NETBOTZ-MIB

File: NETBOTZ-MIB.mib (171436 bytes)

Imported modules

RFC-1212 RFC1213-MIB RFC1155-SMI
RFC-1215

Imported symbols

OBJECT-TYPE DisplayString enterprises
TRAP-TYPE TimeTicks IpAddress

Defined Types

ExpPortEntry  
SEQUENCE    
  expPort-module-id DisplayString
  expPort-module-type DisplayString
  expPort-label DisplayString
  expPort-amps INTEGER
  expPort-total-amp-seconds INTEGER
  expPort-total-amp-seconds-since-time INTEGER
  expPort-amps-enabled INTEGER
  expPort-amps-min INTEGER
  expPort-amps-max INTEGER
  expPort-amps-uV-per-10mA INTEGER
  expPort-amps-max-range INTEGER
  expPort-ext-temp INTEGER
  expPort-ext-temp-enabled INTEGER
  expPort-ext-temp-min INTEGER
  expPort-ext-temp-max INTEGER
  expPort-ext-temp-uV-per-degreeC INTEGER
  expPort-ext-temp-uV-at-0-degreeC INTEGER
  expPort-ext-temp-min-range INTEGER
  expPort-ext-temp-max-range INTEGER
  expPort-ext-dry INTEGER
  expPort-ext-dry-alarm-value INTEGER
  expPort-ext-dry-enabled INTEGER
  expPort-ext-dry-label DisplayString
  expPort-ext-dry-open-label DisplayString
  expPort-ext-dry-closed-label DisplayString
  expPort-ext-dry-open-to-close-millis INTEGER
  expPort-ext-dry-close-to-open-millis INTEGER
  expPort-ext-dry-response DisplayString

Defined Values

netBotz 1.3.6.1.4.1.5528
OBJECT IDENTIFIER    

netBotz-reg 1.3.6.1.4.1.5528.10
OBJECT IDENTIFIER    

netBotz-generic 1.3.6.1.4.1.5528.20
OBJECT IDENTIFIER    

netBotz-products 1.3.6.1.4.1.5528.30
OBJECT IDENTIFIER    

netBotz-metric 1.3.6.1.4.1.5528.32
OBJECT IDENTIFIER    

netBotz-snmp 1.3.6.1.4.1.5528.40
OBJECT IDENTIFIER    

netBotz-device 1.3.6.1.4.1.5528.50
OBJECT IDENTIFIER    

netBotz-addonapp 1.3.6.1.4.1.5528.60
OBJECT IDENTIFIER    

netBotz-addonapp-trap 1.3.6.1.4.1.5528.61
OBJECT IDENTIFIER    

vendor-netBotz 1.3.6.1.4.1.5528.60.5528
OBJECT IDENTIFIER    

device-crawlers-trap 1.3.6.1.4.1.5528.60.5528.2
OBJECT IDENTIFIER    

branch-checker-trap 1.3.6.1.4.1.5528.60.5528.3
OBJECT IDENTIFIER    

device-crawlers-trap-attrib 1.3.6.1.4.1.5528.61.2
OBJECT IDENTIFIER    

branch-checker-trap-attrib 1.3.6.1.4.1.5528.61.3
OBJECT IDENTIFIER    

device-crawlers-trap-target-index 1.3.6.1.4.1.5528.60.2
OBJECT IDENTIFIER    

branch-checker-trap-target-index 1.3.6.1.4.1.5528.60.3
OBJECT IDENTIFIER    

netBotz-prd-bot 1.3.6.1.4.1.5528.30.10
OBJECT IDENTIFIER    

netBotz-metric-onboard 1.3.6.1.4.1.5528.32.10
OBJECT IDENTIFIER    

netBotz-prd-crawlers 1.3.6.1.4.1.5528.30.20
OBJECT IDENTIFIER    

netBotz-prd-crltrap 1.3.6.1.4.1.5528.30.21
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300 1.3.6.1.4.1.5528.30.1000
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300 1.3.6.1.4.1.5528.30.1001
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300U 1.3.6.1.4.1.5528.30.1002
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-400 1.3.6.1.4.1.5528.30.1003
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-400 1.3.6.1.4.1.5528.30.1004
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-303 1.3.6.1.4.1.5528.30.1006
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-310 1.3.6.1.4.1.5528.30.1007
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-310 1.3.6.1.4.1.5528.30.1008
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300B 1.3.6.1.4.1.5528.30.1009
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300C 1.3.6.1.4.1.5528.30.1100
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300C 1.3.6.1.4.1.5528.30.1101
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300UC 1.3.6.1.4.1.5528.30.1102
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-400C 1.3.6.1.4.1.5528.30.1103
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-400C 1.3.6.1.4.1.5528.30.1104
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-303C 1.3.6.1.4.1.5528.30.1106
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-310C 1.3.6.1.4.1.5528.30.1107
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-310C 1.3.6.1.4.1.5528.30.1108
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300BC 1.3.6.1.4.1.5528.30.1109
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300E 1.3.6.1.4.1.5528.30.1200
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300E 1.3.6.1.4.1.5528.30.1201
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-300UE 1.3.6.1.4.1.5528.30.1202
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-400E 1.3.6.1.4.1.5528.30.1203
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-400E 1.3.6.1.4.1.5528.30.1204
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-303E 1.3.6.1.4.1.5528.30.1206
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-310E 1.3.6.1.4.1.5528.30.1207
OBJECT IDENTIFIER    

