LIEBERT-UPSTATION-S3-UPS-MIB

File: LIEBERT-UPSTATION-S3-UPS-MIB.mib (39007 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

enterprises Counter TimeTicks
Gauge OBJECT-TYPE sysUpTime
DisplayString TRAP-TYPE

Defined Types

LcUpsInputEntry  
SEQUENCE    
  lcUpsInputLine INTEGER
  lcUpsInputVoltage INTEGER
  lcUpsInputCurrent INTEGER
  lcUpsInputVA INTEGER

LcUpsOutputEntry  
SEQUENCE    
  lcUpsOutputLine INTEGER
  lcUpsOutputVoltage INTEGER
  lcUpsOutputCurrent INTEGER
  lcUpsOutputVA INTEGER

LcUpsAlarmEntry  
SEQUENCE    
  lcUpsAlarmId INTEGER
  lcUpsAlarmDescr OBJECT IDENTIFIER
  lcUpsAlarmTime TimeTicks

LcUpsSwitchedReceptEntry  
SEQUENCE    
  lcUpsSwitchedReceptIndex INTEGER
  lcUpsSwitchedReceptOnDelay INTEGER
  lcUpsSwitchedReceptOnTrapDelay INTEGER
  lcUpsSwitchedReceptOffDelay INTEGER
  lcUpsSwitchedReceptOffTrapDelay INTEGER
  lcUpsSwitchedReceptStatus INTEGER
  lcUpsSwitchedReceptLabel DisplayString

LsUpsBypassEntry  
SEQUENCE    
  lsUpsBypassLine INTEGER
  lsUpsBypassVoltage INTEGER
  lsUpsBypassCurrent INTEGER

Defined Values

emerson 1.3.6.1.4.1.476
OBJECT IDENTIFIER    

liebertCorp 1.3.6.1.4.1.476.1
OBJECT IDENTIFIER    

liebertUps 1.3.6.1.4.1.476.1.1
OBJECT IDENTIFIER    

luExtensions 1.3.6.1.4.1.476.1.1.1
OBJECT IDENTIFIER    

luExperimental 1.3.6.1.4.1.476.1.1.2
OBJECT IDENTIFIER    

luPrivate 1.3.6.1.4.1.476.1.1.3
OBJECT IDENTIFIER    

luCore 1.3.6.1.4.1.476.1.1.1.1
OBJECT IDENTIFIER    

lcUpsIdent 1.3.6.1.4.1.476.1.1.1.1.1
OBJECT IDENTIFIER    

lcUpsIdentManufacturer 1.3.6.1.4.1.476.1.1.1.1.1.1
The UPS manufacturer.
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentModel 1.3.6.1.4.1.476.1.1.1.1.1.2
The UPS Model designation.
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentSoftwareVersion 1.3.6.1.4.1.476.1.1.1.1.1.3
The UPS SNMP Agent software version.
OBJECT-TYPE    
  DisplayString Size(255)  

lcUpsIdentSpecific 1.3.6.1.4.1.476.1.1.1.1.1.4
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lcUpsBattery 1.3.6.1.4.1.476.1.1.1.1.2
OBJECT IDENTIFIER    

lcUpsBatTimeRemaining 1.3.6.1.4.1.476.1.1.1.1.2.1
The estimated time to depletion of battery charge. (Unit of measure: Minute)
OBJECT-TYPE    
  INTEGER 0..65535  

lcUpsBatTemperature 1.3.6.1.4.1.476.1.1.1.1.2.2
The battery temperature. (Unit of measure: Degree, Centigrade)
OBJECT-TYPE    
  INTEGER -32768..32767  

lcUpsBatVoltage 1.3.6.1.4.1.476.1.1.1.1.2.3
The current battery voltage. (Unit of measure: volt)
OBJECT-TYPE    
  INTEGER -32768..32767  

lcUpsBatCurrent 1.3.6.1.4.1.476.1.1.1.1.2.4
The current battery discharging/charging current. (Unit of measure: Amp)
OBJECT-TYPE    
  INTEGER -32768..32767  

lcUpsInput 1.3.6.1.4.1.476.1.1.1.1.3
OBJECT IDENTIFIER    

lcUpsInputFrequency 1.3.6.1.4.1.476.1.1.1.1.3.1
The current input frequency. (Unit of measure: Hertz)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsInputBrownOuts 1.3.6.1.4.1.476.1.1.1.1.3.2
The number of brown-out conditions the UPS has experienced.
OBJECT-TYPE    
  Counter  

lcUpsInputBlackOuts 1.3.6.1.4.1.476.1.1.1.1.3.3
The number of black-out conditions the UPS has experienced.
OBJECT-TYPE    
  Counter  

