PACKETFLUX-STANDBYPOWER

File: PACKETFLUX-STANDBYPOWER.mib (28315 bytes)

Imported modules

SNMPv2-SMI PACKETFLUX-SMI SNMPv2-CONF
SNMPv2-TC

Imported symbols

MODULE-IDENTITY Integer32 OBJECT-TYPE
Gauge32 TimeTicks packetfluxMgmt
OBJECT-GROUP TruthValue

Defined Values

standbypower 1.3.6.1.4.1.32050.2.2
MIB for the PacketFlux Standby Power Controller
MODULE-IDENTITY    

powercontrollerstate 1.3.6.1.4.1.32050.2.2.1
The status of the standby power controller.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER onprimarypower(1), startingstandby(2), transferringtostandby(3), onstandbypower(4), transferringtoprimary(5)  

transferswitchstate 1.3.6.1.4.1.32050.2.2.2
The current state in the transfer sequence.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER primary(1), transfertostandby1(2), transfertostandby2(3), transfertostandby3(4), standby(5), transfertoprimary1(6), transfertoprimary2(7), transfertoprimary3(8)  

standbypowerstate 1.3.6.1.4.1.32050.2.2.3
The current state in the standby power sequence.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER stopped(1), prepare1(2), prepare2(3), prepare3(4), startup1(5), startup2(6), startup3(7), checkrun(8), reprepare1(9), reprepare2(10), reprepare3(11), warmup1(12), warmup2(13), warmup3(14), verifyrun(15), running(16), cooldown1(17), cooldown2(18), cooldown3(19), shutdown1(20), shutdown2(21), shutdown3(22), verifystopped(23), postshutdown1(24), postshutdown2(25), postshutdown3(26)  

ac1voltage 1.3.6.1.4.1.32050.2.2.4
The voltage of the AC input AC1 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

ac1frequency 1.3.6.1.4.1.32050.2.2.5
The frequency of the AC input AC1 in 1/100ths of a Hertz.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

ac2voltage 1.3.6.1.4.1.32050.2.2.6
The voltage of the AC input AC2 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

ac2frequency 1.3.6.1.4.1.32050.2.2.7
The frequency of the AC input AC2 in 1/100ths of a Hertz.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

mtr1voltage 1.3.6.1.4.1.32050.2.2.8
The voltage of the DC input Mtr1 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

mtr2voltage 1.3.6.1.4.1.32050.2.2.9
The voltage of the DC input Mtr2 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

pwr1voltage 1.3.6.1.4.1.32050.2.2.10
The voltage of the DC input Pwr3 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

pwr2voltage 1.3.6.1.4.1.32050.2.2.11
The voltage of the DC input Pwr2 in 1/10ths of a volt.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

shuntvoltage 1.3.6.1.4.1.32050.2.2.12
The voltage of the DC input Shunt in 1/10ths of a millivolt. Can be negative.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

temperature 1.3.6.1.4.1.32050.2.2.13
The temperature of the onboard temperature sensor in 1/10ths of a degree centigrade.
Status: current Access: read-only
OBJECT-TYPE    
  Gauge32  

recentunsuccessfulstarts 1.3.6.1.4.1.32050.2.2.14
The number of times the standby power source was not successfully started. This counter resets upon a successful start. It can also be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

totalunsuccessfulstarts 1.3.6.1.4.1.32050.2.2.15
The number of times the standby power source was not successfully started. This counter DOES NOT reset upon a successful start. It can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

recentstalls 1.3.6.1.4.1.32050.2.2.16
The number of times the standby power source has stalled. This counter resets upon a clean shutdown. It can also be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

totalstalls 1.3.6.1.4.1.32050.2.2.17
The number of times the standby power source has stalled. This counter DOES NOT reset upon a clean shutdown. It can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

numberofstarts 1.3.6.1.4.1.32050.2.2.18
The number of times the secondary power source has started. This counter increments when the standby sequence reaches the running state. This counter can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

numberoftransfers 1.3.6.1.4.1.32050.2.2.19
The number of times the power has transfered from primary to standby, or back. A complete transfer cycle from primary to standby and back to primary will increment this counter twice. This counter can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

currenttimeonprimary 1.3.6.1.4.1.32050.2.2.20
The amount of time the transfer switch has been in the primary state (position) since the most recent transfer to that state. This timer resets to zero when the transfer switch leaves the primary state (position). This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

totaltimeonprimary 1.3.6.1.4.1.32050.2.2.21
The amount of time the transfer switch has been in the primary state (position) since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

currenttimeonstandby 1.3.6.1.4.1.32050.2.2.22
The amount of time the transfer switch has been in the standby state (position) since the most recent transfer to that state. This timer resets to zero when the transfer switch leaves the primary state (position). This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

