BDFB-MIB

File: BDFB-MIB.mib (11535 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC SNMPv2-CONF

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
Integer32 Counter32 enterprises
mib-2 TEXTUAL-CONVENTION DisplayString
DateAndTime MODULE-COMPLIANCE OBJECT-GROUP
NOTIFICATION-GROUP

Defined Types

BDFBBusEntry  
SEQUENCE    
  bdfbBusIndex INTEGER
  bdfbBusIdentifier DisplayString
  bdfbBusVoltage DisplayString
  bdfbBusCurrent INTEGER

BDFBRelayEntry  
SEQUENCE    
  bdfbRelayIndex INTEGER
  bdfbRelayIdentifier DisplayString
  bdfbRelayStatus INTEGER

Defined Values

bdfbMIB 1.3.6.1.4.1.885.5
Emerson Energy Systems North America(ESNA) mini-BDFB MIB. revision 1.0.0.0
MODULE-IDENTITY    

emersonESNA 1.3.6.1.4.1.885
OBJECT IDENTIFIER    

bdfbInformation 1.3.6.1.4.1.885.5.1
OBJECT IDENTIFIER    

bdfbStatus 1.3.6.1.4.1.885.5.2
OBJECT IDENTIFIER    

bdfbMeasurement 1.3.6.1.4.1.885.5.2.1
OBJECT IDENTIFIER    

bdfbTraps 1.3.6.1.4.1.885.5.3
OBJECT IDENTIFIER    

bdfbGroups 1.3.6.1.4.1.885.5.4
OBJECT IDENTIFIER    

bdfbSystemTraps 1.3.6.1.4.1.885.5.3.0
OBJECT IDENTIFIER    

bdfbBusTypeTraps 1.3.6.1.4.1.885.5.3.1
OBJECT IDENTIFIER    

bdfbBusTraps 1.3.6.1.4.1.885.5.3.1.0
OBJECT IDENTIFIER    

bdfbInformationGroup 1.3.6.1.4.1.885.5.4.1
A collection of objects providing information to identify the BDFB plant and the version of monitoring software.
Status: current Access: read-write
OBJECT-GROUP    

bdfbMeasurementGroup 1.3.6.1.4.1.885.5.4.2
A collection of objects providing BDFB Plant measurements and status.
Status: current Access: read-write
OBJECT-GROUP    

bdfbNotificationsGroup 1.3.6.1.4.1.885.5.4.3
The notifications which indicate BDFB Plant alarms.
Status: current Access: read-write
NOTIFICATION-GROUP    

bdfbMeterPanelVersionNumber 1.3.6.1.4.1.885.5.1.1
Meter Panel Firmware Version Number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbEthernetCardVersionNumber 1.3.6.1.4.1.885.5.1.2
Ethernet Card Firmware Version Number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbIdentifier 1.3.6.1.4.1.885.5.1.3
BDFB Identifier String.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbAverageBusVoltage 1.3.6.1.4.1.885.5.2.1.1
Average Bus Voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbTotalBusCurrent 1.3.6.1.4.1.885.5.2.1.2
Ttotal Bus Current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

bdfbAlarm 1.3.6.1.4.1.885.5.2.1.3
An Alarm Is Active.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER false(0), true(1)  

bdfbBusTable 1.3.6.1.4.1.885.5.2.2
BDFB Bus Table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BDFBBusEntry

bdfbBusEntry 1.3.6.1.4.1.885.5.2.2.1
BDFB Bus Table Entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  BDFBBusEntry  

bdfbBusIndex 1.3.6.1.4.1.885.5.2.2.1.1
BDFB Bus Number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

bdfbBusIdentifier 1.3.6.1.4.1.885.5.2.2.1.2
BDFB Bus Identifier.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbBusVoltage 1.3.6.1.4.1.885.5.2.2.1.3
BDFB Bus Voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbBusCurrent 1.3.6.1.4.1.885.5.2.2.1.4
BDFB Bus Current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

bdfbRelayTable 1.3.6.1.4.1.885.5.2.3
BDFB Relay Table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BDFBRelayEntry

bdfbRelayEntry 1.3.6.1.4.1.885.5.2.3.1
BDFB Relay Table Entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  BDFBRelayEntry  

bdfbRelayIndex 1.3.6.1.4.1.885.5.2.3.1.1
BDFB Relay Number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..4  

bdfbRelayIdentifier 1.3.6.1.4.1.885.5.2.3.1.2
BDFB Relay Identifier String.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

bdfbRelayStatus 1.3.6.1.4.1.885.5.2.3.1.3
BDFB Relay Status String.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

alarmTrapBDFBRelay1 1.3.6.1.4.1.885.5.3.0.1
BDFB Relay 1 Typically Configured as Major Remote.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmTrapBDFBRelay2 1.3.6.1.4.1.885.5.3.0.2
BDFB Relay 2 Typically Configured as Minor Remote.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmTrapBDFBRelay3 1.3.6.1.4.1.885.5.3.0.3
BDFB Relay 3 Typically Configured as Custom Remote.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmTrapBDFBRelay4 1.3.6.1.4.1.885.5.3.0.4
BDFB Relay 4 Typically Configured as Custom Remote.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmTrapBDFBAuxABSFuse 1.3.6.1.4.1.885.5.3.0.5
Auxillary ABS Fuse Trap.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmTrapBDFBCommFail 1.3.6.1.4.1.885.5.3.0.6
Communication failure between ethernet card and main board.
Status: current Access: read-only
NOTIFICATION-TYPE    

trapBusIdentifier 1.3.6.1.4.1.885.5.3.1.0.2
Bus Identifier. This object cannot be accessed. It is used to clarify the source of a Bus trap
Status: current Access: not-accessible
OBJECT-TYPE    
  DisplayString  

trapBDFBBusFuse 1.3.6.1.4.1.885.5.3.1.0.3
BDFB Bus Fuse Alarm.
Status: current Access: not-accessible
NOTIFICATION-TYPE    

trapBDFBBusLowVoltage 1.3.6.1.4.1.885.5.3.1.0.4
BDFB Bus Low Voltage Alarm.
Status: current Access: not-accessible
NOTIFICATION-TYPE    

trapBDFBBusPowerLost 1.3.6.1.4.1.885.5.3.1.0.5
BDFB Bus Power Lost Alarm.
Status: current Access: not-accessible
NOTIFICATION-TYPE    

trapBDFBBusHighCurrent1 1.3.6.1.4.1.885.5.3.1.0.6
BDFB Bus High Current 1 Alarm.
Status: current Access: not-accessible
NOTIFICATION-TYPE    

trapBDFBBusHighCurrent2 1.3.6.1.4.1.885.5.3.1.0.7
BDFB Bus High Current 2 Alarm.
Status: current Access: not-accessible
NOTIFICATION-TYPE