Argus-MIB
File:
Argus-MIB.mib (60680 bytes)
Imported modules
Imported symbols
Defined Types
DcPwrSysRelayEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysRelayIndex |
INTEGER |
|
|
dcPwrSysRelayName |
DisplayString |
|
|
dcPwrSysRelayIntegerValue |
INTEGER |
|
|
dcPwrSysRelayStringValue |
DisplayString |
|
|
dcPwrSysRelaySeverity |
INTEGER |
|
DcPwrSysAnalogOpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysAnalogOpIndex |
INTEGER |
|
|
dcPwrSysAnalogOpName |
DisplayString |
|
|
dcPwrSysAnalogOpIntegerValue |
INTEGER |
|
|
dcPwrSysAnalogOpStringValue |
DisplayString |
|
|
dcPwrSysAnalogOpSeverity |
INTEGER |
|
DcPwrSysRectAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysRectAlrmIndex |
INTEGER |
|
|
dcPwrSysRectAlrmName |
DisplayString |
|
|
dcPwrSysRectAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysRectAlrmStringValue |
DisplayString |
|
|
dcPwrSysRectAlrmSeverity |
INTEGER |
|
DcPwrSysDigAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysDigAlrmIndex |
INTEGER |
|
|
dcPwrSysDigAlrmName |
DisplayString |
|
|
dcPwrSysDigAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysDigAlrmStringValue |
DisplayString |
|
|
dcPwrSysDigAlrmSeverity |
INTEGER |
|
DcPwrSysCurrAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCurrAlrmIndex |
INTEGER |
|
|
dcPwrSysCurrAlrmName |
DisplayString |
|
|
dcPwrSysCurrAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysCurrAlrmStringValue |
DisplayString |
|
|
dcPwrSysCurrAlrmSeverity |
INTEGER |
|
DcPwrSysVoltAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysVoltAlrmIndex |
INTEGER |
|
|
dcPwrSysVoltAlrmName |
DisplayString |
|
|
dcPwrSysVoltAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysVoltAlrmStringValue |
DisplayString |
|
|
dcPwrSysVoltAlrmSeverity |
INTEGER |
|
DcPwrSysBattAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysBattAlrmIndex |
INTEGER |
|
|
dcPwrSysBattAlrmName |
DisplayString |
|
|
dcPwrSysBattAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysBattAlrmStringValue |
DisplayString |
|
|
dcPwrSysBattAlrmSeverity |
INTEGER |
|
DcPwrSysTempAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysTempAlrmIndex |
INTEGER |
|
|
dcPwrSysTempAlrmName |
DisplayString |
|
|
dcPwrSysTempAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysTempAlrmStringValue |
DisplayString |
|
|
dcPwrSysTempAlrmSeverity |
INTEGER |
|
DcPwrSysCustomAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCustomAlrmIndex |
INTEGER |
|
|
dcPwrSysCustomAlrmName |
DisplayString |
|
|
dcPwrSysCustomAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysCustomAlrmStringValue |
DisplayString |
|
|
dcPwrSysCustomAlrmSeverity |
INTEGER |
|
DcPwrSysMiscAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysMiscAlrmIndex |
INTEGER |
|
|
dcPwrSysMiscAlrmName |
DisplayString |
|
|
dcPwrSysMiscAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysMiscAlrmStringValue |
DisplayString |
|
|
dcPwrSysMiscAlrmSeverity |
INTEGER |
|
DcPwrSysCtrlAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCtrlAlrmIndex |
INTEGER |
|
|
dcPwrSysCtrlAlrmName |
DisplayString |
|
|
dcPwrSysCtrlAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysCtrlAlrmStringValue |
DisplayString |
|
|
dcPwrSysCtrlAlrmSeverity |
INTEGER |
|
DcPwrSysAdioAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysAdioAlrmIndex |
INTEGER |
|
|
dcPwrSysAdioAlrmName |
DisplayString |
|
|
dcPwrSysAdioAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysAdioAlrmStringValue |
DisplayString |
|
|
dcPwrSysAdioAlrmSeverity |
INTEGER |
|
DcPwrSysConvAlrmEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysConvAlrmIndex |
INTEGER |
|
|
dcPwrSysConvAlrmName |
DisplayString |
|
|
dcPwrSysConvAlrmIntegerValue |
INTEGER |
|
|
dcPwrSysConvAlrmStringValue |
DisplayString |
|
|
dcPwrSysConvAlrmSeverity |
INTEGER |
|
DcPwrSysDigIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysDigIpIndex |
INTEGER |
|
|
dcPwrSysDigIpName |
DisplayString |
|
|
dcPwrSysDigIpIntegerValue |
INTEGER |
|
|
dcPwrSysDigIpStringValue |
DisplayString |
|
DcPwrSysCntrlrIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCntrlrIpIndex |
INTEGER |
|
|
dcPwrSysCntrlrIpName |
DisplayString |
|
|
dcPwrSysCntrlrIpIntegerValue |
INTEGER |
|
|
dcPwrSysCntrlrIpStringValue |
DisplayString |
|
DcPwrSysRectIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysRectIpIndex |
INTEGER |
|
|
dcPwrSysRectIpName |
DisplayString |
|
|
dcPwrSysRectIpIntegerValue |
INTEGER |
|
|
dcPwrSysRectIpStringValue |
DisplayString |
|
DcPwrSysCustomIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCustomIpIndex |
INTEGER |
|
|
dcPwrSysCustomIpName |
DisplayString |
|
|
dcPwrSysgCustomIpIntegerValue |
INTEGER |
|
|
dcPwrSysCustomIpStringValue |
DisplayString |
|
DcPwrSysConvIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysConvIpIndex |
INTEGER |
|
|
dcPwrSysConvIpName |
DisplayString |
|
|
dcPwrSysConvIpIntegerValue |
INTEGER |
|
|
dcPwrSysConvIpStringValue |
DisplayString |
|
DcPwrSysTimerIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysTimerIpIndex |
INTEGER |
|
|
dcPwrSysTimerIpName |
DisplayString |
|
|
dcPwrSysTimerIpIntegerValue |
INTEGER |
|
|
dcPwrSysTimerIpStringValue |
DisplayString |
|
DcPwrSysCounterIpEntry |
|
SEQUENCE |
|
|
|
|
dcPwrSysCounterIpIndex |
INTEGER |
|
|
dcPwrSysCounterIpName |
DisplayString |
|
|
dcPwrSysCounterIpIntegerValue |
INTEGER |
|
|
dcPwrSysCounterIpStringValue |
DisplayString |
|
Defined Values
argus |
1.3.6.1.4.1.7309 |
This MIB defines the information block(s) available in system controllers
as defined by the following list:
- dcPwrSysDevice: the SM-series of controllers |
MODULE-IDENTITY |
|
|
|
dcpower |
1.3.6.1.4.1.7309.4 |
OBJECT IDENTIFIER |
|
|
|
dcPwrSysChargeVolts |
1.3.6.1.4.1.7309.4.1.1.1 |
Battery Charge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysDischargeVolts |
