
OBJECT IDENTIFIER |
|
|
|
logical |
1.3.6.1.4.1.674.10902.2.130 |
OBJECT IDENTIFIER |
|
|
|
traps |
1.3.6.1.4.1.674.10902.2.140 |
OBJECT IDENTIFIER |
|
|
|
physicalUPS |
1.3.6.1.4.1.674.10902.2.120.4 |
OBJECT IDENTIFIER |
|
|
|
productIDVendor |
1.3.6.1.4.1.674.10902.2.100.3 |
The name of the product manufacturer. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
productIDVersion |
1.3.6.1.4.1.674.10902.2.100.4 |
The version of this product. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
productIDBuildNumber |
1.3.6.1.4.1.674.10902.2.100.5 |
The software build number of the product populating the MIB. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
productIDURL |
1.3.6.1.4.1.674.10902.2.100.6 |
The URL of the web-based application to manage this device, should the device provide one. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
productIDDeviceNetworkName |
1.3.6.1.4.1.674.10902.2.100.7 |
Operating system specific computer name if product SNMP service is hosted. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..32) |
|
productStatusGlobalStatus |
1.3.6.1.4.1.674.10902.2.110.1 |
Current status of the product.
This is a rollup for the entire product including any
monitored devices. The status is intended to give
initiative to an SNMP monitor to get further data when
this status is abnormal. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), unknown(2), ok(3), non-critical(4), critical(5), non-recoverable(6) |
|
productStatusLastGlobalStatus |
1.3.6.1.4.1.674.10902.2.110.2 |
The status before the current status which induced an initiative
to issue a global status change trap. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
productStatusTimeStamp |
1.3.6.1.4.1.674.10902.2.110.3 |
The last time that the SNMP table geometries changed and/or
attribute data was significantly updated. This is to be used by
management applications to trigger a refresh of data acquired
from the MIB. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
TimeStamp |
|
|
productStatusGetTimeOut |
1.3.6.1.4.1.674.10902.2.110.4 |
Suggested time out value in milliseconds for how long the SNMP getter
should wait while attempting to poll the product SNMP service. |
Status: optional |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
productStatusRefreshRate |
1.3.6.1.4.1.674.10902.2.110.5 |
Rate in seconds at which the SNMP service cached data is being updated. |
Status: optional |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
productStatusGeneratingTrapFlag |
1.3.6.1.4.1.674.10902.2.110.6 |
Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps.
This variable can take the following values:
1 True, this service is capable of sending traps and is the originator of SNMP
traps generated for the devices represented in this MIB and is currently generating traps.
2 False, this service not capable of sending traps and is not the originator of
any SNMP traps generated for the devices represented in this MIB.
3 Disabled, this service is capable of sending traps and is the originator of SNMP
traps for the devices represented in this MIB, but traps are currently disabled. |
Status: optional |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
true(1), false(2), disabled(3) |
|
physicalIdentConverterType |
1.3.6.1.4.1.674.10902.2.120.1.3 |
UPS type. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
lineInteractive(1), onLine(2), onLineUnitaryParallel(3), onLineParallelWithNS(4), onLineHotStandbyRedundancy(5) |
|
physicalOutputInstantHeadroom |
1.3.6.1.4.1.674.10902.2.120.2.1 |
This is the present amount of watt capacity remaining before overload. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalOutputPeakHeadroom |
1.3.6.1.4.1.674.10902.2.120.2.2 |
Statistical value holding the lowest value that Instantaneous Headroom
Watts was ever set too since the last time this statistic was reset. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalOutputPeakConsumption |
1.3.6.1.4.1.674.10902.2.120.2.4 |
Statistical value of the maximum RMS Watts the UPS has seen since
the last time this statistic was reset. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalOutputPresentConsumption |
1.3.6.1.4.1.674.10902.2.120.2.6 |
Derived by averaging the watt second consumption over the past hour.
