RITTAL-CMC-TC-MIB

File: RITTAL-CMC-TC-MIB.mib (153093 bytes)

Imported modules

RFC1155-SMI RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

enterprises DisplayString sysName
sysDescr sysContact sysLocation
OBJECT-TYPE TRAP-TYPE

Defined Types

CmcTcUnit1SensorEntry  
SEQUENCE    
  unit1SensorIndex INTEGER
  unit1SensorType INTEGER
  unit1SensorText DisplayString
  unit1SensorStatus INTEGER
  unit1SensorValue INTEGER
  unit1SensorSetHigh INTEGER
  unit1SensorSetLow INTEGER
  unit1SensorSetWarn INTEGER
  unit1SensorHysteresis INTEGER
  unit1SensorDisplayFactor INTEGER
  unit1SensorScaleStart INTEGER
  unit1SensorScaleEnd INTEGER
  unit1SensorUnit DisplayString
  unit1SensorInfo DisplayString

CmcTcUnit1OutputEntry  
SEQUENCE    
  unit1OutputIndex INTEGER
  unit1OutputType INTEGER
  unit1OutputText DisplayString
  unit1OutputStatus INTEGER
  unit1OutputValue INTEGER
  unit1OutputSet INTEGER
  unit1OutputConfig INTEGER
  unit1OutputDelay INTEGER
  unit1OutputTimeoutAction INTEGER

CmcTcUnit1MsgEntry  
SEQUENCE    
  unit1MsgIndex INTEGER
  unit1MsgText DisplayString
  unit1MsgStatus INTEGER
  unit1MsgRelay INTEGER
  unit1MsgBeeper INTEGER
  unit1MsgTrap1 INTEGER
  unit1MsgTrap2 INTEGER
  unit1MsgTrap3 INTEGER
  unit1MsgTrap4 INTEGER
  unit1MsgQuit INTEGER
  unit1MsgDelay INTEGER

CmcTcUnit2SensorEntry  
SEQUENCE    
  unit2SensorIndex INTEGER
  unit2SensorType INTEGER
  unit2SensorText DisplayString
  unit2SensorStatus INTEGER
  unit2SensorValue INTEGER
  unit2SensorSetHigh INTEGER
  unit2SensorSetLow INTEGER
  unit2SensorSetWarn INTEGER
  unit2SensorHysteresis INTEGER
  unit2SensorDisplayFactor INTEGER
  unit2SensorScaleStart INTEGER
  unit2SensorScaleEnd INTEGER
  unit2SensorUnit DisplayString
  unit2SensorInfo DisplayString

CmcTcUnit2OutputEntry  
SEQUENCE    
  unit2OutputIndex INTEGER
  unit2OutputType INTEGER
  unit2OutputText DisplayString
  unit2OutputStatus INTEGER
  unit2OutputValue INTEGER
  unit2OutputSet INTEGER
  unit2OutputConfig INTEGER
  unit2OutputDelay INTEGER
  unit2OutputTimeoutAction INTEGER

CmcTcUnit2MsgEntry  
SEQUENCE    
  unit2MsgIndex INTEGER
  unit2MsgText DisplayString
  unit2MsgStatus INTEGER
  unit2MsgRelay INTEGER
  unit2MsgBeeper INTEGER
  unit2MsgTrap1 INTEGER
  unit2MsgTrap2 INTEGER
  unit2MsgTrap3 INTEGER
  unit2MsgTrap4 INTEGER
  unit2MsgQuit INTEGER
  unit2MsgDelay INTEGER

CmcTcUnit3SensorEntry  
SEQUENCE    
  unit3SensorIndex INTEGER
  unit3SensorType INTEGER
  unit3SensorText DisplayString
  unit3SensorStatus INTEGER
  unit3SensorValue INTEGER
  unit3SensorSetHigh INTEGER
  unit3SensorSetLow INTEGER
  unit3SensorSetWarn INTEGER
  unit3SensorHysteresis INTEGER
  unit3SensorDisplayFactor INTEGER
  unit3SensorScaleStart INTEGER
  unit3SensorScaleEnd INTEGER
  unit3SensorUnit DisplayString
  unit3SensorInfo DisplayString

CmcTcUnit3OutputEntry  
SEQUENCE    
  unit3OutputIndex INTEGER
  unit3OutputType INTEGER
  unit3OutputText DisplayString
  unit3OutputStatus INTEGER
  unit3OutputValue INTEGER
  unit3OutputSet INTEGER
  unit3OutputConfig INTEGER
  unit3OutputDelay INTEGER
  unit3OutputTimeoutAction INTEGER

CmcTcUnit3MsgEntry  
SEQUENCE    
  unit3MsgIndex INTEGER
  unit3MsgText DisplayString
  unit3MsgStatus INTEGER
  unit3MsgRelay INTEGER
  unit3MsgBeeper INTEGER
  unit3MsgTrap1 INTEGER
  unit3MsgTrap2 INTEGER
  unit3MsgTrap3 INTEGER
  unit3MsgTrap4 INTEGER
  unit3MsgQuit INTEGER
  unit3MsgDelay INTEGER

