ELTEK-DISTRIBUTED-MIB

File: ELTEK-DISTRIBUTED-MIB.mib (104726 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC

Imported symbols

NOTIFICATION-TYPE OBJECT-TYPE MODULE-IDENTITY
enterprises Counter32 Integer32
NOTIFICATION-GROUP DisplayString

Defined Types

SystemControlUnitEntry  
SEQUENCE    
  inputControlUnitID Integer32
  inputUserConfigurable1 INTEGER
  inputUserConfigurable2 INTEGER
  inputUserConfigurable3 INTEGER
  inputUserConfigurable4 INTEGER
  inputUserConfigurable5 INTEGER
  inputUserConfigurable6 INTEGER
  inputUserConfigurable7 INTEGER
  inputUserConfigurable8 INTEGER
  inputUserConfigurable9 INTEGER
  inputUserConfigurable10 INTEGER

SystemControlUnitInputEntry  
SEQUENCE    
  inputUnitID Integer32
  inputUserConfigurableText1 DisplayString
  inputUserConfigurableText2 DisplayString
  inputUserConfigurableText3 DisplayString
  inputUserConfigurableText4 DisplayString
  inputUserConfigurableText5 DisplayString
  inputUserConfigurableText6 DisplayString
  inputUserConfigurableText7 DisplayString
  inputUserConfigurableText8 DisplayString
  inputUserConfigurableText9 DisplayString
  inputUserConfigurableText10 DisplayString

IoUnitsEntry  
SEQUENCE    
  ioUnitID Integer32
  ioUnitOutDoorTemp1 Integer32
  ioUnitOutDoorTemp2 Integer32
  ioUnitFanSpeed1 Integer32
  ioUnitFanSpeedDeltaValue1 Integer32
  ioUnitFanSpeed2 Integer32
  ioUnitFanSpeedDeltaValue2 Integer32
  ioUnitProgInputText1 DisplayString
  ioUnitProgInputStatus1 INTEGER
  ioUnitProgInputText2 DisplayString
  ioUnitProgInputStatus2 INTEGER
  ioUnitProgInputText3 DisplayString
  ioUnitProgInputStatus3 INTEGER
  ioUnitProgInputText4 DisplayString
  ioUnitProgInputStatus4 INTEGER
  ioUnitProgInputText5 DisplayString
  ioUnitProgInputStatus5 INTEGER
  ioUnitProgInputText6 DisplayString
  ioUnitProgInputStatus6 INTEGER
  ioUnitProgInputValue1 Integer32
  ioUnitProgInputValue2 Integer32
  ioUnitProgInputValue3 Integer32
  ioUnitProgInputValue4 Integer32
  ioUnitProgInputValue5 Integer32
  ioUnitProgInputValue6 Integer32

BatteryBanksEntry  
SEQUENCE    
  batteryBankID Integer32
  batteryBanksSymmetry1enable INTEGER
  batteryBanksSymmetry1status INTEGER
  batteryBanksSymmetry1deltaVoltage Integer32
  batteryBanksSymmetry2enable INTEGER
  batteryBanksSymmetry2status INTEGER
  batteryBanksSymmetry2deltaVoltage Integer32
  batteryBanksSymmetry3enable INTEGER
  batteryBanksSymmetry3status INTEGER
  batteryBanksSymmetry3deltaVoltage Integer32
  batteryBanksSymmetry4enable INTEGER
  batteryBanksSymmetry4status INTEGER
  batteryBanksSymmetry4deltaVoltage Integer32
  batteryBanksSymmetry5enable INTEGER
  batteryBanksSymmetry5status INTEGER
  batteryBanksSymmetry5deltaVoltage Integer32
  batteryBanksSymmetry6enable INTEGER
  batteryBanksSymmetry6status INTEGER
  batteryBanksSymmetry6deltaVoltage Integer32
  batteryBanksSymmetry7enable INTEGER
  batteryBanksSymmetry7status INTEGER
  batteryBanksSymmetry7deltaVoltage Integer32
  batteryBanksSymmetry8enable INTEGER
  batteryBanksSymmetry8status INTEGER
  batteryBanksSymmetry8deltaVoltage Integer32

BatteryBanksExtensionEntry  
SEQUENCE    
  batteryBanksExtensionID Integer32
  batteryBanksExtensionSymmetryInputValue1 Integer32
  batteryBanksExtensionSymmetryInputValue2 Integer32
  batteryBanksExtensionSymmetryInputValue3 Integer32
  batteryBanksExtensionSymmetryInputValue4 Integer32
  batteryBanksExtensionSymmetryInputValue5 Integer32
  batteryBanksExtensionSymmetryInputValue6 Integer32
  batteryBanksExtensionSymmetryInputValue7 Integer32
  batteryBanksExtensionSymmetryInputValue8 Integer32

