DELL-SNMP-UPS-MIB

File: DELL-SNMP-UPS-MIB.mib (46883 bytes)

Imported modules

RFC1155-SMI SNMPv2-TC RFC-1212
RFC-1215

Imported symbols

enterprises TimeStamp DisplayString
OBJECT-TYPE TRAP-TYPE

Defined Types

PhysicalEnvironmentInputEntry  
SEQUENCE    
  physicalEnvironmentInputIndex INTEGER
  physicalEnvironmentInputName DisplayString
  physicalEnvironmentInputState INTEGER
  physicalEnvironmentInputOpenedState DisplayString
  physicalEnvironmentInputClosedState DisplayString

Defined Values

dell 1.3.6.1.4.1.674
OBJECT IDENTIFIER    

upsdell 1.3.6.1.4.1.674.10902
OBJECT IDENTIFIER    

hardware 1.3.6.1.4.1.674.10902.2
OBJECT IDENTIFIER    

productID 1.3.6.1.4.1.674.10902.2.100
OBJECT IDENTIFIER    

productStatus 1.3.6.1.4.1.674.10902.2.110
OBJECT IDENTIFIER    

physical 1.3.6.1.4.1.674.10902.2.120
OBJECT IDENTIFIER    

logical 1.3.6.1.4.1.674.10902.2.130
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.674.10902.2.140
OBJECT IDENTIFIER    

physicalIdent 1.3.6.1.4.1.674.10902.2.120.1
OBJECT IDENTIFIER    

physicalOutput 1.3.6.1.4.1.674.10902.2.120.2
OBJECT IDENTIFIER    

physicalRectifier 1.3.6.1.4.1.674.10902.2.120.3
OBJECT IDENTIFIER    

physicalUPS 1.3.6.1.4.1.674.10902.2.120.4
OBJECT IDENTIFIER    

physicalBattery 1.3.6.1.4.1.674.10902.2.120.5
OBJECT IDENTIFIER    

physicalLoadSegment 1.3.6.1.4.1.674.10902.2.120.6
OBJECT IDENTIFIER    

physicalEnvironment 1.3.6.1.4.1.674.10902.2.120.7
OBJECT IDENTIFIER    

productIDDisplayName 1.3.6.1.4.1.674.10902.2.100.1
Name of this product for display purposes.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

productIDDescription 1.3.6.1.4.1.674.10902.2.100.2
A short description of this product.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productIDVendor 1.3.6.1.4.1.674.10902.2.100.3
The name of the product manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productIDVersion 1.3.6.1.4.1.674.10902.2.100.4
The version of this product.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productIDBuildNumber 1.3.6.1.4.1.674.10902.2.100.5
The software build number of the product populating the MIB.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productIDURL 1.3.6.1.4.1.674.10902.2.100.6
The URL of the web-based application to manage this device, should the device provide one.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productIDDeviceNetworkName 1.3.6.1.4.1.674.10902.2.100.7
Operating system specific computer name if product SNMP service is hosted.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

productStatusGlobalStatus 1.3.6.1.4.1.674.10902.2.110.1
Current status of the product. This is a rollup for the entire product including any monitored devices. The status is intended to give initiative to an SNMP monitor to get further data when this status is abnormal.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), unknown(2), ok(3), non-critical(4), critical(5), non-recoverable(6)  

productStatusLastGlobalStatus 1.3.6.1.4.1.674.10902.2.110.2
The status before the current status which induced an initiative to issue a global status change trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

productStatusTimeStamp 1.3.6.1.4.1.674.10902.2.110.3
The last time that the SNMP table geometries changed and/or attribute data was significantly updated. This is to be used by management applications to trigger a refresh of data acquired from the MIB.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

productStatusGetTimeOut 1.3.6.1.4.1.674.10902.2.110.4
Suggested time out value in milliseconds for how long the SNMP getter should wait while attempting to poll the product SNMP service.
Status: optional Access: read-only
OBJECT-TYPE    
  INTEGER  

productStatusRefreshRate 1.3.6.1.4.1.674.10902.2.110.5
Rate in seconds at which the SNMP service cached data is being updated.
Status: optional Access: read-only
OBJECT-TYPE    
  INTEGER  