CmcTcUnit4SensorEntry  
SEQUENCE    
  unit4SensorIndex INTEGER
  unit4SensorType INTEGER
  unit4SensorText DisplayString
  unit4SensorStatus INTEGER
  unit4SensorValue INTEGER
  unit4SensorSetHigh INTEGER
  unit4SensorSetLow INTEGER
  unit4SensorSetWarn INTEGER
  unit4SensorHysteresis INTEGER
  unit4SensorDisplayFactor INTEGER
  unit4SensorScaleStart INTEGER
  unit4SensorScaleEnd INTEGER
  unit4SensorUnit DisplayString
  unit4SensorInfo DisplayString

CmcTcUnit4OutputEntry  
SEQUENCE    
  unit4OutputIndex INTEGER
  unit4OutputType INTEGER
  unit4OutputText DisplayString
  unit4OutputStatus INTEGER
  unit4OutputValue INTEGER
  unit4OutputSet INTEGER
  unit4OutputConfig INTEGER
  unit4OutputDelay INTEGER
  unit4OutputTimeoutAction INTEGER

CmcTcUnit4MsgEntry  
SEQUENCE    
  unit4MsgIndex INTEGER
  unit4MsgText DisplayString
  unit4MsgStatus INTEGER
  unit4MsgRelay INTEGER
  unit4MsgBeeper INTEGER
  unit4MsgTrap1 INTEGER
  unit4MsgTrap2 INTEGER
  unit4MsgTrap3 INTEGER
  unit4MsgTrap4 INTEGER
  unit4MsgQuit INTEGER
  unit4MsgDelay INTEGER

CmcTcValuesEntry  
SEQUENCE    
  valuesIndex INTEGER
  valuesText DisplayString
  valuesStatus INTEGER
  valuesValue INTEGER
  valuesSetHigh INTEGER
  valuesSetLow INTEGER
  valuesHysteresis INTEGER

CmcTcTimerEntry  
SEQUENCE    
  cmcTcTimerIndex INTEGER
  cmcTcTimerStatus INTEGER
  cmcTcTimerDayOfWeek INTEGER
  cmcTcTimeOn DisplayString
  cmcTcTimeOff DisplayString
  cmcTcTimeControl INTEGER
  cmcTcTimerFunction INTEGER

CmcTcTrapTableEntry  
SEQUENCE    
  trapIndex INTEGER
  trapStatus INTEGER
  trapIPaddress DisplayString