BattmonUnitsEntry  
SEQUENCE    
  batteryMonitorID Integer32
  batteryMonitorSymmetry1status INTEGER
  batteryMonitorSymmetry1InputValue Integer32
  batteryMonitorSymmetry2status INTEGER
  batteryMonitorSymmetry2InputValue Integer32
  batteryMonitorSymmetry3status INTEGER
  batteryMonitorSymmetry3InputValue Integer32
  batteryMonitorSymmetry4status INTEGER
  batteryMonitorSymmetry4InputValue Integer32
  batteryMonitorCurrentValue Integer32
  batteryMonitorFuseStatus INTEGER
  batteryMonitorTemperature Integer32

LoadMonitorUnitsEntry  
SEQUENCE    
  loadMonitorID Integer32
  loadMonitorFuseStatus1 INTEGER
  loadMonitorCurrent1 Integer32
  loadMonitorFuseStatus2 INTEGER
  loadMonitorCurrent2 Integer32
  loadMonitorFuseStatus3 INTEGER
  loadMonitorCurrent3 Integer32
  loadMonitorFuseStatus4 INTEGER
  loadMonitorCurrent4 Integer32
  loadMonitorFuseStatus5 INTEGER
  loadMonitorCurrent5 Integer32
  loadMonitorFuseStatus6 INTEGER
  loadMonitorCurrent6 Integer32
  loadMonitorFuseStatus7 INTEGER
  loadMonitorCurrent7 Integer32
  loadMonitorFuseStatus8 INTEGER
  loadMonitorCurrent8 Integer32

RectifierStatusEntry  
SEQUENCE    
  rectifierStatusID Integer32
  rectifierStatusStatus INTEGER
  rectifierStatusOutputCurrent Integer32
  rectifierStatusOutputVoltage Integer32
  rectifierStatusTemp Integer32
  rectifierStatusType DisplayString
  rectifierStatusSKU DisplayString
  rectifierStatusSerialNo DisplayString
  rectifierStatusRevisionLevel DisplayString

SolarChargerStatusEntry  
SEQUENCE    
  solarChargerStatusID Integer32
  solarChargerStatusStatus INTEGER
  solarChargerOutputCurrent Integer32
  solarChargerOutputVoltage Integer32
  solarChargerTemp Integer32
  solarChargerType DisplayString
  solarChargerSKU DisplayString
  solarChargerSerialNo DisplayString
  solarChargerRevisionLevel DisplayString

Defined Values

eltek 1.3.6.1.4.1.12148
An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3 and compack 1.xx) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack w/WebPower sw V4.6, Smartpack2 V1.1) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.7, ComPack V1.04, Smartpack2 V1.1, V1.2)
MODULE-IDENTITY    