productStatusGeneratingTrapFlag 1.3.6.1.4.1.674.10902.2.110.6
Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps. This variable can take the following values: 1 True, this service is capable of sending traps and is the originator of SNMP traps generated for the devices represented in this MIB and is currently generating traps. 2 False, this service not capable of sending traps and is not the originator of any SNMP traps generated for the devices represented in this MIB. 3 Disabled, this service is capable of sending traps and is the originator of SNMP traps for the devices represented in this MIB, but traps are currently disabled.
Status: optional Access: read-only
OBJECT-TYPE    
  INTEGER true(1), false(2), disabled(3)  

physicalIdentFamilyName 1.3.6.1.4.1.674.10902.2.120.1.1
UPS Family name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

physicalIdentSerialNumber 1.3.6.1.4.1.674.10902.2.120.1.2
UPS Serial number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

physicalIdentConverterType 1.3.6.1.4.1.674.10902.2.120.1.3
UPS type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER lineInteractive(1), onLine(2), onLineUnitaryParallel(3), onLineParallelWithNS(4), onLineHotStandbyRedundancy(5)  

physicalIdentReferenceNumber 1.3.6.1.4.1.674.10902.2.120.1.4
Technical Reference of UPS firmware.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

physicalOutputInstantHeadroom 1.3.6.1.4.1.674.10902.2.120.2.1
This is the present amount of watt capacity remaining before overload.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalOutputPeakHeadroom 1.3.6.1.4.1.674.10902.2.120.2.2
Statistical value holding the lowest value that Instantaneous Headroom Watts was ever set too since the last time this statistic was reset.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalOutputPeakHeadroomTimestamp 1.3.6.1.4.1.674.10902.2.120.2.3
Time and date stamp of the last time the Peak Headroom Watts value was updated.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

physicalOutputPeakConsumption 1.3.6.1.4.1.674.10902.2.120.2.4
Statistical value of the maximum RMS Watts the UPS has seen since the last time this statistic was reset.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalOutputPeakConsumptionTimestamp 1.3.6.1.4.1.674.10902.2.120.2.5
Time and date stamp of the last time the Peak Consumption Watts value was updated.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

physicalOutputPresentConsumption 1.3.6.1.4.1.674.10902.2.120.2.6
Derived by averaging the watt second consumption over the past hour. Use an array of 60 words to store the average watt seconds consumed over the last minute then after you have a full hours worth of data in the 60 word array, average those values to get your Present KWH Consumption meter. Then every minute after that update the oldest value in the array, average again and update the meter. Value is 0 until the minimum 1 hour of data has been accumulated.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalOutputCumulativeConsumption 1.3.6.1.4.1.674.10902.2.120.2.7
64 bit meter value that is derived by reading the Present KWH Consumption meter once per hour and adding it to the last value of this meter. Value accumulates until it is reset from the LCD or via the SHUT protocol or the meter rolls over.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalOutputCumulativeConsumptionTimestamp 1.3.6.1.4.1.674.10902.2.120.2.8
Time and date stamp of last time this meter value was reset.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

physicalOutputVA 1.3.6.1.4.1.674.10902.2.120.2.9
Output VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalRectifierPosVoltage 1.3.6.1.4.1.674.10902.2.120.3.1
DC bus positive voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalRectifierNegVoltage 1.3.6.1.4.1.674.10902.2.120.3.2
DC bus negative voltage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalUPSDateTime 1.3.6.1.4.1.674.10902.2.120.4.1
Real Time Clock with Date and Time.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeStamp  

physicalUPSAlarmsStatus 1.3.6.1.4.1.674.10902.2.120.4.2
List of traps that are in active mode. This list is coded in ASCI format and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps are listed.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

physicalUPSRuntimeToShutdown 1.3.6.1.4.1.674.10902.2.120.4.3
Number of seconds remaining until UPS will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalUPSOutpoutSwitchable 1.3.6.1.4.1.674.10902.2.120.4.4
Parameter to enable or not remote UPS commands coming from all communication ports.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER switchable(1), notSwitchable(2)  

physicalBatteryABMStatus 1.3.6.1.4.1.674.10902.2.120.5.1
Advanced Battery Monitoring satus.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER abmCharging(1), abmDischarging(2), abmFloating(3), abmResting(4), abmOff(5)  

physicalBatteryTestStatus 1.3.6.1.4.1.674.10902.2.120.5.2
Battery test satus.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestIniated(6), testScheduled(7)  

