VALERE-DC-POWER-MIB
File:
VALERE-DC-POWER-MIB.mib (102911 bytes)
Imported modules
Imported symbols
Defined Types
PositiveInteger |
|
This data type is a non-zero and non-negative value. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
1..2147483647 |
|
NonNegativeInteger |
|
This data type is a non-negative value. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
0..2147483647 |
|
VpwrSystemIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrBayIndex |
PositiveInteger |
|
|
vpwrModuleIndex |
PositiveInteger |
|
|
vpwrModuleOID |
OBJECT IDENTIFIER |
|
|
vpwrModuleCurrent |
INTEGER |
|
|
vpwrModuleOperStatus |
INTEGER |
|
|
vpwrModuleCapacity |
INTEGER |
|
VpwrPanelIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrPanelBayIndex |
PositiveInteger |
|
|
vpwrPanelModuleIndex |
PositiveInteger |
|
|
vpwrPanelModuleOID |
OBJECT IDENTIFIER |
|
|
vpwrPanelModuleCurrent |
INTEGER |
|
|
vpwrPanelModuleOperStatus |
INTEGER |
|
|
vpwrPanelModuleCapacity |
INTEGER |
|
VpwrBayctrlIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrBayctrlIndex |
PositiveInteger |
|
|
vpwrBayctrlOID |
OBJECT IDENTIFIER |
|
|
vpwrBayctrlCurrent |
INTEGER |
|
|
vpwrBayctrlOperStatus |
INTEGER |
|
|
vpwrBayctrlCapacity |
INTEGER |
|
VpwrAlarmEntry |
|
SEQUENCE |
|
|
|
|
vpwrAlarmIndex |
PositiveInteger |
|
|
vpwrAlarmDescr |
AutonomousType |
|
|
vpwrAlarmTime |
TimeStamp |
|
VpwrBatteryTempEntry |
|
SEQUENCE |
|
|
|
|
vpwrBatteryTempIndex |
INTEGER |
|
|
vpwrBatteryTempName |
DisplayString |
|
|
vpwrBatteryTemp |
INTEGER |
|
ThermalProbeEntry |
|
SEQUENCE |
|
|
|
|
thermalProbeState |
INTEGER |
|
VpwrTrapEntry |
|
SEQUENCE |
|
|
|
|
vpwrTrapIpIndex |
INTEGER |
|
|
vpwrTrapIpAddress |
IpAddress |
|
|
vpwrTrapCriticality |
INTEGER |
|
SysRelayConfigEntry |
|
SEQUENCE |
|
|
|
|
sysRelayIndex |
INTEGER |
|
|
sysRelayDefaultName |
DisplayString |
|
|
sysRelayCustomName |
DisplayString |
|
|
sysRelayAlarmSeverity |
INTEGER |
|
SysAlarmConfigEntry |
|
SEQUENCE |
|
|
|
|
sysAlarmIndex |
INTEGER |
|
|
sysAlarmDefaultName |
DisplayString |
|
|
sysAlarmCustomName |
DisplayString |
|
|
sysAlarmSeverity |
INTEGER |
|
|
sysAlarmToRelayMapping |
DisplayString |
|
|
sysAlarmOperStatus |
INTEGER |
|
SysAuxAlarmConfigEntry |
|
SEQUENCE |
|
|
|
|
sysAuxAlarmIndex |
INTEGER |
|
|
sysAuxAlarmDefaultName |
DisplayString |
|
|
sysAuxAlarmCustomName |
DisplayString |
|
|
sysAuxAlarmSeverity |
INTEGER |
|
|
sysAuxAlarmToRelayMapping |
DisplayString |
|
|
sysAuxAlarmPolarity |
INTEGER |
|
|
sysAuxAlarmOperStatus |
INTEGER |
|
VpwrRingerParameterEntry |
|
SEQUENCE |
|
|
|
|
vpwrRingerIndex |
INTEGER |
|
|
vpwrRingerParameterAdminState |
INTEGER |
|
|
vpwrRingerParameterAcVoltage |
INTEGER |
|
|
vpwrRingerParameterDcVoltage |
INTEGER |
|
|
vpwrRingerParameterFrequency |
INTEGER |
|
VpwrModuleIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrModuleSerialNumber |
DisplayString |
|
|
vpwrModuleModelNumber |
DisplayString |
|
|
vpwrModuleFwVersion |
DisplayString |
|
|
vpwrModuleTestDate |
DisplayString |
|
|
vpwrModuleOperHours |
Counter32 |
|
VpwrPanelModuleIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrPanelModuleSerialNumber |
DisplayString |
|
|
vpwrPanelModuleModelNumber |
DisplayString |
|
|
vpwrPanelModuleFwVersion |