eltekDistributedPlantV7 1.3.6.1.4.1.12148.9
OBJECT IDENTIFIER    

controlSystem 1.3.6.1.4.1.12148.9.1
OBJECT IDENTIFIER    

systemTime 1.3.6.1.4.1.12148.9.1.1
OBJECT IDENTIFIER    

ioUnits 1.3.6.1.4.1.12148.9.1.17
OBJECT IDENTIFIER    

dcSystem 1.3.6.1.4.1.12148.9.2
OBJECT IDENTIFIER    

dcPlant 1.3.6.1.4.1.12148.9.2.1
OBJECT IDENTIFIER    

systemSiteInfo 1.3.6.1.4.1.12148.9.2.1.3
OBJECT IDENTIFIER    

battery 1.3.6.1.4.1.12148.9.3
OBJECT IDENTIFIER    

batteryLVD 1.3.6.1.4.1.12148.9.3.17
OBJECT IDENTIFIER    

batteryBanks 1.3.6.1.4.1.12148.9.3.19
OBJECT IDENTIFIER    

batteryCapacityData 1.3.6.1.4.1.12148.9.3.20
OBJECT IDENTIFIER    

batteryMonitorUnits 1.3.6.1.4.1.12148.9.3.21
OBJECT IDENTIFIER    

loadDistribution 1.3.6.1.4.1.12148.9.4
OBJECT IDENTIFIER    

loadDistributionLVDStatus 1.3.6.1.4.1.12148.9.4.3
OBJECT IDENTIFIER    

loadMonitorUnits 1.3.6.1.4.1.12148.9.4.4
OBJECT IDENTIFIER    

rectifier 1.3.6.1.4.1.12148.9.5
OBJECT IDENTIFIER    

rectifierStatus 1.3.6.1.4.1.12148.9.5.5
OBJECT IDENTIFIER    

acDistribution 1.3.6.1.4.1.12148.9.6
OBJECT IDENTIFIER    

alarmGroup 1.3.6.1.4.1.12148.9.7
OBJECT IDENTIFIER    

alarmWellknownAlarms 1.3.6.1.4.1.12148.9.7.1
OBJECT IDENTIFIER    

solarCharger 1.3.6.1.4.1.12148.9.9
OBJECT IDENTIFIER    

solarChargerStatus 1.3.6.1.4.1.12148.9.9.5
OBJECT IDENTIFIER    

systemTimeTime 1.3.6.1.4.1.12148.9.1.1.1
The system date and time. Used for event timestamps and logging
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

systemInfoRefresh 1.3.6.1.4.1.12148.9.1.2
This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), refreshdata(1)  

systemTrapRepeatRate 1.3.6.1.4.1.12148.9.1.3
This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1440  

systemSendOffTrap 1.3.6.1.4.1.12148.9.1.4
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

systemNumOfControlUnits 1.3.6.1.4.1.12148.9.1.5
The number of Control units in a distributed system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

systemControlUnitIndex 1.3.6.1.4.1.12148.9.1.6
Index used for navigating in the table for configurable inputs.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..7  

systemControlUnitTable 1.3.6.1.4.1.12148.9.1.7
This table contains the status of the programmable inputs. There is one row for each Control unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SystemControlUnitEntry

systemControlUnitEntry 1.3.6.1.4.1.12148.9.1.7.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SystemControlUnitEntry  

inputControlUnitID 1.3.6.1.4.1.12148.9.1.7.1.1
The ID of which Control unit to be read.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

inputUserConfigurable1 1.3.6.1.4.1.12148.9.1.7.1.2
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable2 1.3.6.1.4.1.12148.9.1.7.1.3
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable3 1.3.6.1.4.1.12148.9.1.7.1.4
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable4 1.3.6.1.4.1.12148.9.1.7.1.5
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable5 1.3.6.1.4.1.12148.9.1.7.1.6
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable6 1.3.6.1.4.1.12148.9.1.7.1.7
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable7 1.3.6.1.4.1.12148.9.1.7.1.8
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable8 1.3.6.1.4.1.12148.9.1.7.1.9
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable9 1.3.6.1.4.1.12148.9.1.7.1.10
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

inputUserConfigurable10 1.3.6.1.4.1.12148.9.1.7.1.11
Programmable input status. The description of the input is found in the systemControlUnitInputTable
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

systemLinkStatus 1.3.6.1.4.1.12148.9.1.8
A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER linkdown(0), linkup(1)  

systemInitiateEEPROM 1.3.6.1.4.1.12148.9.1.9
Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly.
Status: deprecated Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), start(1)  

systemLastDigInput 1.3.6.1.4.1.12148.9.1.10
The last Prog.Input that generated a trap. Used by Traps only.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 1..10  

systemTrapCounter 1.3.6.1.4.1.12148.9.1.11
The number of times a trap has been repeated.. Only acessible for Traps.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Counter32  

systemHeartBeatTrapRepeatRate 1.3.6.1.4.1.12148.9.1.12
The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1440  

systemResetManualAlarms 1.3.6.1.4.1.12148.9.1.13
A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), apply(1)  

systemControlUnitInputIndex 1.3.6.1.4.1.12148.9.1.14
Index used for navigating in the table for configurable inputs.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..7  

systemControlUnitInputTable 1.3.6.1.4.1.12148.9.1.15
This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput .x
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SystemControlUnitInputEntry

systemControlUnitInputEntry 1.3.6.1.4.1.12148.9.1.15.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SystemControlUnitInputEntry  

inputUnitID 1.3.6.1.4.1.12148.9.1.15.1.1
The ID of which Control unit to be read.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

inputUserConfigurableText1 1.3.6.1.4.1.12148.9.1.15.1.2
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText2 1.3.6.1.4.1.12148.9.1.15.1.3
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText3 1.3.6.1.4.1.12148.9.1.15.1.4
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText4 1.3.6.1.4.1.12148.9.1.15.1.5
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText5 1.3.6.1.4.1.12148.9.1.15.1.6
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText6 1.3.6.1.4.1.12148.9.1.15.1.7
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText7 1.3.6.1.4.1.12148.9.1.15.1.8
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .7.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText8 1.3.6.1.4.1.12148.9.1.15.1.9
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .8.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText9 1.3.6.1.4.1.12148.9.1.15.1.10
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .9.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

