RackMonitor-MIB

File: RackMonitor-MIB.mib (49925 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

IpAddress enterprises OBJECT-TYPE
DisplayString TRAP-TYPE

Defined Types

RmConfigTrapsReceiversEntry  
SEQUENCE    
  trapsIndex INTEGER
  trapsReceiverAddr IpAddress
  receiverCommunityString DisplayString
  receiverSeverityLevel INTEGER
  receiverDescription DisplayString

RmConfigAccessControlEntry  
SEQUENCE    
  accessIndex INTEGER
  accessControlAddr IpAddress
  accessCommunityString DisplayString
  accessControlMode INTEGER

SmSensorEntry  
SEQUENCE    
  smDeviceIndex INTEGER
  smDeviceStatus INTEGER
  smDeviceTemperature INTEGER
  smDeviceTemperatureAlarm INTEGER
  smDeviceHumidity INTEGER
  smDeviceHumidityAlarm INTEGER
  smAlarm1 INTEGER
  smAlarm2 INTEGER

ScSensorEntry  
SEQUENCE    
  scDeviceIndex INTEGER
  scDeviceName DisplayString
  scDeviceState INTEGER

Defined Values

powerware 1.3.6.1.4.1.534
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.534.6
OBJECT IDENTIFIER    

dataCenter 1.3.6.1.4.1.534.6.7
OBJECT IDENTIFIER    

environmentalMonitor 1.3.6.1.4.1.534.6.7.1
OBJECT IDENTIFIER    

insObjects 1.3.6.1.4.1.534.6.7.1.1
OBJECT IDENTIFIER    

rmTraps 1.3.6.1.4.1.534.6.7.1.2
OBJECT IDENTIFIER    

rmIdent 1.3.6.1.4.1.534.6.7.1.1.1
OBJECT IDENTIFIER    

rmConfig 1.3.6.1.4.1.534.6.7.1.1.2
OBJECT IDENTIFIER    

sensorMonitor 1.3.6.1.4.1.534.6.7.1.1.3
OBJECT IDENTIFIER    

sensorConfig 1.3.6.1.4.1.534.6.7.1.1.4
OBJECT IDENTIFIER    

insIdentManufacturer 1.3.6.1.4.1.534.6.7.1.1.1.1
The name of the RackMonitor manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

insIdentModel 1.3.6.1.4.1.534.6.7.1.1.1.2
The RackMonitor Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

insIdentAgentSoftwareVersion 1.3.6.1.4.1.534.6.7.1.1.1.3
The RackMonitor software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

insIdentName 1.3.6.1.4.1.534.6.7.1.1.1.4
A string identifying the RackMonitor. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

rmConfigMibVersion 1.3.6.1.4.1.534.6.7.1.1.2.1
The version of MIB spec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

rmConfigNetwork 1.3.6.1.4.1.534.6.7.1.1.2.2
OBJECT IDENTIFIER    

rmConfigIpAddress 1.3.6.1.4.1.534.6.7.1.1.2.2.1
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

rmConfigGateway 1.3.6.1.4.1.534.6.7.1.1.2.2.2
The default gateway that allow device managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

rmConfigSubnetMask 1.3.6.1.4.1.534.6.7.1.1.2.2.3
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

rmConfigDateTime 1.3.6.1.4.1.534.6.7.1.1.2.3
OBJECT IDENTIFIER    

rmConfigDate 1.3.6.1.4.1.534.6.7.1.1.2.3.1
The date in Environmental Rack Monitor, format is (dd/mm/yyyy)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

rmConfigTime 1.3.6.1.4.1.534.6.7.1.1.2.3.2
The time in Environmental Rack Monitor, format is (hh:mm:ss)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

rmConfigTimeFromNtp 1.3.6.1.4.1.534.6.7.1.1.2.3.3
Enable/disable update of the date and time from the NTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigNtpIpAddress 1.3.6.1.4.1.534.6.7.1.1.2.3.4
NTP IP address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

rmConfigNtpTimeZone 1.3.6.1.4.1.534.6.7.1.1.2.3.5
Enable/disable update of the date and time from the NTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER gMT-1200(1), gMT-1100(2), gMT-1000(3), gMT-0900(4), gMT-0800(5), gMT-0700(6), gMT-0600(7), gMT-0500(8), gMT-0400(9), gMT-0330(10), gMT-0300(11), gMT-0200(12), gMT-0100(13), gMT-0000(14), gMT0100(15), gMT0200(16), gMT0300(17), gMT0330(18), gMT0400(19), gMT0500(20), gMT0530(21), gMT0600(22), gMT0700(23), gMT0800(24), gMT0900(25), gMT1000(26), gMT1100(27), gMT1200(28)  

