netBotz-prd-bot-temp |
1.3.6.1.4.1.5528.30.10.1 |
The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-humidity |
1.3.6.1.4.1.5528.30.10.2 |
The reading of the humidity probe, in percent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-airflow |
1.3.6.1.4.1.5528.30.10.3 |
The reading of the airflow probe. Each unit represents approximately 40 feet/minute or
13 meters/minute of airflow velocity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-audio |
1.3.6.1.4.1.5528.30.10.4 |
The reading of the audio alarm probe on/off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-doorajar |
1.3.6.1.4.1.5528.30.10.5 |
The reading of the door switch probe open(0) or closed(1). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-temp-min |
1.3.6.1.4.1.5528.30.10.6 |
The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-temp-max |
1.3.6.1.4.1.5528.30.10.7 |
The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-humidity-min |
1.3.6.1.4.1.5528.30.10.8 |
The humidity probe minimum, from 10 to 90 percent. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-humidity-max |
1.3.6.1.4.1.5528.30.10.9 |
The humidity probe maximum, from 10 to 90 percent. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-airflow-mins |
1.3.6.1.4.1.5528.30.10.10 |
Minutes without airflow before alarm set. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-audio-secs |
1.3.6.1.4.1.5528.30.10.11 |
Seconds of alarm audio before alarm set. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-temp-enabled |
1.3.6.1.4.1.5528.30.10.12 |
Temperature probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-hum-enabled |
1.3.6.1.4.1.5528.30.10.13 |
Humidity probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-air-enabled |
1.3.6.1.4.1.5528.30.10.14 |
Airflow probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-audio-enabled |
1.3.6.1.4.1.5528.30.10.15 |
Audio probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-switch-state |
1.3.6.1.4.1.5528.30.10.16 |
Switch state setting. The state controls which
condition of the door switch indicates an alarm.
If set to 0, alarm is set when the switch is closed.
If set to 1, alarm is set when the switch is open. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-switch-enabled |
1.3.6.1.4.1.5528.30.10.17 |
Door switch enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-audio-level |
1.3.6.1.4.1.5528.30.10.18 |
Audio level setting. This is the relative audio level, from 0-11,
above which an alarm will be sent. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-doorpic-delay |
1.3.6.1.4.1.5528.30.10.19 |
Number of seconds between door alert and first picture. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-trap-index |
1.3.6.1.4.1.5528.30.10.20 |
The crawler ID of the last trap. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-trap-oid |
1.3.6.1.4.1.5528.30.10.22 |
The object id of the last trap. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
OBJECT IDENTIFIER |
|
|
netBotz-prd-bot-trap-value |
1.3.6.1.4.1.5528.30.10.23 |
The value of the last object trap. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-trap-date |
1.3.6.1.4.1.5528.30.10.24 |
The date and time of a specific trap. This field
contains the number of seconds elapsed since
midnight (00:00:00), January 1, 1970 |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-refresh |
1.3.6.1.4.1.5528.30.10.26 |
Rate of web page refresh, in seconds. This must be greater than 5 seconds. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-airflow-level |
1.3.6.1.4.1.5528.30.10.27 |
Airflow alert level. This is the relative level of airflow below which
an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of
airflow velocity. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-doorpic-count |
1.3.6.1.4.1.5528.30.10.28 |
Number of pictures to take when door activated.
These pictures will be sent as attachments to the door alert e-mail.