netBotz-prd-RackBotz-310E 1.3.6.1.4.1.5528.30.1208
OBJECT IDENTIFIER    

netBotz-prd-WallBotz-300BE 1.3.6.1.4.1.5528.30.1209
OBJECT IDENTIFIER    

netBotz-dev-host 1.3.6.1.4.1.5528.50.1
NetBotz device's host name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-domain 1.3.6.1.4.1.5528.50.2
NetBotz device's default DNS domain.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-ip 1.3.6.1.4.1.5528.50.3
NetBotz device's IP address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-netmask 1.3.6.1.4.1.5528.50.4
NetBotz device's netmask.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-gateway 1.3.6.1.4.1.5528.50.5
NetBotz device's default gateway/router. 0.0.0.0 if not defined.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-primarydns 1.3.6.1.4.1.5528.50.6
Primary Domain Name Server. 0.0.0.0 if not defined.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-secondarydns 1.3.6.1.4.1.5528.50.7
Secondary Domain Name Server. 0.0.0.0 if not defined.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-smtp 1.3.6.1.4.1.5528.50.8
SMTP server address. This is the mail server used for sending alert e-mails.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-smtpport 1.3.6.1.4.1.5528.50.9
SMTP port. Port number of SMTP server used for sending alert e-mails.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-popport 1.3.6.1.4.1.5528.50.10
POP port. Currently, not used.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-loglevel 1.3.6.1.4.1.5528.50.11
This field contains the log level of the NetBotz device. Log messages will be filtered, so that only same or lower-level messages will be passed. The default log level is 5, for warnings and lower levels. The log levels are the following: 1 - emergency 2 - alert 3 - critical 4 - error 5 - warning 6 - notice 7 - info 8 - trace
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-primaryemail 1.3.6.1.4.1.5528.50.14
The primary email addresses for alerts and messages (list separated by commas for multiple addresses).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-secondaryemail 1.3.6.1.4.1.5528.50.15
The secondary email address for alerts and messages (list separated by commas for multiple addresses).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-serialno 1.3.6.1.4.1.5528.50.17
The serial number of the NetBotz device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-dev-pop 1.3.6.1.4.1.5528.50.18
POP server name. Currently, not used.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-version 1.3.6.1.4.1.5528.50.19
The current NetBotz device firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-dev-registered 1.3.6.1.4.1.5528.50.20
Indicates if the device has been registered with NetBotz, Inc. 1=registered, 0=not registered.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-default-applet 1.3.6.1.4.1.5528.50.21
Setting to control if default web page should launch applet by default(1) or the HTML status page(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-guibar-color 1.3.6.1.4.1.5528.50.22
Setting for color of GUI bar (RGB). Value = 0xRRGGBB.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-locale 1.3.6.1.4.1.5528.50.23
The locale ID of the NetBotz device. Format is ISO 639 language (lower case), an underscore, and ISO 3166 country (upper case). Some locales are just the ISO 639 language code.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-timezone 1.3.6.1.4.1.5528.50.24
The timezone ID of the NetBotz device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-24hourpreferred 1.3.6.1.4.1.5528.50.25
Indicates if 24-hour(1) versus 12-hour(0) time format is preferred.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-utc-clock 1.3.6.1.4.1.5528.50.26
Current time of clock on NetBotz device, in UTC seconds (seconds since 1/1/1970 12:00am GMT).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-ismetric 1.3.6.1.4.1.5528.50.27
Units are metric (1) or U.S. (0). Applies to temperature and airflow rate.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-alert-url 1.3.6.1.4.1.5528.50.28
The URL, if defined, to which non-picture alerts are HTTP POSTed
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-picture-alert-url 1.3.6.1.4.1.5528.50.29
The URL, if defined, to which picture alerts are HTTP POSTed, using multipart/form-data encoding.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-data-url 1.3.6.1.4.1.5528.50.30
The URL, if defined, to which sensor data is periodically HTTP POSTed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-alert-url-logon 1.3.6.1.4.1.5528.50.31
The user ID and password, if defined, used for POSTing non-picture alerts. Field is write-only, and formatted /
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-picture-alert-url-logon 1.3.6.1.4.1.5528.50.32
The user ID and password, if defined, used for POSTing picture alerts. Field is write-only, and formatted /
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-data-url-logon 1.3.6.1.4.1.5528.50.33
The user ID and password, if defined, used for POSTing sensor data. Field is write-only, and formatted /
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-data-url-period 1.3.6.1.4.1.5528.50.34
Default number of minutes between periodic sensor data HTTP POSTs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-sensor-data-url-flags 1.3.6.1.4.1.5528.50.35
Option flags for data POSTs of sensor data. Bit 0=1 if current picture should be included. Bits 1-31 are reserved.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-backup-smtp 1.3.6.1.4.1.5528.50.36
Backup SMTP server address. This is the backup mail server used for sending alert e-mails.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-tertiarydns 1.3.6.1.4.1.5528.50.37
Tertiary Domain Name Server. 0.0.0.0 if not defined.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-dev-ntp-server 1.3.6.1.4.1.5528.50.38
NTP (Network Time Protocol) Server configured for appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-ntp-period 1.3.6.1.4.1.5528.50.39
Hours between automatic refreshes of the appliance clock using the NTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-socks-server 1.3.6.1.4.1.5528.50.40
Socks V4 or V5 proxy server configured for appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-socks-portnum 1.3.6.1.4.1.5528.50.41
Port number of Socks Proxy.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-dev-socks-user-id 1.3.6.1.4.1.5528.50.42
User ID for Socks V4 or V5 proxy server configured for appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-dev-socks-password 1.3.6.1.4.1.5528.50.43
Password for Socks V4 or V5 proxy server configured for appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-alert-ftp-site 1.3.6.1.4.1.5528.50.44
The hostname or dotted-decimal IP address of the FTP server to deliver alerts to
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-alert-ftp-path 1.3.6.1.4.1.5528.50.45
The directory on the FTP server to store alerts in.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-alert-ftp-filename 1.3.6.1.4.1.5528.50.46
The base filename for the files on the FTP server to store alerts in.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-alert-ftp-logon 1.3.6.1.4.1.5528.50.47
The user-id and password on the FTP server to store alerts in. Field is write-only, and formatted /
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-ftp-site 1.3.6.1.4.1.5528.50.48
The hostname or dotted-decimal IP address of the FTP server to deliver periodic sensor reports to
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-ftp-path 1.3.6.1.4.1.5528.50.49
The directory on the FTP server to store periodic sensor reports in.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-ftp-filename 1.3.6.1.4.1.5528.50.50
The base filename for the files on the FTP server to store periodic sensor reports in.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-ftp-logon 1.3.6.1.4.1.5528.50.51
The user-id and password on the FTP server to store sensor reports in. Field is write-only, and formatted /
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-sensor-ftp-period 1.3.6.1.4.1.5528.50.52
The period, in minutes, between delivery of sensor data reports.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-use-syslog 1.3.6.1.4.1.5528.50.53
Enable syslog
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-syslog-address 1.3.6.1.4.1.5528.50.54
Host address to use for syslogging
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-syslog-facility 1.3.6.1.4.1.5528.50.55
Syslog facility code
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-color-balance 1.3.6.1.4.1.5528.50.56
Color balance for color camera. AUTO=automatic, FLUOR=fluorescent, DAY=daylight, INCAND=incandescent, x/y=Custom (scale red by x/64, scale blue by y/64)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-metric-onboard-model 1.3.6.1.4.1.5528.32.10.1
The model description of the appliance.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-metric-onboard-temp 1.3.6.1.4.1.5528.32.10.2
The reading of the built-in temperature probe, in tenths of a degree C.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-humidity 1.3.6.1.4.1.5528.32.10.3
The reading of the built-in humidity probe, in percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-airflow 1.3.6.1.4.1.5528.32.10.4
The reading of the built-in airflow probe, in meters/minute.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-audio 1.3.6.1.4.1.5528.32.10.5
The reading of the built-in audio alarm probe on/off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-doorajar 1.3.6.1.4.1.5528.32.10.6
The reading of the door switch probe open(1) or closed(0).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-temp-min 1.3.6.1.4.1.5528.32.10.7
The temperature probe minimum, from 1 to 50 degrees C in tenths of a degree C.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-temp-max 1.3.6.1.4.1.5528.32.10.8
The temperature probe maximum, from 1 to 50 degrees C in tenths of a degree C.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-humidity-min 1.3.6.1.4.1.5528.32.10.9
The humidity probe minimum, from 10 to 90 percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-humidity-max 1.3.6.1.4.1.5528.32.10.10
The humidity probe maximum, from 10 to 90 percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-airflow-mins 1.3.6.1.4.1.5528.32.10.11
Minutes without airflow before alarm set.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-audio-secs 1.3.6.1.4.1.5528.32.10.12
Seconds of alarm audio before alarm set.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-switch-state 1.3.6.1.4.1.5528.32.10.13
Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-audio-level 1.3.6.1.4.1.5528.32.10.14
Audio level setting, this is the relative audio level, from 0-11, above which an alarm will be sent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-airflow-level 1.3.6.1.4.1.5528.32.10.15
Airflow alert level. This is the level, in meters per second, below which an alarm will be sent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-cam-motion 1.3.6.1.4.1.5528.32.10.16
The current motion reading for the camera motion sensor (0=none, 1=motion detected, -1=not licensed).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-metric-onboard-cam-motion-sensitivity 1.3.6.1.4.1.5528.32.10.17
Camera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-temp 1.3.6.1.4.1.5528.30.10.1
The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-humidity 1.3.6.1.4.1.5528.30.10.2
The reading of the humidity probe, in percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-airflow 1.3.6.1.4.1.5528.30.10.3
The reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-audio 1.3.6.1.4.1.5528.30.10.4
The reading of the audio alarm probe on/off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-doorajar 1.3.6.1.4.1.5528.30.10.5
The reading of the door switch probe open(1) or closed(0).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-temp-min 1.3.6.1.4.1.5528.30.10.6
The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-temp-max 1.3.6.1.4.1.5528.30.10.7
The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-humidity-min 1.3.6.1.4.1.5528.30.10.8
The humidity probe minimum, from 10 to 90 percent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-humidity-max 1.3.6.1.4.1.5528.30.10.9
The humidity probe maximum, from 10 to 90 percent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-airflow-mins 1.3.6.1.4.1.5528.30.10.10
Minutes without airflow before alarm set.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-audio-secs 1.3.6.1.4.1.5528.30.10.11
Seconds of alarm audio before alarm set.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-temp-enabled 1.3.6.1.4.1.5528.30.10.12
Temperature probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-hum-enabled 1.3.6.1.4.1.5528.30.10.13
Humidity probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-air-enabled 1.3.6.1.4.1.5528.30.10.14
Airflow probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-audio-enabled 1.3.6.1.4.1.5528.30.10.15
Audio probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-switch-state 1.3.6.1.4.1.5528.30.10.16
Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-switch-enabled 1.3.6.1.4.1.5528.30.10.17
Door switch enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-audio-level 1.3.6.1.4.1.5528.30.10.18
Audio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-trap-index 1.3.6.1.4.1.5528.30.10.20
The crawler ID of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-trap-address 1.3.6.1.4.1.5528.30.10.21
The IP address of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