rmConfigDayLightSaving 1.3.6.1.4.1.534.6.7.1.1.2.3.6
Enable/disable daylight saving for NTP time, if enabled, the time obtained from the NTP will be set one hour in advance to reflect daylight saving status.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigLog 1.3.6.1.4.1.534.6.7.1.1.2.4
OBJECT IDENTIFIER    

rmConfigHistoryLogFrequency 1.3.6.1.4.1.534.6.7.1.1.2.4.1
The frequency of the history log update. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 5..3600  

rmConfigExtHistoryLogFrequency 1.3.6.1.4.1.534.6.7.1.1.2.4.2
The frequency of the extended history log update. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..1440  

rmConfigConfigurationLog 1.3.6.1.4.1.534.6.7.1.1.2.4.3
Enable/Disable Environmental Rack Monitor parameters change logging.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigDhcpStatue 1.3.6.1.4.1.534.6.7.1.1.2.5
Enable or Disable DHCP/BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigPingStatue 1.3.6.1.4.1.534.6.7.1.1.2.6
Enable or Disable Ping Echo capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigTftpStatue 1.3.6.1.4.1.534.6.7.1.1.2.7
Enable or Disable TFTP network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigTelnet 1.3.6.1.4.1.534.6.7.1.1.2.8
OBJECT IDENTIFIER    

rmConfigTelnetStatue 1.3.6.1.4.1.534.6.7.1.1.2.8.1
Enable or Disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigTelnetPortNumber 1.3.6.1.4.1.534.6.7.1.1.2.8.2
Setting the server port for telnet.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

rmConfigHttp 1.3.6.1.4.1.534.6.7.1.1.2.9
OBJECT IDENTIFIER    

rmConfigHttpStatue 1.3.6.1.4.1.534.6.7.1.1.2.9.1
Enable or Disable HTTP access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigHttpPortNumber 1.3.6.1.4.1.534.6.7.1.1.2.9.2
Setting the server port of HTTP.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

rmConfigHttpSecurity 1.3.6.1.4.1.534.6.7.1.1.2.9.3
Enable/Disable HTTP access for read-only users
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigSnmp 1.3.6.1.4.1.534.6.7.1.1.2.10
OBJECT IDENTIFIER    

rmConfigSnmpStatue 1.3.6.1.4.1.534.6.7.1.1.2.10.1
Enable or Disable SNMP access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

rmConfigSnmpPortNumber 1.3.6.1.4.1.534.6.7.1.1.2.10.2
Setting the server port for SNMP.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

rmConfigControl 1.3.6.1.4.1.534.6.7.1.1.2.11
OBJECT IDENTIFIER    

rmConfigResetToDefault 1.3.6.1.4.1.534.6.7.1.1.2.11.1
Reset all parameters of Environmental Rack Monitor to default values
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER reset(1), nothing(2)  

rmConfigRestart 1.3.6.1.4.1.534.6.7.1.1.2.11.2
Restart rm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restart(1), nothing(2)  

rmConfigTrap 1.3.6.1.4.1.534.6.7.1.1.2.12
OBJECT IDENTIFIER    

rmConfigTrapRetryCount 1.3.6.1.4.1.534.6.7.1.1.2.12.1
The count of repeat traps to send to NMS before trap acknowledge received.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

rmConfigTrapRetryTime 1.3.6.1.4.1.534.6.7.1.1.2.12.2
The time between retry traps sent to NMS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

rmConfigTrapAckSignature 1.3.6.1.4.1.534.6.7.1.1.2.12.3
The signature of trap acknowledge.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

rmConfigPollRate 1.3.6.1.4.1.534.6.7.1.1.2.13
The frequency that the Rack Monitor will read from sensors (unit : second).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 3..60  

rmConfigTrapsReceiversTable 1.3.6.1.4.1.534.6.7.1.1.2.14
A list of managers to send traps to. The number of entries is given by the value of rmConfigNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RmConfigTrapsReceiversEntry

rmConfigTrapsReceiversEntry 1.3.6.1.4.1.534.6.7.1.1.2.14.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  RmConfigTrapsReceiversEntry  

trapsIndex 1.3.6.1.4.1.534.6.7.1.1.2.14.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

trapsReceiverAddr 1.3.6.1.4.1.534.6.7.1.1.2.14.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

receiverCommunityString 1.3.6.1.4.1.534.6.7.1.1.2.14.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

receiverSeverityLevel 1.3.6.1.4.1.534.6.7.1.1.2.14.1.4
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), severe(3)  