inputUserConfigurableText10 1.3.6.1.4.1.12148.9.1.15.1.11
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .10.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

systemResetCtrlSystem 1.3.6.1.4.1.12148.9.1.16
A pushbutton function that resets the control system. Configuration data will be kept.
Status: deprecated Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), reboot(1)  

ioUnitNumberOfUnits 1.3.6.1.4.1.12148.9.1.17.1
Tok_String
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitsIndex 1.3.6.1.4.1.12148.9.1.17.2
Tok_String
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..13  

ioUnitsTable 1.3.6.1.4.1.12148.9.1.17.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IoUnitsEntry

ioUnitsEntry 1.3.6.1.4.1.12148.9.1.17.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  IoUnitsEntry  

ioUnitID 1.3.6.1.4.1.12148.9.1.17.3.1.1
Tok_String
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitOutDoorTemp1 1.3.6.1.4.1.12148.9.1.17.3.1.2
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitOutDoorTemp2 1.3.6.1.4.1.12148.9.1.17.3.1.3
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitFanSpeed1 1.3.6.1.4.1.12148.9.1.17.3.1.4
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitFanSpeedDeltaValue1 1.3.6.1.4.1.12148.9.1.17.3.1.5
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitFanSpeed2 1.3.6.1.4.1.12148.9.1.17.3.1.6
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitFanSpeedDeltaValue2 1.3.6.1.4.1.12148.9.1.17.3.1.7
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputText1 1.3.6.1.4.1.12148.9.1.17.3.1.8
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus1 1.3.6.1.4.1.12148.9.1.17.3.1.9
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputText2 1.3.6.1.4.1.12148.9.1.17.3.1.10
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus2 1.3.6.1.4.1.12148.9.1.17.3.1.11
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputText3 1.3.6.1.4.1.12148.9.1.17.3.1.12
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus3 1.3.6.1.4.1.12148.9.1.17.3.1.13
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputText4 1.3.6.1.4.1.12148.9.1.17.3.1.14
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus4 1.3.6.1.4.1.12148.9.1.17.3.1.15
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputText5 1.3.6.1.4.1.12148.9.1.17.3.1.16
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus5 1.3.6.1.4.1.12148.9.1.17.3.1.17
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputText6 1.3.6.1.4.1.12148.9.1.17.3.1.18
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

ioUnitProgInputStatus6 1.3.6.1.4.1.12148.9.1.17.3.1.19
Programmable input status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

ioUnitProgInputValue1 1.3.6.1.4.1.12148.9.1.17.3.1.20
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputValue2 1.3.6.1.4.1.12148.9.1.17.3.1.21
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputValue3 1.3.6.1.4.1.12148.9.1.17.3.1.22
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputValue4 1.3.6.1.4.1.12148.9.1.17.3.1.23
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputValue5 1.3.6.1.4.1.12148.9.1.17.3.1.24
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

ioUnitProgInputValue6 1.3.6.1.4.1.12148.9.1.17.3.1.25
The value read on input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

systemServiceMode 1.3.6.1.4.1.12148.9.1.18
This is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail.
Status: deprecated Access: read-write
OBJECT-TYPE    
  INTEGER deactivate(0), activate(1)  

systemSiteInfoCustomer 1.3.6.1.4.1.12148.9.2.1.3.1
The Customer name (as stored in the Control Unit).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoLocation 1.3.6.1.4.1.12148.9.2.1.3.2
The system/site Location details (as stored in the Control Unit).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoMessage1 1.3.6.1.4.1.12148.9.2.1.3.3
The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoMessage2 1.3.6.1.4.1.12148.9.2.1.3.4
The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoInstalledDate 1.3.6.1.4.1.12148.9.2.1.3.5
The system's Installed Date text string (as stored in the Control Unit) 16bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemSiteInfoControllerType 1.3.6.1.4.1.12148.9.2.1.3.6
The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER al175(0), al4000(1), al6000(2), al175oem(3), mcu(4), smartpack(5), compack(6), smartpack2(7)  

systemSiteInfoSystemSeriaNum 1.3.6.1.4.1.12148.9.2.1.3.7
The serial number for the complete system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemSiteInfoControllerSeriaNum 1.3.6.1.4.1.12148.9.2.1.3.8
The serial number for Control unit 1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemNominalVoltage 1.3.6.1.4.1.12148.9.2.1.4
The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER prs48v(0), prs24v(1), prs12v(2), prs26v(3), prs60v(4)  