netBotz-prd-bot-trap-oid 1.3.6.1.4.1.5528.30.10.22
The object id of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

netBotz-prd-bot-trap-value 1.3.6.1.4.1.5528.30.10.23
The value of the last object trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-trap-date 1.3.6.1.4.1.5528.30.10.24
The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-refresh 1.3.6.1.4.1.5528.30.10.26
Rate of web page refresh, in seconds. This must be greater than 5 seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-airflow-level 1.3.6.1.4.1.5528.30.10.27
Airflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of airflow velocity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-doorpic-count 1.3.6.1.4.1.5528.30.10.28
Number of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps1 1.3.6.1.4.1.5528.30.10.29
The reading of the first amperage probe, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps1-enabled 1.3.6.1.4.1.5528.30.10.30
Amperage[1] probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps1-min 1.3.6.1.4.1.5528.30.10.31
The amperage[1] probe minimum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps1-max 1.3.6.1.4.1.5528.30.10.32
The amperage[1] probe maximum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2 1.3.6.1.4.1.5528.30.10.34
The reading of the second amperage probe, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2-enabled 1.3.6.1.4.1.5528.30.10.35
Amperage[2] probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2-min 1.3.6.1.4.1.5528.30.10.36
The amperage[2] probe minimum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2-max 1.3.6.1.4.1.5528.30.10.37
The amperage[2] probe maximum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3 1.3.6.1.4.1.5528.30.10.39
The reading of the third amperage probe, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3-enabled 1.3.6.1.4.1.5528.30.10.40
Amperage[3] probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3-min 1.3.6.1.4.1.5528.30.10.41
The amperage[3] probe minimum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3-max 1.3.6.1.4.1.5528.30.10.42
The amperage[3] probe maximum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps-total 1.3.6.1.4.1.5528.30.10.44
The total of the readings of all amperage probes, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps-total-enabled 1.3.6.1.4.1.5528.30.10.45
Total amperage alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps-total-min 1.3.6.1.4.1.5528.30.10.46
The total amperage minimum, from 0 to 90000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps-total-max 1.3.6.1.4.1.5528.30.10.47
The total amperage maximum, from 0 to 90000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps-total-support-enabled 1.3.6.1.4.1.5528.30.10.48
Total Amperage Support enabled(Y) or disabled(N).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-amps1-uV-per-10mA 1.3.6.1.4.1.5528.30.10.49
The scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2-uV-per-10mA 1.3.6.1.4.1.5528.30.10.50
The scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3-uV-per-mA 1.3.6.1.4.1.5528.30.10.51
The scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps1-max-range 1.3.6.1.4.1.5528.30.10.52
The maximum RMS milliamps measureable by the first Amp Detect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps2-max-range 1.3.6.1.4.1.5528.30.10.53
The maximum RMS milliamps measureable by the second Amp Detect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps3-max-range 1.3.6.1.4.1.5528.30.10.54
The maximum RMS milliamps measureable by the third Amp Detect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4 1.3.6.1.4.1.5528.30.10.55
The reading of the fourth amperage probe, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4-enabled 1.3.6.1.4.1.5528.30.10.56
Amperage[4] probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4-min 1.3.6.1.4.1.5528.30.10.57
The amperage[4] probe minimum, in milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4-max 1.3.6.1.4.1.5528.30.10.58
The amperage[4] probe maximum, in milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4-uV-per-10mA 1.3.6.1.4.1.5528.30.10.60
The scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amps4-max-range 1.3.6.1.4.1.5528.30.10.61
The maximum RMS milliamps measureable by the fourth Amp Detect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1 1.3.6.1.4.1.5528.30.10.62
The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2 1.3.6.1.4.1.5528.30.10.63
The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3 1.3.6.1.4.1.5528.30.10.64
The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-enabled 1.3.6.1.4.1.5528.30.10.66
External temperature probe on port 1 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-min 1.3.6.1.4.1.5528.30.10.67
The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-max 1.3.6.1.4.1.5528.30.10.68
The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-enabled 1.3.6.1.4.1.5528.30.10.69
External temperature probe on port 2 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-min 1.3.6.1.4.1.5528.30.10.70
The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-max 1.3.6.1.4.1.5528.30.10.71
The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-enabled 1.3.6.1.4.1.5528.30.10.72
External temperature probe on port 3 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-min 1.3.6.1.4.1.5528.30.10.73
The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-max 1.3.6.1.4.1.5528.30.10.74
The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-uV-per-degreeC 1.3.6.1.4.1.5528.30.10.78
The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-uV-at-0-degreeC 1.3.6.1.4.1.5528.30.10.79
The offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-max-range 1.3.6.1.4.1.5528.30.10.81
The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp1-min-range 1.3.6.1.4.1.5528.30.10.80
The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-uV-per-degreeC 1.3.6.1.4.1.5528.30.10.82
The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-uV-at-0-degreeC 1.3.6.1.4.1.5528.30.10.83
The offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-max-range 1.3.6.1.4.1.5528.30.10.85
The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp2-min-range 1.3.6.1.4.1.5528.30.10.84
The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-uV-per-degreeC 1.3.6.1.4.1.5528.30.10.86
The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-uV-at-0-degreeC 1.3.6.1.4.1.5528.30.10.87
The offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-max-range 1.3.6.1.4.1.5528.30.10.89
The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-temp3-min-range 1.3.6.1.4.1.5528.30.10.88
The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-port1-module-id 1.3.6.1.4.1.5528.30.10.94
The module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-port1-module-type 1.3.6.1.4.1.5528.30.10.95
The type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-port2-module-id 1.3.6.1.4.1.5528.30.10.96
The module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-port2-module-type 1.3.6.1.4.1.5528.30.10.97
The type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-port3-module-id 1.3.6.1.4.1.5528.30.10.98
The module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-port3-module-type 1.3.6.1.4.1.5528.30.10.99
The type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-amp1-total-amp-seconds 1.3.6.1.4.1.5528.30.10.102
The accumulated total of amp-seconds on the AmpDetect on port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp1-total-amp-seconds-since-time 1.3.6.1.4.1.5528.30.10.103