physicalBatterySecondsRemaining 1.3.6.1.4.1.674.10902.2.120.5.3
Battery remaining time calculated by the autonometer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment1ShutdownAfterDelay 1.3.6.1.4.1.674.10902.2.120.6.1
Number of seconds remaining until load segment 1 will switch off. -1 if no shutdown countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment1StartupAfterDelay 1.3.6.1.4.1.674.10902.2.120.6.2
Number of seconds remaining until load segment 1 will switch on. -1 if no startup countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment2ShutdownAfterDelay 1.3.6.1.4.1.674.10902.2.120.6.3
Number of seconds remaining until load segment 2 will switch off. -1 if no shutdown countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment2StartupAfterDelay 1.3.6.1.4.1.674.10902.2.120.6.4
Number of seconds remaining until load segment 2 will switch on. -1 if no startup countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment1RuntimeToShutdown 1.3.6.1.4.1.674.10902.2.120.6.5
Number of seconds remaining until load segment 1 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalLoadSegment2RuntimeToShutdown 1.3.6.1.4.1.674.10902.2.120.6.6
Number of seconds remaining until load segment 2 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentSensorPresent 1.3.6.1.4.1.674.10902.2.120.7.1
Informations, if there is Environment Measurement Probe connected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentSensorName 1.3.6.1.4.1.674.10902.2.120.7.2
User name of EMP.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..59)  

physicalEnvironmentValues 1.3.6.1.4.1.674.10902.2.120.7.3
OBJECT IDENTIFIER    

physicalEnvironmentValuesTemperatureUnit 1.3.6.1.4.1.674.10902.2.120.7.3.1
Temperature unit setting.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

physicalEnvironmentValuesTemperature 1.3.6.1.4.1.674.10902.2.120.7.3.2
Current temperature value in 0.1 degree Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesHumidity 1.3.6.1.4.1.674.10902.2.120.7.3.3
Current humidity value in 0.1 percents.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesTemperatureLow 1.3.6.1.4.1.674.10902.2.120.7.3.4
Temperature low threshhold in units of degree Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesTemperatureHigh 1.3.6.1.4.1.674.10902.2.120.7.3.5
Temperature high threshhold in units of degree Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesTemperatureHysteresis 1.3.6.1.4.1.674.10902.2.120.7.3.6
Temperature hysteresis in units of degree Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValueshHumidityLow 1.3.6.1.4.1.674.10902.2.120.7.3.7
Humidity low threshhold in percents.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesHumidityHigh 1.3.6.1.4.1.674.10902.2.120.7.3.8
Humidity high threshhold in percents.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentValuesHumidityHysteresis 1.3.6.1.4.1.674.10902.2.120.7.3.9
Humidity hysteresis in percents.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

physicalEnvironmentInputTable 1.3.6.1.4.1.674.10902.2.120.7.4
The table containins dry contact inputs information.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PhysicalEnvironmentInputEntry

physicalEnvironmentInputEntry 1.3.6.1.4.1.674.10902.2.120.7.4.1
The description of an entry in the table.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PhysicalEnvironmentInputEntry  

physicalEnvironmentInputIndex 1.3.6.1.4.1.674.10902.2.120.7.4.1.1
The input index, ranging from 1 to 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

physicalEnvironmentInputName 1.3.6.1.4.1.674.10902.2.120.7.4.1.2
The input user-friendly name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..27)  

physicalEnvironmentInputState 1.3.6.1.4.1.674.10902.2.120.7.4.1.3
Current state of input.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER opened(1), closed(2)  

physicalEnvironmentInputOpenedState 1.3.6.1.4.1.674.10902.2.120.7.4.1.4
The input opened state user-friendly name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..21)  

physicalEnvironmentInputClosedState 1.3.6.1.4.1.674.10902.2.120.7.4.1.5
The input closed state user-friendly name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..21)  