receiverDescription 1.3.6.1.4.1.534.6.7.1.1.2.14.1.5
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

rmConfigAccessControlTable 1.3.6.1.4.1.534.6.7.1.1.2.15
A list of managers which can access rm with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RmConfigAccessControlEntry

rmConfigAccessControlEntry 1.3.6.1.4.1.534.6.7.1.1.2.15.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  RmConfigAccessControlEntry  

accessIndex 1.3.6.1.4.1.534.6.7.1.1.2.15.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

accessControlAddr 1.3.6.1.4.1.534.6.7.1.1.2.15.1.2
The IP address of the manager to access RackMonitor
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

accessCommunityString 1.3.6.1.4.1.534.6.7.1.1.2.15.1.3
The community name to use in the manager when access RackMonitor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

accessControlMode 1.3.6.1.4.1.534.6.7.1.1.2.15.1.4
Access type, only read/Write access type can change parameter of RackMonitor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), read-write(2), notAccess(3)  

rmConfigTemperatureUnit 1.3.6.1.4.1.534.6.7.1.1.2.16
The temperature unit of the system, can be Celsius or Fahrenheit
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

rmConfigDateFormat 1.3.6.1.4.1.534.6.7.1.1.2.17
The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER mm-dd-yyyy(1), dd-mm-yyyy(2), yyyy-mm-dd(3), dd-mmm-yyyy(4)  

smSensorNumber 1.3.6.1.4.1.534.6.7.1.1.3.1
The number of sensors that can be monitored.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

smSensorTable 1.3.6.1.4.1.534.6.7.1.1.3.2
A list of sensor devices to be monitored.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SmSensorEntry

smSensorEntry 1.3.6.1.4.1.534.6.7.1.1.3.2.1
The sensor device.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SmSensorEntry  

smDeviceIndex 1.3.6.1.4.1.534.6.7.1.1.3.2.1.1
The index to a sensor device entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

smDeviceStatus 1.3.6.1.4.1.534.6.7.1.1.3.2.1.2
The device type plugged into RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), eMD-HT(3), eMD-T(4)  

smDeviceTemperature 1.3.6.1.4.1.534.6.7.1.1.3.2.1.3
The temperature of sensor on device RackMonitor, the unit is 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

smDeviceTemperatureAlarm 1.3.6.1.4.1.534.6.7.1.1.3.2.1.4
The status of temperature sensor on device RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)  

smDeviceHumidity 1.3.6.1.4.1.534.6.7.1.1.3.2.1.5
The humidity of sensor on device RackMonitor, the unit is 0.1%.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

smDeviceHumidityAlarm 1.3.6.1.4.1.534.6.7.1.1.3.2.1.6
The device type plugged into RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)  

smAlarm1 1.3.6.1.4.1.534.6.7.1.1.3.2.1.7
The device type plugged into RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

smAlarm2 1.3.6.1.4.1.534.6.7.1.1.3.2.1.8
The device type plugged into RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknow(1), disabled(2), active(3), inactive(4)  

scSensorNumber 1.3.6.1.4.1.534.6.7.1.1.4.1
The number of sensors that can be plugged into RackMonitor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

scSensorTable 1.3.6.1.4.1.534.6.7.1.1.4.2
A list of sensor devices to be configured.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ScSensorEntry

scSensorEntry 1.3.6.1.4.1.534.6.7.1.1.4.2.1
The sensor device.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  ScSensorEntry  

scDeviceIndex 1.3.6.1.4.1.534.6.7.1.1.4.2.1.1
The index to a sensor device entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

scDeviceName 1.3.6.1.4.1.534.6.7.1.1.4.2.1.2
The name of the sensor device for identification.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scDeviceState 1.3.6.1.4.1.534.6.7.1.1.4.2.1.3
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

scSensor1 1.3.6.1.4.1.534.6.7.1.1.4.3
OBJECT IDENTIFIER    

scSensor1DeviceName 1.3.6.1.4.1.534.6.7.1.1.4.3.1
The name of sensor device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor1DeviceState 1.3.6.1.4.1.534.6.7.1.1.4.3.2
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