systemOperationalStatus 1.3.6.1.4.1.12148.9.2.2
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER floatvoltreg(0), floattempcomp(1), batteryboost(2), batterytest(3)  

batteryName 1.3.6.1.4.1.12148.9.3.1
A descriptive name of the battery installed in the system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

batteryVoltage 1.3.6.1.4.1.12148.9.3.2
The measured battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..7500  

batteryCurrent 1.3.6.1.4.1.12148.9.3.3
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTemp 1.3.6.1.4.1.12148.9.3.4
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..9999  

batteryBreakerStatus 1.3.6.1.4.1.12148.9.3.5
The state of the battery fuses/breakers can be either normal(0) or alarm(1).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

batteryChargeCurrentLimitCtrl 1.3.6.1.4.1.12148.9.3.6
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryChargeCurrentLimitValue 1.3.6.1.4.1.12148.9.3.7
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..32000  

batteryTempCompEnable 1.3.6.1.4.1.12148.9.3.8
Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryFloatVoltConfig 1.3.6.1.4.1.12148.9.3.9
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryBoostVoltConfig 1.3.6.1.4.1.12148.9.3.10
The Voltage at which the DC System boost charges the batteries.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryHighMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.11
The Major High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryHighMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.12
The Minor High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLowMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.13
The Major Low Battery Voltage Alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLowMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.14
The Minor Low Battery Voltage Alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryStartManualTest 1.3.6.1.4.1.12148.9.3.15
This pushbutton will start or stop a manual battery test if the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), starttest(1), stoptest(2)  

batteryStartManualBoost 1.3.6.1.4.1.12148.9.3.16
This pushbutton will start or stop a manual battery boost if the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), startboost(1), stopboost(2)  

batteryLVDStatus 1.3.6.1.4.1.12148.9.3.17.1
The Battery Contactor is connected(0), disconnected(1) or disabled(2)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connected(0), disconnected(1), disabled(2)  

batteryLVDDisconnectVoltage 1.3.6.1.4.1.12148.9.3.17.2
The Battery Contactors Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

batteryLVDConnectVoltage 1.3.6.1.4.1.12148.9.3.17.3
The Battery Contactors Reconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

batteryBanksNumofBanks 1.3.6.1.4.1.12148.9.3.18
The number of Control units that is used to measure battery parameters.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

batterySymmetryDeltaLimitVoltage 1.3.6.1.4.1.12148.9.3.19.1
The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryBanksIndex 1.3.6.1.4.1.12148.9.3.19.2
Index used for navigating the rows 1..8 of batteryBanksTable
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..7  

batteryBanksTable 1.3.6.1.4.1.12148.9.3.19.3
A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBanksEntry

batteryBanksEntry 1.3.6.1.4.1.12148.9.3.19.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBanksEntry  

batteryBankID 1.3.6.1.4.1.12148.9.3.19.3.1.1
The ID of the selected row in the table. i.e. the battery bank.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

batteryBanksSymmetry1enable 1.3.6.1.4.1.12148.9.3.19.3.1.2
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry1status 1.3.6.1.4.1.12148.9.3.19.3.1.3
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry1deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.4
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry2enable 1.3.6.1.4.1.12148.9.3.19.3.1.5
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry2status 1.3.6.1.4.1.12148.9.3.19.3.1.6
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry2deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.7
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry3enable 1.3.6.1.4.1.12148.9.3.19.3.1.8
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry3status 1.3.6.1.4.1.12148.9.3.19.3.1.9
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry3deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.10
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry4enable 1.3.6.1.4.1.12148.9.3.19.3.1.11
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry4status 1.3.6.1.4.1.12148.9.3.19.3.1.12
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry4deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.13
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry5enable 1.3.6.1.4.1.12148.9.3.19.3.1.14
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry5status 1.3.6.1.4.1.12148.9.3.19.3.1.15
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry5deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.16
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry6enable 1.3.6.1.4.1.12148.9.3.19.3.1.17
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry6status 1.3.6.1.4.1.12148.9.3.19.3.1.18
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry6deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.19
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry7enable 1.3.6.1.4.1.12148.9.3.19.3.1.20
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry7status 1.3.6.1.4.1.12148.9.3.19.3.1.21
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry7deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.22
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksSymmetry8enable 1.3.6.1.4.1.12148.9.3.19.3.1.23
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryBanksSymmetry8status 1.3.6.1.4.1.12148.9.3.19.3.1.24
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryBanksSymmetry8deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.25
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksNumberOfStrings 1.3.6.1.4.1.12148.9.3.19.4
Number of strings in the power system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionIndex 1.3.6.1.4.1.12148.9.3.19.5
Index used for navigating the rows 1..14 of batteryBanksExtensionTable
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..7  