The range is from 0 to 5 pictures. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1 |
1.3.6.1.4.1.5528.30.10.29 |
The reading of the first amperage probe, in milliamps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1-enabled |
1.3.6.1.4.1.5528.30.10.30 |
Amperage[1] probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1-min |
1.3.6.1.4.1.5528.30.10.31 |
The amperage[1] probe minimum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1-max |
1.3.6.1.4.1.5528.30.10.32 |
The amperage[1] probe maximum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2 |
1.3.6.1.4.1.5528.30.10.34 |
The reading of the second amperage probe, in milliamps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2-enabled |
1.3.6.1.4.1.5528.30.10.35 |
Amperage[2] probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2-min |
1.3.6.1.4.1.5528.30.10.36 |
The amperage[2] probe minimum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2-max |
1.3.6.1.4.1.5528.30.10.37 |
The amperage[2] probe maximum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3 |
1.3.6.1.4.1.5528.30.10.39 |
The reading of the third amperage probe, in milliamps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3-enabled |
1.3.6.1.4.1.5528.30.10.40 |
Amperage[3] probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3-min |
1.3.6.1.4.1.5528.30.10.41 |
The amperage[3] probe minimum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3-max |
1.3.6.1.4.1.5528.30.10.42 |
The amperage[3] probe maximum, from 0 to 30000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps-total |
1.3.6.1.4.1.5528.30.10.44 |
The total of the readings of all amperage probes, in milliamps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps-total-min |
1.3.6.1.4.1.5528.30.10.46 |
The total amperage minimum, from 0 to 90000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps-total-max |
1.3.6.1.4.1.5528.30.10.47 |
The total amperage maximum, from 0 to 90000 milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1-uV-per-10mA |
1.3.6.1.4.1.5528.30.10.49 |
The scaling factor used for the first amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2-uV-per-10mA |
1.3.6.1.4.1.5528.30.10.50 |
The scaling factor used for the second amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3-uV-per-mA |
1.3.6.1.4.1.5528.30.10.51 |
The scaling factor used for the third amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps1-max-range |
1.3.6.1.4.1.5528.30.10.52 |
The maximum RMS milliamps measureable by the first Amp Detect. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps2-max-range |
1.3.6.1.4.1.5528.30.10.53 |
The maximum RMS milliamps measureable by the second Amp Detect. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps3-max-range |
1.3.6.1.4.1.5528.30.10.54 |
The maximum RMS milliamps measureable by the third Amp Detect. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4 |
1.3.6.1.4.1.5528.30.10.55 |
The reading of the fourth amperage probe, in milliamps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4-enabled |
1.3.6.1.4.1.5528.30.10.56 |
Amperage[4] probe alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4-min |
1.3.6.1.4.1.5528.30.10.57 |
The amperage[4] probe minimum, in milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4-max |
1.3.6.1.4.1.5528.30.10.58 |
The amperage[4] probe maximum, in milliamps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4-uV-per-10mA |
1.3.6.1.4.1.5528.30.10.60 |
The scaling factor used for the fourth amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amps4-max-range |
1.3.6.1.4.1.5528.30.10.61 |
The maximum RMS milliamps measureable by the fourth Amp Detect. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1 |
1.3.6.1.4.1.5528.30.10.62 |
The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2 |
1.3.6.1.4.1.5528.30.10.63 |
The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3 |
1.3.6.1.4.1.5528.30.10.64 |
The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4 |
1.3.6.1.4.1.5528.30.10.65 |
The reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-enabled |
1.3.6.1.4.1.5528.30.10.66 |
External temperature probe on port 1 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-min |
1.3.6.1.4.1.5528.30.10.67 |
The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-max |
1.3.6.1.4.1.5528.30.10.68 |
The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-enabled |
1.3.6.1.4.1.5528.30.10.69 |
External temperature probe on port 2 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-min |
1.3.6.1.4.1.5528.30.10.70 |
The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-max |
1.3.6.1.4.1.5528.30.10.71 |
The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-enabled |
1.3.6.1.4.1.5528.30.10.72 |
External temperature probe on port 3 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-min |
1.3.6.1.4.1.5528.30.10.73 |
The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-max |
1.3.6.1.4.1.5528.30.10.74 |
The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-enabled |
1.3.6.1.4.1.5528.30.10.75 |
External temperature probe on port 4 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-min |
1.3.6.1.4.1.5528.30.10.76 |
The external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-max |
1.3.6.1.4.1.5528.30.10.77 |
The external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-uV-per-degreeC |
1.3.6.1.4.1.5528.30.10.78 |
The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-uV-at-0-degreeC |
1.3.6.1.4.1.5528.30.10.79 |
The offset used for the external temperature probe on port 1 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-max-range |
1.3.6.1.4.1.5528.30.10.81 |
The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp1-min-range |
1.3.6.1.4.1.5528.30.10.80 |
The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-uV-per-degreeC |
1.3.6.1.4.1.5528.30.10.82 |
The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-uV-at-0-degreeC |
1.3.6.1.4.1.5528.30.10.83 |