1.3.6.1.4.1.7309.4.1.1.2 |
Battery Discharge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysChargeAmps |
1.3.6.1.4.1.7309.4.1.1.3 |
Battery Charge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysDischargeAmps |
1.3.6.1.4.1.7309.4.1.1.4 |
Battery Discharge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysMajorAlarm |
1.3.6.1.4.1.7309.4.1.1.5 |
Major Alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysMinorAlarm |
1.3.6.1.4.1.7309.4.1.1.6 |
Minor Alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysSystemType |
1.3.6.1.4.1.7309.4.1.2.8 |
The type of system being monitored by the agent |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysRelayCount |
1.3.6.1.4.1.7309.4.1.4.1.1 |
Number of relay variables in system controller relay table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRelayTable |
1.3.6.1.4.1.7309.4.1.4.1.2 |
A table of DC power system controller rectifier relay output variables |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
DcPwrSysRelayEntry |
|
dcPwrSysRelayEntry |
1.3.6.1.4.1.7309.4.1.4.1.2.1 |
An entry into the DC power system controller relay output group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysRelayEntry |
|
|
dcPwrSysRelayIndex |
1.3.6.1.4.1.7309.4.1.4.1.2.1.1 |
The index of the relay variable in the power system controller relay output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRelayName |
1.3.6.1.4.1.7309.4.1.4.1.2.1.2 |
The description of the relay variable as reported by the DC power system controller relay output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysRelayIntegerValue |
1.3.6.1.4.1.7309.4.1.4.1.2.1.3 |
The integer value of the relay variable as reported by the DC power system controller relay output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysRelayStringValue |
1.3.6.1.4.1.7309.4.1.4.1.2.1.4 |
The string value of the relay variable as reported by the DC power system controller relay output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysRelaySeverity |
1.3.6.1.4.1.7309.4.1.4.1.2.1.5 |
The integer value of relay severity level of the extra variable as reported by the DC power system controller relay output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAnalogOpCount |
1.3.6.1.4.1.7309.4.1.4.2.1 |
Number of analog output variables in system controller analog output table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAnalogOpEntry |
1.3.6.1.4.1.7309.4.1.4.2.2.1 |
An entry into the DC power system controller analog output group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysAnalogOpEntry |
|
|
dcPwrSysAnalogOpIndex |
1.3.6.1.4.1.7309.4.1.4.2.2.1.1 |
The index of the analog variable in the power system controller analog output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAnalogOpName |
1.3.6.1.4.1.7309.4.1.4.2.2.1.2 |
The description of the analog variable as reported by the DC power system controller analog output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysAnalogOpIntegerValue |
1.3.6.1.4.1.7309.4.1.4.2.2.1.3 |
The integer value of the analog variable as reported by the DC power system controller analog output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysAnalogOpStringValue |
1.3.6.1.4.1.7309.4.1.4.2.2.1.4 |
The string value of the analog variable as reported by the DC power system controller analog output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysAnalogOpSeverity |
1.3.6.1.4.1.7309.4.1.4.2.2.1.5 |
The integer value of analog severity level of the extra variable as reported by the DC power system controller analog output group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRectAlrmCount |
1.3.6.1.4.1.7309.4.1.5.1.1 |
Number of rectifier alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRectAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.1.2.1 |
An entry into the DC power system controller rectifier alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysRectAlrmEntry |
|
|
dcPwrSysRectAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.1.2.1.1 |
The index of the alarm variable in the DC power system controller table rectifier alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRectAlrmName |
1.3.6.1.4.1.7309.4.1.5.1.2.1.2 |
The description of the alarm variable as reported by the DC power system controller rectifier alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysRectAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.1.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller rectifier alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysRectAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.1.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller rectifier alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysRectAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.1.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller rectifier alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigAlrmCount |
1.3.6.1.4.1.7309.4.1.5.2.1 |
Number of digital alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.2.2.1 |
An entry into the DC power system controller digital alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysDigAlrmEntry |
|
|
dcPwrSysDigAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.2.2.1.1 |
The index of the alarm variable in the DC power system controller table digital alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigAlrmName |
1.3.6.1.4.1.7309.4.1.5.2.2.1.2 |
The description of the alarm variable as reported by the DC power system controller digital alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysDigAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.2.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller digital alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysDigAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.2.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller digital alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysDigAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.2.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller digital alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCurrAlrmCount |
