InterSeptor-MIB

File: InterSeptor-MIB.mib (52936 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

enterprises IpAddress OBJECT-TYPE
DisplayString TRAP-TYPE

Defined Types

InSeptConfigTrapsReceiversEntry  
SEQUENCE    
  inSepttrapsIndex INTEGER
  inSepttrapsReceiverAddr IpAddress
  inSeptreceiverCommunityString DisplayString
  inSeptreceiverSeverityLevel INTEGER
  inSeptreceiverDescription DisplayString

InSeptConfigAccessControlEntry  
SEQUENCE    
  accessIndex INTEGER
  accessControlAddr IpAddress
  accessCommunityString DisplayString
  accessControlMode INTEGER

SensorMonitorSensorEntry  
SEQUENCE    
  inSeptsensorMonitorDeviceIndex INTEGER
  inSeptsensorMonitorDeviceStatus INTEGER
  inSeptsensorMonitorDeviceTemperature INTEGER
  inSeptsensorMonitorDeviceTemperatureAlarm INTEGER
  inSeptsensorMonitorDeviceHumidity INTEGER
  inSeptsensorMonitorDeviceHumidityAlarm INTEGER
  inSeptsensorMonitorAlarm1 INTEGER
  inSeptsensorMonitorAlarm2 INTEGER

InSeptsensorConfigSensorEntry  
SEQUENCE    
  inSeptsensorConfigDeviceIndex INTEGER
  inSeptsensorConfigDeviceName DisplayString
  inSeptsensorConfigDeviceState INTEGER

Defined Values

jacarta 1.3.6.1.4.1.19011
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.19011.1
OBJECT IDENTIFIER    

webAppliance 1.3.6.1.4.1.19011.1.3
OBJECT IDENTIFIER    

inSept 1.3.6.1.4.1.19011.1.3.1
OBJECT IDENTIFIER    

inSeptObjects 1.3.6.1.4.1.19011.1.3.1.1
OBJECT IDENTIFIER    

inSeptTraps 1.3.6.1.4.1.19011.1.3.1.2
OBJECT IDENTIFIER    

inSeptIdent 1.3.6.1.4.1.19011.1.3.1.1.1
OBJECT IDENTIFIER    

inSeptConfig 1.3.6.1.4.1.19011.1.3.1.1.2
OBJECT IDENTIFIER    

inSeptsensorMonitor 1.3.6.1.4.1.19011.1.3.1.1.3
OBJECT IDENTIFIER    

inSeptsensorConfig 1.3.6.1.4.1.19011.1.3.1.1.4
OBJECT IDENTIFIER    

inSeptIdentManufacturer 1.3.6.1.4.1.19011.1.3.1.1.1.1
The name of the interSeptor manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

inSeptIdentModel 1.3.6.1.4.1.19011.1.3.1.1.1.2
The interSeptor Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

inSeptIdentAgentSoftwareVersion 1.3.6.1.4.1.19011.1.3.1.1.1.3
The interSeptor software/firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

inSeptIdentName 1.3.6.1.4.1.19011.1.3.1.1.1.4
A string identifying the interSeptor. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

inSeptConfigMibVersion 1.3.6.1.4.1.19011.1.3.1.1.2.1
The version of MIB spec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

inSeptConfigNetwork 1.3.6.1.4.1.19011.1.3.1.1.2.2
OBJECT IDENTIFIER    

inSeptConfigIpAddress 1.3.6.1.4.1.19011.1.3.1.1.2.2.1
The ip address that NMS can identify the managed device
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

inSeptConfigGateway 1.3.6.1.4.1.19011.1.3.1.1.2.2.2
The default gateway that allows the device to be managed through routers
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

inSeptConfigSubnetMask 1.3.6.1.4.1.19011.1.3.1.1.2.2.3
Internet address subnet mask
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

inSeptConfigDateTime 1.3.6.1.4.1.19011.1.3.1.1.2.3
OBJECT IDENTIFIER    

inSeptConfigDate 1.3.6.1.4.1.19011.1.3.1.1.2.3.1
The date in inSept, format is (dd/mm/yyyy)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

inSeptConfigTime 1.3.6.1.4.1.19011.1.3.1.1.2.3.2
The time in interSeptor, format is (hh:mm:ss)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

inSeptConfigTimeFromNtp 1.3.6.1.4.1.19011.1.3.1.1.2.3.3
Enable/disable update date/time from NTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigNtpIpAddress 1.3.6.1.4.1.19011.1.3.1.1.2.3.4
NTP IP address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