The offset used for the external temperature probe on port 2 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-max-range |
1.3.6.1.4.1.5528.30.10.85 |
The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp2-min-range |
1.3.6.1.4.1.5528.30.10.84 |
The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-uV-per-degreeC |
1.3.6.1.4.1.5528.30.10.86 |
The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-uV-at-0-degreeC |
1.3.6.1.4.1.5528.30.10.87 |
The offset used for the external temperature probe on port 3 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-max-range |
1.3.6.1.4.1.5528.30.10.89 |
The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp3-min-range |
1.3.6.1.4.1.5528.30.10.88 |
The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-uV-per-degreeC |
1.3.6.1.4.1.5528.30.10.90 |
The scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-uV-at-0-degreeC |
1.3.6.1.4.1.5528.30.10.91 |
The offset used for the external temperature probe on port 4 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-max-range |
1.3.6.1.4.1.5528.30.10.93 |
The maximum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-temp4-min-range |
1.3.6.1.4.1.5528.30.10.92 |
The minimum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-port1-module-type |
1.3.6.1.4.1.5528.30.10.95 |
The type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-port2-module-type |
1.3.6.1.4.1.5528.30.10.97 |
The type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-port3-module-type |
1.3.6.1.4.1.5528.30.10.99 |
The type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-port4-module-type |
1.3.6.1.4.1.5528.30.10.101 |
The type of sensor module installed on port 4. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-amp1-total-amp-seconds-since-time |
1.3.6.1.4.1.5528.30.10.103 |
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amp2-total-amp-seconds-since-time |
1.3.6.1.4.1.5528.30.10.105 |
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amp3-total-amp-seconds-since-time |
1.3.6.1.4.1.5528.30.10.107 |
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amp4-total-amp-seconds-since-time |
1.3.6.1.4.1.5528.30.10.109 |
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-amptotal-total-amp-seconds-since-time |
1.3.6.1.4.1.5528.30.10.111 |
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1 |
1.3.6.1.4.1.5528.30.10.112 |
The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry2 |
1.3.6.1.4.1.5528.30.10.113 |
The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry3 |
1.3.6.1.4.1.5528.30.10.114 |
The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry4 |
1.3.6.1.4.1.5528.30.10.115 |
The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1-alarm-value |
1.3.6.1.4.1.5528.30.10.116 |
The value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1-enabled |
1.3.6.1.4.1.5528.30.10.117 |
External dry contact sensor on Ext1 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry2-alarm-value |
1.3.6.1.4.1.5528.30.10.118 |
The value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry2-enabled |
1.3.6.1.4.1.5528.30.10.119 |
External dry contact sensor on Ext2 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry3-alarm-value |
1.3.6.1.4.1.5528.30.10.120 |
The value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry3-enabled |
1.3.6.1.4.1.5528.30.10.121 |
External dry contact sensor on Ext3 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry4-alarm-value |
1.3.6.1.4.1.5528.30.10.122 |
The value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry4-enabled |
1.3.6.1.4.1.5528.30.10.123 |
External dry contact sensor on Ext4 alarm enabled(1) or disabled(0). |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1-open-to-close-millis |
1.3.6.1.4.1.5528.30.10.127 |
The minimum number of milliseconds that the dry contact sensor on Ext1
must read closed before the state is changed from open to closed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1-close-to-open-millis |
1.3.6.1.4.1.5528.30.10.128 |
The minimum number of milliseconds that the dry contact sensor on Ext1
must read openbefore the state is changed from closed to open. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry1-response |
1.3.6.1.4.1.5528.30.10.129 |
The type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-dry2-open-to-close-millis |
1.3.6.1.4.1.5528.30.10.133 |
The minimum number of milliseconds that the dry contact sensor on Ext2
must read closed before the state is changed from open to closed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry2-close-to-open-millis |
1.3.6.1.4.1.5528.30.10.134 |
The minimum number of milliseconds that the dry contact sensor on Ext2
must read openbefore the state is changed from closed to open. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry2-response |
1.3.6.1.4.1.5528.30.10.135 |
The type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-dry3-open-to-close-millis |
1.3.6.1.4.1.5528.30.10.139 |
The minimum number of milliseconds that the dry contact sensor on Ext3
must read closed before the state is changed from open to closed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry3-close-to-open-millis |
1.3.6.1.4.1.5528.30.10.140 |
The minimum number of milliseconds that the dry contact sensor on Ext3
must read openbefore the state is changed from closed to open. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry3-response |
1.3.6.1.4.1.5528.30.10.141 |
The type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-ext-dry4-open-to-close-millis |
1.3.6.1.4.1.5528.30.10.145 |
The minimum number of milliseconds that the dry contact sensor on Ext4
must read closed before the state is changed from open to closed. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry4-close-to-open-millis |
1.3.6.1.4.1.5528.30.10.146 |
The minimum number of milliseconds that the dry contact sensor on Ext4
must read openbefore the state is changed from closed to open. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