batteryBanksExtensionTable 1.3.6.1.4.1.12148.9.3.19.6
This table shows the measured value on the symmetry inputs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryBanksExtensionEntry

batteryBanksExtensionEntry 1.3.6.1.4.1.12148.9.3.19.6.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryBanksExtensionEntry  

batteryBanksExtensionID 1.3.6.1.4.1.12148.9.3.19.6.1.1
The ID of the selected row in the table. i.e. the battery bank.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue1 1.3.6.1.4.1.12148.9.3.19.6.1.2
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue2 1.3.6.1.4.1.12148.9.3.19.6.1.3
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue3 1.3.6.1.4.1.12148.9.3.19.6.1.4
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue4 1.3.6.1.4.1.12148.9.3.19.6.1.5
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue5 1.3.6.1.4.1.12148.9.3.19.6.1.6
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue6 1.3.6.1.4.1.12148.9.3.19.6.1.7
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue7 1.3.6.1.4.1.12148.9.3.19.6.1.8
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryBanksExtensionSymmetryInputValue8 1.3.6.1.4.1.12148.9.3.19.6.1.9
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTimeToDisconnect 1.3.6.1.4.1.12148.9.3.20.1
Remaining time to low voltage battery disconnect.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCapacityLeft 1.3.6.1.4.1.12148.9.3.20.2
Capacity left in the battery.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCapacityUsed 1.3.6.1.4.1.12148.9.3.20.3
Capacity consumed.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryCapacityTotal 1.3.6.1.4.1.12148.9.3.20.4
This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryQuality 1.3.6.1.4.1.12148.9.3.20.5
This is the battery quality (%) of the latest battery test.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

battmonNumberOfUnits 1.3.6.1.4.1.12148.9.3.21.1
Number of battery monitor units in the power system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

battmonUnitsIndex 1.3.6.1.4.1.12148.9.3.21.2
Index used for navigating the rows 1..14 of battmonUnitsTable
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

battmonUnitsTable 1.3.6.1.4.1.12148.9.3.21.3
A table of up to 14 battery monitor control units.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BattmonUnitsEntry

battmonUnitsEntry 1.3.6.1.4.1.12148.9.3.21.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  BattmonUnitsEntry  

batteryMonitorID 1.3.6.1.4.1.12148.9.3.21.3.1.1
The ID of the selected row
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..14  

batteryMonitorSymmetry1status 1.3.6.1.4.1.12148.9.3.21.3.1.2
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryMonitorSymmetry1InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.3
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetry2status 1.3.6.1.4.1.12148.9.3.21.3.1.4
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryMonitorSymmetry2InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.5
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetry3status 1.3.6.1.4.1.12148.9.3.21.3.1.6
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryMonitorSymmetry3InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.7
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorSymmetry4status 1.3.6.1.4.1.12148.9.3.21.3.1.8
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)  

batteryMonitorSymmetry4InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.9
The measured voltage on the symmetry input.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorCurrentValue 1.3.6.1.4.1.12148.9.3.21.3.1.10
The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryMonitorFuseStatus 1.3.6.1.4.1.12148.9.3.21.3.1.11
The state of the battery fuse/breaker can be either normal(0) or alarm(1).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

batteryMonitorTemperature 1.3.6.1.4.1.12148.9.3.21.3.1.12
The battery temperature.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryHighMajorTempAlarmLevel 1.3.6.1.4.1.12148.9.3.22
This is the Major High Temperature Alarm level.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryHighMinorTempAlarmLevel 1.3.6.1.4.1.12148.9.3.23
This is the Minor High Temperature Alarm level.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

loadDistributionCurrent 1.3.6.1.4.1.12148.9.4.1
The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadDistributionBreakerStatus 1.3.6.1.4.1.12148.9.4.2
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadLVD1Enable 1.3.6.1.4.1.12148.9.4.3.1
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD1Status 1.3.6.1.4.1.12148.9.4.3.2
The load Contactor 1 is connected(0), disconnected(1) or disabled(2)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connected(0), disconnected(1), disabled(2)  

loadLVD1ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.3
LVLD1 Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD1DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.4
LVLD1 Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD2Enable 1.3.6.1.4.1.12148.9.4.3.5
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD2Status 1.3.6.1.4.1.12148.9.4.3.6
The load Contactor 2 is connected(0), disconnected(1) or disabled(2)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connected(0), disconnected(1), disabled(2)  