inSeptConfigNtpTimeZone 1.3.6.1.4.1.19011.1.3.1.1.2.3.5
Enable/disable update date/time from NTP server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER gMT-1200(1), gMT-1100(2), gMT-1000(3), gMT-0900(4), gMT-0800(5), gMT-0700(6), gMT-0600(7), gMT-0500(8), gMT-0400(9), gMT-0330(10), gMT-0300(11), gMT-0200(12), gMT-0100(13), gMT-0000(14), gMT0100(15), gMT0200(16), gMT0300(17), gMT0330(18), gMT0400(19), gMT0500(20), gMT0530(21), gMT0600(22), gMT0700(23), gMT0800(24), gMT0900(25), gMT1000(26), gMT1100(27), gMT1200(28)  

inSeptConfigDayLightSaving 1.3.6.1.4.1.19011.1.3.1.1.2.3.6
Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set set one hour in advance to reflect daylight saving status.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigLog 1.3.6.1.4.1.19011.1.3.1.1.2.4
OBJECT IDENTIFIER    

inSeptConfigHistoryLogFrequency 1.3.6.1.4.1.19011.1.3.1.1.2.4.1
The frequency of the update of the history log. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 5..3600  

inSeptConfigExtHistoryLogFrequency 1.3.6.1.4.1.19011.1.3.1.1.2.4.2
The frequency of the update of the extended history log. The value is in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..1440  

inSeptConfigConfigurationLog 1.3.6.1.4.1.19011.1.3.1.1.2.4.3
Enable/disable inSept to log parameter change.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigDhcpStatue 1.3.6.1.4.1.19011.1.3.1.1.2.5
Enable or disable DHCP/BootP capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigPingStatue 1.3.6.1.4.1.19011.1.3.1.1.2.6
Enable or disable Ping Echo capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigTftpStatue 1.3.6.1.4.1.19011.1.3.1.1.2.7
Enable or disable TFTP network upgrade capability
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigTelnet 1.3.6.1.4.1.19011.1.3.1.1.2.8
OBJECT IDENTIFIER    

inSeptConfigTelnetStatue 1.3.6.1.4.1.19011.1.3.1.1.2.8.1
Enable or disable telnet access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigTelnetPortNumber 1.3.6.1.4.1.19011.1.3.1.1.2.8.2
Setting the server port of telnet.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

inSeptConfigHttp 1.3.6.1.4.1.19011.1.3.1.1.2.9
OBJECT IDENTIFIER    

inSeptConfigHttpStatue 1.3.6.1.4.1.19011.1.3.1.1.2.9.1
Enable or disable HTTP access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigHttpPortNumber 1.3.6.1.4.1.19011.1.3.1.1.2.9.2
Setting the server port of HTTP.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

inSeptConfigHttpSecurity 1.3.6.1.4.1.19011.1.3.1.1.2.9.3
Enable/disable HTTP access for read-only users
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigSnmp 1.3.6.1.4.1.19011.1.3.1.1.2.10
OBJECT IDENTIFIER    

inSeptConfigSnmpStatue 1.3.6.1.4.1.19011.1.3.1.1.2.10.1
Enable or disable SNMP access
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptConfigSnmpPortNumber 1.3.6.1.4.1.19011.1.3.1.1.2.10.2
Setting the server port of SNMP.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..65535  

inSeptConfigControl 1.3.6.1.4.1.19011.1.3.1.1.2.11
OBJECT IDENTIFIER    

inSeptConfigResetToDefault 1.3.6.1.4.1.19011.1.3.1.1.2.11.1
Reset all parameters of interSeptor to default value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER reset(1), nothing(2)  

inSeptConfigRestart 1.3.6.1.4.1.19011.1.3.1.1.2.11.2
Restart interSeptor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER restart(1), nothing(2)  

inSeptConfigTrap 1.3.6.1.4.1.19011.1.3.1.1.2.12
OBJECT IDENTIFIER    

inSeptConfigTrapRetryCount 1.3.6.1.4.1.19011.1.3.1.1.2.12.1
The count of repeat traps to send to NMS before trap acknowledgement is received.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptConfigTrapRetryTime 1.3.6.1.4.1.19011.1.3.1.1.2.12.2
The time between retrying to send traps to NMS.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptConfigTrapAckSignature 1.3.6.1.4.1.19011.1.3.1.1.2.12.3
The signature of trap acknowledgement.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptConfigPollRate 1.3.6.1.4.1.19011.1.3.1.1.2.13
The frequency that interSeptor updates readings from sensors (unit : second).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 3..60  