Defined Values

rittal 1.3.6.1.4.1.2606
OBJECT IDENTIFIER    

cmcTc 1.3.6.1.4.1.2606.4
OBJECT IDENTIFIER    

cmcTcMibRev 1.3.6.1.4.1.2606.4.1
OBJECT IDENTIFIER    

cmcTcStatus 1.3.6.1.4.1.2606.4.2
OBJECT IDENTIFIER    

cmcTcStatusSensorUnit1 1.3.6.1.4.1.2606.4.2.3
OBJECT IDENTIFIER    

cmcTcStatusUnit1Sensors 1.3.6.1.4.1.2606.4.2.3.5
OBJECT IDENTIFIER    

cmcTcStatusUnit1Outputs 1.3.6.1.4.1.2606.4.2.3.6
OBJECT IDENTIFIER    

cmcTcStatusUnit1Msg 1.3.6.1.4.1.2606.4.2.3.7
OBJECT IDENTIFIER    

cmcTcStatusSensorUnit2 1.3.6.1.4.1.2606.4.2.4
OBJECT IDENTIFIER    

cmcTcStatusUnit2Sensors 1.3.6.1.4.1.2606.4.2.4.5
OBJECT IDENTIFIER    

cmcTcStatusUnit2Outputs 1.3.6.1.4.1.2606.4.2.4.6
OBJECT IDENTIFIER    

cmcTcStatusUnit2Msg 1.3.6.1.4.1.2606.4.2.4.7
OBJECT IDENTIFIER    

cmcTcStatusSensorUnit3 1.3.6.1.4.1.2606.4.2.5
OBJECT IDENTIFIER    

cmcTcStatusUnit3Sensors 1.3.6.1.4.1.2606.4.2.5.5
OBJECT IDENTIFIER    

cmcTcStatusUnit3Outputs 1.3.6.1.4.1.2606.4.2.5.6
OBJECT IDENTIFIER    

cmcTcStatusUnit3Msg 1.3.6.1.4.1.2606.4.2.5.7
OBJECT IDENTIFIER    

cmcTcStatusSensorUnit4 1.3.6.1.4.1.2606.4.2.6
OBJECT IDENTIFIER    

cmcTcStatusUnit4Sensors 1.3.6.1.4.1.2606.4.2.6.5
OBJECT IDENTIFIER    

cmcTcStatusUnit4Outputs 1.3.6.1.4.1.2606.4.2.6.6
OBJECT IDENTIFIER    

cmcTcStatusUnit4Msg 1.3.6.1.4.1.2606.4.2.6.7
OBJECT IDENTIFIER    

cmcTcStatusExtUnit 1.3.6.1.4.1.2606.4.2.7
OBJECT IDENTIFIER    

cmcTcSetup 1.3.6.1.4.1.2606.4.3
OBJECT IDENTIFIER    

cmcTcSetupGeneral 1.3.6.1.4.1.2606.4.3.1
OBJECT IDENTIFIER    

cmcTcTimerTable1 1.3.6.1.4.1.2606.4.3.1.8
OBJECT IDENTIFIER    

cmcTcTrapControl 1.3.6.1.4.1.2606.4.4
OBJECT IDENTIFIER    

cmcTcTraps 1.3.6.1.4.1.2606.4.4.7
OBJECT IDENTIFIER    

cmcTcControl 1.3.6.1.4.1.2606.4.5
OBJECT IDENTIFIER    

cmcTcMibMajRev 1.3.6.1.4.1.2606.4.1.1
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cmcTcMibMinRev 1.3.6.1.4.1.2606.4.1.2
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

cmcTcMibCondition 1.3.6.1.4.1.2606.4.1.3
The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major problem (red LED on CMC) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on CMC)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4), configChanged(5)  

cmcTcStatusDeviceCMC 1.3.6.1.4.1.2606.4.2.1
General Status of CMC-TC unit itself (1) failed (2) OK
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER failed(1), ok(2)  

cmcTcUnitsConnected 1.3.6.1.4.1.2606.4.2.2
Number of sensor units connected to the CMC, Port 1 to 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit1TypeOfDevice 1.3.6.1.4.1.2606.4.2.3.1
Type of sensor unit connected to port 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13), unitFuelCell(14), unitDRC(15), unitTECooler(16), unitPSMMetered32(17), unitPSM8x8(18), unitPSM6x6Schuko(19), unitPSM6x6C19(20)  

cmcTcUnit1Text 1.3.6.1.4.1.2606.4.2.3.2
Descriptional text for sensor unit connected to port 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cmcTcUnit1Serial 1.3.6.1.4.1.2606.4.2.3.3
Serialnumber of sensor unit connected to port 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit1Status 1.3.6.1.4.1.2606.4.2.3.4
General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low (9) Firmware upgrade running
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8), fwUpgrade(9)  

cmcTcUnit1NumberOfSensors 1.3.6.1.4.1.2606.4.2.3.5.1
Number of sensors connected to sensor unit 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit1SensorTable 1.3.6.1.4.1.2606.4.2.3.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit1SensorEntry

cmcTcUnit1SensorEntry 1.3.6.1.4.1.2606.4.2.3.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit1SensorEntry  

unit1SensorIndex 1.3.6.1.4.1.2606.4.2.3.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit1SensorType 1.3.6.1.4.1.2606.4.2.3.5.2.1.2
Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from CMC-TC-FAS-Unit 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 38: DRC: RFID Tag 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rfidTag(38), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)  

unit1SensorText 1.3.6.1.4.1.2606.4.2.3.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit1SensorStatus 1.3.6.1.4.1.2606.4.2.3.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9), error(10)  

unit1SensorValue 1.3.6.1.4.1.2606.4.2.3.5.2.1.5
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit1SensorSetHigh 1.3.6.1.4.1.2606.4.2.3.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorSetLow 1.3.6.1.4.1.2606.4.2.3.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorSetWarn 1.3.6.1.4.1.2606.4.2.3.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorHysteresis 1.3.6.1.4.1.2606.4.2.3.5.2.1.9
% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorDisplayFactor 1.3.6.1.4.1.2606.4.2.3.5.2.1.10
Factor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit1SensorScaleStart 1.3.6.1.4.1.2606.4.2.3.5.2.1.11
Value for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 10, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorScaleEnd 1.3.6.1.4.1.2606.4.2.3.5.2.1.12
Value for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 60, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1SensorUnit 1.3.6.1.4.1.2606.4.2.3.5.2.1.13
Unit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

unit1SensorInfo 1.3.6.1.4.1.2606.4.2.3.5.2.1.14
Additional information to the sensor, e. g. Serialnumber, Signal Quality..
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cmcTcUnit1NumberOfOutputs 1.3.6.1.4.1.2606.4.2.3.6.1
Number of outputs available on sensor unit 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit1OutputTable 1.3.6.1.4.1.2606.4.2.3.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit1OutputEntry

cmcTcUnit1OutputEntry 1.3.6.1.4.1.2606.4.2.3.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit1OutputEntry  

unit1OutputIndex 1.3.6.1.4.1.2606.4.2.3.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit1OutputType 1.3.6.1.4.1.2606.4.2.3.6.2.1.2
Type of output which is connected to sensor unit 1 to output[unit1OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, LCP) 15: setpoint temperature monitoring (LCP) 16: hysteresis of setpoint (LCP) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 24: door magnet (automatic door release) 30: control mode, LCP 31: min fan speed (fan control), LCP 32: min delta T (fan control), LCP 33: max delta T (fan control), LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187), LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), doorMagnet(24), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)  

unit1OutputText 1.3.6.1.4.1.2606.4.2.3.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit1OutputStatus 1.3.6.1.4.1.2606.4.2.3.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