trapInverterOverVoltage 1
Inverter AC over voltage.
TRAP-TYPE    

trapInverterOverVoltageOk 2
Inverter AC over voltage ok.
TRAP-TYPE    

trapInverterUnderVoltage 3
Inverter AC under voltage.
TRAP-TYPE    

trapInverterUnderVoltageOk 4
Inverter AC under voltage ok.
TRAP-TYPE    

trapBypassFrequencyOutOfRange 5
Bypass under or over frequency.
TRAP-TYPE    

trapBypassFrequencyOutOfRangeOk 6
Bypass under or over frequency ok.
TRAP-TYPE    

trapOnBuck 7
On Buck / Input Voltage Reducer.
TRAP-TYPE    

trapReturnFromBuck 8
Return from Buck.
TRAP-TYPE    

trapOnBoost 9
On Boost / Input Voltage Booster.
TRAP-TYPE    

trapReturnFromBoost 10
Return from Boost.
TRAP-TYPE    

trapInputOverVoltage 11
Input AC over voltage.
TRAP-TYPE    

trapInputOverVoltageOk 12
Input AC over voltage ok.
TRAP-TYPE    

trapInputUnderVoltage 13
Input AC under voltage.
TRAP-TYPE    

trapInputUnderVoltageOk 14
Input AC under voltage ok.
TRAP-TYPE    

trapInputFrequencyOutOfRange 15
Input under or over frequency.
TRAP-TYPE    

trapInputFrequencyOutOfRangeOk 16
Input under or over frequency ok.
TRAP-TYPE    

trapRemoteEmergencyPowerOff 17
Remote emergency power off.
TRAP-TYPE    

trapReturnFromEmergencyPowerOff 18
Return from remote emergency power off.
TRAP-TYPE    

trapLevel1Overload 19
Output Level 1 overload.
TRAP-TYPE    

trapLevel1OverloadOk 20
Output Level 1 overload ok.
TRAP-TYPE    

trapLevel2Overload 21
Level 2 overload.
TRAP-TYPE    

trapLevel2OverloadOk 22
Level 2 overload ok.
TRAP-TYPE    

trapLevel3Overload 23
Level 3 overload.
TRAP-TYPE    

trapLevel3OverloadOk 24
Level 3 overload ok.
TRAP-TYPE    

trapPosDCLinkOverVoltage 25
Positive DC link over voltage.
TRAP-TYPE    

trapPosDCLinkOverVoltageOk 26
Positive DC link over voltage ok.
TRAP-TYPE    

trapPosDCLinkUnderVoltage 27
Positive DC link under voltage.
TRAP-TYPE    

trapPosDCLinkUnderVoltageOk 28
Positive DC link under voltage ok.
TRAP-TYPE    

trapNegDCLinkOverVoltage 29
Negative DC link over voltage.
TRAP-TYPE    

trapNegDCLinkOverVoltageOk 30
Negative DC link over voltage ok.
TRAP-TYPE    

trapNegDCLinkUnderVoltage 31
Negative DC link under voltage.
TRAP-TYPE    

trapNegDCLinkUnderVoltageOk 32
Negative DC link under voltage ok.
TRAP-TYPE    

trapRectifierFault 33
Rectifier fault.
TRAP-TYPE    

trapRectifierOk 34
Rectifier ok.
TRAP-TYPE    

trapInverterFault 35
Inverter fault.
TRAP-TYPE    

trapInverterOk 36
Inverter ok.
TRAP-TYPE    

trapChargerFailure 37
Charger failure.
TRAP-TYPE    

trapChargerOk 38
Charger ok.
TRAP-TYPE    

trapEepromFailure 39
EEPROM failure.
TRAP-TYPE    

trapEepromOk 40
EEPROM off.
TRAP-TYPE    

trapShutdownImminent 41
Shutdown imminent.
TRAP-TYPE    

trapShutdownImminentOver 42
Shutdown imminent over.
TRAP-TYPE    

trapBatteryLow 43
Battery low.
TRAP-TYPE    

trapBatteryOk 44
Battery ok.
TRAP-TYPE    

trapOutputShortCircuit 45
Output short circuit.
TRAP-TYPE    

trapOutputReturnFromShortCircuit 46
Output return from short circuit.
TRAP-TYPE    

trapUtilityNotPresent 47
Utility not present.
TRAP-TYPE    

trapUtilityPresent 48
Utility present.
TRAP-TYPE    

trapBatteryOverVoltage 49
Battery DC over voltage.
TRAP-TYPE    

trapBatteryOverVoltageOk 50
Battery DC over voltage ok.
TRAP-TYPE    

trapHeatsinkOvertemperature 51
Heatsink overtemperature.
TRAP-TYPE    

trapHeatsinkOvertemperatureOk 52
Heatsink overtemperature ok.
TRAP-TYPE    

trapBypassNotAvailable 53
Bypass not available.
TRAP-TYPE    

trapBypassNotAvailableOk 54
Bypass not available ok.
TRAP-TYPE    

trapOnManualBypass 55
On manual/ maintenance bypass.
TRAP-TYPE    

trapUPSOnBattery 57
UPS on battery.
TRAP-TYPE    

trapUPSReturnFromBattery 58
UPS return from battery.
TRAP-TYPE    

trapUPSOnBypass 59
UPS on bypass.
TRAP-TYPE    

trapUPSReturnFromBypass 60
UPS return from bypass.
TRAP-TYPE    

trapBatteryTestInProgress 61
Battery manual or automatic test in progress.
TRAP-TYPE    