loadLVD2ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.7
LVLD2 Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD2DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.8
LVLD2 Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD3Enable 1.3.6.1.4.1.12148.9.4.3.9
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD3Status 1.3.6.1.4.1.12148.9.4.3.10
The load Contactor 3 is connected(0), disconnected(1) or disabled(2)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connected(0), disconnected(1), disabled(2)  

loadLVD3ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.11
LVLD3 Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD3DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.12
LVLD3 Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadmonitorNumberOfUnits 1.3.6.1.4.1.12148.9.4.4.1
Tok_String
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorUnitsIndex 1.3.6.1.4.1.12148.9.4.4.2
Tok_String
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32 0..13  

loadMonitorUnitsTable 1.3.6.1.4.1.12148.9.4.4.3
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LoadMonitorUnitsEntry

loadMonitorUnitsEntry 1.3.6.1.4.1.12148.9.4.4.3.1
Tok_String
Status: current Access: not-accessible
OBJECT-TYPE    
  LoadMonitorUnitsEntry  

loadMonitorID 1.3.6.1.4.1.12148.9.4.4.3.1.1
Tok_String
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus1 1.3.6.1.4.1.12148.9.4.4.3.1.2
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent1 1.3.6.1.4.1.12148.9.4.4.3.1.3
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus2 1.3.6.1.4.1.12148.9.4.4.3.1.4
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent2 1.3.6.1.4.1.12148.9.4.4.3.1.5
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus3 1.3.6.1.4.1.12148.9.4.4.3.1.6
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent3 1.3.6.1.4.1.12148.9.4.4.3.1.7
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus4 1.3.6.1.4.1.12148.9.4.4.3.1.8
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent4 1.3.6.1.4.1.12148.9.4.4.3.1.9
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus5 1.3.6.1.4.1.12148.9.4.4.3.1.10
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent5 1.3.6.1.4.1.12148.9.4.4.3.1.11
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus6 1.3.6.1.4.1.12148.9.4.4.3.1.12
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent6 1.3.6.1.4.1.12148.9.4.4.3.1.13
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus7 1.3.6.1.4.1.12148.9.4.4.3.1.14
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent7 1.3.6.1.4.1.12148.9.4.4.3.1.15
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadMonitorFuseStatus8 1.3.6.1.4.1.12148.9.4.4.3.1.16
The state of the load fuses/breakers can be either normal(0) or alarm(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

loadMonitorCurrent8 1.3.6.1.4.1.12148.9.4.4.3.1.17
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifierInstalledRectifiers 1.3.6.1.4.1.12148.9.5.1
The number of installed rectifiers for this DC Power System.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

rectifierRectifiersActive 1.3.6.1.4.1.12148.9.5.2
Not Used!
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

rectifierTotalCurrent 1.3.6.1.4.1.12148.9.5.3
The DC system's total delivered rectifier current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifierUtilization 1.3.6.1.4.1.12148.9.5.4
Utilization in % of available rectifier capacity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..100  

rectifierStatusNoIndex 1.3.6.1.4.1.12148.9.5.5.1
An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..95  

rectifierStatusTable 1.3.6.1.4.1.12148.9.5.5.2
A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifierStatusEntry

rectifierStatusEntry 1.3.6.1.4.1.12148.9.5.5.2.1
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifierStatusEntry  

rectifierStatusID 1.3.6.1.4.1.12148.9.5.5.2.1.1
The rectifier ID number of the rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..100  

rectifierStatusStatus 1.3.6.1.4.1.12148.9.5.5.2.1.2
The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)  

rectifierStatusOutputCurrent 1.3.6.1.4.1.12148.9.5.5.2.1.3
The output current of the rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusOutputVoltage 1.3.6.1.4.1.12148.9.5.5.2.1.4
The rectifier voltage of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusTemp 1.3.6.1.4.1.12148.9.5.5.2.1.5
The input air temperature of the rectifier.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusType 1.3.6.1.4.1.12148.9.5.5.2.1.6
The rectifier article number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

rectifierStatusSKU 1.3.6.1.4.1.12148.9.5.5.2.1.7
The rectifier part number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..32)  

rectifierStatusSerialNo 1.3.6.1.4.1.12148.9.5.5.2.1.8
The rectifier serial number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifierStatusRevisionLevel 1.3.6.1.4.1.12148.9.5.5.2.1.9
The rectifier HW revision number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