unit1OutputValue 1.3.6.1.4.1.2606.4.2.3.6.2.1.5
Value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1OutputSet 1.3.6.1.4.1.2606.4.2.3.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

unit1OutputConfig 1.3.6.1.4.1.2606.4.2.3.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

unit1OutputDelay 1.3.6.1.4.1.2606.4.2.3.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit1OutputTimeoutAction 1.3.6.1.4.1.2606.4.2.3.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cmcTcUnit1NumberOfMsgs 1.3.6.1.4.1.2606.4.2.3.7.1
Number of messages that can be created with sensor unit 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit1MsgTable 1.3.6.1.4.1.2606.4.2.3.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit1MsgEntry

cmcTcUnit1MsgEntry 1.3.6.1.4.1.2606.4.2.3.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit1MsgEntry  

unit1MsgIndex 1.3.6.1.4.1.2606.4.2.3.7.2.1.1
Index for the list of message entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit1MsgText 1.3.6.1.4.1.2606.4.2.3.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit1MsgStatus 1.3.6.1.4.1.2606.4.2.3.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)  

unit1MsgRelay 1.3.6.1.4.1.2606.4.2.3.7.2.1.4
Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgBeeper 1.3.6.1.4.1.2606.4.2.3.7.2.1.5
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgTrap1 1.3.6.1.4.1.2606.4.2.3.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgTrap2 1.3.6.1.4.1.2606.4.2.3.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgTrap3 1.3.6.1.4.1.2606.4.2.3.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgTrap4 1.3.6.1.4.1.2606.4.2.3.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit1MsgQuit 1.3.6.1.4.1.2606.4.2.3.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

unit1MsgDelay 1.3.6.1.4.1.2606.4.2.3.7.2.1.11
Delay of alarm condition
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cmcTcUnit2TypeOfDevice 1.3.6.1.4.1.2606.4.2.4.1
Type of sensor unit connected to port 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13), unitFuelCell(14), unitDRC(15), unitTECooler(16), unitPSMMetered32(17), unitPSM8x8(18), unitPSM6x6Schuko(19), unitPSM6x6C19(20)  

cmcTcUnit2Text 1.3.6.1.4.1.2606.4.2.4.2
Descriptional text for sensor unit connected to port 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cmcTcUnit2Serial 1.3.6.1.4.1.2606.4.2.4.3
Serialnumber of sensor unit connected to port 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit2Status 1.3.6.1.4.1.2606.4.2.4.4
General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low (9) Firmware upgrade running
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8), fwUpgrade(9)  

cmcTcUnit2NumberOfSensors 1.3.6.1.4.1.2606.4.2.4.5.1
Number of sensors connected to sensor unit 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit2SensorTable 1.3.6.1.4.1.2606.4.2.4.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit2SensorEntry

cmcTcUnit2SensorEntry 1.3.6.1.4.1.2606.4.2.4.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit2SensorEntry  

unit2SensorIndex 1.3.6.1.4.1.2606.4.2.4.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit2SensorType 1.3.6.1.4.1.2606.4.2.4.5.2.1.2
Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 38: DRC: RFID Tag 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rfidTag(38), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)  

unit2SensorText 1.3.6.1.4.1.2606.4.2.4.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit2SensorStatus 1.3.6.1.4.1.2606.4.2.4.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9), error(10)  

unit2SensorValue 1.3.6.1.4.1.2606.4.2.4.5.2.1.5
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit2SensorSetHigh 1.3.6.1.4.1.2606.4.2.4.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorSetLow 1.3.6.1.4.1.2606.4.2.4.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorSetWarn 1.3.6.1.4.1.2606.4.2.4.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorHysteresis 1.3.6.1.4.1.2606.4.2.4.5.2.1.9
% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorDisplayFactor 1.3.6.1.4.1.2606.4.2.4.5.2.1.10
Factor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit2SensorScaleStart 1.3.6.1.4.1.2606.4.2.4.5.2.1.11
Value for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 10, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorScaleEnd 1.3.6.1.4.1.2606.4.2.4.5.2.1.12
Value for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 60, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2SensorUnit 1.3.6.1.4.1.2606.4.2.4.5.2.1.13
Unit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

unit2SensorInfo 1.3.6.1.4.1.2606.4.2.4.5.2.1.14
Additional information to the sensor, e. g. Serialnumber, Signal Quality..
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cmcTcUnit2NumberOfOutputs 1.3.6.1.4.1.2606.4.2.4.6.1
Number of outputs available on sensor unit 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit2OutputTable 1.3.6.1.4.1.2606.4.2.4.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit2OutputEntry

cmcTcUnit2OutputEntry 1.3.6.1.4.1.2606.4.2.4.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit2OutputEntry  

unit2OutputIndex 1.3.6.1.4.1.2606.4.2.4.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit2OutputType 1.3.6.1.4.1.2606.4.2.4.6.2.1.2
Type of output which is connected to sensor unit 2 to output[unit2OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 24: door magnet (automatic door release) 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), doorMagnet(24), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)  

