ATS-MIB

File: ATS-MIB.mib (46082 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215 UPS-MIB

Imported symbols

enterprises Counter IpAddress
OBJECT-TYPE DisplayString TRAP-TYPE
PositiveInteger NonNegativeInteger

Defined Types

AgentConfigTrapsReceiversEntry  
SEQUENCE    
  trapsIndex INTEGER
  trapsReceiverAddr DisplayString
  receiverCommunityString DisplayString
  receiverNmsType INTEGER
  receiverSeverityLevel INTEGER
  receiverDescription DisplayString

AgentConfigAccessControlEntry  
SEQUENCE    
  accessIndex INTEGER
  accessControlAddr IpAddress
  accessCommunityString DisplayString
  accessControlMode INTEGER

Defined Values

ats 1.3.6.1.4.1.37662
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.37662.1
OBJECT IDENTIFIER    

webAppliance 1.3.6.1.4.1.37662.1.2
OBJECT IDENTIFIER    

atsAgent 1.3.6.1.4.1.37662.1.2.2
OBJECT IDENTIFIER    

single 1.3.6.1.4.1.37662.1.2.2.1
OBJECT IDENTIFIER    

atsObjectGroup 1.3.6.1.4.1.37662.1.2.2.1.1
OBJECT IDENTIFIER    

atsTrapGroup 1.3.6.1.4.1.37662.1.2.2.1.2
OBJECT IDENTIFIER    

atsIdentGroup 1.3.6.1.4.1.37662.1.2.2.1.1.1
OBJECT IDENTIFIER    

atsInputGroup 1.3.6.1.4.1.37662.1.2.2.1.1.2
OBJECT IDENTIFIER    

atsOutputGroup 1.3.6.1.4.1.37662.1.2.2.1.1.3
OBJECT IDENTIFIER    

atsHmiSwitchGroup 1.3.6.1.4.1.37662.1.2.2.1.1.4
OBJECT IDENTIFIER    

atsMiscellaneousGroup 1.3.6.1.4.1.37662.1.2.2.1.1.5
OBJECT IDENTIFIER    

atsControlGroup 1.3.6.1.4.1.37662.1.2.2.1.1.6
OBJECT IDENTIFIER    

agentConfig 1.3.6.1.4.1.37662.1.2.2.1.1.7
OBJECT IDENTIFIER    

emdStatus 1.3.6.1.4.1.37662.1.2.2.1.1.8
OBJECT IDENTIFIER    

emdConfig 1.3.6.1.4.1.37662.1.2.2.1.1.9
OBJECT IDENTIFIER    

atsIdentGroupModel 1.3.6.1.4.1.37662.1.2.2.1.1.1.1
The device model name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsIdentGroupSerialNumber 1.3.6.1.4.1.37662.1.2.2.1.1.1.2
The device serial number.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsIdentGroupManufacturer 1.3.6.1.4.1.37662.1.2.2.1.1.1.3
The device manufacturer name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsIdentGroupFirmwareRevision 1.3.6.1.4.1.37662.1.2.2.1.1.1.4
The device firmware revision.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsIdentGroupAgentFirmwareRevision 1.3.6.1.4.1.37662.1.2.2.1.1.1.5
The agent firmware revision.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsInputGroupPreference 1.3.6.1.4.1.37662.1.2.2.1.1.2.1
This shows the Output Source Priority by Source A or Source B.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsInputGroupSourceAstatus 1.3.6.1.4.1.37662.1.2.2.1.1.2.2
This field shows the status of the source A. Status included? 'OK','Fail'. 'OK' mean frequency and voltage of Source A are normal.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER fail(1), ok(2)  

atsInputGroupSourceAinputVoltage 1.3.6.1.4.1.37662.1.2.2.1.1.2.3
The source A input voltage of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceAinputFrequency 1.3.6.1.4.1.37662.1.2.2.1.1.2.4
The source A input frequency of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBstatus 1.3.6.1.4.1.37662.1.2.2.1.1.2.5
This field shows the status of the source B. Status included? 'OK','Fail'. 'OK' mean frequency and voltage of Source B are normal.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER fail(1), ok(2)  