lcUpsInputTransients 1.3.6.1.4.1.476.1.1.1.1.3.4
The number of transient (surge and spike) conditions the UPS has experienced.
OBJECT-TYPE    
  Counter  

lcUpsInputNumLines 1.3.6.1.4.1.476.1.1.1.1.3.5
The number of input lines utilized in this device. This entry indicates the number of rows in the input table.
OBJECT-TYPE    
  INTEGER 1..3  

lcUpsInputTable 1.3.6.1.4.1.476.1.1.1.1.3.6
OBJECT-TYPE    
  SEQUENCE OF  
    LcUpsInputEntry

lcUpsInputEntry 1.3.6.1.4.1.476.1.1.1.1.3.6.1
OBJECT-TYPE    
  LcUpsInputEntry  

lcUpsInputLine 1.3.6.1.4.1.476.1.1.1.1.3.6.1.1
The input Line.
OBJECT-TYPE    
  INTEGER 1..3  

lcUpsInputVoltage 1.3.6.1.4.1.476.1.1.1.1.3.6.1.2
The input voltage. (Unit of measure: Volt)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsInputCurrent 1.3.6.1.4.1.476.1.1.1.1.3.6.1.3
The input current. (Unit of measure: Amp)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsInputVA 1.3.6.1.4.1.476.1.1.1.1.3.6.1.4
The input volt-amps.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsOutput 1.3.6.1.4.1.476.1.1.1.1.4
OBJECT IDENTIFIER    

lcUpsOutputFrequency 1.3.6.1.4.1.476.1.1.1.1.4.1
The current output frequency. (Unit of measure: Hertz)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsOutputLoad 1.3.6.1.4.1.476.1.1.1.1.4.2
The current output load percentage.
OBJECT-TYPE    
  INTEGER 0..100  

lcUpsOutputNumLines 1.3.6.1.4.1.476.1.1.1.1.4.3
The number of output lines utilized in this device. This entry indicates the number of rows in the output table.
OBJECT-TYPE    
  INTEGER 1..3  

lcUpsOutputTable 1.3.6.1.4.1.476.1.1.1.1.4.4
OBJECT-TYPE    
  SEQUENCE OF  
    LcUpsOutputEntry

lcUpsOutputEntry 1.3.6.1.4.1.476.1.1.1.1.4.4.1
OBJECT-TYPE    
  LcUpsOutputEntry  

lcUpsOutputLine 1.3.6.1.4.1.476.1.1.1.1.4.4.1.1
The output Line.
OBJECT-TYPE    
  INTEGER 1..3  

lcUpsOutputVoltage 1.3.6.1.4.1.476.1.1.1.1.4.4.1.2
The output voltage. (Unit of measure: Volt)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsOutputCurrent 1.3.6.1.4.1.476.1.1.1.1.4.4.1.3
The output current. (Unit of measure: Amp)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsOutputVA 1.3.6.1.4.1.476.1.1.1.1.4.4.1.4
The output volt-amps.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsInverter 1.3.6.1.4.1.476.1.1.1.1.5
OBJECT IDENTIFIER    

lcUpsInverterStatus 1.3.6.1.4.1.476.1.1.1.1.5.1
The state of the inverter. Unknown is returned if the state can not be determined.
OBJECT-TYPE    
  INTEGER unknown(1), on(2), off(3)  

lcUpsInverterTemp 1.3.6.1.4.1.476.1.1.1.1.5.2
The temperature of the inverter. (Unit of measure: degree, Centigrade)
OBJECT-TYPE    
  INTEGER -32768..32767  

lcUpsAlarm 1.3.6.1.4.1.476.1.1.1.1.6
OBJECT IDENTIFIER    

lcUpsAlarms 1.3.6.1.4.1.476.1.1.1.1.6.1
The current number of alarm conditions.
OBJECT-TYPE    
  Gauge  

lcUpsAlarmTable 1.3.6.1.4.1.476.1.1.1.1.6.2
OBJECT-TYPE    
  SEQUENCE OF  
    LcUpsAlarmEntry

lcUpsAlarmEntry 1.3.6.1.4.1.476.1.1.1.1.6.2.1
OBJECT-TYPE    
  LcUpsAlarmEntry  

lcUpsAlarmId 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsAlarmDescr 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lcUpsAlarmTime 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3
The value of sysUpTime when the alarm condition occured.
OBJECT-TYPE    
  TimeTicks  

lcUpsAlarmConditions 1.3.6.1.4.1.476.1.1.1.1.6.3
OBJECT IDENTIFIER    

lcUpsAlarmLowBatteryWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.1
OBJECT IDENTIFIER    