unit2OutputText 1.3.6.1.4.1.2606.4.2.4.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit2OutputStatus 1.3.6.1.4.1.2606.4.2.4.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

unit2OutputValue 1.3.6.1.4.1.2606.4.2.4.6.2.1.5
Signed value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2OutputSet 1.3.6.1.4.1.2606.4.2.4.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

unit2OutputConfig 1.3.6.1.4.1.2606.4.2.4.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

unit2OutputDelay 1.3.6.1.4.1.2606.4.2.4.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit2OutputTimeoutAction 1.3.6.1.4.1.2606.4.2.4.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cmcTcUnit2NumberOfMsgs 1.3.6.1.4.1.2606.4.2.4.7.1
Number of alarms that can be created with sensor unit 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit2MsgTable 1.3.6.1.4.1.2606.4.2.4.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit2MsgEntry

cmcTcUnit2MsgEntry 1.3.6.1.4.1.2606.4.2.4.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit2MsgEntry  

unit2MsgIndex 1.3.6.1.4.1.2606.4.2.4.7.2.1.1
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit2MsgText 1.3.6.1.4.1.2606.4.2.4.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit2MsgStatus 1.3.6.1.4.1.2606.4.2.4.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)  

unit2MsgRelay 1.3.6.1.4.1.2606.4.2.4.7.2.1.4
Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgBeeper 1.3.6.1.4.1.2606.4.2.4.7.2.1.5
Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgTrap1 1.3.6.1.4.1.2606.4.2.4.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgTrap2 1.3.6.1.4.1.2606.4.2.4.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgTrap3 1.3.6.1.4.1.2606.4.2.4.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgTrap4 1.3.6.1.4.1.2606.4.2.4.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit2MsgQuit 1.3.6.1.4.1.2606.4.2.4.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

unit2MsgDelay 1.3.6.1.4.1.2606.4.2.4.7.2.1.11
Delay of alarm condition
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cmcTcUnit3TypeOfDevice 1.3.6.1.4.1.2606.4.2.5.1
Type of sensor unit connected to port 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13), unitFuelCell(14), unitDRC(15), unitTECooler(16), unitPSMMetered32(17), unitPSM8x8(18), unitPSM6x6Schuko(19), unitPSM6x6C19(20)  

cmcTcUnit3Text 1.3.6.1.4.1.2606.4.2.5.2
Descriptional text for sensor unit connected to port 3
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cmcTcUnit3Serial 1.3.6.1.4.1.2606.4.2.5.3
Serialnumber of sensor unit connected to port 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit3Status 1.3.6.1.4.1.2606.4.2.5.4
General Status sensor unit connected to port 3 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low (9) Firmware upgrade running
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8), fwUpgrade(9)  

cmcTcUnit3NumberOfSensors 1.3.6.1.4.1.2606.4.2.5.5.1
Number of sensors connected to sensor unit 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit3SensorTable 1.3.6.1.4.1.2606.4.2.5.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit3SensorEntry

cmcTcUnit3SensorEntry 1.3.6.1.4.1.2606.4.2.5.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit3SensorEntry  

unit3SensorIndex 1.3.6.1.4.1.2606.4.2.5.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit3SensorType 1.3.6.1.4.1.2606.4.2.5.5.2.1.2
Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 38: DRC: RFID Tag 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rfidTag(38), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)  

unit3SensorText 1.3.6.1.4.1.2606.4.2.5.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit3SensorStatus 1.3.6.1.4.1.2606.4.2.5.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9), error(10)  

unit3SensorValue 1.3.6.1.4.1.2606.4.2.5.5.2.1.5
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit3SensorSetHigh 1.3.6.1.4.1.2606.4.2.5.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorSetLow 1.3.6.1.4.1.2606.4.2.5.5.2.1.7
Value for low setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorSetWarn 1.3.6.1.4.1.2606.4.2.5.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorHysteresis 1.3.6.1.4.1.2606.4.2.5.5.2.1.9
% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorDisplayFactor 1.3.6.1.4.1.2606.4.2.5.5.2.1.10
Factor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit3SensorScaleStart 1.3.6.1.4.1.2606.4.2.5.5.2.1.11
Value for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 10, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorScaleEnd 1.3.6.1.4.1.2606.4.2.5.5.2.1.12
Value for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 60, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3SensorUnit 1.3.6.1.4.1.2606.4.2.5.5.2.1.13
Unit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

unit3SensorInfo 1.3.6.1.4.1.2606.4.2.5.5.2.1.14
Additional information to the sensor, e. g. Serialnumber, Signal Quality..
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cmcTcUnit3NumberOfOutputs 1.3.6.1.4.1.2606.4.2.5.6.1
Number of outputs available on sensor unit 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit3OutputTable 1.3.6.1.4.1.2606.4.2.5.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit3OutputEntry

cmcTcUnit3OutputEntry 1.3.6.1.4.1.2606.4.2.5.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit3OutputEntry  

unit3OutputIndex 1.3.6.1.4.1.2606.4.2.5.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit3OutputType 1.3.6.1.4.1.2606.4.2.5.6.2.1.2
Type of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 24: door magnet (automatic door release) 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), doorMagnet(24), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)  