inSeptConfigTrapsReceiversTable 1.3.6.1.4.1.19011.1.3.1.1.2.14
A list of managers to send traps to. The number of entries is given by the value of inSeptConfigNumTrapReceivers
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InSeptConfigTrapsReceiversEntry

inSeptConfigTrapsReceiversEntry 1.3.6.1.4.1.19011.1.3.1.1.2.14.1
The managers to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  InSeptConfigTrapsReceiversEntry  

inSepttrapsIndex 1.3.6.1.4.1.19011.1.3.1.1.2.14.1.1
The index to a trap receiver entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

inSepttrapsReceiverAddr 1.3.6.1.4.1.19011.1.3.1.1.2.14.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

inSeptreceiverCommunityString 1.3.6.1.4.1.19011.1.3.1.1.2.14.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

inSeptreceiverSeverityLevel 1.3.6.1.4.1.19011.1.3.1.1.2.14.1.4
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), severe(3)  

inSeptreceiverDescription 1.3.6.1.4.1.19011.1.3.1.1.2.14.1.5
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

inSeptConfigAccessControlTable 1.3.6.1.4.1.19011.1.3.1.1.2.15
A list of managers which can access interSeptor with private community string.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InSeptConfigAccessControlEntry

inSeptConfigAccessControlEntry 1.3.6.1.4.1.19011.1.3.1.1.2.15.1
The managers.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  InSeptConfigAccessControlEntry  

accessIndex 1.3.6.1.4.1.19011.1.3.1.1.2.15.1.1
The index to a access control entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

accessControlAddr 1.3.6.1.4.1.19011.1.3.1.1.2.15.1.2
The IP address of the manager to access interSeptor
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

accessCommunityString 1.3.6.1.4.1.19011.1.3.1.1.2.15.1.3
The community name to use in the manager when access interSeptor
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

accessControlMode 1.3.6.1.4.1.19011.1.3.1.1.2.15.1.4
Access type, only read/Write access type can change parameter of interSeptor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER readOnly(1), read-write(2), notAccess(3)  

inSeptConfigTemperatureUnit 1.3.6.1.4.1.19011.1.3.1.1.2.16
The temperature unit of the system, can be Celsius or Farenheit
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

inSeptConfigDateFormat 1.3.6.1.4.1.19011.1.3.1.1.2.17
The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER dd-mm-yyyy(1), mm-dd-yyyy(2)  

inSeptsensorMonitorSensorNumber 1.3.6.1.4.1.19011.1.3.1.1.3.1
The number of sensors that can be monitored.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

inSeptsensorMonitorSensorTable 1.3.6.1.4.1.19011.1.3.1.1.3.2
A list of sensor devices to be monitored.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SensorMonitorSensorEntry

inSeptsensorMonitorSensorEntry 1.3.6.1.4.1.19011.1.3.1.1.3.2.1
The sensor device.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SensorMonitorSensorEntry  

inSeptsensorMonitorDeviceIndex 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.1
The index to a sensor device entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

inSeptsensorMonitorDeviceStatus 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.2
The device type connected to interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), eMD-HT(3), eMD-T(4)  

inSeptsensorMonitorDeviceTemperature 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.3
The temperature of sensor on device interSeptor, the unit is 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

inSeptsensorMonitorDeviceTemperatureAlarm 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.4
The alarm type of sensor on device interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)  

inSeptsensorMonitorDeviceHumidity 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.5
The humidity of sensor on device interSeptor, the unit is 0.1%.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

inSeptsensorMonitorDeviceHumidityAlarm 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.6
The alarm type of sensor on device interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)  

inSeptsensorMonitorAlarm1 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.7
The device status of sensor 1 connected to interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), active(3), inactive(4)  

inSeptsensorMonitorAlarm2 1.3.6.1.4.1.19011.1.3.1.1.3.2.1.8
The device status of sensor 2 connected to interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), disabled(2), active(3), inactive(4)  

inSeptsensorConfigSensorNumber 1.3.6.1.4.1.19011.1.3.1.1.4.1
The number of sensors that are connected to interSeptor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensorTable 1.3.6.1.4.1.19011.1.3.1.1.4.2
A list of sensor devices to be configured.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    InSeptsensorConfigSensorEntry

inSeptsensorConfigSensorEntry 1.3.6.1.4.1.19011.1.3.1.1.4.2.1
The sensor device.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  InSeptsensorConfigSensorEntry  

inSeptsensorConfigDeviceIndex 1.3.6.1.4.1.19011.1.3.1.1.4.2.1.1
The index to a sensor device entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..2147483647  