DisplayString |
|
|
vpwrPanelModuleTestDate |
DisplayString |
|
|
vpwrPanelModuleOperHours |
Counter32 |
|
VpwrBayctrlModuleIdentEntry |
|
SEQUENCE |
|
|
|
|
vpwrBayctrlSerialNumber |
DisplayString |
|
|
vpwrBayctrlModelNumber |
DisplayString |
|
|
vpwrBayctrlFwVersion |
DisplayString |
|
|
vpwrBayctrlTestDate |
DisplayString |
|
|
vpwrBayctrlOperHours |
Counter32 |
|
Defined Values
vpwrDcPowerMgt |
1.3.6.1.4.1.13858 |
MIB Version 0.8
Need description here.
History
Add table to retrieve module inventory info
MIB Version 0.7
Dec 1, 05
Fixed HP Openview error
Fixed warnings generated by MG-SOFT
Add table to retrieve rectifier inventory info
MIB Version 0.6
Feb 10, 2004 Added additional traps.
Defined Ringers and other modules.
Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
This fixes errors generated by MG-SOFT mib compiler.
Oct 30, 2002 initial release - version 0.4
|
MODULE-IDENTITY |
|
|
|
vpwrIdentModel |
1.3.6.1.4.1.13858.2.1.2 |
The DC Power Model designation. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
vpwrIdentControllerVersion |
1.3.6.1.4.1.13858.2.1.3 |
The hardware/firmware version(s). This variable
may or may not have the same value as
vpwrIdentAgentSoftwareVersion. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
vpwrIdentAgentSoftwareVersion |
1.3.6.1.4.1.13858.2.1.4 |
The SNMP agent software version. This variable may or
may not have the same value as
vpwrIdentControllerFirmwareVersion. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
vpwrIdentName |
1.3.6.1.4.1.13858.2.1.5 |
A string identifying the system. This object should be
set by the administrator. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
vpwrSystemIdentEntry |
1.3.6.1.4.1.13858.2.1.6.1 |
An entry containing information applicable to a
particular alarm. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrSystemIdentEntry |
|
|
vpwrBayIndex |
1.3.6.1.4.1.13858.2.1.6.1.1 |
Identifies Bay number that this module belongs to.
The possible values are 1 through 16 limited by vpwrSystemShelfCapacity. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrModuleIndex |
1.3.6.1.4.1.13858.2.1.6.1.2 |
This object identifies the module by its position in the shelf.
Module numbering is left to right starting with module 1. So, the
module in the first slot has an index of 1, the next module is 2 and
so on. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrModuleOID |
1.3.6.1.4.1.13858.2.1.6.1.3 |
It indicates the type of the module by specifiying its OID |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OBJECT IDENTIFIER |
|
|
vpwrModuleCurrent |
1.3.6.1.4.1.13858.2.1.6.1.4 |
The meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Current for Rectifier module.
- Not Applicable for LVD module
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrModuleOperStatus |
1.3.6.1.4.1.13858.2.1.6.1.5 |
This object indicates current over all status of the module. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
moduleStatusOK(0), moduleStatusAlarm(1), moduleStatusDisabled(2), moduleStatusRingerAOn(3), moduleStatusRingerBOn(4), moduleStatusUnknown(5) |
|
vpwrModuleCapacity |
1.3.6.1.4.1.13858.2.1.6.1.6 |
The meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Capacity for Rectifier module.