unit3OutputText 1.3.6.1.4.1.2606.4.2.5.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit3OutputStatus 1.3.6.1.4.1.2606.4.2.5.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

unit3OutputValue 1.3.6.1.4.1.2606.4.2.5.6.2.1.5
Value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3OutputSet 1.3.6.1.4.1.2606.4.2.5.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

unit3OutputConfig 1.3.6.1.4.1.2606.4.2.5.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

unit3OutputDelay 1.3.6.1.4.1.2606.4.2.5.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit3OutputTimeoutAction 1.3.6.1.4.1.2606.4.2.5.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cmcTcUnit3NumberOfMsgs 1.3.6.1.4.1.2606.4.2.5.7.1
Number of alarms that can be created with sensor unit 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit3MsgTable 1.3.6.1.4.1.2606.4.2.5.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit3MsgEntry

cmcTcUnit3MsgEntry 1.3.6.1.4.1.2606.4.2.5.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit3MsgEntry  

unit3MsgIndex 1.3.6.1.4.1.2606.4.2.5.7.2.1.1
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit3MsgText 1.3.6.1.4.1.2606.4.2.5.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit3MsgStatus 1.3.6.1.4.1.2606.4.2.5.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)  

unit3MsgRelay 1.3.6.1.4.1.2606.4.2.5.7.2.1.4
Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgBeeper 1.3.6.1.4.1.2606.4.2.5.7.2.1.5
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgTrap1 1.3.6.1.4.1.2606.4.2.5.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgTrap2 1.3.6.1.4.1.2606.4.2.5.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgTrap3 1.3.6.1.4.1.2606.4.2.5.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgTrap4 1.3.6.1.4.1.2606.4.2.5.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit3MsgQuit 1.3.6.1.4.1.2606.4.2.5.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

unit3MsgDelay 1.3.6.1.4.1.2606.4.2.5.7.2.1.11
Delay of alarm condition
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cmcTcUnit4TypeOfDevice 1.3.6.1.4.1.2606.4.2.6.1
Type of sensor unit connected to port 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13), unitFuelCell(14), unitDRC(15), unitTECooler(16), unitPSMMetered32(17), unitPSM8x8(18), unitPSM6x6Schuko(19), unitPSM6x6C19(20)  

cmcTcUnit4Text 1.3.6.1.4.1.2606.4.2.6.2
Descriptional text for sensor unit connected to port 4
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cmcTcUnit4Serial 1.3.6.1.4.1.2606.4.2.6.3
Serialnumber of sensor unit connected to port 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit4Status 1.3.6.1.4.1.2606.4.2.6.4
General Status sensor unit connected to port 4 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low (9) Firmware upgrade running
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8), fwUpgrade(9)  

cmcTcUnit4NumberOfSensors 1.3.6.1.4.1.2606.4.2.6.5.1
Number of sensors connected to sensor unit 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit4SensorTable 1.3.6.1.4.1.2606.4.2.6.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit4SensorEntry

cmcTcUnit4SensorEntry 1.3.6.1.4.1.2606.4.2.6.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit4SensorEntry  

unit4SensorIndex 1.3.6.1.4.1.2606.4.2.6.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit4SensorType 1.3.6.1.4.1.2606.4.2.6.5.2.1.2
Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 38: DRC: RFID Tag 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rfidTag(38), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)  

unit4SensorText 1.3.6.1.4.1.2606.4.2.6.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit4SensorStatus 1.3.6.1.4.1.2606.4.2.6.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9), error(10)  

unit4SensorValue 1.3.6.1.4.1.2606.4.2.6.5.2.1.5
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit4SensorSetHigh 1.3.6.1.4.1.2606.4.2.6.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorSetLow 1.3.6.1.4.1.2606.4.2.6.5.2.1.7
Value for low setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorSetWarn 1.3.6.1.4.1.2606.4.2.6.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorHysteresis 1.3.6.1.4.1.2606.4.2.6.5.2.1.9
% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorDisplayFactor 1.3.6.1.4.1.2606.4.2.6.5.2.1.10
Factor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

unit4SensorScaleStart 1.3.6.1.4.1.2606.4.2.6.5.2.1.11
Value for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 10, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorScaleEnd 1.3.6.1.4.1.2606.4.2.6.5.2.1.12
Value for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 60, also valid for setpoints
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4SensorUnit 1.3.6.1.4.1.2606.4.2.6.5.2.1.13
Unit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

unit4SensorInfo 1.3.6.1.4.1.2606.4.2.6.5.2.1.14
Additional information to the sensor, e. g. Serialnumber, Signal Quality..
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cmcTcUnit4NumberOfOutputs 1.3.6.1.4.1.2606.4.2.6.6.1
Number of outputs available on sensor unit 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit4OutputTable 1.3.6.1.4.1.2606.4.2.6.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit4OutputEntry

cmcTcUnit4OutputEntry 1.3.6.1.4.1.2606.4.2.6.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit4OutputEntry  

