ROOMALERT24E-MIB

File: ROOMALERT24E-MIB.mib (22170 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC-1215

Imported symbols

enterprises IpAddress Counter
TimeTicks OBJECT-TYPE TRAP-TYPE

Defined Values

avtech 1.3.6.1.4.1.20916
OBJECT IDENTIFIER    

products 1.3.6.1.4.1.20916.1
OBJECT IDENTIFIER    

roomalert24e 1.3.6.1.4.1.20916.1.5
OBJECT IDENTIFIER    

sensors 1.3.6.1.4.1.20916.1.5.1
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.20916.1.5.2
OBJECT IDENTIFIER    

internal 1.3.6.1.4.1.20916.1.5.1.1
OBJECT IDENTIFIER    

temperature 1.3.6.1.4.1.20916.1.5.1.1.1
OBJECT IDENTIFIER    

humidity 1.3.6.1.4.1.20916.1.5.1.1.2
OBJECT IDENTIFIER    

heat-index 1.3.6.1.4.1.20916.1.5.1.1.3
OBJECT IDENTIFIER    

digital 1.3.6.1.4.1.20916.1.5.1.2
OBJECT IDENTIFIER    

digital-sen1 1.3.6.1.4.1.20916.1.5.1.2.1
OBJECT IDENTIFIER    

digital-sen2 1.3.6.1.4.1.20916.1.5.1.2.2
OBJECT IDENTIFIER    

digital-sen3 1.3.6.1.4.1.20916.1.5.1.2.3
OBJECT IDENTIFIER    

digital-sen4 1.3.6.1.4.1.20916.1.5.1.2.4
OBJECT IDENTIFIER    

digital-sen5 1.3.6.1.4.1.20916.1.5.1.2.5
OBJECT IDENTIFIER    

digital-sen6 1.3.6.1.4.1.20916.1.5.1.2.6
OBJECT IDENTIFIER    

switch 1.3.6.1.4.1.20916.1.5.1.3
OBJECT IDENTIFIER    

internal-tempf 1.3.6.1.4.1.20916.1.5.1.1.1.1
The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-tempc 1.3.6.1.4.1.20916.1.5.1.1.1.2
The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-humidity 1.3.6.1.4.1.20916.1.5.1.1.2.1
The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-heat-index 1.3.6.1.4.1.20916.1.5.1.1.3.1
The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-heat-indexc 1.3.6.1.4.1.20916.1.5.1.1.3.2
The internal heat index reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-1 1.3.6.1.4.1.20916.1.5.1.2.1.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-2 1.3.6.1.4.1.20916.1.5.1.2.1.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-3 1.3.6.1.4.1.20916.1.5.1.2.1.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-4 1.3.6.1.4.1.20916.1.5.1.2.1.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-5 1.3.6.1.4.1.20916.1.5.1.2.1.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-1 1.3.6.1.4.1.20916.1.5.1.2.2.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-2 1.3.6.1.4.1.20916.1.5.1.2.2.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-3 1.3.6.1.4.1.20916.1.5.1.2.2.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-4 1.3.6.1.4.1.20916.1.5.1.2.2.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-5 1.3.6.1.4.1.20916.1.5.1.2.2.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen3-1 1.3.6.1.4.1.20916.1.5.1.2.3.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen3-2 1.3.6.1.4.1.20916.1.5.1.2.3.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen3-3 1.3.6.1.4.1.20916.1.5.1.2.3.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen3-4 1.3.6.1.4.1.20916.1.5.1.2.3.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen3-5 1.3.6.1.4.1.20916.1.5.1.2.3.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen4-1 1.3.6.1.4.1.20916.1.5.1.2.4.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen4-2 1.3.6.1.4.1.20916.1.5.1.2.4.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen4-3 1.3.6.1.4.1.20916.1.5.1.2.4.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen4-4 1.3.6.1.4.1.20916.1.5.1.2.4.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen4-5 1.3.6.1.4.1.20916.1.5.1.2.4.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen5-1 1.3.6.1.4.1.20916.1.5.1.2.5.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen5-2 1.3.6.1.4.1.20916.1.5.1.2.5.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen5-3 1.3.6.1.4.1.20916.1.5.1.2.5.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen5-4 1.3.6.1.4.1.20916.1.5.1.2.5.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen5-5 1.3.6.1.4.1.20916.1.5.1.2.5.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen6-1 1.3.6.1.4.1.20916.1.5.1.2.6.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen6-2 1.3.6.1.4.1.20916.1.5.1.2.6.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen6-3 1.3.6.1.4.1.20916.1.5.1.2.6.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen6-4 1.3.6.1.4.1.20916.1.5.1.2.6.4
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen6-5 1.3.6.1.4.1.20916.1.5.1.2.6.5
If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

