-- -- ACC-NC-ALARM-MIB.my -- MIB generated by MG-SOFT Visual MIB Builder Version 3.0 Build 285 -- Tuesday, August 06, 2002 at 11:20:44 -- ACC-NC-ALARM-MIB DEFINITIONS ::= BEGIN IMPORTS accNetController FROM ANDOVER-CONTROLS-MIB OBJECT-GROUP, MODULE-COMPLIANCE, NOTIFICATION-GROUP FROM SNMPv2-CONF Integer32, Unsigned32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE FROM SNMPv2-SMI DisplayString, DateAndTime, TruthValue, StorageType, RowStatus FROM SNMPv2-TC; -- 1.3.6.1.4.1.10829.5.2.1 accAlarmMIB MODULE-IDENTITY LAST-UPDATED "200210300946Z" -- October 30, 2002 at 09:46 GMT ORGANIZATION "Andover Controls Corporation" CONTACT-INFO "Technical Support Andover Controls Corporation 300 Brickstone Square Andover, MA 01810 USA 978-470-0555" DESCRIPTION "This MIB module defines MIB objects and notifications which are mapped from Andover Controls Continuum Alarms" REVISION "200210300946Z" -- October 30, 2002 at 09:46 GMT DESCRIPTION "Revision 1.0" ::= { accNetController 1 } -- -- Node definitions -- -- 1.3.6.1.4.1.10829.5.2.1.1 alarmListMax OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum number of elements in the Alarm List table not including internal alarms, such as Controller Reset, Alarm Table Overflow." ::= { accAlarmMIB 1 } -- 1.3.6.1.4.1.10829.5.2.1.2 alarmList OBJECT IDENTIFIER::= { accAlarmMIB 2 } -- 1.3.6.1.4.1.10829.5.2.1.2.2 alarmTable OBJECT-TYPE SYNTAX SEQUENCE OF AlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Description." ::= { alarmList 2 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1 alarmEntry OBJECT-TYPE SYNTAX AlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Description." INDEX { alarmIENAD, alarmLink } ::= { alarmTable 1 } AlarmEntry ::= SEQUENCE { alarmControllerName DisplayString, alarmInfinetControllerName DisplayString, alarmPointName DisplayString, alarmPointDescription DisplayString, alarmAlarmName DisplayString, alarmState INTEGER, alarmAlmTime DateAndTime, alarmAlmValue DisplayString, alarmRtnTime DateAndTime, alarmRtnValue DisplayString, alarmIENAD OCTET STRING, alarmLink INTEGER } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.1 alarmControllerName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "NetController name upon which this table exists." ::= { alarmEntry 1 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.2 alarmInfinetControllerName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Infinet controller name upon which the point in alarm resides. This could also be null, if the point is on the NetController itself." ::= { alarmEntry 2 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.3 alarmPointName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Continuum point name." ::= { alarmEntry 3 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.4 alarmPointDescription OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Continuum point description." ::= { alarmEntry 4 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.5 alarmAlarmName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Continuum alarm name." ::= { alarmEntry 5 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.6 alarmState OBJECT-TYPE SYNTAX INTEGER { null(0), rtn(1), alm(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "This is the state of the corresponding Continuum alarm as was learned from the last alarm transition." ::= { alarmEntry 6 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.7 alarmAlmTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time stamp when point entered alarm (ALM) state. This could also be null, if no transition to ALM occured." ::= { alarmEntry 7 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.8 alarmAlmValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Value when point went into alarm (ALM) state. This could also be null, if no transition to ALM occured." ::= { alarmEntry 8 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.9 alarmRtnTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time stamp when point returned to normal (RTN) state. This could also be null, if no transition to RTN occured." ::= { alarmEntry 9 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.10 alarmRtnValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Value when point state returned to normal (RTN). This could also be null, if no transition to RTN occured." ::= { alarmEntry 10 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.12 alarmIENAD OBJECT-TYPE SYNTAX OCTET STRING (SIZE (4)) MAX-ACCESS read-only STATUS current DESCRIPTION "IENAD that identifies point in IE table; 0 for internal alarm." ::= { alarmEntry 12 } -- 1.3.6.1.4.1.10829.5.2.1.2.2.1.13 alarmLink OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Number identifying which Continuum alarm link 1-8; 1 for Controller Reset alarm; 2 for Alarm Table Overflow" ::= { alarmEntry 13 } -- 1.3.6.1.4.1.10829.5.2.1.3 alarmTransitionEvent NOTIFICATION-TYPE OBJECTS { alarmControllerName, alarmInfinetControllerName, alarmPointName, alarmPointDescription, alarmAlarmName, alarmState, alarmAlmTime, alarmAlmValue, alarmRtnTime, alarmRtnValue } STATUS current DESCRIPTION "This is the row of the alarm table that is sent as a notification to an SNMP manager." ::= { accAlarmMIB 3 } -- Agents must support the following MIBs, -- groups, and events. -- 1.3.6.1.4.1.10829.5.2.1.4 alarmConformance OBJECT IDENTIFIER::= { accAlarmMIB 4 } -- 1.3.6.1.4.1.10829.5.2.1.4.1 alarmCompliances OBJECT IDENTIFIER::= { alarmConformance 1 } -- 1.3.6.1.4.1.10829.5.2.1.4.1.1 alarmBasicCompliance MODULE-COMPLIANCE STATUS current DESCRIPTION "Module Compliance for agent. Agent must support these groups." MODULE -- this module MANDATORY-GROUPS { alarmGroup, alarmEvents } ::= { alarmCompliances 1 } -- 1.3.6.1.4.1.10829.5.2.1.4.2 alarmGroups OBJECT IDENTIFIER::= { alarmConformance 2 } -- 1.3.6.1.4.1.10829.5.2.1.4.2.1 alarmGroup OBJECT-GROUP OBJECTS { alarmListMax, alarmControllerName, alarmInfinetControllerName, alarmPointName, alarmPointDescription, alarmAlarmName, alarmState, alarmAlmTime, alarmAlmValue, alarmRtnTime, alarmRtnValue, alarmIENAD, alarmLink } STATUS current DESCRIPTION "Objects the agent must support." ::= { alarmGroups 1 } -- 1.3.6.1.4.1.10829.5.2.1.4.2.2 alarmEvents NOTIFICATION-GROUP NOTIFICATIONS { alarmTransitionEvent } STATUS current DESCRIPTION "Events the agent must support." ::= { alarmGroups 2 } END -- -- ACC-NC-ALARM-MIB.my --