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp2-total-amp-seconds 1.3.6.1.4.1.5528.30.10.104
The accumulated total of amp-seconds on the AmpDetect on port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp2-total-amp-seconds-since-time 1.3.6.1.4.1.5528.30.10.105
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp3-total-amp-seconds 1.3.6.1.4.1.5528.30.10.106
The accumulated total of amp-seconds on the AmpDetect on port 3.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp3-total-amp-seconds-since-time 1.3.6.1.4.1.5528.30.10.107
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp4-total-amp-seconds 1.3.6.1.4.1.5528.30.10.108
The accumulated total of amp-seconds on the AmpDetect on port 4.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amp4-total-amp-seconds-since-time 1.3.6.1.4.1.5528.30.10.109
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amptotal-total-amp-seconds 1.3.6.1.4.1.5528.30.10.110
The accumulated total of amp-seconds on the total of all AmpDetects.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-amptotal-total-amp-seconds-since-time 1.3.6.1.4.1.5528.30.10.111
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1 1.3.6.1.4.1.5528.30.10.112
The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry2 1.3.6.1.4.1.5528.30.10.113
The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry3 1.3.6.1.4.1.5528.30.10.114
The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry4 1.3.6.1.4.1.5528.30.10.115
The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1-alarm-value 1.3.6.1.4.1.5528.30.10.116
The value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1-enabled 1.3.6.1.4.1.5528.30.10.117
External dry contact sensor on Ext1 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry2-alarm-value 1.3.6.1.4.1.5528.30.10.118
The value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry2-enabled 1.3.6.1.4.1.5528.30.10.119
External dry contact sensor on Ext2 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry3-alarm-value 1.3.6.1.4.1.5528.30.10.120
The value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry3-enabled 1.3.6.1.4.1.5528.30.10.121
External dry contact sensor on Ext3 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry4-alarm-value 1.3.6.1.4.1.5528.30.10.122
The value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry4-enabled 1.3.6.1.4.1.5528.30.10.123
External dry contact sensor on Ext4 alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1-label 1.3.6.1.4.1.5528.30.10.124
The sensor name/label for the dry contact sensor on Ext1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry1-open-label 1.3.6.1.4.1.5528.30.10.125
The sensor name/label for the open(0) state for the dry contact sensor on Ext1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry1-closed-label 1.3.6.1.4.1.5528.30.10.126
The sensor name/label for the closed(0) state for the dry contact sensor on Ext1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry1-open-to-close-millis 1.3.6.1.4.1.5528.30.10.127
The minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1-close-to-open-millis 1.3.6.1.4.1.5528.30.10.128
The minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry1-response 1.3.6.1.4.1.5528.30.10.129
The type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry2-label 1.3.6.1.4.1.5528.30.10.130
The sensor name/label for the dry contact sensor on Ext2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry2-open-label 1.3.6.1.4.1.5528.30.10.131
The sensor name/label for the open(0) state for the dry contact sensor on Ext2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry2-closed-label 1.3.6.1.4.1.5528.30.10.132
The sensor name/label for the closed(0) state for the dry contact sensor on Ext2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry2-open-to-close-millis 1.3.6.1.4.1.5528.30.10.133
The minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry2-close-to-open-millis 1.3.6.1.4.1.5528.30.10.134
The minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry2-response 1.3.6.1.4.1.5528.30.10.135
The type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry3-label 1.3.6.1.4.1.5528.30.10.136
The sensor name/label for the dry contact sensor on Ext3
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry3-open-label 1.3.6.1.4.1.5528.30.10.137
The sensor name/label for the open(0) state for the dry contact sensor on Ext3
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry3-closed-label 1.3.6.1.4.1.5528.30.10.138
The sensor name/label for the closed(0) state for the dry contact sensor on Ext3
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-ext-dry3-open-to-close-millis 1.3.6.1.4.1.5528.30.10.139
The minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry3-close-to-open-millis 1.3.6.1.4.1.5528.30.10.140
The minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-ext-dry3-response 1.3.6.1.4.1.5528.30.10.141
The type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-prd-bot-cam-motion 1.3.6.1.4.1.5528.30.10.148
The current motion reading for the camera motion sensor (0=none, 1=motion detected)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-cam-motion-enabled 1.3.6.1.4.1.5528.30.10.149
Camera motion sensor alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-cam-motion-sensitivity 1.3.6.1.4.1.5528.30.10.150
Camera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-cam-motion-delay 1.3.6.1.4.1.5528.30.10.151
Camera motion sensor delay. This is the minimum number of milliseconds of detected motion required before the alarm is triggered.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-camera-event-autocycle 1.3.6.1.4.1.5528.30.10.152
Enables (1) or disables (0) the option to have the camera-based responses to alarm conditions automatically cycle as long as the condition persists.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-num-pix-before-alarm 1.3.6.1.4.1.5528.30.10.153
Controls the number of pictures to be captured before any triggered alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-delay-before-event-pix 1.3.6.1.4.1.5528.30.10.154
Controls the number of milliseconds before the first picture is captured after any triggered alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-delay-between-event-pix 1.3.6.1.4.1.5528.30.10.155
Controls the number of milliseconds between pictures captured after any triggered alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-cam-motion-area-of-motion 1.3.6.1.4.1.5528.30.10.156
Camera motion sensor area of motion: 1=max, 15=min, 0=disabled.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-cam-pix-for-duration-of-alerts 1.3.6.1.4.1.5528.30.10.157
Camera images gathered for duration of camera related alert: 0=no, 1=yes.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-camera-enabled 1.3.6.1.4.1.5528.30.10.158
Controls whether the camera is enabled or not: 0=no, 1=yes. Changing this will reboot the appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-camera-is-flipped 1.3.6.1.4.1.5528.30.10.159
Controls whether the camera image is flipped 180 degress or not: 0=no, 1=yes. Changing this will reboot the appliance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-camera-brightness 1.3.6.1.4.1.5528.30.10.160
Sets the brightness on the camera, from 20 to 180 (20 is low, 180 is high).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-prd-bot-traps 1.3.6.1.4.1.5528.30.100
OBJECT IDENTIFIER    