inSeptsensorConfigDeviceName 1.3.6.1.4.1.19011.1.3.1.1.4.2.1.2
The name of the sensor device for identification.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigDeviceState 1.3.6.1.4.1.19011.1.3.1.1.4.2.1.3
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

inSeptsensorConfigSensor1 1.3.6.1.4.1.19011.1.3.1.1.4.3
OBJECT IDENTIFIER    

inSeptsensorConfigSensor1DeviceName 1.3.6.1.4.1.19011.1.3.1.1.4.3.1
The name of sensor device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor1DeviceState 1.3.6.1.4.1.19011.1.3.1.1.4.3.2
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

inSeptsensorConfigSensor1Temperature 1.3.6.1.4.1.19011.1.3.1.1.4.3.3
OBJECT IDENTIFIER    

inSeptsensorConfigSensor1TemperatureName 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.1
The temperature sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor1TemperatureLowWarning 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1TemperatureLowCritical 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1TemperatureHighWarning 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1TemperatureHighCritical 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1TemperatureHysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.6
The set value to prevent too many alarms when temperature is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1TemperatureCalibration 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)  

inSeptsensorConfigSensor1TemperatureLowWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.8
Enable/disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1TemperatureLowCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.9
Enable/disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1TemperatureHighWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.10
Enable/disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1TemperatureHighCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.3.11
Enable/disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1Humidity 1.3.6.1.4.1.19011.1.3.1.1.4.3.4
OBJECT IDENTIFIER    

inSeptsensorConfigSensor1HumdityName 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.1
The humidity sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor1HumidityLowWarning 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1HumidityLowCritical 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.3
The threshole to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1HumidityHighWarning 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1HumidityHighCritical 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1HumidityHysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.6
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1HumidityCalibration 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)  

inSeptsensorConfigSensor1HumidityLowWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.8
Enable/disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1HumidityLowCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.9
Enable/disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1HumidityHighWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.10
Enable/disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1HumidityHighCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.3.4.11
Enable/disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor1Alarm1 1.3.6.1.4.1.19011.1.3.1.1.4.3.5
OBJECT IDENTIFIER    

inSeptsensorConfigSensor1Alarm1Name 1.3.6.1.4.1.19011.1.3.1.1.4.3.5.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor1Alarm1State 1.3.6.1.4.1.19011.1.3.1.1.4.3.5.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

inSeptsensorConfigSensor1Alarm1Hysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.3.5.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor1Alarm2 1.3.6.1.4.1.19011.1.3.1.1.4.3.6
OBJECT IDENTIFIER    

inSeptsensorConfigSensor1Alarm2Name 1.3.6.1.4.1.19011.1.3.1.1.4.3.6.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor1Alarm2State 1.3.6.1.4.1.19011.1.3.1.1.4.3.6.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

inSeptsensorConfigSensor1Alarm2Hysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.3.6.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2 1.3.6.1.4.1.19011.1.3.1.1.4.4
OBJECT IDENTIFIER    

inSeptsensorConfigSensor2DeviceName 1.3.6.1.4.1.19011.1.3.1.1.4.4.1
The name of sensor device.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor2DeviceState 1.3.6.1.4.1.19011.1.3.1.1.4.4.2
The setup of sensor device type.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), auto(2)  

inSeptsensorConfigSensor2Temperature 1.3.6.1.4.1.19011.1.3.1.1.4.4.3
OBJECT IDENTIFIER    

inSeptsensorConfigSensor2TemperatureName 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.1
The temperature sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor2TemperatureLowWarning 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2TemperatureLowCritical 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2TemperatureHighWarning 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2TemperatureHighCritical 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2TemperatureHysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.6
The set value to prevent too many alarms when temperature is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2TemperatureCalibration 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)  

inSeptsensorConfigSensor2TemperatureLowWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.8
Enable/disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2TemperatureLowCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.9
Enable/disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2TemperatureHighWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.10
Enable/disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2TemperatureHighCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.3.11
Enable/disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2Humidity 1.3.6.1.4.1.19011.1.3.1.1.4.4.4
OBJECT IDENTIFIER    

inSeptsensorConfigSensor2HumdityName 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.1
The humidity sensor name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor2HumidityLowWarning 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.2
The set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2HumidityLowCritical 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.3
The threshold to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2HumidityHighWarning 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.4
The threshold to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2HumidityHighCritical 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.5
The threshold to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2HumidityHysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.6
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2HumidityCalibration 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.7
The set value to get the correct temperature according to your reference temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)  