scSensor1Temperature 1.3.6.1.4.1.534.6.7.1.1.4.3.3
OBJECT IDENTIFIER    

scSensor1TemperatureName 1.3.6.1.4.1.534.6.7.1.1.4.3.3.1
The temperature sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor1TemperatureLowWarning 1.3.6.1.4.1.534.6.7.1.1.4.3.3.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1TemperatureLowCritical 1.3.6.1.4.1.534.6.7.1.1.4.3.3.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1TemperatureHighWarning 1.3.6.1.4.1.534.6.7.1.1.4.3.3.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1TemperatureHighCritical 1.3.6.1.4.1.534.6.7.1.1.4.3.3.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1TemperatureHysteresis 1.3.6.1.4.1.534.6.7.1.1.4.3.3.6
The set value to prevent too many alarms when temperature is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1TemperatureCalibration 1.3.6.1.4.1.534.6.7.1.1.4.3.3.7
The set value to get the correct temperature according to the reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)  

scSensor1TemperatureLowWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.3.8
Enable/Disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1TemperatureLowCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.3.9
Enable/Disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1TemperatureHighWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.3.10
Enable/Disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1TemperatureHighCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.3.11
Enable/disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1Humidity 1.3.6.1.4.1.534.6.7.1.1.4.3.4
OBJECT IDENTIFIER    

scSensor1HumdityName 1.3.6.1.4.1.534.6.7.1.1.4.3.4.1
The humidity sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor1HumidityLowWarning 1.3.6.1.4.1.534.6.7.1.1.4.3.4.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1HumidityLowCritical 1.3.6.1.4.1.534.6.7.1.1.4.3.4.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1HumidityHighWarning 1.3.6.1.4.1.534.6.7.1.1.4.3.4.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1HumidityHighCritical 1.3.6.1.4.1.534.6.7.1.1.4.3.4.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1HumidityHysteresis 1.3.6.1.4.1.534.6.7.1.1.4.3.4.6
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1HumidityCalibration 1.3.6.1.4.1.534.6.7.1.1.4.3.4.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)  

scSensor1HumidityLowWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.4.8
Enable/Disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1HumidityLowCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.4.9
Enable/Disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1HumidityHighWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.4.10
Enable/Disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1HumidityHighCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.3.4.11
Enable/Disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor1Alarm1 1.3.6.1.4.1.534.6.7.1.1.4.3.5
OBJECT IDENTIFIER    

scSensor1Alarm1Name 1.3.6.1.4.1.534.6.7.1.1.4.3.5.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor1Alarm1State 1.3.6.1.4.1.534.6.7.1.1.4.3.5.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

scSensor1Alarm1Hysteresis 1.3.6.1.4.1.534.6.7.1.1.4.3.5.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor1Alarm2 1.3.6.1.4.1.534.6.7.1.1.4.3.6
OBJECT IDENTIFIER    

scSensor1Alarm2Name 1.3.6.1.4.1.534.6.7.1.1.4.3.6.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor1Alarm2State 1.3.6.1.4.1.534.6.7.1.1.4.3.6.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

scSensor1Alarm2Hysteresis 1.3.6.1.4.1.534.6.7.1.1.4.3.6.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2 1.3.6.1.4.1.534.6.7.1.1.4.4
OBJECT IDENTIFIER    

scSensor2DeviceName 1.3.6.1.4.1.534.6.7.1.1.4.4.1
The name of sensor device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor2DeviceState 1.3.6.1.4.1.534.6.7.1.1.4.4.2
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

scSensor2Temperature 1.3.6.1.4.1.534.6.7.1.1.4.4.3
OBJECT IDENTIFIER    

scSensor2TemperatureName 1.3.6.1.4.1.534.6.7.1.1.4.4.3.1
The temperature sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor2TemperatureLowWarning 1.3.6.1.4.1.534.6.7.1.1.4.4.3.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2TemperatureLowCritical 1.3.6.1.4.1.534.6.7.1.1.4.4.3.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2TemperatureHighWarning 1.3.6.1.4.1.534.6.7.1.1.4.4.3.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2TemperatureHighCritical 1.3.6.1.4.1.534.6.7.1.1.4.4.3.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2TemperatureHysteresis 1.3.6.1.4.1.534.6.7.1.1.4.4.3.6
The set value to prevent too many alarms when temperature is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2TemperatureCalibration 1.3.6.1.4.1.534.6.7.1.1.4.4.3.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)  

scSensor2TemperatureLowWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.3.8
Enable/Disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2TemperatureLowCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.3.9
Enable/Disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2TemperatureHighWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.3.10
Enable/Disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2TemperatureHighCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.3.11
Enable/Disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2Humidity 1.3.6.1.4.1.534.6.7.1.1.4.4.4
OBJECT IDENTIFIER    