switch-sen1 1.3.6.1.4.1.20916.1.5.1.3.1
The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen2 1.3.6.1.4.1.20916.1.5.1.3.2
The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen3 1.3.6.1.4.1.20916.1.5.1.3.3
The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen4 1.3.6.1.4.1.20916.1.5.1.3.4
The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen5 1.3.6.1.4.1.20916.1.5.1.3.5
The reading for switch sensor 5 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen6 1.3.6.1.4.1.20916.1.5.1.3.6
The reading for switch sensor 6 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen7 1.3.6.1.4.1.20916.1.5.1.3.7
The reading for switch sensor 7 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen8 1.3.6.1.4.1.20916.1.5.1.3.8
The reading for switch sensor 8 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen9 1.3.6.1.4.1.20916.1.5.1.3.9
The reading for switch sensor 9 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen10 1.3.6.1.4.1.20916.1.5.1.3.10
The reading for switch sensor 10 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen11 1.3.6.1.4.1.20916.1.5.1.3.11
The reading for switch sensor 11 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen12 1.3.6.1.4.1.20916.1.5.1.3.12
The reading for switch sensor 12 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen13 1.3.6.1.4.1.20916.1.5.1.3.13
The reading for switch sensor 13 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen14 1.3.6.1.4.1.20916.1.5.1.3.14
The reading for switch sensor 14 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen15 1.3.6.1.4.1.20916.1.5.1.3.15
The reading for switch sensor 15 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-sen16 1.3.6.1.4.1.20916.1.5.1.3.16
The reading for switch sensor 16 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

alarmmessage 1.3.6.1.4.1.20916.1.5.2.1
Last Alarm Message
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

tempalarm1-24e 1
A tempalarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE    

room-alert-24e-snmp-trap 2
A room-alert-24e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable.
TRAP-TYPE    

tempalarm2-24e 3
A tempalarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE    

tempclear2-24e 4
A tempclear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

tempalarm3-24e 5
A tempalarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE    

tempclear3-24e 6
A tempclear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityalarm1-24e 7
A humidityalarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE    

humidityclear1-24e 8
A humidityclear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityalarm2-24e 9
A humidityalarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE    

humidityclear2-24e 10
A humidityclear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityalarm3-24e 11
A humidityalarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE    

humidityclear3-24e 12
A humidityclear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

switchalarm1-24e 13
A switchalarm1 trap signifies that switch sensor 1 is in an alarm state.
TRAP-TYPE    

switchclear1-24e 14
A switchclear1 trap signifies that the switch sensor 1 has returned to a normal state.
TRAP-TYPE    

switchalarm2-24e 15
A switchalarm2 trap signifies that switch sensor 2 is in an alarm state.
TRAP-TYPE    

switchclear2-24e 16
A switchclear2 trap signifies that the switch sensor 2 has returned to a normal state.
TRAP-TYPE    

switchalarm3-24e 17
A switchalarm1 trap signifies that switch sensor 1 is in an alarm state.
TRAP-TYPE    

switchclear3-24e 18
A switchclear3 trap signifies that the switch sensor 3 has returned to a normal state.
TRAP-TYPE    

switchalarm4-24e 19
A switchalarm4 trap signifies that switch sensor 4 is in an alarm state.
TRAP-TYPE    

switchclear4-24e 20
A switchclear4 trap signifies that the switch sensor 4 has returned to a normal state.
TRAP-TYPE    

switchalarm5-24e 21
A switchalarm5 trap signifies that switch sensor 5 is in an alarm state.
TRAP-TYPE    

switchclear5-24e 22
A switchclear5 trap signifies that the switch sensor 5 has returned to a normal state.
TRAP-TYPE    

switchalarm6-24e 23
A switchalarm6 trap signifies that switch sensor 6 is in an alarm state.
TRAP-TYPE    

switchclear6-24e 24
A switchclear6 trap signifies that the switch sensor 6 has returned to a normal state.
TRAP-TYPE    

switchalarm7-24e 25
A switchalarm7 trap signifies that switch sensor 7 is in an alarm state.
TRAP-TYPE    

switchclear7-24e 26
A switchclear7 trap signifies that the switch sensor 7 has returned to a normal state.
TRAP-TYPE    

switchalarm8-24e 27
A switchalarm8 trap signifies that switch sensor 8 is in an alarm state.
TRAP-TYPE    

switchclear8-24e 28
A switchclear8 trap signifies that the switch sensor 8 has returned to a normal state.
TRAP-TYPE