- Not Applicable for LVD module
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrPanelIdentTable |
1.3.6.1.4.1.13858.2.4.1 |
This table describes shelves and modules
that make up the panels.
|
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
VpwrPanelIdentEntry |
|
vpwrPanelIdentEntry |
1.3.6.1.4.1.13858.2.4.1.1 |
An entry containing information applicable to a
particular panel making up the system. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrPanelIdentEntry |
|
|
vpwrPanelBayIndex |
1.3.6.1.4.1.13858.2.4.1.1.1 |
Identifies bay number that this module belongs to.
The possible values are 1 through 16, starting from the top. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrPanelModuleIndex |
1.3.6.1.4.1.13858.2.4.1.1.2 |
This object identifies the module within the panel.
The orentation of modules within the panel is mappable. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrPanelModuleOID |
1.3.6.1.4.1.13858.2.4.1.1.3 |
It indicates the type of the module by specifiying its OID |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OBJECT IDENTIFIER |
|
|
vpwrPanelModuleCurrent |
1.3.6.1.4.1.13858.2.4.1.1.4 |
This is the Current of the first shunt of the module. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrPanelModuleOperStatus |
1.3.6.1.4.1.13858.2.4.1.1.5 |
This object indicates over all status of the module. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
moduleStatusOK(0), moduleStatusAlarm(1) |
|
vpwrPanelModuleCapacity |
1.3.6.1.4.1.13858.2.4.1.1.6 |
This is the overall Capacity of the module and is for reference only. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrBayctrlIdentEntry |
1.3.6.1.4.1.13858.2.5.1.1 |
An entry containing information applicable to a
particular bay controller making up the system. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrBayctrlIdentEntry |
|
|
vpwrBayctrlIndex |
1.3.6.1.4.1.13858.2.5.1.1.1 |
Identifies bay number that this module belongs to.
The possible values are 0 through 15, starting from the top. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrBayctrlOID |
1.3.6.1.4.1.13858.2.5.1.1.2 |
It indicates the type of the module by specifiying its OID |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OBJECT IDENTIFIER |
|
|
vpwrBayctrlCurrent |
1.3.6.1.4.1.13858.2.5.1.1.3 |
This is the total output Current of the bay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrBayctrlOperStatus |
1.3.6.1.4.1.13858.2.5.1.1.4 |
This object indicates over all status of the bay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
moduleStatusOK(0), moduleStatusAlarm(1) |
|
vpwrBayctrlCapacity |
1.3.6.1.4.1.13858.2.5.1.1.5 |
This is the overall Capacity of the bay and is for reference only. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemTempCompensation |
1.3.6.1.4.1.13858.2.2.1 |
This parameter enables/disables temperature compensation.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
tempCompDisabled(0), tempCompEnabled(1) |
|
vpwrSystemTempCompStartTemperature |
1.3.6.1.4.1.13858.2.2.2 |
The temperature at which temperature compensation becomes
active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
25..60 |
|
vpwrSystemTempCompStopVoltage |
1.3.6.1.4.1.13858.2.2.3 |
When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemTempCompensationSlope |
1.3.6.1.4.1.13858.2.2.4 |
The rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..250 |
|
vpwrSystemThermalSenseType |
1.3.6.1.4.1.13858.2.2.5 |
This parameter selects the temperature sensing point for temperature
compensation (in)activation.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
external(0), internal(1) |
|
vpwrSystemHVAlarmSetpoint |
1.3.6.1.4.1.13858.2.2.6 |
System High voltage alarm voltage setting.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemBDAlarmSetpoint |
1.3.6.1.4.1.13858.2.2.7 |
System Battery Discharge voltage setting. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemInternalTempLThreshold |
1.3.6.1.4.1.13858.2.2.8 |
Temperature value at which temperature compensation inactive (clear)
trap would be sent if temperature compensation was active when this
value is reached.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemInternalTempUThreshold |
1.3.6.1.4.1.13858.2.2.9 |
Temperature value at which temperature compensation active (set) trap
would be sent.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemShelfCapacity |
1.3.6.1.4.1.13858.2.3.1 |
It describes the maximum number of shelves that can/are controlled
by the controller. Each shelf is uniquely numbered in the range
from 1 to vpwrShelfCapacity.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..16 |
|
vpwrSystemVoltage |
1.3.6.1.4.1.13858.2.3.2 |
The current system voltage.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemCurrent |
1.3.6.1.4.1.13858.2.3.3 |
The current system current.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemControllerState |
1.3.6.1.4.1.13858.2.3.4 |
Current System state as shown on the enhanced display.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
systemControllerStateUnknown(0), systemControllerStateNormal(1), systemControllerStateChange(2), systemControllerStateAlarm(3), systemControllerStateMenu(4), systemControllerStateIrActive(5) |
|
vpwrSystemInternalTemperature |
1.3.6.1.4.1.13858.2.3.5 |
The current controller internal temperature.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrSystemTempCompensationState |
1.3.6.1.4.1.13858.2.3.6 |
Active or Inactive. Applicable only if temperature compensation is enabled.