netBotz-prd-bot-temperature-traps 1.3.6.1.4.1.5528.30.100.1
OBJECT IDENTIFIER    

netBotz-prd-bot-humidity-traps 1.3.6.1.4.1.5528.30.100.2
OBJECT IDENTIFIER    

netBotz-prd-bot-airflow-traps 1.3.6.1.4.1.5528.30.100.3
OBJECT IDENTIFIER    

netBotz-prd-bot-audio-traps 1.3.6.1.4.1.5528.30.100.4
OBJECT IDENTIFIER    

netBotz-prd-bot-door-traps 1.3.6.1.4.1.5528.30.100.5
OBJECT IDENTIFIER    

netBotz-prd-bot-amp1-traps 1.3.6.1.4.1.5528.30.100.6
OBJECT IDENTIFIER    

netBotz-prd-bot-amp2-traps 1.3.6.1.4.1.5528.30.100.7
OBJECT IDENTIFIER    

netBotz-prd-bot-amp3-traps 1.3.6.1.4.1.5528.30.100.8
OBJECT IDENTIFIER    

netBotz-prd-bot-amp4-traps 1.3.6.1.4.1.5528.30.100.9
OBJECT IDENTIFIER    

netBotz-prd-bot-amp-total-traps 1.3.6.1.4.1.5528.30.100.10
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp1-traps 1.3.6.1.4.1.5528.30.100.11
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp2-traps 1.3.6.1.4.1.5528.30.100.12
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp3-traps 1.3.6.1.4.1.5528.30.100.13
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp4-traps 1.3.6.1.4.1.5528.30.100.14
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry1-traps 1.3.6.1.4.1.5528.30.100.15
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry2-traps 1.3.6.1.4.1.5528.30.100.16
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry3-traps 1.3.6.1.4.1.5528.30.100.17
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry4-traps 1.3.6.1.4.1.5528.30.100.18
OBJECT IDENTIFIER    

netBotz-prd-bot-amp5-traps 1.3.6.1.4.1.5528.30.100.19
OBJECT IDENTIFIER    

netBotz-prd-bot-amp6-traps 1.3.6.1.4.1.5528.30.100.20
OBJECT IDENTIFIER    

netBotz-prd-bot-amp7-traps 1.3.6.1.4.1.5528.30.100.21
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp5-traps 1.3.6.1.4.1.5528.30.100.22
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp6-traps 1.3.6.1.4.1.5528.30.100.23
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-temp7-traps 1.3.6.1.4.1.5528.30.100.24
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry5-traps 1.3.6.1.4.1.5528.30.100.25
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry6-traps 1.3.6.1.4.1.5528.30.100.26
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-dry7-traps 1.3.6.1.4.1.5528.30.100.27
OBJECT IDENTIFIER    

netBotz-prd-bot-camera-motion-traps 1.3.6.1.4.1.5528.30.100.28
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi1-traps 1.3.6.1.4.1.5528.30.100.29
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi2-traps 1.3.6.1.4.1.5528.30.100.30
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi3-traps 1.3.6.1.4.1.5528.30.100.31
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi4-traps 1.3.6.1.4.1.5528.30.100.32
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi5-traps 1.3.6.1.4.1.5528.30.100.33
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi6-traps 1.3.6.1.4.1.5528.30.100.34
OBJECT IDENTIFIER    

netBotz-prd-bot-ext-humi7-traps 1.3.6.1.4.1.5528.30.100.35
OBJECT IDENTIFIER    

netBotz-prd-bot-temperature-low-trap 1
NetBotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-temperature-high-trap 2
NetBotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-temperature-trap-clear 3
NetBotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-humidity-low-trap 1
NetBotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-humidity-high-trap 2
NetBotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-humidity-trap-clear 3
NetBotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-airflow-low-trap 1
NetBotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-airflow-trap-clear 3
NetBotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-audio-high-trap 2
NetBotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-audio-trap-clear 3
NetBotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-door-trap-tripped 2
NetBotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise).
TRAP-TYPE    

netBotz-prd-bot-door-trap-clear 3
NetBotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open).
TRAP-TYPE    

netBotz-prd-bot-amp1-low-trap 1
NetBotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp1-high-trap 2
NetBotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp1-trap-clear 3
NetBotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp1-sensor-unplugged 6
NetBotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp1-sensor-replugged 7
NetBotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp2-low-trap 1
NetBotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp2-high-trap 2
NetBotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp2-trap-clear 3
NetBotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp2-sensor-unplugged 6
NetBotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp2-sensor-replugged 7
NetBotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp3-low-trap 1
NetBotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp3-high-trap 2
NetBotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp3-trap-clear 3
NetBotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp3-sensor-unplugged 6
NetBotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp3-sensor-replugged 7
NetBotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp4-low-trap 1
NetBotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp4-high-trap 2
NetBotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp4-trap-clear 3
NetBotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp4-sensor-unplugged 6
NetBotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp4-sensor-replugged 7
NetBotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp5-low-trap 1
NetBotz Amp 5 Low Trap. This trap indicates that the lower limit for the fifth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp5-high-trap 2
NetBotz Amp 5 High Trap. This trap indicates that the upper limit for the fifth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp5-trap-clear 3
NetBotz Amp 5 Cleared Trap. The trap has been cleared because the fifth amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp5-sensor-unplugged 6
NetBotz Amp 5 Sensor Unplugged Trap. The sensor for the fifth AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp5-sensor-replugged 7
NetBotz Amp 5 Sensor Replugged Trap. The sensor for the fifth AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp6-low-trap 1
NetBotz Amp 6 Low Trap. This trap indicates that the lower limit for the sixth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp6-high-trap 2
NetBotz Amp 6 High Trap. This trap indicates that the upper limit for the sixth amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp6-trap-clear 3
NetBotz Amp 6 Cleared Trap. The trap has been cleared because the sixth amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp6-sensor-unplugged 6
NetBotz Amp 6 Sensor Unplugged Trap. The sensor for the sixth AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp6-sensor-replugged 7
NetBotz Amp 6 Sensor Replugged Trap. The sensor for the sixth AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp7-low-trap 1
NetBotz Amp 7 Low Trap. This trap indicates that the lower limit for the seventh amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp7-high-trap 2
NetBotz Amp 7 High Trap. This trap indicates that the upper limit for the seventh amp detect has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp7-trap-clear 3
NetBotz Amp 7 Cleared Trap. The trap has been cleared because the seventh amp detect value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-amp7-sensor-unplugged 6
NetBotz Amp 7 Sensor Unplugged Trap. The sensor for the seventh AmpDetect is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-amp7-sensor-replugged 7
NetBotz Amp 7 Sensor Replugged Trap. The sensor for the seventh AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-amp-total-low-trap 1
NetBotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp-total-high-trap 2
NetBotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-amp-total-trap-clear 3
NetBotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-low-trap 1
NetBotz Low Trap. This trap indicates that a lower limit has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-high-trap 2
NetBotz High Trap. This trap indicates that an upper limit has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-trap-clear 3
NetBotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-offline-trap 4
NetBotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
TRAP-TYPE    