atsInputGroupSourceBinputVoltage 1.3.6.1.4.1.37662.1.2.2.1.1.2.6
The source B input voltage of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBinputFrequency 1.3.6.1.4.1.37662.1.2.2.1.1.2.7
The source B input frequency of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceAvoltageUpperLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.8
The source A voltage upper limit of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceAvoltageLowerLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.9
The source A voltage lower limit of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceAfrequencyUpperLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.10
The source A frequency upper limit of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceAfrequencyLowerLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.11
The source A frequency lower limit of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBvoltageUpperLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.12
The source B voltage upper limit of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBvoltageLowerLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.13
The source B voltage lower limit of the ATS input in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBfrequencyUpperLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.14
The source B frequency upper limit of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInputGroupSourceBfrequencyLowerLimit 1.3.6.1.4.1.37662.1.2.2.1.1.2.15
The source B frequency lower limit of the ATS input in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsOutputGroupOutputSource 1.3.6.1.4.1.37662.1.2.2.1.1.3.1
Output source is supply by Source A or Source B. Status included? 'Source A','Source B'.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

atsOutputGroupOutputVoltage 1.3.6.1.4.1.37662.1.2.2.1.1.3.2
The Output Voltage in volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsOutputGroupOutputFequency 1.3.6.1.4.1.37662.1.2.2.1.1.3.3
The output fequency in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsOutputGroupOutputCurrent 1.3.6.1.4.1.37662.1.2.2.1.1.3.4
The output current in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsOutputGroupLoad 1.3.6.1.4.1.37662.1.2.2.1.1.3.5
The load in %.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsHmiSwitchGroupBuzzer 1.3.6.1.4.1.37662.1.2.2.1.1.4.1
This field shows the status of the buzzer. Status included? 'Enable','Disable'.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER buzzerDisabled(1), buzzerEnabled(2)  

atsHmiSwitchGroupAtsAlarm 1.3.6.1.4.1.37662.1.2.2.1.1.4.2
This shows the alarm occured.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER nothing(1), atsOccurAlarm(2)  

atsHmiSwitchGroupAutoReturn 1.3.6.1.4.1.37662.1.2.2.1.1.4.3
Auto recover to that setting value when two input source normal.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

atsHmiSwitchGroupSourceTransferByLoad 1.3.6.1.4.1.37662.1.2.2.1.1.4.4
On: If overload timeout occurred , ATS will tranfer to another source automaticlly. Off:If overload timeout occurred , ATS will turn off the output source.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

atsHmiSwitchGroupSourceTransferByPhase 1.3.6.1.4.1.37662.1.2.2.1.1.4.5
On: when the transfer of output source occur, the transfer can active if differernce of phase less than setting value Off: Switch transfer immed... whatever difference of phase.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

atsMiscellaneousGroupAtsSystemTemperture 1.3.6.1.4.1.37662.1.2.2.1.1.5.1
The ATS system temperture in degree C.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsMiscellaneousGroupSystemMaxCurrent 1.3.6.1.4.1.37662.1.2.2.1.1.5.2
The system max current int 0.1 Amp.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

atsControlGroupBuzzerAlarmControl 1.3.6.1.4.1.37662.1.2.2.1.1.6.1
The buzzer alarm control.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER buzzerOff(1), buzzerOn(2)  

atsControlGroupManualTransfer 1.3.6.1.4.1.37662.1.2.2.1.1.6.2
User can click this bottom to decide output source supply is Source A or Source B.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigIpaddress 1.3.6.1.4.1.37662.1.2.2.1.1.7.1
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigGateway 1.3.6.1.4.1.37662.1.2.2.1.1.7.2
The default gateway that allow device managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigSubnetMask 1.3.6.1.4.1.37662.1.2.2.1.1.7.3
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

agentConfigDate 1.3.6.1.4.1.37662.1.2.2.1.1.7.4
The date in agent, format is (dd/mm/yyyy)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

agentConfigTime 1.3.6.1.4.1.37662.1.2.2.1.1.7.5
The time in agent, format is (hh:mm:ss)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

agentConfigHistoryLogFrequency 1.3.6.1.4.1.37662.1.2.2.1.1.7.6
The frequency of the updation of the history log. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..28800  

agentConfigExtHistoryLogFrequency 1.3.6.1.4.1.37662.1.2.2.1.1.7.7
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10080  

agentConfigPollRate 1.3.6.1.4.1.37662.1.2.2.1.1.7.8
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..999  

agentConfigBaudRate 1.3.6.1.4.1.37662.1.2.2.1.1.7.9
The serial port communication speed. only 9600 allowed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

agentConfigDhcpStatue 1.3.6.1.4.1.37662.1.2.2.1.1.7.10
Enable or disable DHCP/BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigTelnetStatue 1.3.6.1.4.1.37662.1.2.2.1.1.7.11
Enable or disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigTftpStatue 1.3.6.1.4.1.37662.1.2.2.1.1.7.12
Enable or disable network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

