CPQUPS-MIB
File:
CPQUPS-MIB.mib (24215 bytes)
Imported modules
Imported symbols
Defined Types
CpqUpsOsCommonModuleEntry |
|
SEQUENCE |
|
|
|
|
cpqUpsOsCommonModuleIndex |
INTEGER |
|
|
cpqUpsOsCommonModuleName |
DisplayString |
|
|
cpqUpsOsCommonModuleVersion |
DisplayString |
|
|
cpqUpsOsCommonModuleDate |
OCTET STRING |
|
|
cpqUpsOsCommonModulePurpose |
DisplayString |
|
CpqUpsMemberEntry |
|
SEQUENCE |
|
|
|
|
cpqUpsMemberIndex |
INTEGER |
|
|
cpqUpsMemberName |
DisplayString |
|
|
cpqUpsMemberCommunityStr |
DisplayString |
|
Defined Values
cpqUps |
1.3.6.1.4.1.232.12 |
OBJECT IDENTIFIER |
|
|
|
cpqUpsMibRevMajor |
1.3.6.1.4.1.232.12.1.1 |
The Major Revision level of the MIB.
A change in the major revision level represents a major change in
the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information
supported and/or the meaning of the supported information,
correct interpretation of data may require a MIB document with
the same major revision level. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..65535 |
|
cpqUpsMibRevMinor |
1.3.6.1.4.1.232.12.1.2 |
The Minor Revision level of the MIB.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
cpqUpsMibCondition |
1.3.6.1.4.1.232.12.1.3 |
The overall condition.
This object represents the overall status of the UPS system
represented by this MIB. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), ok(2), degraded(3), failed(4) |
|
cpqUpsOsCommonPollFreq |
1.3.6.1.4.1.232.12.2.1.4.1 |
The Insight Agent's polling frequency.
The frequency, in seconds, at which the Insight Agent requests
information from the device driver. A frequency of zero (0)
indicates that the Insight Agent retrieves the information upon
request of a management station, it does not poll the device
driver at a specific interval.
If the poll frequency is zero (0) all attempts to write to this
object will fail. If the poll frequency is non-zero,
setting this value will change the polling frequency of the
Insight Agent. Setting the poll frequency to zero (0) will
always fail, an agent may also choose to fail any request to
change the poll frequency to a value that would severely impact
system performance. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
cpqUpsOsCommonModuleEntry |
1.3.6.1.4.1.232.12.2.1.4.2.1 |
A description of a software module that provides an interface
to the device this MIB describes. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
CpqUpsOsCommonModuleEntry |
|
|
cpqUpsOsCommonModuleIndex |
1.3.6.1.4.1.232.12.2.1.4.2.1.1 |
A unique index for this module description. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..255 |
|
cpqUpsOsCommonModuleVersion |
1.3.6.1.4.1.232.12.2.1.4.2.1.3 |
The module version in XX.YY format.
Where XX is the major version number and YY is the minor version
number. This field will be a null (size 0) string if the agent
cannot provide the module version. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..5) |
|
cpqUpsOsCommonModuleDate |
1.3.6.1.4.1.232.12.2.1.4.2.1.4 |
The module date.
field octets contents range
===== ====== ======= =====
1 1-2 year 0..65536
2 3 month 1..12
3 4 day 1..31
4 5 hour 0..23
5 6 minute 0..59
6 7 second 0..60
(use 60 for leap-second)
This field will be set to year = 0 if the agent cannot provide
the module date. The hour, minute, and second field will be set
to zero (0) if they are not relevant. The year field is set
with the most significant octet first. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OCTET STRING |
Size(7) |
|
cpqUpsLineStatus |
1.3.6.1.4.1.232.12.2.2.1 |
The status of the AC line input to the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), ok(2), failed(4) |
|
cpqUpsName |
1.3.6.1.4.1.232.12.2.2.2 |
The UPS name (type). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..20) |
|
cpqUpsEstimatedBatteryLife |
1.3.6.1.4.1.232.12.2.2.3 |
The estimated time, in minutes, of battery power available.
The value will be negative one (-1) if the agent is unable to
determine this information. A UPS may not provide this
information when AC power is available. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
cpqUpsAutoShutdownDelay |
1.3.6.1.4.1.232.12.2.2.4 |
The number of minutes of battery power remaining before the UPS
driver will begin a graceful shutdown of the OS.
A value of -1 indicates that no automatic shutdown will occur. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
cpqUpsLaunchCommand |
1.3.6.1.4.1.232.12.2.2.5 |
Application to launch for UPS support. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OCTET STRING |
Size(0..250) |
|
cpqUpsAlarm |
1.3.6.1.4.1.232.12.2.2.6 |
This variable contains the UPS alarm text. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..250) |
|
cpqUpsMemberTable |
1.3.6.1.4.1.232.12.2.3.1 |
A table of entries that describes the family of rack-mounted
servers that a single UPS supports. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
CpqUpsMemberEntry |
|
cpqUpsMemberEntry |
1.3.6.1.4.1.232.12.2.3.1.1 |
A table of entries that describes the family of rack-mounted
servers that a single UPS supports. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
CpqUpsMemberEntry |
|
|
cpqUpsMemberIndex |
1.3.6.1.4.1.232.12.2.3.1.1.1 |
A unique index for this module description. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..255 |
|
cpqUpsMemberName |
1.3.6.1.4.1.232.12.2.3.1.1.2 |
The name or address of one of the individual servers
that is served by the rack-mounted UPS. Set cpqUpsMemberName
to 0 to delete this row. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
cpqUpsAddMemberName |
1.3.6.1.4.1.232.12.2.3.2 |
To add a row to the cpqUpsMemberTable, this variable must
be set, followed immediately by the set of the
cpqUpsAddMemberCommunityStr. Sets must occur in this order,
or else a new row will not be added to the table. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
cpqUpsLineFailed |
12001 |
AC Line power failure.
The UPS reports that the AC line power has failed. |
TRAP-TYPE |
|
|
|
cpqUpsLineOk |
12002 |
AC line power ok.
The UPS reports that the AC line power has returned. |
TRAP-TYPE |
|
|
|
cpqUpsShutdown |
12003 |
UPS initiating graceful server shutdown.
The UPS software is initiating a graceful server shutdown.
Every attempt to preserve the state of the file system
will be made. The server shutdown will be initiated due to
a power anomaly. |
TRAP-TYPE |
|
|
|
cpqUpsConfirmation |
12004 |
Server now operational after power down.
This server has previously been shutdown due to a power
anomaly and has just become operational again. |
TRAP-TYPE |
|
|
|
cpqUpsBatteryLow |
12005 |
UPS Battery Low. The server will soon lose power. |
TRAP-TYPE |
|
|
|
cpqUps2LineFailed |
12006 |
AC Line power failure.
The UPS reports that the AC line power has failed. |
TRAP-TYPE |
|
|
|
cpqUps2LineOk |
12007 |
AC line power ok.
The UPS reports that the AC line power has returned. |
TRAP-TYPE |
|
|
|
cpqUps2Shutdown |
12008 |
UPS initiating graceful server shutdown.
The UPS software is initiating a graceful server shutdown.
Every attempt to preserve the state of the file system
will be made. The server shutdown will be initiated due to
a power anomaly. |
TRAP-TYPE |
|
|
|
cpqUps2Confirmation |
12009 |
Server now operational after power down.
This server has previously been shutdown due to a power
anomaly and has just become operational again. |
TRAP-TYPE |
|
|
|
cpqUpsOverload |
12011 |
The UPS has entered an overload condition. A failure
may occur unless the overload is corrected. |
TRAP-TYPE |
|
|
|