This means that the controller is temperature compensating the float voltage.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
systemTempCompInactive(0), systemTempCompActive(1) |
|
vpwrSystemType |
1.3.6.1.4.1.13858.2.3.7 |
This parameter describes the type of the system being managed.
This object is set by Valere Power Inc.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
sysTypeUnknow(0), sysType48V(1), sysType24V(2), sysType12V(3) |
|
vpwrLvdWarningSetpoint |
1.3.6.1.4.1.13858.4.1.1 |
LVD Warning voltage setpoint. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrLvdDisconnectSetpoint |
1.3.6.1.4.1.13858.4.1.2 |
LVD disconnect voltage setpoint. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrLvdReconnectSetpoint |
1.3.6.1.4.1.13858.4.1.3 |
LVD Reconnect voltage setpoint. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrLvdReconnectDelayTimer |
1.3.6.1.4.1.13858.4.1.4 |
The delay time, in seconds, before LVD is reconnected |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
20..240 |
|
vpwrRectifierFVSetpoint |
1.3.6.1.4.1.13858.3.1.1 |
System Float Voltage setting |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrRectifierHVSDSetpoint |
1.3.6.1.4.1.13858.3.1.2 |
System High Voltage Shutdown voltage setting |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrRectifierCurrentLimitAdminState |
1.3.6.1.4.1.13858.3.1.3 |
This parameter allows enabling or disabling boost.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
rectCurrentLimitDisabled(0), rectCurrentLimitEnabled(1) |
|
vpwrRectifierCurrentLimit |
1.3.6.1.4.1.13858.3.1.4 |
Rectifier current limit setpoint |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
5..200 |
|
vpwrAlarmsPresent |
1.3.6.1.4.1.13858.8.1 |
The present number of active alarm conditions. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge32 |
|
|
vpwrAlarmTable |
1.3.6.1.4.1.13858.8.2 |
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.
The vpwrAlarmIndex, for each type of module starts at 1
and is limited by the total number of alarams that can be
generated by the module.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
reflect alarms for different type of modules.
The number of rows in the table at any given time is
reflected by the value of vpwrAlarmsPresent. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
VpwrAlarmEntry |
|
vpwrAlarmEntry |
1.3.6.1.4.1.13858.8.2.1 |
An entry containing information applicable to a
particular alarm. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrAlarmEntry |
|
|
vpwrAlarmIndex |
1.3.6.1.4.1.13858.8.2.1.1 |
Identifies the alarm associated with the module.
It is unique on per module type basis. For example,
multiple rectifiers can have the same alarm and therefore same
vpwrAlarmIndex active at any one time.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
vpwrAlarmDescr |
1.3.6.1.4.1.13858.8.2.1.2 |
A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AutonomousType |
|
|
vpwrAlarmTime |
1.3.6.1.4.1.13858.8.2.1.3 |
The value of sysUpTime when the alarm condition was
detected. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
TimeStamp |
|
|
vpwrBatteryTempEntry |
1.3.6.1.4.1.13858.7.1.1.1 |
An entry containing information applicable to a
particular temperature probe. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrBatteryTempEntry |
|
|
vpwrBatteryTempIndex |
1.3.6.1.4.1.13858.7.1.1.1.1 |
Index into temperature table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrBatteryTemp |
1.3.6.1.4.1.13858.7.1.1.1.3 |
Current temperature as recorded by the probe. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrBatteryTempLThreshold |
1.3.6.1.4.1.13858.7.1.2 |
Temperature value at which a clear trap would be sent.