unit4OutputIndex 1.3.6.1.4.1.2606.4.2.6.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit4OutputType 1.3.6.1.4.1.2606.4.2.6.6.2.1.2
Type of output which is connected to sensor unit 4 to output[unit4OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 24: door magnet (automatic door release) 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), doorMagnet(24), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)  

unit4OutputText 1.3.6.1.4.1.2606.4.2.6.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit4OutputStatus 1.3.6.1.4.1.2606.4.2.6.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

unit4OutputValue 1.3.6.1.4.1.2606.4.2.6.6.2.1.5
Value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4OutputSet 1.3.6.1.4.1.2606.4.2.6.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

unit4OutputConfig 1.3.6.1.4.1.2606.4.2.6.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

unit4OutputDelay 1.3.6.1.4.1.2606.4.2.6.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

unit4OutputTimeoutAction 1.3.6.1.4.1.2606.4.2.6.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cmcTcUnit4NumberOfMsgs 1.3.6.1.4.1.2606.4.2.6.7.1
Number of alarms that can be created with sensor unit 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcUnit4MsgTable 1.3.6.1.4.1.2606.4.2.6.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcUnit4MsgEntry

cmcTcUnit4MsgEntry 1.3.6.1.4.1.2606.4.2.6.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcUnit4MsgEntry  

unit4MsgIndex 1.3.6.1.4.1.2606.4.2.6.7.2.1.1
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

unit4MsgText 1.3.6.1.4.1.2606.4.2.6.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

unit4MsgStatus 1.3.6.1.4.1.2606.4.2.6.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)  

unit4MsgRelay 1.3.6.1.4.1.2606.4.2.6.7.2.1.4
Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgBeeper 1.3.6.1.4.1.2606.4.2.6.7.2.1.5
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgTrap1 1.3.6.1.4.1.2606.4.2.6.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgTrap2 1.3.6.1.4.1.2606.4.2.6.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgTrap3 1.3.6.1.4.1.2606.4.2.6.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgTrap4 1.3.6.1.4.1.2606.4.2.6.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

unit4MsgQuit 1.3.6.1.4.1.2606.4.2.6.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

unit4MsgDelay 1.3.6.1.4.1.2606.4.2.6.7.2.1.11
Delay of alarm condition
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cmcTcValuesRelay 1.3.6.1.4.1.2606.4.2.7.1
Setup of Alarm relay for alarm ext. unit(s) 1: no switching of alarm relay 2: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcValuesBeeper 1.3.6.1.4.1.2606.4.2.7.2
Setup of Alarm beeper for alarm ext. unit(s) 1: no audible alarm 2: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcValuesTrap1 1.3.6.1.4.1.2606.4.2.7.3
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcValuesTrap2 1.3.6.1.4.1.2606.4.2.7.4
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcValuesTrap3 1.3.6.1.4.1.2606.4.2.7.5
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcValuesTrap4 1.3.6.1.4.1.2606.4.2.7.6
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

cmcTcNumberOfValues 1.3.6.1.4.1.2606.4.2.7.7
Number of values availabel on extension units connected to the CMC
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcValuesTable 1.3.6.1.4.1.2606.4.2.7.8
Headline of values-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcValuesEntry

cmcTcValuesEntry 1.3.6.1.4.1.2606.4.2.7.8.1
Entries of values-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcValuesEntry  

valuesIndex 1.3.6.1.4.1.2606.4.2.7.8.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcNumberOfValues.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

valuesText 1.3.6.1.4.1.2606.4.2.7.8.1.2
Descriptional text for each value (entry in the table) of the extension card
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

valuesStatus 1.3.6.1.4.1.2606.4.2.7.8.1.3
Actual status of the value of the extension card
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), tooLow(5), tooHigh(6), error(7)  

valuesValue 1.3.6.1.4.1.2606.4.2.7.8.1.4
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuesSetHigh 1.3.6.1.4.1.2606.4.2.7.8.1.5
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

valuesSetLow 1.3.6.1.4.1.2606.4.2.7.8.1.6
Value for low setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

valuesHysteresis 1.3.6.1.4.1.2606.4.2.7.8.1.7
% -Value for hysteresis for High and Low setpoints, input in % from actual setpoint
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cmcTcSetTempUnit 1.3.6.1.4.1.2606.4.3.1.1
Unit of all temperature values and setpoints, Celsius or Fahrenheit
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

cmcTcSetBeeper 1.3.6.1.4.1.2606.4.3.1.2
Audible alarm in CMC-TC unit: (2): beeper is on (1): beeper is off (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2)  

cmcTcQuitRelay 1.3.6.1.4.1.2606.4.3.1.3
Enable or disable acknowledging currently active alarm relay (with 'C' on CMC-TC).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cmcTcLogicRelay 1.3.6.1.4.1.2606.4.3.1.4
Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER closeAtAlarm(1), openAtAlarm(2), off(3)  

cmcTcWebAccess 1.3.6.1.4.1.2606.4.3.1.5
Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER viewOnly(1), fullAccess(2), off(3)  

cmcTcSetupDate 1.3.6.1.4.1.2606.4.3.1.6
actual Date in format DD.MM.YYYY
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cmcTcSetupTime 1.3.6.1.4.1.2606.4.3.1.7
actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