1.3.6.1.4.1.7309.4.1.5.3.1 |
Number of current alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCurrAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.3.2.1 |
An entry into the DC power system controller current alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCurrAlrmEntry |
|
|
dcPwrSysCurrAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.3.2.1.1 |
The index of the alarm variable in the DC power system controller table current alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCurrAlrmName |
1.3.6.1.4.1.7309.4.1.5.3.2.1.2 |
The description of the alarm variable as reported by the DC power system controller current alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysCurrAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.3.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller current alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCurrAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.3.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller current alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCurrAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.3.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller current alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysVoltAlrmCount |
1.3.6.1.4.1.7309.4.1.5.4.1 |
Number of voltage alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysVoltAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.4.2.1 |
An entry into the DC power system controller voltage alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysVoltAlrmEntry |
|
|
dcPwrSysVoltAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.4.2.1.1 |
The index of the alarm variable in the DC power system controller table voltage alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysVoltAlrmName |
1.3.6.1.4.1.7309.4.1.5.4.2.1.2 |
The description of the alarm variable as reported by the DC power system controller voltage alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysVoltAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.4.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller voltage alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysVoltAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.4.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller voltage alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysVoltAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.4.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller voltage alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysBattAlrmCount |
1.3.6.1.4.1.7309.4.1.5.5.1 |
Number of battery alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysBattAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.5.2.1 |
An entry into the DC power system controller battery alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysBattAlrmEntry |
|
|
dcPwrSysBattAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.5.2.1.1 |
The index of the alarm variable in the DC power system controller table battery alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysBattAlrmName |
1.3.6.1.4.1.7309.4.1.5.5.2.1.2 |
The description of the alarm variable as reported by the DC power system controller battery alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysBattAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.5.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller battery alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysBattAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.5.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller battery alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysBattAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.5.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller battery alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysTempAlrmCount |
1.3.6.1.4.1.7309.4.1.5.6.1 |
Number of temperature alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysTempAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.6.2.1 |
An entry into the DC power system controller temperature alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysTempAlrmEntry |
|
|
dcPwrSysTempAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.6.2.1.1 |
The index of the alarm variable in the DC power system controller table temperature alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysTempAlrmName |
1.3.6.1.4.1.7309.4.1.5.6.2.1.2 |
The description of the alarm variable as reported by the DC power system controller temperature alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysTempAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.6.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller temperature alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysTempAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.6.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller temperature alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysTempAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.6.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller temperature alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCustomAlrmCount |
1.3.6.1.4.1.7309.4.1.5.7.1 |
Number of custom alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCustomAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.7.2.1 |
An entry into the DC power system controller custom alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCustomAlrmEntry |
|
|
dcPwrSysCustomAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.7.2.1.1 |
The index of the alarm variable in the DC power system controller table custom alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCustomAlrmName |
1.3.6.1.4.1.7309.4.1.5.7.2.1.2 |
The description of the alarm variable as reported by the DC power system controller custom alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysCustomAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.7.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller custom alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCustomAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.7.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller custom alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCustomAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.7.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller custom alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysMiscAlrmCount |
1.3.6.1.4.1.7309.4.1.5.8.1 |
Number of misc alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysMiscAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.8.2.1 |
An entry into the DC power system controller misc alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysMiscAlrmEntry |
|
|
dcPwrSysMiscAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.8.2.1.1 |
The index of the alarm variable in the DC power system controller table misc alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysMiscAlrmName |
1.3.6.1.4.1.7309.4.1.5.8.2.1.2 |
The description of the alarm variable as reported by the DC power system controller misc alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysMiscAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.8.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller misc alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysMiscAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.8.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller misc alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysMiscAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.8.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller misc alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCtrlAlrmCount |
1.3.6.1.4.1.7309.4.1.5.9.1 |
Number of control alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCtrlAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.9.2.1 |
An entry into the DC power system controller control alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCtrlAlrmEntry |
|
|
dcPwrSysCtrlAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.9.2.1.1 |
The index of the alarm variable in the DC power system controller table control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCtrlAlrmName |
1.3.6.1.4.1.7309.4.1.5.9.2.1.2 |
The description of the alarm variable as reported by the DC power system controller control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysCtrlAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.9.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCtrlAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.9.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCtrlAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.9.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAdioAlrmCount |
1.3.6.1.4.1.7309.4.1.5.10.1 |
Number of control alarm variables in Adio alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAdioAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.10.2.1 |
An entry into the DC power system controller Adio alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysAdioAlrmEntry |
|
|
dcPwrSysAdioAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.10.2.1.1 |
The index of the alarm variable in the DC power system controller table Adio alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysAdioAlrmName |
1.3.6.1.4.1.7309.4.1.5.10.2.1.2 |
The description of the alarm variable as reported by the DC power system controller Adio alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysAdioAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.10.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller Adio alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysAdioAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.10.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller Adio alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysAdioAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.10.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC Adio system controller control alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysConvAlrmCount |
1.3.6.1.4.1.7309.4.1.5.11.1 |
Number of Converter alarm variables in system controller alarm table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysConvAlrmEntry |
1.3.6.1.4.1.7309.4.1.5.11.2.1 |
An entry into the DC power system controller Converter alarm group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysConvAlrmEntry |
|
|
dcPwrSysConvAlrmIndex |
1.3.6.1.4.1.7309.4.1.5.11.2.1.1 |
The index of the alarm variable in the DC power system controller table Converter alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysConvAlrmName |
1.3.6.1.4.1.7309.4.1.5.11.2.1.2 |
The description of the alarm variable as reported by the DC power system controller Converter alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysConvAlrmIntegerValue |
1.3.6.1.4.1.7309.4.1.5.11.2.1.3 |
The integer value of the alarm variable as reported by the DC power system controller Converter alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysConvAlrmStringValue |
1.3.6.1.4.1.7309.4.1.5.11.2.1.4 |
The string value of the alarm variable as reported by the DC power system controller Converter alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysConvAlrmSeverity |
1.3.6.1.4.1.7309.4.1.5.11.2.1.5 |