agentConfigResetToDefault 1.3.6.1.4.1.37662.1.2.2.1.1.7.13
Reset all parameters of ATS to default value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER reset(1), nothing(2)  

agentConfigRestart 1.3.6.1.4.1.37662.1.2.2.1.1.7.14
Restart ATS
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restart(1), nothing(2)  

agentConfigClearAgentLog 1.3.6.1.4.1.37662.1.2.2.1.1.7.15
Clear agent log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearEventLog 1.3.6.1.4.1.37662.1.2.2.1.1.7.16
Clear event log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearExtHistoryLog 1.3.6.1.4.1.37662.1.2.2.1.1.7.17
Clear extented history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigClearHistoryLog 1.3.6.1.4.1.37662.1.2.2.1.1.7.18
Clear history log data
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clear(1), nothing(2)  

agentConfigTrapRetryCount 1.3.6.1.4.1.37662.1.2.2.1.1.7.19
The count of repeat traps to send to NMS before trap acknowledge received.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigTrapRetryTime 1.3.6.1.4.1.37662.1.2.2.1.1.7.20
The time between retry traps sned to NMS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigTrapAckSignature 1.3.6.1.4.1.37662.1.2.2.1.1.7.21
The signature of trap acknowledge.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

agentConfigMibVersion 1.3.6.1.4.1.37662.1.2.2.1.1.7.22
The version of MIB spec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

agentConfigTrapsReceiversTable 1.3.6.1.4.1.37662.1.2.2.1.1.7.23
A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AgentConfigTrapsReceiversEntry

agentConfigTrapsReceiversEntry 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  AgentConfigTrapsReceiversEntry  

trapsIndex 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

trapsReceiverAddr 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

receiverCommunityString 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

receiverNmsType 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.4
The trap group that NMS desired.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), ats-trap(2)  

receiverSeverityLevel 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.5
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), severe(3)  

receiverDescription 1.3.6.1.4.1.37662.1.2.2.1.1.7.23.1.6
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

agentConfigAccessControlTable 1.3.6.1.4.1.37662.1.2.2.1.1.7.24
A list of managers which can access ATS with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AgentConfigAccessControlEntry

agentConfigAccessControlEntry 1.3.6.1.4.1.37662.1.2.2.1.1.7.24.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  AgentConfigAccessControlEntry  

accessIndex 1.3.6.1.4.1.37662.1.2.2.1.1.7.24.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

accessControlAddr 1.3.6.1.4.1.37662.1.2.2.1.1.7.24.1.2
The IP address of the manager to access ATS
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

accessCommunityString 1.3.6.1.4.1.37662.1.2.2.1.1.7.24.1.3
The community name to use in the manager when access ATS
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

accessControlMode 1.3.6.1.4.1.37662.1.2.2.1.1.7.24.1.4
Access type, only read/Write access type can change parameter of ATS
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), readWrite(2), notAccess(3)  

agentConfigDefaultLanguage 1.3.6.1.4.1.37662.1.2.2.1.1.7.25
The default languauge for browser, when set to auto(1) ATS will send page in the language depends on the request language of browser.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), english(2), traditionalChinese(3), simplifiedChinese(4)  

agentConfigIPv6AddrStatus 1.3.6.1.4.1.37662.1.2.2.1.1.7.26
The status of IPv6 global address. When the auto-configuration of IPv6 address is disabled, it shows manual configuration(3). Otherwise, it shows valid(2) for auto-configured successfully, or shows invalid(1) for the failure in auto-configured.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER invalid(1), valid(2), manualConfiguration(3)  

agentConfigIPv6AddrAutoConfig 1.3.6.1.4.1.37662.1.2.2.1.1.7.27
The state of IPv6 address auto-configuration. If set to enable(1), ATS will try to get a valid global/site-local address from IPv6 router or DHCPv6 server on the same link.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

agentConfigIPv6LinkLocalAddr 1.3.6.1.4.1.37662.1.2.2.1.1.7.28
The IPv6 link-local address of ATS. It is auto-configured based on MAC address of ATS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

agentConfigIPv6GlobalAddr 1.3.6.1.4.1.37662.1.2.2.1.1.7.29
The IPv6 global/site-local address of ATS. If change it manually, the agentConfigIPv6AddrStatus and agentConfigIPv6AddrAutoConfig will be changed to manual configuration and disabled respectively.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