All three battery temperature must be at or below this value
to trigger this trap.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrBatteryTempUThreshold |
1.3.6.1.4.1.13858.7.1.3 |
Temperature value at which a set trap would be sent.
Any one of the three battery temperatures at or exceeding this limit
would trigger the trap.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTempCompensation |
1.3.6.1.4.1.13858.7.1.4 |
This parameter enables/disables temperature compensation.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
tempCompDisabled(0), tempCompEnabled(1) |
|
batteryTempCompHighStartTemperature |
1.3.6.1.4.1.13858.7.1.5 |
The temperature at which temperature compensation becomes
active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
25..60 |
|
batteryTempCompHighStopVoltage |
1.3.6.1.4.1.13858.7.1.6 |
When temperature compensation is active, batteryTempCompHighStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTempCompHighSlope |
1.3.6.1.4.1.13858.7.1.7 |
The rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..250 |
|
batteryTempCompLowStartTemperature |
1.3.6.1.4.1.13858.7.1.8 |
The temperature at which temperature compensation becomes
active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTempCompLowStopVoltage |
1.3.6.1.4.1.13858.7.1.9 |
When temperature compensation is active, batteryTempCompLowStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTempCompLowSlope |
1.3.6.1.4.1.13858.7.1.10 |
The rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..250 |
|
batteryTempCompRunawayTemperature |
1.3.6.1.4.1.13858.7.1.11 |
The temperature at which system voltage will be set to
batteryTempCompRunawayStopVoltage.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
25..60 |
|
batteryTempCompRunawayStopVoltage |
1.3.6.1.4.1.13858.7.1.12 |
When temperature compensation is enabled, float voltage will be reduced to
batteryTempCompRunawayStopVoltage if temperature
reaches batteryTempCompRunawayTemperature.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTempCompSenseSource |
1.3.6.1.4.1.13858.7.1.13 |
This parameter selects the temperature sensing point for temperature
compensation (in)activation.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
external(0), internal(1) |
|
batteryTempCompRunawayState |
1.3.6.1.4.1.13858.7.1.14 |
This parameter selects the temperature sensing point for temperature
compensation (in)activation.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(0), active(1) |
|
thermalProbeTable |
1.3.6.1.4.1.13858.7.1.15 |
This table describes battery temperature probes.
|
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
ThermalProbeEntry |
|
thermalProbeEntry |
1.3.6.1.4.1.13858.7.1.15.1 |
An entry containing information applicable to a
particular temperature probe. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
ThermalProbeEntry |
|
|
thermalProbeState |
1.3.6.1.4.1.13858.7.1.15.1.1 |
State of thermal probe. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
notPresent(0), present(1), removed(2), shorted(3) |
|
vpwrTrapTable |
1.3.6.1.4.1.13858.9.1 |
A list of possible trap destinations depending upon
the criticality of the trap.