Use an array of 60 words to store the average watt seconds consumed over
the last minute then after you have a full hours worth of data in the 60
word array, average those values to get your Present KWH Consumption meter.
Then every minute after that update the oldest value in the array, average
again and update the meter.
Value is 0 until the minimum 1 hour of data has been accumulated. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalOutputCumulativeConsumption |
1.3.6.1.4.1.674.10902.2.120.2.7 |
64 bit meter value that is derived by reading the Present KWH Consumption meter
once per hour and adding it to the last value of this meter. Value accumulates
until it is reset from the LCD or via the SHUT protocol or the meter rolls over. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalOutputVA |
1.3.6.1.4.1.674.10902.2.120.2.9 |
Output VA. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalRectifierPosVoltage |
1.3.6.1.4.1.674.10902.2.120.3.1 |
DC bus positive voltage. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalRectifierNegVoltage |
1.3.6.1.4.1.674.10902.2.120.3.2 |
DC bus negative voltage. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalUPSDateTime |
1.3.6.1.4.1.674.10902.2.120.4.1 |
Real Time Clock with Date and Time. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
TimeStamp |
|
|
physicalUPSAlarmsStatus |
1.3.6.1.4.1.674.10902.2.120.4.2 |
List of traps that are in active mode. This list is coded in ASCI format
and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps
are listed. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
physicalUPSRuntimeToShutdown |
1.3.6.1.4.1.674.10902.2.120.4.3 |
Number of seconds remaining until UPS will receive a ShutdownAfterDelay command.
2147483647 if no countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalUPSOutpoutSwitchable |
1.3.6.1.4.1.674.10902.2.120.4.4 |
Parameter to enable or not remote UPS commands coming from all communication ports. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
switchable(1), notSwitchable(2) |
|
physicalBatteryABMStatus |
1.3.6.1.4.1.674.10902.2.120.5.1 |
Advanced Battery Monitoring satus. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
abmCharging(1), abmDischarging(2), abmFloating(3), abmResting(4), abmOff(5) |
|
physicalBatteryTestStatus |
1.3.6.1.4.1.674.10902.2.120.5.2 |
Battery test satus. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestIniated(6), testScheduled(7) |
|
physicalBatterySecondsRemaining |
1.3.6.1.4.1.674.10902.2.120.5.3 |
Battery remaining time calculated by the autonometer. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment1ShutdownAfterDelay |
1.3.6.1.4.1.674.10902.2.120.6.1 |
Number of seconds remaining until load segment 1 will switch off.
-1 if no shutdown countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment1StartupAfterDelay |
1.3.6.1.4.1.674.10902.2.120.6.2 |
Number of seconds remaining until load segment 1 will switch on.
-1 if no startup countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment2ShutdownAfterDelay |
1.3.6.1.4.1.674.10902.2.120.6.3 |
Number of seconds remaining until load segment 2 will switch off.
-1 if no shutdown countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment2StartupAfterDelay |
1.3.6.1.4.1.674.10902.2.120.6.4 |
Number of seconds remaining until load segment 2 will switch on.
-1 if no startup countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment1RuntimeToShutdown |
1.3.6.1.4.1.674.10902.2.120.6.5 |
Number of seconds remaining until load segment 1 will receive a
ShutdownAfterDelay command. 2147483647 if no countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalLoadSegment2RuntimeToShutdown |
1.3.6.1.4.1.674.10902.2.120.6.6 |
Number of seconds remaining until load segment 2 will receive a
ShutdownAfterDelay command. 2147483647 if no countdown is in effect. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
physicalEnvironmentSensorPresent |
1.3.6.1.4.1.674.10902.2.120.7.1 |
Informations, if there is Environment Measurement Probe connected. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
trapOnBuck |
7 |
On Buck / Input Voltage Reducer. |
TRAP-TYPE |
|
|
|
trapOnBoost |
9 |
On Boost / Input Voltage Booster. |
TRAP-TYPE |
|
|
|