scSensor2HumdityName 1.3.6.1.4.1.534.6.7.1.1.4.4.4.1
The humidity sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor2HumidityLowWarning 1.3.6.1.4.1.534.6.7.1.1.4.4.4.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2HumidityLowCritical 1.3.6.1.4.1.534.6.7.1.1.4.4.4.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2HumidityHighWarning 1.3.6.1.4.1.534.6.7.1.1.4.4.4.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2HumidityHighCritical 1.3.6.1.4.1.534.6.7.1.1.4.4.4.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2HumidityHysteresis 1.3.6.1.4.1.534.6.7.1.1.4.4.4.6
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2HumidityCalibration 1.3.6.1.4.1.534.6.7.1.1.4.4.4.7
The set value to get the correct temperature according to the reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)  

scSensor2HumidityLowWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.4.8
Enable/Disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2HumidityLowCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.4.9
Enable/Disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2HumidityHighWarningStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.4.10
Enable/Disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2HumidityHighCriticalStatus 1.3.6.1.4.1.534.6.7.1.1.4.4.4.11
Enable/Disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

scSensor2Alarm1 1.3.6.1.4.1.534.6.7.1.1.4.4.5
OBJECT IDENTIFIER    

scSensor2Alarm1Name 1.3.6.1.4.1.534.6.7.1.1.4.4.5.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor2Alarm1State 1.3.6.1.4.1.534.6.7.1.1.4.4.5.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

scSensor2Alarm1Hysteresis 1.3.6.1.4.1.534.6.7.1.1.4.4.5.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

scSensor2Alarm2 1.3.6.1.4.1.534.6.7.1.1.4.4.6
OBJECT IDENTIFIER    

scSensor2Alarm2Name 1.3.6.1.4.1.534.6.7.1.1.4.4.6.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

scSensor2Alarm2State 1.3.6.1.4.1.534.6.7.1.1.4.4.6.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

scSensor2Alarm2Hysteresis 1.3.6.1.4.1.534.6.7.1.1.4.4.6.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

rmCommunicationRestored 1
INFORMATION: Communication between RackMonitor and sensor had established.
TRAP-TYPE    

rmCommunicationLost 2
WARNING: Communication between RackMonitor and sensor had lost.
TRAP-TYPE    

rmAlarm1Inactive 3
INFORMATION: Alarm1 of sensor had return from active state.
TRAP-TYPE    

rmAlarm1Active 4
WARNING: Alarm1 has become active.
TRAP-TYPE    

rmAlarm2Inactive 5
INFORMATION: Alarm2 of sensor has returned to normal state.
TRAP-TYPE    

rmAlarm2Active 6
WARNING: Alarm2 had became active.
TRAP-TYPE    

rmTemperatureNotHighWarning 7
INFORMATION: The temperature of sensor had return from High warning to normal.
TRAP-TYPE    

rmTemperatureHighWarning 8
WARNING: The temperature of sensor was higher than High warning set point.
TRAP-TYPE    

rmTemperatureNotLowWarning 9
INFORMATION: The temperature of sensor had return from low warning to normal.
TRAP-TYPE    

rmTemperatureLowWarning 10
WARNING: The temperature of sensor was lower than low warning set point.
TRAP-TYPE    

rmTemperatureNotHighCritical 11
INFORMATION: The temperature of sensor lower than high critical set point.
TRAP-TYPE    

rmTemperatureHighCritical 12
CRITICAL: The temperature of sensor was higher than high critical set point.
TRAP-TYPE    

rmTemperatureNotLowCritical 13
INFORMATION: The temperature of sensor was higher than low critical set point.
TRAP-TYPE    

rmTemperatureLowCritical 14
CRITICAL: The temperature of sensor was lower than low critical set point.
TRAP-TYPE    

rmHumidityNotHighWarning 15
INFORMATION: The humidity of sensor had return from High warning to normal.
TRAP-TYPE    

rmHumidityHighWarning 16
WARNING: The humidity of sensor was higher than High warning set point.
TRAP-TYPE    

rmHumidityNotLowWarning 17
INFORMATION: The humidity of sensor had return from low warning to normal.
TRAP-TYPE    

rmHumidityLowWarning 18
WARNING: The humidity of sensor was lower than low warning set point.
TRAP-TYPE    

rmHumidityNotHighCritical 19
INFORMATION: The humidity of sensor lower than high critical set point.
TRAP-TYPE    

rmHumidityHighCritical 20
CRITICAL: The humidity of sensor was higher than high critical set point.
TRAP-TYPE    

rmHumidityNotLowCritical 21
INFORMATION: The humidity of sensor was higher than low critical set point.
TRAP-TYPE    

rmHumidityLowCritical 22
CRITICAL: The humidity of sensor was lower than low critical set point.
TRAP-TYPE