totaltimeonstandby 1.3.6.1.4.1.32050.2.2.23
The amount of time the transfer switch has been in the standby state (position) since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

currentstandbyruntime 1.3.6.1.4.1.32050.2.2.24
The amount of time the standby power source has been running during it's current run. This timer resets to zero when the standby power source shuts down. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

totalstandbyruntime 1.3.6.1.4.1.32050.2.2.25
The amount of time the standby power source has been running since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

laststandbyrun 1.3.6.1.4.1.32050.2.2.26
The amount of time since the standby power source ran last. This timer resets upon start of the standby power source and starts timing upon shutdown of the standby power source. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

laststandbygracefulstop 1.3.6.1.4.1.32050.2.2.27
The amount of time since standby power source was gracefully shutdown. This timer resets and starts timing upon graceful shutdown of the standby power source. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

laststandbyunsuccessfulstart 1.3.6.1.4.1.32050.2.2.28
The amount of time since the last failed start of the standby power source . This timer resets and starts timing upon a unsuccessful start of the power source. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

laststandbyfailure 1.3.6.1.4.1.32050.2.2.29
The amount of time since the stall or failure while running of the standby power source . This timer resets and starts timing upon a stall/failure of the power source. This timer can be reset via the web interface or by writing 0 to this object.
Status: current Access: read-write
OBJECT-TYPE    
  TimeTicks  

switch1closed 1.3.6.1.4.1.32050.2.2.30
True(1) if the Switch 1 input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

switch2closed 1.3.6.1.4.1.32050.2.2.31
True(1) if the Switch 2 input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

switch3closed 1.3.6.1.4.1.32050.2.2.32
True(1) if the Switch 3 input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

switch4closed 1.3.6.1.4.1.32050.2.2.33
True(1) if the Switch 4 input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

switch5closed 1.3.6.1.4.1.32050.2.2.34
True(1) if the Switch 5 input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

enabled 1.3.6.1.4.1.32050.2.2.35
True(1) if the enable input is closed (shorted/on). False(2) if it is open.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay1on 1.3.6.1.4.1.32050.2.2.36
True(1) if the Relay 1 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay2on 1.3.6.1.4.1.32050.2.2.37
True(1) if the Relay 2 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay3on 1.3.6.1.4.1.32050.2.2.38
True(1) if the Relay 3 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay4on 1.3.6.1.4.1.32050.2.2.39
True(1) if the Relay 4 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay5on 1.3.6.1.4.1.32050.2.2.40
True(1) if the Relay 5 output is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay6on 1.3.6.1.4.1.32050.2.2.41
True(1) if the Relay 6 output is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

relay7on 1.3.6.1.4.1.32050.2.2.42
True(1) if the Relay 7 output is on (C and NO connected). False(2) if it is off (C and NC connected).
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

ruleswitchstandby 1.3.6.1.4.1.32050.2.2.43
True(1) if the switch to standby rule is true. False(2) if it is not.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

rulereturnprimary 1.3.6.1.4.1.32050.2.2.44
True(1) if the return to primary rule is true. False(2) if it is not.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

rulestandbygood 1.3.6.1.4.1.32050.2.2.45
True(1) if the standby power good rule is true. False(2) if it is not.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

rulestopstandby 1.3.6.1.4.1.32050.2.2.46
True(1) if the stop standby and consider it failed rule is true. False(2) if it is not.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

ruleexercisestandby 1.3.6.1.4.1.32050.2.2.47
True(1) if the exercise standby without transfer rule is true. False(2) if it is not.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

webcontrol1 1.3.6.1.4.1.32050.2.2.48
True(1) if the webcontrol 1 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol2 1.3.6.1.4.1.32050.2.2.49
True(1) if the webcontrol 2 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol3 1.3.6.1.4.1.32050.2.2.50
True(1) if the webcontrol 3 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol4 1.3.6.1.4.1.32050.2.2.51
True(1) if the webcontrol 4 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol5 1.3.6.1.4.1.32050.2.2.52
True(1) if the webcontrol 5 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol6 1.3.6.1.4.1.32050.2.2.53
True(1) if the webcontrol 6 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol7 1.3.6.1.4.1.32050.2.2.54
True(1) if the webcontrol 7 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

webcontrol8 1.3.6.1.4.1.32050.2.2.55
True(1) if the webcontrol 8 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

standbypowerConformance 1.3.6.1.4.1.32050.2.2.256
OBJECT IDENTIFIER    

standbypowerGroups 1.3.6.1.4.1.32050.2.2.256.1
OBJECT IDENTIFIER    

packetfluxStandbypowerAllObjects 1.3.6.1.4.1.32050.2.2.256.1.1
This automatically created object group contains all those objects that do not belong to any other OBJECT-GROUP
Status: current Access: read-write
OBJECT-GROUP