netBotz-prd-bot-ext-dry4-response |
1.3.6.1.4.1.5528.30.10.147 |
The type of alert response for the dry contact sensor on Ext4: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
netBotz-prd-bot-door-trap-tripped |
2 |
Netbotz Door Sensor Tripped Trap. This trap indicates that the door sensor
has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise). |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-door-trap-clear |
3 |
Netbotz Door Cleared Trap. The trap has been cleared because
the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open). |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp1-low-trap |
1 |
Netbotz Amp1 Low Trap. This trap indicates that the lower
limit for the first amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp1-high-trap |
2 |
Netbotz Amp1 High Trap. This trap indicates that the upper
limit for the first amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp1-trap-clear |
3 |
Netbotz Amp1 Cleared Trap. The trap has been cleared because
the first amp detect value has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp2-low-trap |
1 |
Netbotz Amp2 Low Trap. This trap indicates that the lower
limit for the second amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp2-high-trap |
2 |
Netbotz Amp2 High Trap. This trap indicates that the upper
limit for the second amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp2-trap-clear |
3 |
Netbotz Amp2 Cleared Trap. The trap has been cleared because
the second amp detect value has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp3-low-trap |
1 |
Netbotz Amp3 Low Trap. This trap indicates that the lower
limit for the third amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp3-high-trap |
2 |
Netbotz Amp3 High Trap. This trap indicates that the upper
limit for the third amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp3-trap-clear |
3 |
Netbotz Amp3 Cleared Trap. The trap has been cleared because
the third amp detect value has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp4-low-trap |
1 |
Netbotz Amp4 Low Trap. This trap indicates that the lower
limit for the fourth amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp4-high-trap |
2 |
Netbotz Amp4 High Trap. This trap indicates that the upper
limit for the fourth amp detect has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-amp4-trap-clear |
3 |
Netbotz Amp4 Cleared Trap. The trap has been cleared because
the fourth amp detect value has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-trap-clear |
3 |
Netbotz Cleared Trap. The trap has been cleared because
the value has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-offline-trap |
4 |
Netbotz Device Offline Trap. This trap indicates that a device or function
has been determined to be offline. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-online-trap |
5 |
Netbotz Device Online Trap. This trap indicates that a device or function
has been determined to be online. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp1-low-trap |
1 |
Netbotz External Temperature 1 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 1 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp1-high-trap |
2 |
Netbotz External Temperature 1 High Trap. This trap indicates that the upper
limit for external temperature probe on port 1 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp1-trap-clear |
3 |
Netbotz External Temperature 1 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 1 has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp2-low-trap |
1 |
Netbotz External Temperature 2 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 2 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp2-high-trap |
2 |
Netbotz External Temperature 2 High Trap. This trap indicates that the upper
limit for external temperature probe on port 2 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp2-trap-clear |
3 |
Netbotz External Temperature 2 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 2 has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp3-low-trap |
1 |
Netbotz External Temperature 3 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 3 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp3-high-trap |
2 |
Netbotz External Temperature 3 High Trap. This trap indicates that the upper
limit for external temperature probe on port 3 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp3-trap-clear |
3 |
Netbotz External Temperature 3 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 3 has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp4-low-trap |
1 |
Netbotz External Temperature 4 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 4 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp4-high-trap |
2 |
Netbotz External Temperature 4 High Trap. This trap indicates that the upper
limit for external temperature probe on port 4 has been exceeded. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-temp4-trap-clear |
3 |
Netbotz External Temperature 4 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 4 has returned to acceptable limits. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-dry1-trap-clear |
3 |
Netbotz External Dry Contact 1 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext1 no longer matches the alarm value. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-dry2-trap-clear |
3 |
Netbotz External Dry Contact 2 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext2 no longer matches the alarm value. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-dry3-trap-clear |
3 |
Netbotz External Dry Contact 3 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext3 no longer matches the alarm value. |
TRAP-TYPE |
|
|
|
netBotz-prd-bot-ext-dry4-trap-clear |
3 |
Netbotz External Dry Contact 4 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext4 no longer matches the alarm value. |
TRAP-TYPE |
|
|
|