trapBatteryTestDone 62
Battery test done.
TRAP-TYPE    

trapBatteryNeedReplacement 63
Battery test failed, battery needs to be replaced.
TRAP-TYPE    

trapBatteryReplacementDone 64
Battery replacement done.
TRAP-TYPE    

trapFanFailure 65
Fan failure.
TRAP-TYPE    

trapFanOk 66
Fan ok.
TRAP-TYPE    

trapSiteWiringFault 67
Site wiring fault.
TRAP-TYPE    

trapSiteWiringOk 68
Site wiring ok.
TRAP-TYPE    

trapBatteryDisconnected 69
Batteries disconnected.
TRAP-TYPE    

trapBatteryConnected 70
Batteries connected.
TRAP-TYPE    

trapUPSOff 71
UPS off.
TRAP-TYPE    

trapUPSOn 72
UPS on.
TRAP-TYPE    

trapDCLinkImbalance 73
DC link imbalance.
TRAP-TYPE    

trapDCLinkImbalanceOk 74
DC link imbalance ok.
TRAP-TYPE    

trapABMOn 79
ABM state on.
TRAP-TYPE    

trapABMOff 80
ABM state off.
TRAP-TYPE    

trapLoadSegment1Off 81
Load segment 1 off.
TRAP-TYPE    

trapLoadSegment1On 82
Load segment 1 on.
TRAP-TYPE    

trapLoadSegment2Off 83
Load segment 2 off.
TRAP-TYPE    

trapLoadSegment2On 84
Load segment 2 on.
TRAP-TYPE    

trapInHighEfficiencyMode 85
In High Efficiency mode.
TRAP-TYPE    

trapReturnFromHighEfficiencyMode 86
Return from High Efficiency mode.
TRAP-TYPE    

trapRectifierOverload 87
Rectifier input over current.
TRAP-TYPE    

trapRectifierOverloadOk 88
Rectifier current ok.
TRAP-TYPE    

trapInverterOverload 89
Inverter output over current.
TRAP-TYPE    

trapInverterOverloadOk 90
Inverter output current ok.
TRAP-TYPE    

trapBypassVoltageOutOfRange 91
Bypass AC under or over voltage.
TRAP-TYPE    

trapBypassVoltageOutOfRangeOk 92
Bypass AC under or over voltage ok.
TRAP-TYPE    

trapServiceBattery 93
Service battery.
TRAP-TYPE    

trapToBypassCommand 94
UPS received command to switch on bypass.
TRAP-TYPE    

trapFromBypassCommand 95
UPS received command to switch on inverter.
TRAP-TYPE    

trapCommunicationLost 96
Lost communication with UPS, HID databasis is not updated.
TRAP-TYPE    

trapCommunicationRestored 97
Communication restored with UPS, HID databasis is updated.
TRAP-TYPE    

trapEnvironComFailure 98
Environment Probe communication failure.
TRAP-TYPE    

trapEnvironComOK 99
Environment Probe communication restored.
TRAP-TYPE    

trapEnvironTemperatureLow 100
Temperature is below low threshold.
TRAP-TYPE    

trapEnvironTemperatureHigh 102
Temperature is above high threshold.
TRAP-TYPE    

trapEnvironTemperatureOK 103
Temperature is in normal range.
TRAP-TYPE    

trapEnvironHumidityLow 104
Humidity is below low threshold.
TRAP-TYPE    

trapEnvironHumidityHigh 106
Humidity is above high threshold.
TRAP-TYPE    

trapEnvironHumidityOK 107
Humidity is in normal range.
TRAP-TYPE    

trapEnvironInput1Closed 108
Input #1 is Closed.
TRAP-TYPE    

trapEnvironInput1Open 109
Input #1 is Open.
TRAP-TYPE    

trapEnvironInput2Closed 110
Input #2 is Closed.
TRAP-TYPE    

trapEnvironInput2Open 111
Input #2 is Open.
TRAP-TYPE