agentConfigIPv6PrefixlLength 1.3.6.1.4.1.37662.1.2.2.1.1.7.30
The prefix length of IPv6 global/site-local address.If change it manually, the agentConfigIPv6AddrStatus and agentConfigIPv6AddrAutoConfig will be changed to manual configuration and disabled respectively.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..128  

agentConfigIPv6DefaultRouter 1.3.6.1.4.1.37662.1.2.2.1.1.7.31
The address of IPv6 default router. If change it manually, the agentConfigIPv6AddrStatus and agentConfigIPv6AddrAutoConfig will be changed to manual configuration and disabled respectively.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

emdSatatusEmdType 1.3.6.1.4.1.37662.1.2.2.1.1.8.1
The type of EMD plugged into the port.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), emdHT(3), emdT(4)  

emdSatatusTemperature 1.3.6.1.4.1.37662.1.2.2.1.1.8.2
The measurement of EMD temperature, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

emdSatatusHumidity 1.3.6.1.4.1.37662.1.2.2.1.1.8.3
The measurement of EMD humidity, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

emdSatatusAlarm1 1.3.6.1.4.1.37662.1.2.2.1.1.8.4
The EMD alarm-1 status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

emdSatatusAlarm2 1.3.6.1.4.1.37662.1.2.2.1.1.8.5
The EMD alarm-2 status
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

usahEmdConfigEmdConfig 1.3.6.1.4.1.37662.1.2.2.1.1.9.1
Enable or disable to detect presence of EMD
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

emdConfigEmdName 1.3.6.1.4.1.37662.1.2.2.1.1.9.2
Description of EMD
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigTemperature 1.3.6.1.4.1.37662.1.2.2.1.1.9.3
OBJECT IDENTIFIER    

emdConfigTempName 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.1
Description of EMD temperature sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigTempHighSetPoint 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.2
The set point for high temperature warning, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigTempHighStatus 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.3
To enable/disable high set point check with emd temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigTempLowSetPoint 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.4
The set point for low temperature warning, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigTempLowStatus 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.5
To enable/disable low set point check with emd temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigTempOffset 1.3.6.1.4.1.37662.1.2.2.1.1.9.3.6
The offset to calibrate temperature of EMD, in degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidity 1.3.6.1.4.1.37662.1.2.2.1.1.9.4
OBJECT IDENTIFIER    

emdConfigHumidityName 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.1
Description of EMD humidity sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigHumidityHighSetPoint 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.2
The set point for high humidity warning, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidityHighStatus 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.3
To enable/disable high set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigHumidityLowSetPoint 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.4
The set point for low humidity warning, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigHumidityLowStatus 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.5
To enable/disable low set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

emdConfigHumidityOffset 1.3.6.1.4.1.37662.1.2.2.1.1.9.4.6
The offset to calibrate humidity of EMD, in %
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

emdConfigAlarm1 1.3.6.1.4.1.37662.1.2.2.1.1.9.5
OBJECT IDENTIFIER    

emdConfigAlarm1Name 1.3.6.1.4.1.37662.1.2.2.1.1.9.5.1
Description of EMD alarm-1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigAlarm1Type 1.3.6.1.4.1.37662.1.2.2.1.1.9.5.2
The alarm-1 operation type
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), nomralOpen(2), normalClose(3)  

emdConfigAlarm2 1.3.6.1.4.1.37662.1.2.2.1.1.9.6
OBJECT IDENTIFIER    

emdConfigAlarm2Name 1.3.6.1.4.1.37662.1.2.2.1.1.9.6.1
Description of EMD alarm-2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

emdConfigAlarm2Type 1.3.6.1.4.1.37662.1.2.2.1.1.9.6.2
The alarm-1 operation type
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), nomralOpen(2), normalClose(3)  