netBotz-prd-bot-online-trap 5
NetBotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
TRAP-TYPE    

netBotz-prd-bot-ext-temp1-low-trap 1
NetBotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp1-high-trap 2
NetBotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp1-trap-clear 3
NetBotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp1-sensor-unplugged 6
NetBotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp1-sensor-replugged 7
NetBotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp2-low-trap 1
NetBotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp2-high-trap 2
NetBotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp2-trap-clear 3
NetBotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp2-sensor-unplugged 6
NetBotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp2-sensor-replugged 7
NetBotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp3-low-trap 1
NetBotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp3-high-trap 2
NetBotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp3-trap-clear 3
NetBotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp3-sensor-unplugged 6
NetBotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp3-sensor-replugged 7
NetBotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp4-low-trap 1
NetBotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp4-high-trap 2
NetBotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp4-trap-clear 3
NetBotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp4-sensor-unplugged 6
NetBotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp4-sensor-replugged 7
NetBotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp5-low-trap 1
NetBotz External Temperature 5 Low Trap. This trap indicates that the lower limit for external temperature probe on port 5 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp5-high-trap 2
NetBotz External Temperature 5 High Trap. This trap indicates that the upper limit for external temperature probe on port 5 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp5-trap-clear 3
NetBotz External Temperature 5 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 5 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp5-sensor-unplugged 6
NetBotz External Temperature 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp5-sensor-replugged 7
NetBotz External Temperature 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp6-low-trap 1
NetBotz External Temperature 6 Low Trap. This trap indicates that the lower limit for external temperature probe on port 6 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp6-high-trap 2
NetBotz External Temperature 6 High Trap. This trap indicates that the upper limit for external temperature probe on port 6 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp6-trap-clear 3
NetBotz External Temperature 6 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 6 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp6-sensor-unplugged 6
NetBotz External Temperature 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp6-sensor-replugged 7
NetBotz External Temperature 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-temp7-low-trap 1
NetBotz External Temperature 7 Low Trap. This trap indicates that the lower limit for external temperature probe on port 7 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp7-high-trap 2
NetBotz External Temperature 7 High Trap. This trap indicates that the upper limit for external temperature probe on port 7 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-temp7-trap-clear 3
NetBotz External Temperature 7 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 7 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-temp7-sensor-unplugged 6
NetBotz External Temperature 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-temp7-sensor-replugged 7
NetBotz External Temperature 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-dry1-triggered-trap 2
NetBotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry1-trap-clear 3
NetBotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry2-triggered-trap 2
NetBotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry2-trap-clear 3
NetBotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry3-triggered-trap 2
NetBotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry3-trap-clear 3
NetBotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry4-triggered-trap 2
NetBotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry4-trap-clear 3
NetBotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry5-triggered-trap 2
NetBotz External Dry Contact 5 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext5 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry5-trap-clear 3
NetBotz External Dry Contact 5 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext5 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry6-triggered-trap 2
NetBotz External Dry Contact 6 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext6 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry6-trap-clear 3
NetBotz External Dry Contact 6 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext6 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry7-triggered-trap 2
NetBotz External Dry Contact 7 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext7 matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-ext-dry7-trap-clear 3
NetBotz External Dry Contact 7 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext7 no longer matches the alarm value.
TRAP-TYPE    

netBotz-prd-bot-camera-motion-trap-tripped 2
NetBotz Camera Motion Sensor Tripped Trap. This trap indicates that the camera motion sensor has been triggered (motion has been detected).
TRAP-TYPE    

netBotz-prd-bot-camera-motion-trap-clear 3
NetBotz Camera Motion Cleared Trap. The trap has been cleared because the camera motion sensor has returned to normal (no longer is detecting motion).
TRAP-TYPE    

netBotz-prd-bot-ext-humi1-low-trap 1
NetBotz External Humidity 1 Low Trap. This trap indicates that the lower limit for external humidity probe on port 1 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi1-high-trap 2
NetBotz External Humidity 1 High Trap. This trap indicates that the upper limit for external humidity probe on port 1 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi1-trap-clear 3
NetBotz External Humidity 1 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 1 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi1-sensor-unplugged 6
NetBotz External Humidity 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi1-sensor-replugged 7
NetBotz External Humidity 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi2-low-trap 1
NetBotz External Humidity 2 Low Trap. This trap indicates that the lower limit for external humidity probe on port 2 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi2-high-trap 2
NetBotz External Humidity 2 High Trap. This trap indicates that the upper limit for external humidity probe on port 2 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi2-trap-clear 3
NetBotz External Humidity 2 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 2 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi2-sensor-unplugged 6
NetBotz External Humidity 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi2-sensor-replugged 7
NetBotz External Humidity 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi3-low-trap 1
NetBotz External Humidity 3 Low Trap. This trap indicates that the lower limit for external humidity probe on port 3 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi3-high-trap 2
NetBotz External Humidity 3 High Trap. This trap indicates that the upper limit for external humidity probe on port 3 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi3-trap-clear 3
NetBotz External Humidity 3 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 3 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi3-sensor-unplugged 6
NetBotz External Humidity 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi3-sensor-replugged 7
NetBotz External Humidity 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi4-low-trap 1
NetBotz External Humidity 4 Low Trap. This trap indicates that the lower limit for external humidity probe on port 4 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi4-high-trap 2
NetBotz External Humidity 4 High Trap. This trap indicates that the upper limit for external humidity probe on port 4 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi4-trap-clear 3
NetBotz External Humidity 4 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 4 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi4-sensor-unplugged 6
NetBotz External Humidity 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi4-sensor-replugged 7
NetBotz External Humidity 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi5-low-trap 1
NetBotz External Humidity 5 Low Trap. This trap indicates that the lower limit for external humidity probe on port 5 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi5-high-trap 2
NetBotz External Humidity 5 High Trap. This trap indicates that the upper limit for external humidity probe on port 5 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi5-trap-clear 3
NetBotz External Humidity 5 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 5 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi5-sensor-unplugged 6
NetBotz External Humidity 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi5-sensor-replugged 7
NetBotz External Humidity 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi6-low-trap 1
NetBotz External Humidity 6 Low Trap. This trap indicates that the lower limit for external humidity probe on port 6 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi6-high-trap 2
NetBotz External Humidity 6 High Trap. This trap indicates that the upper limit for external humidity probe on port 6 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi6-trap-clear 3
NetBotz External Humidity 6 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 6 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi6-sensor-unplugged 6
NetBotz External Humidity 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi6-sensor-replugged 7
NetBotz External Humidity 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