inSeptsensorConfigSensor2HumidityLowWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.8
Enable/disable the set point to trigger low warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2HumidityLowCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.9
Enable/disable the set point to trigger low critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2HumidityHighWarningStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.10
Enable/disable the set point to trigger high warning alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2HumidityHighCriticalStatus 1.3.6.1.4.1.19011.1.3.1.1.4.4.4.11
Enable/disable the set point to trigger high critical alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

inSeptsensorConfigSensor2Alarm1 1.3.6.1.4.1.19011.1.3.1.1.4.4.5
OBJECT IDENTIFIER    

inSeptsensorConfigSensor2Alarm1Name 1.3.6.1.4.1.19011.1.3.1.1.4.4.5.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor2Alarm1State 1.3.6.1.4.1.19011.1.3.1.1.4.4.5.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

inSeptsensorConfigSensor2Alarm1Hysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.4.5.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptsensorConfigSensor2Alarm2 1.3.6.1.4.1.19011.1.3.1.1.4.4.6
OBJECT IDENTIFIER    

inSeptsensorConfigSensor2Alarm2Name 1.3.6.1.4.1.19011.1.3.1.1.4.4.6.1
The name of alarm-1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

inSeptsensorConfigSensor2Alarm2State 1.3.6.1.4.1.19011.1.3.1.1.4.4.6.2
Setup the signal type to trigger alarm.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)  

inSeptsensorConfigSensor2Alarm2Hysteresis 1.3.6.1.4.1.19011.1.3.1.1.4.4.6.3
The set value to delay the alarm triggered when event occurs.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

inSeptCommunicationRestored 1
INFORMATION: Communication between interSeptor and sensor has been established.
TRAP-TYPE    

inSeptCommunicationLost 2
WARNING: Communication between interSeptor and sensor has been lost.
TRAP-TYPE    

inSeptAlarm1Inactive 3
INFORMATION: Alarm1 of sensor has returned from active state.
TRAP-TYPE    

inSeptAlarm1Active 4
WARNING: Alarm1 has become active.
TRAP-TYPE    

inSeptAlarm2Inactive 5
INFORMATION: Alarm2 of sensor has returned from active state.
TRAP-TYPE    

inSeptAlarm2Active 6
WARNING: Alarm2 has become active.
TRAP-TYPE    

inSeptTemperatureNotHighWarning 7
INFORMATION: The temperature of sensor has returned from High warning to normal.
TRAP-TYPE    

inSeptTemperatureHighWarning 8
WARNING: The temperature of sensor is higher than High warning set point.
TRAP-TYPE    

inSeptTemperatureNotLowWarning 9
INFORMATION: The temperature of sensor has returned from low warning to normal.
TRAP-TYPE    

inSeptTemperatureLowWarning 10
WARNING: The temperature of sensor is lower than low warning set point.
TRAP-TYPE    

inSeptTemperatureNotHighCritical 11
INFORMATION: The temperature of sensor is lower than high critical set point.
TRAP-TYPE    

inSeptTemperatureHighCritical 12
CRITICAL: The temperature of sensor is higher than high critical set point.
TRAP-TYPE    

inSeptTemperatureNotLowCritical 13
INFORMATION: The temperature of sensor is higher than low critical set point.
TRAP-TYPE    

inSeptTemperatureLowCritical 14
CRITICAL: The temperature of sensor is lower than low critical set point.
TRAP-TYPE    

inSeptHumidityNotHighWarning 15
INFORMATION: The humidity of sensor has returned from High warning to normal.
TRAP-TYPE    

inSeptHumidityHighWarning 16
WARNING: The humidity of sensor is higher than High warning set point.
TRAP-TYPE    

inSeptHumidityNotLowWarning 17
INFORMATION: The humidity of sensor has returned from low warning to normal.
TRAP-TYPE    

inSeptHumidityLowWarning 18
WARNING: The humidity of sensor is lower than low warning set point.
TRAP-TYPE    

inSeptHumidityNotHighCritical 19
INFORMATION: The humidity of sensor is lower than high critical set point.
TRAP-TYPE    

inSeptHumidityHighCritical 20
CRITICAL: The humidity of sensor is higher than high critical set point.
TRAP-TYPE    

inSeptHumidityNotLowCritical 21
INFORMATION: The humidity of sensor is higher than low critical set point.
TRAP-TYPE    

inSeptHumidityLowCritical 22
CRITICAL: The humidity of sensor is lower than low critical set point.
TRAP-TYPE