ADH3-NETCOM-MIB
File:
ADH3-NETCOM-MIB.mib (5771 bytes)
Imported modules
Imported symbols
Defined Values
environmentalTechnology |
1.3.6.1.4.1.32185 |
The Structure of Management Information for
Environmental Technology Inc. SNMP devices |
MODULE-IDENTITY |
|
|
|
netcom |
1.3.6.1.4.1.32185.2 |
ADH-3 NETCOM |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
statusInfo |
1.3.6.1.4.1.32185.2.1 |
OBJECT IDENTIFIER |
|
|
|
paramsInfo |
1.3.6.1.4.1.32185.2.2 |
OBJECT IDENTIFIER |
|
|
|
allStatuses |
1.3.6.1.4.1.32185.2.1.1 |
Summary: same as objects 2-7, separated by semicolons |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(80) |
|
pressurePSI |
1.3.6.1.4.1.32185.2.1.2 |
Pressure, in PSI |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
dutycycle |
1.3.6.1.4.1.32185.2.1.3 |
Current duty cycle, in percent; --- if none available |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
statusVars |
1.3.6.1.4.1.32185.2.1.4 |
Summary of the status of the unit.
Is always 6 characters
Character 1 is major state: N=normal, S=standby, L=leaky
Character 2 is environment: N=normal, C=cold, H=hot
Character 3 is canister 1 condition:
O=OK (ie dry), F=full (wet), U=unknown, D=dead
Character 4 is canister 1 usage:
I=idle, U=in use, R=regenerating
Character 5 is canister 2 condition, as in character 3
Character 5 is canister 2 usage, as in character 4 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(6) |
|
temperature |
1.3.6.1.4.1.32185.2.1.5 |
Current temperature, in degrees F |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
alarms |
1.3.6.1.4.1.32185.2.1.6 |
Current alarm conditions: is a list of them
Each character has a - for no alarm, or an A or W if there
is an alarm. A means alarm (serious), W means a warning
(not so serious). |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(30) |
|
compressorHours |
1.3.6.1.4.1.32185.2.1.7 |
Number of hours that the compressor has been running;
resolution is tenths of an hour. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(30) |
|
majorState |
1.3.6.1.4.1.32185.2.1.8 |
Major state of the dehydrator.
Online: currently pressurizing.
Standby: not pressurizing.
Leaky: shut down because of inability to pressurize. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
online(1), standby(2), leaky(3) |
|
lowerLimit |
1.3.6.1.4.1.32185.2.2.1 |
The pressure, in PSI, at which the unit starts to pump |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
upperLimit |
1.3.6.1.4.1.32185.2.2.2 |
The pressure, in PSI, which the unit pressurizes to |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
lowerAlarmLimit |
1.3.6.1.4.1.32185.2.2.3 |
The pressure, in PSI, below which the unit declares a
low pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|
upperAlarmLimit |
1.3.6.1.4.1.32185.2.2.4 |
The pressure, in PSI, above which the unit declares a
high pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10) |
|