lcUpsAlarmLowBatteryShutdown 1.3.6.1.4.1.476.1.1.1.1.6.3.2
OBJECT IDENTIFIER    

lcUpsAlarmUtilFailed 1.3.6.1.4.1.476.1.1.1.1.6.3.3
OBJECT IDENTIFIER    

lcUpsAlarmOverTempWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.4
OBJECT IDENTIFIER    

lcUpsAlarmOutputOverloadWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.6
OBJECT IDENTIFIER    

lcUpsAlarmInputOverVoltage 1.3.6.1.4.1.476.1.1.1.1.6.3.8
OBJECT IDENTIFIER    

lcUpsAlarmBatteryBad 1.3.6.1.4.1.476.1.1.1.1.6.3.9
OBJECT IDENTIFIER    

lcUpsAlarmOnBattery 1.3.6.1.4.1.476.1.1.1.1.6.3.10
OBJECT IDENTIFIER    

lcUpsAlarmUpsOff 1.3.6.1.4.1.476.1.1.1.1.6.3.12
OBJECT IDENTIFIER    

lcUpsTest 1.3.6.1.4.1.476.1.1.1.1.7
OBJECT IDENTIFIER    

lcUpsTestBattery 1.3.6.1.4.1.476.1.1.1.1.7.1
Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state.
OBJECT-TYPE    
  INTEGER unknown(1), start(2), abort(3)  

lcUpsTestBatteryStatus 1.3.6.1.4.1.476.1.1.1.1.7.2
The status of the battery test.
OBJECT-TYPE    
  INTEGER unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7)  

lcUpsTestDiag 1.3.6.1.4.1.476.1.1.1.1.7.3
Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'.
OBJECT-TYPE    
  INTEGER unknown(1), start(2), abort(3)  

lcUpsTestDiagStatus 1.3.6.1.4.1.476.1.1.1.1.7.4
The status of the diagnostics test.
OBJECT-TYPE    
  INTEGER unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7)  

lcUpsControl 1.3.6.1.4.1.476.1.1.1.1.8
OBJECT IDENTIFIER    

lcUpsControlOutputOffDelay 1.3.6.1.4.1.476.1.1.1.1.8.1
Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlOutputOnDelay 1.3.6.1.4.1.476.1.1.1.1.8.2
Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlOutputOffTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.3
When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlOutputOnTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.4
When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlUnixShutdownDelay 1.3.6.1.4.1.476.1.1.1.1.8.5
Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlUnixShutdownTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.6
When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsControlCancelCommands 1.3.6.1.4.1.476.1.1.1.1.8.7
Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.
OBJECT-TYPE    
  INTEGER unknown(1), cancel(2)  

lcUpsControlRebootAgentDelay 1.3.6.1.4.1.476.1.1.1.1.8.8
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsNominal 1.3.6.1.4.1.476.1.1.1.1.9
OBJECT IDENTIFIER    

lcUpsNominalOutputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.1
The nominal output voltage. (Unit of measure: volt)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalInputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.2
The nominal input voltage. (Unit of measure: volt)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputVA 1.3.6.1.4.1.476.1.1.1.1.9.3
The nominal Volt-Amp rating.
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputWatts 1.3.6.1.4.1.476.1.1.1.1.9.4
The nominal power rating. (Unit of measure: watt)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalOutputFreq 1.3.6.1.4.1.476.1.1.1.1.9.5
The nominal output frequency. (Unit of measure: Hertz)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsNominalInputFreq 1.3.6.1.4.1.476.1.1.1.1.9.6
The nominal input frequency. (Unit of measure: Hertz)
OBJECT-TYPE    
  INTEGER 0..65536  

lcUpsSwitchedReceptacles 1.3.6.1.4.1.476.1.1.1.1.12
OBJECT IDENTIFIER    

lcUpsSwitchedReceptMaxNum 1.3.6.1.4.1.476.1.1.1.1.12.1
The maximum number of switched receptacles supported by the Ups.
OBJECT-TYPE    
  INTEGER 0..255  

lcUpsSwitchedReceptTable 1.3.6.1.4.1.476.1.1.1.1.12.2
OBJECT-TYPE    
  SEQUENCE OF  
    LcUpsSwitchedReceptEntry

lcUpsSwitchedReceptEntry 1.3.6.1.4.1.476.1.1.1.1.12.2.1
OBJECT-TYPE    
  LcUpsSwitchedReceptEntry  

lcUpsSwitchedReceptIndex 1.3.6.1.4.1.476.1.1.1.1.12.2.1.1
OBJECT-TYPE    
  INTEGER  