atsAtsAlarm 1
WARNING: ATS Alarm.
TRAP-TYPE    

atsSourceAvoltageAbnormal 2
WARNING: Source A voltage abnormal.
TRAP-TYPE    

atsSourceBvoltageAbnormal 3
WARNING: Source B voltage abnormal.
TRAP-TYPE    

atsSourceAfrequencyAbnormal 4
WARNING: Source A frequency abnormal.
TRAP-TYPE    

atsSourceBfrequencyAbnormal 5
WARNING: Source B frequency abnormal.
TRAP-TYPE    

atsOutputOverLoad 6
SEVERE: Output over load.
TRAP-TYPE    

atsWorkPowerAabnormal 7
SEVERE: Unit fault (Working power A abnormal).
TRAP-TYPE    

atsWorkPowerBabnormal 8
SEVERE: Unit fault (Working power B abnormal).
TRAP-TYPE    

atsOverTemperature 9
WARNING: Cabinet over temperature.
TRAP-TYPE    

atsDcOffsetAbnormal 10
SEVERE: Unit fault (Sensor circuit abnormal).
TRAP-TYPE    

atsEepromAbnormal 11
SEVERE: Unit fault (EEPROM data abnormal)
TRAP-TYPE    

atsLcdNotConnect 12
SEVERE: LCD panel connection abnormal.
TRAP-TYPE    

atsOutputExceedsOverloadTime 13
SEVERE: Overload time out, Output off, Reset needed.
TRAP-TYPE    

atsInputPhaseDifference 14
SEVERE: Phase difference between resources exceed user defined value, Output off, Reset needed.
TRAP-TYPE    

atsUserSetOverLoad 15
WARNING: User defined load pre-alarm.
TRAP-TYPE    

atsAtsAlarmToNormal 16
INFORMATION: ATS Alarm Normal.
TRAP-TYPE    

atsSourceAvoltageAbnormalToNormal 17
INFORMATION: Source A Voltage Normal.
TRAP-TYPE    

atsSourceBvoltageAbnormalToNormal 18
INFORMATION: Source B Voltage Normal.
TRAP-TYPE    

atsSourceAfrequencyAbnormalToNormal 19
INFORMATION: Source A Frequency Normal.
TRAP-TYPE    

atsSourceBfrequencyAbnormalToNormal 20
INFORMATION: Source B Frequency Normal.
TRAP-TYPE    

atsOutputOverLoadToNormal 21
INFORMATION: Output Load Normal.
TRAP-TYPE    

atsWorkPowerAabnormalToNormal 22
INFORMATION: Unit Normal (Working power A normal).
TRAP-TYPE    

atsWorkPowerBabnormalToNormal 23
INFORMATION: Unit Normal (Working power B normal).
TRAP-TYPE    

atsOverTemperatureToNormal 24
INFORMATION: Cabinet temperature Normal.
TRAP-TYPE    

atsDcOffsetAbnormalToNormal 25
INFORMATION: Unit Normal (Sensor circuit normal).
TRAP-TYPE    

atsEepromAbnormalToNormal 26
INFORMATION: Unit normal (EEPROM data normal)
TRAP-TYPE    

atsLcdNotConnectToNormal 27
INFORMATION: LCD panel connection normal.
TRAP-TYPE    

atsOutputExceedsOverloadTimeToNormal 28
INFORMATION: Output Load Normal.
TRAP-TYPE    

atsInputPhaseDifferenceToNormal 29
INFORMATION: Input sources return to normal phase.
TRAP-TYPE    

atsUserSetOverLoadToNormal 30
INFORMATION: User defined load return to Normal.
TRAP-TYPE    

atsCommunicationLost 31
SEVERE: Communication to the ATS has been lost. Steps to reestablish communication are in progress.
TRAP-TYPE    

atsCommunicationEstablished 32
INFORMATION: Communication with the ATS has been established.
TRAP-TYPE    

emdTemperatureNotHigh 33
INFORMATION: The temperature of EMD back to normal from high warning.
TRAP-TYPE    

emdTemperatureTooHigh 34
WARNING: The temperature of EMD higher than set point.
TRAP-TYPE    

emdTemperatureNotLow 35
INFORMATION: The temperature of EMD back to normal from low warning.
TRAP-TYPE    

emdTemperatureTooLow 36
WARNING: The temperature of EMD lower than set point.
TRAP-TYPE    

emdHumidityNotHigh 37
INFORMATION: The humidity of EMD back to normal from high warning.
TRAP-TYPE    

emdHumidityTooHigh 38
WARNING: The humidity of EMD higher than set point.
TRAP-TYPE    

emdHumidityNotLow 39
INFORMATION: The humidity of EMD back to normal from low warning.
TRAP-TYPE    

emdHumidityTooLow 40
WARNING: The humidity of EMD lower than set point.
TRAP-TYPE    

emdAlarm1Normal 41
INFORMATION: The status of emd alarm-1 back to normal from active.
TRAP-TYPE    

emdAlarm1Active 42
WARNING: The status of emd alarm-1 activated.
TRAP-TYPE    

emdAlarm2Normal 43
INFORMATION: The status of emd alarm-2 back to normal from active.
TRAP-TYPE    

emdAlarm2Active 44
WARNING: The status of emd alarm-2 activated.
TRAP-TYPE