|
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
VpwrTrapEntry |
|
vpwrTrapEntry |
1.3.6.1.4.1.13858.9.1.1 |
An entry containing information applicable to a
particular trap destination. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrTrapEntry |
|
|
vpwrTrapIpIndex |
1.3.6.1.4.1.13858.9.1.1.1 |
Trap Entry Index |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrTrapCriticality |
1.3.6.1.4.1.13858.9.1.1.3 |
Criticality of traps sent to this IP Address |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrTrapClearEventHistory |
32 |
Clear Event history buffer clear request. |
TRAP-TYPE |
|
|
|
vpwrLvdAlarmCBOpen |
1.3.6.1.4.1.13858.4.2.2 |
Circuit Breaker open |
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
vpwrTrapLvdFuseOpen |
1.3.6.1.4.1.13858.4.2.3 |
Fuse open |
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
vpwrLvdAlarmWarning |
1.3.6.1.4.1.13858.4.2.4 |
Plant Voltage below warning threshold |
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
vpwrRectAlarmHVSD |
1.3.6.1.4.1.13858.3.2.4 |
|
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
vpwrRectAlarmUV |
1.3.6.1.4.1.13858.3.2.9 |
|
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
vpwrTrapsMsgString |
1.3.6.1.4.1.13858.11.1 |
Place holder for trap notification message string |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..127) |
|
vpwrTrapUserIpAddress |
1.3.6.1.4.1.13858.11.2 |
Place holder for IP address of the user accessing the system |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
sysRelayConfigEntry |
1.3.6.1.4.1.13858.8.3.1 |
An entry containing information applicable to a
particular temperature probe. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SysRelayConfigEntry |
|
|
sysRelayIndex |
1.3.6.1.4.1.13858.8.3.1.1 |
Index into temperature table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
sysRelayAlarmSeverity |
1.3.6.1.4.1.13858.8.3.1.4 |
Current temperature as recorded by the probe. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
alarmNone(0), alarmMajor(1), alarmMinor(2), alarmMajorAndMinor(3) |
|
sysAlarmConfigEntry |
1.3.6.1.4.1.13858.8.4.1 |
An entry containing information applicable to a
particular temperature probe. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SysAlarmConfigEntry |
|
|
sysAlarmIndex |
1.3.6.1.4.1.13858.8.4.1.1 |
Index into temperature table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
sysAlarmSeverity |
1.3.6.1.4.1.13858.8.4.1.4 |
Alarm Severity as denoted by Major and Minor Alarm Mask |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(0), major(1), minor(2), majorAndMinor(3) |
|
sysAlarmToRelayMapping |
1.3.6.1.4.1.13858.8.4.1.5 |
No additional mapping = 0
Map to Relay A = 1
Map to Relay B = 2
Map to Relay C = 4
Map to Relay D = 8
Map to Relay E = 16
Map to Relay F = 32
Map to Relay A and B = (1 + 2) and so on
The major/minor classification of alarms automatically
associates it with Major/Minor relay. Assigning a null
mapping here does not override sysRelayAlarmSeverity for
the alarm.
It should be used to define mapping to additional relays.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(1..8) |
|
sysAlarmOperStatus |
1.3.6.1.4.1.13858.8.4.1.6 |
Indicates current alarm status |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(0), active(1) |
|
sysAuxAlarmConfigEntry |
1.3.6.1.4.1.13858.8.5.1 |
An entry containing information applicable to a
particular temperature probe. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SysAuxAlarmConfigEntry |
|
|
sysAuxAlarmIndex |
1.3.6.1.4.1.13858.8.5.1.1 |
Index into temperature table |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
sysAuxAlarmSeverity |
1.3.6.1.4.1.13858.8.5.1.4 |
Aux Alarm Severity |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(0), major(1), minor(2), majorAndMinor(3) |
|
sysAuxAlarmToRelayMapping |
1.3.6.1.4.1.13858.8.5.1.5 |
No additional mapping = 0
Map to Relay A = 1
Map to Relay B = 2
Map to Relay C = 4
Map to Relay D = 8
Map to Relay E = 16
Map to Relay F = 32
Map to Relay A and B = (1 + 2) and so on
The major/minor classification of alarms automatically
associates it with Major/Minor relay. Assigning a null
mapping here does not override sysRelayAlarmSeverity for
the alarm.
It should be used to define mapping to additional relays.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(1..8) |
|
sysAuxAlarmPolarity |
1.3.6.1.4.1.13858.8.5.1.6 |
Current temperature as recorded by the probe. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
alarmOnOpen(0), alarmOnClose(1) |
|
sysAuxAlarmOperStatus |
1.3.6.1.4.1.13858.8.5.1.7 |
Indicates current alarm status |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(0), active(1) |
|
sysAlarmComFailState |
1.3.6.1.4.1.13858.8.6 |
Enable/Disable generation of comm fail alarm. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1), other(2) |
|
sysAlarmIShareState |
1.3.6.1.4.1.13858.8.7 |
Enable/Disable generation of current share alarm. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), enabled(1), other(2) |
|
sysAlarmRedundancyState |
1.3.6.1.4.1.13858.8.8 |
Enable/Disable generation of redundancy alarm. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(0), nPlus1(1), nPlus2(2) |
|
vpwrRingerParameterTable |
1.3.6.1.4.1.13858.12.1.1 |
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.