netBotz-prd-bot-ext-humi7-low-trap 1
NetBotz External Humidity 7 Low Trap. This trap indicates that the lower limit for external humidity probe on port 7 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi7-high-trap 2
NetBotz External Humidity 7 High Trap. This trap indicates that the upper limit for external humidity probe on port 7 has been exceeded.
TRAP-TYPE    

netBotz-prd-bot-ext-humi7-trap-clear 3
NetBotz External Humidity 7 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 7 has returned to acceptable limits.
TRAP-TYPE    

netBotz-prd-bot-ext-humi7-sensor-unplugged 6
NetBotz External Humidity 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE    

netBotz-prd-bot-ext-humi7-sensor-replugged 7
NetBotz External Humidity 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE    

expPortTable 1.3.6.1.4.1.5528.31
A list of expansion port entries.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ExpPortEntry

expPortEntry 1.3.6.1.4.1.5528.31.1
An expansion port entry for a single port
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  ExpPortEntry  

expPort-module-id 1.3.6.1.4.1.5528.31.1.1
The module ID of the sensor module installed. Blank string indicates that no module is installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-module-type 1.3.6.1.4.1.5528.31.1.2
The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-label 1.3.6.1.4.1.5528.31.1.3
The label for the expansion port. Ports default to the label 'Extn', for port n.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-amps 1.3.6.1.4.1.5528.31.1.20
The reading of the amperage probe, in milliamps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

expPort-total-amp-seconds 1.3.6.1.4.1.5528.31.1.21
The accumulated total of amp-seconds on the AmpDetect.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

expPort-total-amp-seconds-since-time 1.3.6.1.4.1.5528.31.1.22
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-amps-enabled 1.3.6.1.4.1.5528.31.1.23
Amperage probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-amps-min 1.3.6.1.4.1.5528.31.1.24
The amperage probe minimum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-amps-max 1.3.6.1.4.1.5528.31.1.25
The amperage probe maximum, from 0 to 30000 milliamps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-amps-uV-per-10mA 1.3.6.1.4.1.5528.31.1.26
The scaling factor used for the amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-amps-max-range 1.3.6.1.4.1.5528.31.1.27
The maximum RMS milliamps measureable by the AmpDetect.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp 1.3.6.1.4.1.5528.31.1.40
The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-enabled 1.3.6.1.4.1.5528.31.1.41
External temperature probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-min 1.3.6.1.4.1.5528.31.1.42
The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-max 1.3.6.1.4.1.5528.31.1.43
The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-uV-per-degreeC 1.3.6.1.4.1.5528.31.1.44
The scaling factor used for the external temperature probe to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-uV-at-0-degreeC 1.3.6.1.4.1.5528.31.1.45
The offset used for the external temperature probe of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-min-range 1.3.6.1.4.1.5528.31.1.46
The minimum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-temp-max-range 1.3.6.1.4.1.5528.31.1.47
The maximum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry 1.3.6.1.4.1.5528.31.1.60
The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry-alarm-value 1.3.6.1.4.1.5528.31.1.61
The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry-enabled 1.3.6.1.4.1.5528.31.1.62
External dry contact sensor alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry-label 1.3.6.1.4.1.5528.31.1.63
The sensor name/label for the dry contact sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-ext-dry-open-label 1.3.6.1.4.1.5528.31.1.64
The sensor name/label for the open(0) state for the dry contact sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-ext-dry-closed-label 1.3.6.1.4.1.5528.31.1.65
The sensor name/label for the closed(0) state for the dry contact sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-ext-dry-open-to-close-millis 1.3.6.1.4.1.5528.31.1.66
The minimum number of milliseconds that the dry contact sensor must read closed before the state is changed from open to closed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry-close-to-open-millis 1.3.6.1.4.1.5528.31.1.67
The minimum number of milliseconds that the dry contact sensor must read openbefore the state is changed from closed to open.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-dry-response 1.3.6.1.4.1.5528.31.1.68
The type of alert response for the dry contact sensor: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

expPort-ext-humi 1.3.6.1.4.1.5528.31.1.80
The reading of the external humidity probe, in percent.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-enabled 1.3.6.1.4.1.5528.31.1.81
External humidity probe alarm enabled(1) or disabled(0).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-min 1.3.6.1.4.1.5528.31.1.82
The external humidity probe minimum, in percent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-max 1.3.6.1.4.1.5528.31.1.83
The external humidity probe maximum, in percent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-uV-per-percent 1.3.6.1.4.1.5528.31.1.84
The scaling factor used for the external humidity probe to convert microvolts measured from the humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-uV-at-0-percent 1.3.6.1.4.1.5528.31.1.85
The offset used for the external humidity probe of microvolts measured from the humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-min-range 1.3.6.1.4.1.5528.31.1.86
The minimum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

expPort-ext-humi-max-range 1.3.6.1.4.1.5528.31.1.87
The maximum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netbotz-crawlers 1.3.6.1.4.1.5528.30.20.5528
OBJECT IDENTIFIER    

netBotz-prd-crl-mib2 1.3.6.1.4.1.5528.30.20.5528.1
OBJECT IDENTIFIER    

netBotz-prd-crl-mib2if 1.3.6.1.4.1.5528.30.20.5528.2
OBJECT IDENTIFIER    

netBotz-prd-crl-mib2-ping 1.3.6.1.4.1.5528.30.20.5528.1.3
NetBotz device ping. This object indicates the status of a ping on a device monitored by a NetBotz device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-mib2-uptime 1.3.6.1.4.1.5528.30.20.5528.1.8
The uptime of a device monitored by a NetBotz device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  TimeTicks  

netBotz-prd-crl-mib2-snmpstatus 1.3.6.1.4.1.5528.30.20.5528.1.9
The SNMP status of a device monitored by a NetBotz device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-prd-crl-mib2if-opstatus 1.3.6.1.4.1.5528.30.20.5528.2.6
The operational status of a device monitored by a NetBotz device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-trap-index 1.3.6.1.4.1.5528.30.21.20
The ID of the crawler which sent the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-trap-address 1.3.6.1.4.1.5528.30.21.21
The IP address of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

netBotz-prd-crl-trap-oid 1.3.6.1.4.1.5528.30.21.22
The object id of the attribute on the target device which is the concern of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

netBotz-prd-crl-trap-botoid 1.3.6.1.4.1.5528.30.21.23
The object id of the attribute on the NetBotz device which is the concern of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

netBotz-prd-crl-trap-value 1.3.6.1.4.1.5528.30.21.24
The value of the attribute associated with the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-trap-date 1.3.6.1.4.1.5528.30.21.25
The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-trap-attrib 1.3.6.1.4.1.5528.30.21.26
The identification number of the attribute in error
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

netBotz-prd-crl-trap-desc 1.3.6.1.4.1.5528.30.21.27
Description or name of the attribute in error
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-prd-crl-ping-offline-trap 4
NetBotz Ping Trap. This trap indicates that replies to a set of pings were not received from a monitored IP address.
TRAP-TYPE    

netBotz-prd-crl-ping-online-trap 5
NetBotz Ping Trap. This trap indicates that replies to a set of pings were received from a monitored IP address after a period when no replies had been received.
TRAP-TYPE    