The integer value of alarm severity level of the extra variable as reported by the DC power system controller Converter alarm group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigIpCount |
1.3.6.1.4.1.7309.4.1.6.1.1 |
Number of digital input variables in system controller digital input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigIpTable |
1.3.6.1.4.1.7309.4.1.6.1.2 |
A table of DC power system controller digital input variables |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
DcPwrSysDigIpEntry |
|
dcPwrSysDigIpEntry |
1.3.6.1.4.1.7309.4.1.6.1.2.1 |
An entry into the DC power system controller digital input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysDigIpEntry |
|
|
dcPwrSysDigIpIndex |
1.3.6.1.4.1.7309.4.1.6.1.2.1.1 |
The index of the digital input variable in the DC power system controller table digital input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysDigIpName |
1.3.6.1.4.1.7309.4.1.6.1.2.1.2 |
The description of the digital input variable as reported by the DC power system controller digital input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysDigIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.1.2.1.3 |
The integer value of the digital input variable as reported by the DC power system controller digital input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysDigIpStringValue |
1.3.6.1.4.1.7309.4.1.6.1.2.1.4 |
The string value of the digital input variable as reported by the DC power system controller digital input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCntrlrIpCount |
1.3.6.1.4.1.7309.4.1.6.2.1 |
Number of controller input variables in system controller controller input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCntrlrIpEntry |
1.3.6.1.4.1.7309.4.1.6.2.2.1 |
An entry into the DC power system controller controller input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCntrlrIpEntry |
|
|
dcPwrSysCntrlrIpIndex |
1.3.6.1.4.1.7309.4.1.6.2.2.1.1 |
The index of the controller input variable in the DC power system controller table controller input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCntrlrIpName |
1.3.6.1.4.1.7309.4.1.6.2.2.1.2 |
The description of the controller input variable as reported by the DC power system controller controller input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysCntrlrIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.2.2.1.3 |
The integer value of the controller input variable as reported by the DC power system controller controller input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCntrlrIpStringValue |
1.3.6.1.4.1.7309.4.1.6.2.2.1.4 |
The string value of the controller input variable as reported by the DC power system controller controller input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysRectIpCount |
1.3.6.1.4.1.7309.4.1.6.3.1 |
Number of rectifier input variables in system controller rectifier input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRectIpTable |
1.3.6.1.4.1.7309.4.1.6.3.2 |
A table of DC power system controller rectifier input variables |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
DcPwrSysRectIpEntry |
|
dcPwrSysRectIpEntry |
1.3.6.1.4.1.7309.4.1.6.3.2.1 |
An entry into the DC power system controller rectifier input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysRectIpEntry |
|
|
dcPwrSysRectIpIndex |
1.3.6.1.4.1.7309.4.1.6.3.2.1.1 |
The index of the rectifier input variable in the DC power system controller table rectifier input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysRectIpName |
1.3.6.1.4.1.7309.4.1.6.3.2.1.2 |
The description of the rectifier input variable as reported by the DC power system controller rectifier input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysRectIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.3.2.1.3 |
The integer value of the rectifier input variable as reported by the DC power system controller rectifier input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysRectIpStringValue |
1.3.6.1.4.1.7309.4.1.6.3.2.1.4 |
The string value of the rectifier input variable as reported by the DC power system controller rectifier input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCustomIpCount |
1.3.6.1.4.1.7309.4.1.6.4.1 |
Number of custom input variables in system controller custom input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCustomIpEntry |
1.3.6.1.4.1.7309.4.1.6.4.2.1 |
An entry into the DC power system controller custom input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCustomIpEntry |
|
|
dcPwrSysCustomIpIndex |
1.3.6.1.4.1.7309.4.1.6.4.2.1.1 |
The index of the custom input variable in the DC power system controller table custom input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCustomIpName |
1.3.6.1.4.1.7309.4.1.6.4.2.1.2 |
The description of the custom input variable as reported by the DC power system controller custom input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysgCustomIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.4.2.1.3 |
The integer value of the custom input variable as reported by the DC power system controller custom input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCustomIpStringValue |
1.3.6.1.4.1.7309.4.1.6.4.2.1.4 |
The string value of the custom input variable as reported by the DC power system controller custom input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysConvIpCount |
1.3.6.1.4.1.7309.4.1.6.5.1 |
Number of Converter input variables in system controller Converter input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysConvIpTable |
1.3.6.1.4.1.7309.4.1.6.5.2 |
A table of DC power system controller Converter input variables |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
DcPwrSysConvIpEntry |
|
dcPwrSysConvIpEntry |
1.3.6.1.4.1.7309.4.1.6.5.2.1 |