cmcTcTimerNumber 1.3.6.1.4.1.2606.4.3.1.8.1
Number of value-table entries=number of outlets available on this unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcTimerTable 1.3.6.1.4.1.2606.4.3.1.8.2
Headline of status-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcTimerEntry

cmcTcTimerEntry 1.3.6.1.4.1.2606.4.3.1.8.2.1
Entries of timer-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcTimerEntry  

cmcTcTimerIndex 1.3.6.1.4.1.2606.4.3.1.8.2.1.1
Index for the list of timer entries. Its value ranges between 1 and the value of cmcTcTimerNumber.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cmcTcTimerStatus 1.3.6.1.4.1.2606.4.3.1.8.2.1.2
Actual status of the timer
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER switchedOff(1), switchedOn(2), noTime(3)  

cmcTcTimerDayOfWeek 1.3.6.1.4.1.2606.4.3.1.8.2.1.3
Selection of day of week for timer to switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat-sun(8), mon-fri(9), mon-sun(10)  

cmcTcTimeOn 1.3.6.1.4.1.2606.4.3.1.8.2.1.4
Time to switch on current function, Format: HH:MM
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..5)  

cmcTcTimeOff 1.3.6.1.4.1.2606.4.3.1.8.2.1.5
Time to switch off current function, Format: HH:MM
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..5)  

cmcTcTimeControl 1.3.6.1.4.1.2606.4.3.1.8.2.1.6
Control via RTC
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cmcTcTimerFunction 1.3.6.1.4.1.2606.4.3.1.8.2.1.7
Function which is controlled via timer 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled 2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled 3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled 4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled 5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled 6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled 7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled 8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled 9: Lock of door 1 on unit 1 will be unlocked 10: Lock of door 2 on unit 1 will be unlocked 11: Lock of door 1 on unit 2 will be unlocked 12: Lock of door 2 on unit 2 will be unlocked 13: Lock of door 1 on unit 3 will be unlocked 14: Lock of door 2 on unit 3 will be unlocked 15: Lock of door 1 on unit 4 will be unlocked 16: Lock of door 2 on unit 4 will be unlocked 17-20: sending Traps to this Trap receiver will be disabled 21: sending SMS will be disabled generally 22-25: Scheduled alarm off 26-29: sending SMS to phone number 1..4 will be disabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disKeypad1-1(1), disKeypad2-1(2), disKeypad1-2(3), disKeypad2-2(4), disKeypad1-3(5), disKeypad2-3(6), disKeypad1-4(7), disKeypad2-4(8), unlDoor1-1(9), unlDoor2-1(10), unlDoor1-2(11), unlDoor2-2(12), unlDoor1-3(13), unlDoor2-3(14), unlDoor1-4(15), unlDoor2-5(16), disTrapRec1(17), disTrapRec2(18), disTrapRec3(19), disTrapRec4(20), disSMS(21), schedule1(22), schedule2(23), schedule3(24), schedule4(25), disSMS1(26), disSMS2(27), disSMS3(28), disSMS4(29)  

cmcTcTraptableNumber 1.3.6.1.4.1.2606.4.4.7.1
Number of trapTable entries. The number of trap-receiver
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cmcTcTrapTableTable 1.3.6.1.4.1.2606.4.4.7.2
A list of trap-receiver entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CmcTcTrapTableEntry

cmcTcTrapTableEntry 1.3.6.1.4.1.2606.4.4.7.2.1
Entries of trapTable
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CmcTcTrapTableEntry  

trapIndex 1.3.6.1.4.1.2606.4.4.7.2.1.1
Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

trapStatus 1.3.6.1.4.1.2606.4.4.7.2.1.2
Enable or disable trap receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

trapIPaddress 1.3.6.1.4.1.2606.4.4.7.2.1.3
IP-address of trap-receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

cmcTcQuitUnit 1.3.6.1.4.1.2606.4.5.1
Command to quit (acknowledge) alarms of CMC-TC unit. Setting to 'quit' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noQuit' (1).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER noQuit(1), quit(2)  

alarmSensorUnit1 1
Alarm of sensor unit 1
TRAP-TYPE    

alarmSensorUnit2 2
Alarm of sensor unit 2
TRAP-TYPE    

alarmSensorUnit3 3
Alarm of sensor unit 3
TRAP-TYPE    

alarmSensorUnit4 4
Alarm of sensor unit 4
TRAP-TYPE    

alarmUnit1 5
Alarm of unit 1
TRAP-TYPE    

alarmUnit2 6
Alarm of unit 2
TRAP-TYPE    

alarmUnit3 7
Alarm of unit 3
TRAP-TYPE    

alarmUnit4 8
Alarm of unit 4
TRAP-TYPE    

alarmValues 9
Alarm of values measured by external card
TRAP-TYPE    

configChanged 10
The configuration of the cmc has changed, this trap is send if new setup is saved. Configuration can be changed by Terminal, Telnet, Web or SNMP *** NOT IMPLEMENTED ***
TRAP-TYPE