netBotz-prd-crl-snmp-offline-trap 4
NetBotz SNMP Offline Trap. This trap indicates that an SNMP request was not possible on an IP address.
TRAP-TYPE    

netBotz-prd-crl-snmp-online-trap 5
NetBotz SNMP Online Trap. This trap indicates that an SNMP request succeeded on an IP address where it had previously failed.
TRAP-TYPE    

netBotz-prd-crl-uptime-online-trap 5
NetBotz Uptime Trap. This trap indicates that a device restart has been detected due to the uptime of the device being reported as less than the previously reported reading.
TRAP-TYPE    

netBotz-prd-crl-opstatus-offline-trap 4
NetBotz Interface Offline Trap. This trap indicates that an interface on a device did not respond to an SNMP query on the ifAdminStatus or ifOperStatus objects.
TRAP-TYPE    

netBotz-prd-crl-opstatus-mismatch-trap 1
NetBotz Interface Status Mismatch Trap. This trap indicates that the operational status of a device interface does not match the administrative status.
TRAP-TYPE    

netBotz-prd-crl-opstatus-match-trap 2
NetBotz Interface Status Match Trap. This trap indicates that the operational status of a device interface now matches the administrative status. This trap indicates a transition from a state in which the administrative and operational status did not match.
TRAP-TYPE    

netBotz-snmp-traptarget 1.3.6.1.4.1.5528.40.1
Target of traps from the NetBotz device. This field contains the IP address where NetBotz traps are to be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-snmp-community 1.3.6.1.4.1.5528.40.2
The read/write community of the NetBotz device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-snmp-timeout 1.3.6.1.4.1.5528.40.3
SNMP Timeout period.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-snmp-retries 1.3.6.1.4.1.5528.40.4
SNMP Retry count.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

netBotz-userid-1 1.3.6.1.4.1.5528.40.5
The userID of the supervisor account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-password-1 1.3.6.1.4.1.5528.40.6
The password of the supervisor account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-userid-2 1.3.6.1.4.1.5528.40.7
The userID of the full read access account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-password-2 1.3.6.1.4.1.5528.40.8
The password of the full read access account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-userid-3 1.3.6.1.4.1.5528.40.9
The userID of the minimum read access account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-password-3 1.3.6.1.4.1.5528.40.10
The password of the minimum read access account (write-only).
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

netBotz-snmp-traptarget2 1.3.6.1.4.1.5528.40.11
Second target of traps from the NetBotz device. This field contains an additional IP address where NetBotz traps are to be sent.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netBotz-snmp-read-community 1.3.6.1.4.1.5528.40.12
The read-only community of the NetBotz device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

device-crawlers-trap-index 1.3.6.1.4.1.5528.61.2.20
The ID of the device crawler which sent the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

device-crawlers-trap-address 1.3.6.1.4.1.5528.61.2.21
The IP address of the appliance actually creating the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

device-crawlers-trap-oid 1.3.6.1.4.1.5528.61.2.22
The object id of the attribute on the device crawlers target device which is the concern of the last trap. The second to last element indicates the index of the source of the problem (1=ICMP Ping, 2=SNMP Agent Status, 256-10239=Network Interfaces 1-9984, 10240 and above, indicates Advanced crawlers data). The last element is the decimal representation of the IP address of the source of the problem.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

device-crawlers-trap-botoid 1.3.6.1.4.1.5528.61.2.23
The object id of the device crawlers attribute on the NetBotz device which is the concern of the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

device-crawlers-trap-value 1.3.6.1.4.1.5528.61.2.24
The integer value of the device crawlers attribute associated with the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

device-crawlers-trap-stringvalue 1.3.6.1.4.1.5528.61.2.25
The string representation of the value of the device crawlers attribute associated with the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

device-crawlers-trap-date 1.3.6.1.4.1.5528.61.2.26
The date and time of a specific device crawlers trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

device-crawlers-trap-attrib-index 1.3.6.1.4.1.5528.61.2.27
The identification number of the device crawlers attribute in error
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

device-crawlers-crawlers-trap-desc 1.3.6.1.4.1.5528.61.2.28
Description of the Device Crawlers Trap Attribute
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-device-crawlers-value-low-alert-trap 1
NetBotz Device Crawlers Value Low Trap. This trap indicates that the lower limit on a monitored value has been exceeded.
TRAP-TYPE    

netBotz-device-crawlers-value-high-alert-trap 2
NetBotz Device Crawlers Value High Trap. This trap indicates that the upper limit on a monitored value has been exceeded.
TRAP-TYPE    

netBotz-device-crawlers-clear-alert-trap 3
NetBotz Device Crawlers Clear Trap. This trap indicates that the previous alert condition has been cleared.
TRAP-TYPE    

netBotz-device-crawlers-offline-alert-trap 4
NetBotz Device Crawlers Offline Trap. This trap indicates that a monitored target could not be contacted.
TRAP-TYPE    

netBotz-device-crawlers-online-alert-trap 5
NetBotz Device Crawlers Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
TRAP-TYPE    

netBotz-device-crawlers-ifopstatus-alert-trap 8
NetBotz Device Crawlers Interface Operational Status Trap. This trap indicates that one or more of a monitored target's network interfaces operational status is not equal to the desired status.
TRAP-TYPE    

branch-checker-trap-index 1.3.6.1.4.1.5528.61.3.20
The ID of the branch checker which sent the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

branch-checker-trap-address 1.3.6.1.4.1.5528.61.3.21
The IP address of the appliance actually creating the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  IpAddress  

branch-checker-trap-oid 1.3.6.1.4.1.5528.61.3.22
The object id of the attribute on the branch checker target device which is the concern of the last trap The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

branch-checker-trap-botoid 1.3.6.1.4.1.5528.61.3.23
The object id of the branch checker attribute on the NetBotz device which is the concern of the last trap. The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

branch-checker-trap-value 1.3.6.1.4.1.5528.61.3.24
The integer value of the branch checker attribute associated with the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

branch-checker-trap-stringvalue 1.3.6.1.4.1.5528.61.3.25
The string representation of the value of the branch checker attribute associated with the last trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

branch-checker-trap-date 1.3.6.1.4.1.5528.61.3.26
The date and time of a specific branch checker trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

branch-checker-trap-attrib-index 1.3.6.1.4.1.5528.61.3.27
The identification number of the branch checker attribute in error
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

branch-checker-trap-desc 1.3.6.1.4.1.5528.61.3.28
Description of the Branch Checker Trap Attribute
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

netBotz-branch-checker-clear-alert-trap 3
NetBotz Branch Checker Clear Trap. This trap indicates that the previous alert condition has been cleared.
TRAP-TYPE    

netBotz-branch-checker-offline-alert-trap 4
NetBotz Branch Checker Offline Trap. This trap indicates that a monitored target could not be contacted.
TRAP-TYPE    

netBotz-branch-checker-online-alert-trap 5
NetBotz Branch Checker Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
TRAP-TYPE    

netBotz-branch-checker-target-error-trap 12
NetBotz Branch Target Error Trap. This trap indicates that a monitored target could be contacted, but not withing the timeout period specified.
TRAP-TYPE