An entry into the DC power system controller Converter input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysConvIpEntry |
|
|
dcPwrSysConvIpIndex |
1.3.6.1.4.1.7309.4.1.6.5.2.1.1 |
The index of the Converter input variable in the DC power system controller table Converter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysConvIpName |
1.3.6.1.4.1.7309.4.1.6.5.2.1.2 |
The description of the Converter input variable as reported by the DC power system controller Converter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysConvIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.5.2.1.3 |
The integer value of the Converter input variable as reported by the DC power system controller Converter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysConvIpStringValue |
1.3.6.1.4.1.7309.4.1.6.5.2.1.4 |
The string value of the Converter input variable as reported by the DC power system controller Converter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysTimerIpCount |
1.3.6.1.4.1.7309.4.1.6.6.1 |
Number of Timererter input variables in system controller Timererter input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysTimerIpEntry |
1.3.6.1.4.1.7309.4.1.6.6.2.1 |
An entry into the DC power system controller Timererter input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysTimerIpEntry |
|
|
dcPwrSysTimerIpIndex |
1.3.6.1.4.1.7309.4.1.6.6.2.1.1 |
The index of the Timererter input variable in the DC power system controller table Timererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysTimerIpName |
1.3.6.1.4.1.7309.4.1.6.6.2.1.2 |
The description of the Timererter input variable as reported by the DC power system controller Timererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysTimerIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.6.2.1.3 |
The integer value of the Timererter input variable as reported by the DC power system controller Timererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysTimerIpStringValue |
1.3.6.1.4.1.7309.4.1.6.6.2.1.4 |
The string value of the Timererter input variable as reported by the DC power system controller Timererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysCounterIpCount |
1.3.6.1.4.1.7309.4.1.6.7.1 |
Number of Countererter input variables in system controller Countererter input table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCounterIpEntry |
1.3.6.1.4.1.7309.4.1.6.7.2.1 |
An entry into the DC power system controller Countererter input group |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DcPwrSysCounterIpEntry |
|
|
dcPwrSysCounterIpIndex |
1.3.6.1.4.1.7309.4.1.6.7.2.1.1 |
The index of the Countererter input variable in the DC power system controller table Countererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
dcPwrSysCounterIpName |
1.3.6.1.4.1.7309.4.1.6.7.2.1.2 |
The description of the Countererter input variable as reported by the DC power system controller Countererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..30) |
|
dcPwrSysCounterIpIntegerValue |
1.3.6.1.4.1.7309.4.1.6.7.2.1.3 |
The integer value of the Countererter input variable as reported by the DC power system controller Countererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1000000000..1000000000 |
|
dcPwrSysCounterIpStringValue |
1.3.6.1.4.1.7309.4.1.6.7.2.1.4 |
The string value of the Countererter input variable as reported by the DC power system controller Countererter input group |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dcPwrSysAlarmActiveTrap |
1.3.6.1.4.1.7309.4.1.3.0.1 |
A trap issued when one of the alarms on the DC power system controller became active |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysAlarmClearedTrap |
1.3.6.1.4.1.7309.4.1.3.0.2 |
A trap issued when one of the active alarms on the DC power system controller is cleared |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysRelayTrap |
1.3.6.1.4.1.7309.4.1.3.0.3 |
A trap issued from a change in state in one of the relays on the DC power system controller |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysComOKTrap |
1.3.6.1.4.1.7309.4.1.3.0.4 |
A trap to indicate that communications with a DC power system controller has been established. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysComErrTrap |
1.3.6.1.4.1.7309.4.1.3.0.5 |
A trap to indicate that communications with a DC power system controller has been lost. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysAgentStartupTrap |
1.3.6.1.4.1.7309.4.1.3.0.6 |
A trap to indicate that the agent software has started up. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysAgentShutdownTrap |
1.3.6.1.4.1.7309.4.1.3.0.7 |
A trap to indicate that the agent software has shutdown. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysMajorAlarmActiveTrap |
1.3.6.1.4.1.7309.4.1.3.0.8 |
A trap issued as a summary of DC power system status. It is sent when the system goes into in Major Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysMajorAlarmClearedTrap |
1.3.6.1.4.1.7309.4.1.3.0.9 |
A trap issued as a summary of DC power system status. It is sent when the system comes out of Major Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysMinorAlarmActiveTrap |
1.3.6.1.4.1.7309.4.1.3.0.10 |
A trap issued as a summary of DC power system status. It is sent when the system goes into in Minor Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysMinorAlarmClearedTrap |
1.3.6.1.4.1.7309.4.1.3.0.11 |
A trap issued as a summary of DC power system status. It is sent when the system comes out of Minor Alarm |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
dcPwrSysResyncAlarms |
1.3.6.1.4.1.7309.4.1.8.1 |
Send/Resend all active alarms that were previously sent through SNMP notification. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|