lcUpsSwitchedReceptOnDelay 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2
Setting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsSwitchedReceptOnTrapDelay 1.3.6.1.4.1.476.1.1.1.1.12.2.1.3
When 'lcUpsSwitchedReceptOnDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOnWarningTrap will be produced and this object will be reset to 0.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsSwitchedReceptOffDelay 1.3.6.1.4.1.476.1.1.1.1.12.2.1.4
Setting this object causes the agent to instruct the UPS to turn off a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsSwitchedReceptOffTrapDelay 1.3.6.1.4.1.476.1.1.1.1.12.2.1.5
When 'lcUpsSwitchedReceptOffDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOffWarningTrap will be produced and this object will be reset to 0.
OBJECT-TYPE    
  INTEGER 0..2147483647  

lcUpsSwitchedReceptStatus 1.3.6.1.4.1.476.1.1.1.1.12.2.1.6
The status of the device receptacle. Note that some devices may support Switched of device receptacles as a group only (by using lcUpsSwitchedOutputOffDelay and lcUpsSwitchedOutputOnDelay).
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lcUpsSwitchedReceptLabel 1.3.6.1.4.1.476.1.1.1.1.12.2.1.7
A user-defined text string associated with a switched receptacle. This may be used to describe the load powered from the receptacle. The text string is stored in non-volatile memory.
OBJECT-TYPE    
  DisplayString Size(32)  

lcUpsTraps 1.3.6.1.4.1.476.1.1.1.1.11
OBJECT IDENTIFIER    

luUPStationS 1.3.6.1.4.1.476.1.1.1.2
OBJECT IDENTIFIER    

lsUpsIdent 1.3.6.1.4.1.476.1.1.1.2.1
OBJECT IDENTIFIER    

lsUpsIdentFirmwareVersion 1.3.6.1.4.1.476.1.1.1.2.1.1
The firmware revision level of the UPS.
OBJECT-TYPE    
  DisplayString Size(255)  

lsUpsAlarm 1.3.6.1.4.1.476.1.1.1.2.6
OBJECT IDENTIFIER    

lsUpsAlarmConditions 1.3.6.1.4.1.476.1.1.1.2.6.1
OBJECT IDENTIFIER    

lsUpsAlarmCheckAirFilter 1.3.6.1.4.1.476.1.1.1.2.6.1.1
OBJECT IDENTIFIER    

lsUpsTraps 1.3.6.1.4.1.476.1.1.1.2.11
OBJECT IDENTIFIER    

lsUpsConfig 1.3.6.1.4.1.476.1.1.1.2.12
OBJECT IDENTIFIER    

lsUpsConfigBypassInstalled 1.3.6.1.4.1.476.1.1.1.2.12.1
Indicates if a bypass is installed in the UPS.
OBJECT-TYPE    
  INTEGER unknown(1), yes(2), no(3)  

lsUpsBypass 1.3.6.1.4.1.476.1.1.1.2.13
OBJECT IDENTIFIER    

lsUpsOnBypass 1.3.6.1.4.1.476.1.1.1.2.13.1
Indicates that the UPS is currently on bypass.
OBJECT-TYPE    
  INTEGER unknown(1), yes(2), no(3)  

lsUpsBypassFrequency 1.3.6.1.4.1.476.1.1.1.2.13.2
The current bypass frequency. (Unit of measure: Hertz)
OBJECT-TYPE    
  INTEGER 0..65536  

lsUpsBypassNumLines 1.3.6.1.4.1.476.1.1.1.2.13.3
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
OBJECT-TYPE    
  INTEGER 1..3  

lsUpsBypassTable 1.3.6.1.4.1.476.1.1.1.2.13.4
OBJECT-TYPE    
  SEQUENCE OF  
    LsUpsBypassEntry

lsUpsBypassEntry 1.3.6.1.4.1.476.1.1.1.2.13.4.1
OBJECT-TYPE    
  LsUpsBypassEntry  

lsUpsBypassLine 1.3.6.1.4.1.476.1.1.1.2.13.4.1.1
The bypass Line.
OBJECT-TYPE    
  INTEGER 1..3  

lsUpsBypassVoltage 1.3.6.1.4.1.476.1.1.1.2.13.4.1.2
The bypass voltage. (Unit of measure: Volt)
OBJECT-TYPE    
  INTEGER 0..65536  

lsUpsBypassCurrent 1.3.6.1.4.1.476.1.1.1.2.13.4.1.3
The bypass current. (Unit of measure: Amp)
OBJECT-TYPE    
  INTEGER 0..65536  

luUPStationS3 1.3.6.1.4.1.476.1.1.1.7
OBJECT IDENTIFIER