The vpwrAlarmIndex, for each type of module starts at 1
and is limited by the total number of alarams that can be
generated by the module.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
reflect alarms for different type of modules.
The number of rows in the table at any given time is
reflected by the value of vpwrAlarmsPresent. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
VpwrRingerParameterEntry |
|
vpwrRingerParameterEntry |
1.3.6.1.4.1.13858.12.1.1.1 |
An entry containing information applicable to a
particular alarm. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrRingerParameterEntry |
|
|
vpwrRingerIndex |
1.3.6.1.4.1.13858.12.1.1.1.1 |
This parameter allows selecting ringer A or Ringer B as the active ringer.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
vpwrRingerParameterAdminState |
1.3.6.1.4.1.13858.12.1.1.1.2 |
This parameter allows selecting ringer A or Ringer B as the active ringer.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ringerDisabled(0), ringerAOn(1), ringerBOn(2) |
|
vpwrRingerAlarmAOTemp |
1.3.6.1.4.1.13858.12.2.2 |
Ringer A Heatsink Over-Temperature |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
vpwrRingerAlarmAOCurrent |
1.3.6.1.4.1.13858.12.2.3 |
Ringer A Over-Current protection |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
vpwrRingerAlarmBOverTemp |
1.3.6.1.4.1.13858.12.2.5 |
Ringer A Heatsink Over-Temperature |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
vpwrRingerAlarmBOverCurrent |
1.3.6.1.4.1.13858.12.2.6 |
Ringer A Over-Current protection |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
vpwrBoostAdminState |
1.3.6.1.4.1.13858.7.3.1 |
This parameter allows enabling or disabling boost.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
boostDisabled(0), boostEnabled(1) |
|
vpwrBoostVoltage |
1.3.6.1.4.1.13858.7.3.2 |
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
7000..11000 |
|
vpwrBoostDuration |
1.3.6.1.4.1.13858.7.3.3 |
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
vpwrBoostOperState |
1.3.6.1.4.1.13858.7.3.4 |
This parameter allows starting or stoping boost if it is enabled.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
boostInactive(0), boostActive(1) |
|
vpwrBatteryCurrentLimitAdminState |
1.3.6.1.4.1.13858.7.2.1 |
This parameter allows enabling or disabling battery current limit.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
battetyCurrentLimitDisabled(0), battetyCurrentLimitEnabled(1) |
|
vpwrBDTAdminState |
1.3.6.1.4.1.13858.7.4.1 |
Enable /Disable Battery Discharge Test execution.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bdtDisabled(0), bdtEnabled(1) |
|
vpwrBDTDuration |
1.3.6.1.4.1.13858.7.4.2 |
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
17..50 |
|
vpwrBDTAlarmVoltage |
1.3.6.1.4.1.13858.7.4.3 |
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
7000..11000 |
|
vpwrBDTAbortVoltage |
1.3.6.1.4.1.13858.7.4.4 |
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..5600 |
|
vpwrBDTOperState |
1.3.6.1.4.1.13858.7.4.6 |
Start/Stop Battery Discharge Test execution.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bdtInactive(0), bdtActive(1) |
|
vpwrBDTClearAlarm |
1.3.6.1.4.1.13858.7.4.7 |
Clears any active bdt alarm.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
bdtNoAlarm(0), bdtAlarmPresent(1) |
|
vpwrModuleIdentEntry |
1.3.6.1.4.1.13858.6.1.1 |
An entry containing information applicable to a
particular Module. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrModuleIdentEntry |
|
|
vpwrPanelModuleIdentEntry |
1.3.6.1.4.1.13858.6.2.1 |
An entry containing information applicable to a
particular alarm. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrPanelModuleIdentEntry |
|
|
vpwrBayctrlModuleIdentEntry |
1.3.6.1.4.1.13858.6.3.1 |
An entry containing information applicable to a particular bay controller. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
VpwrBayctrlModuleIdentEntry |
|
|