acVoltage1 1.3.6.1.4.1.12148.9.6.1
The AC Voltage of phase 1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acVoltage2 1.3.6.1.4.1.12148.9.6.2
The AC Voltage of phase 2
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acVoltage3 1.3.6.1.4.1.12148.9.6.3
The AC Voltage of phase 3
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

alarmMajorHighBattVolt 1.3.6.1.4.1.12148.9.7.1.1
The Major High Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorHighBattVolt 1.3.6.1.4.1.12148.9.7.1.2
The Minor High Battery Voltage alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorLowBattVolt 1.3.6.1.4.1.12148.9.7.1.3
The Major Low Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorLowBattVolt 1.3.6.1.4.1.12148.9.7.1.4
The Minor Low Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorBatteryHighTemp 1.3.6.1.4.1.12148.9.7.1.5
The Major High Battery Temperature alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorBatteryHighTemp 1.3.6.1.4.1.12148.9.7.1.6
The Minor High Battery Temperature alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryDisconnectOpen 1.3.6.1.4.1.12148.9.7.1.7
The Battery Disconnect Contactor alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD1open 1.3.6.1.4.1.12148.9.7.1.8
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD2open 1.3.6.1.4.1.12148.9.7.1.9
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD3open 1.3.6.1.4.1.12148.9.7.1.10
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmACmains 1.3.6.1.4.1.12148.9.7.1.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryBreakerOpen 1.3.6.1.4.1.12148.9.7.1.12
A battery breaker/fuse alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmDistributionBreakerOpen 1.3.6.1.4.1.12148.9.7.1.13
A Load Distribution breaker/fuse alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorRectifier 1.3.6.1.4.1.12148.9.7.1.14
This is a Major Rectifier alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorRectifier 1.3.6.1.4.1.12148.9.7.1.15
This is a Minor Rectifier alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorBatterySymmetry 1.3.6.1.4.1.12148.9.7.1.16
Battery Symmetry Delta Voltage Major alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorBatterySymmetry 1.3.6.1.4.1.12148.9.7.1.17
Battery Symmetry Delta Voltage Minor alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryLifeEnded 1.3.6.1.4.1.12148.9.7.1.18
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryTestmodeEntered 1.3.6.1.4.1.12148.9.7.1.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryBoostmodeEntered 1.3.6.1.4.1.12148.9.7.1.20
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmIoUnitTemp1 1.3.6.1.4.1.12148.9.7.1.21
High or low temperature alarm 1 from any of the IO units.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmIoUnitTemp2 1.3.6.1.4.1.12148.9.7.1.22
High or low temperature alarm 2 from any of the IO units.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmIoUnitDeltaFanSpeed1 1.3.6.1.4.1.12148.9.7.1.23
Delta fan speed 1 from any of the IO units.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmIoUnitDeltaFanSpeed2 1.3.6.1.4.1.12148.9.7.1.24
Delta fan speed 2 from any of the IO units.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorSolar 1.3.6.1.4.1.12148.9.7.1.25
This is a Major Solar alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorSolar 1.3.6.1.4.1.12148.9.7.1.26
This is a Major Solar alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorRectifierCapacity 1.3.6.1.4.1.12148.9.7.1.27
This is a Major Rectifier Capacity alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorRectifierCapacity 1.3.6.1.4.1.12148.9.7.1.28
This is a Minor Rectifier Capacity alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

dcSystemTraps 1.3.6.1.4.1.12148.9.8
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
Status: current Access: read-only
NOTIFICATION-GROUP    

alarmMajorHighBattVoltTrap 1.3.6.1.4.1.12148.9.8.1
The Major High Battery Voltage alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorHighBattVoltTrap 1.3.6.1.4.1.12148.9.8.2
The Minor High Battery Voltage alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorLowBattVoltTrap 1.3.6.1.4.1.12148.9.8.3
The Major Low Battery Voltage Alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorLowBattVoltTrap 1.3.6.1.4.1.12148.9.8.4
The Minor Low Battery Voltage Alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorBatteryHighTempTrap 1.3.6.1.4.1.12148.9.8.5
The Major High Battery Temperature alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorBatteryHighTempTrap 1.3.6.1.4.1.12148.9.8.6
The Minor High Battery Temperature alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryDisconnectOpenTrap 1.3.6.1.4.1.12148.9.8.7
The Battery Disconnect Contactor alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD1openTrap 1.3.6.1.4.1.12148.9.8.8
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD2openTrap 1.3.6.1.4.1.12148.9.8.9
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD3openTrap 1.3.6.1.4.1.12148.9.8.10
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmACmainsTrap 1.3.6.1.4.1.12148.9.8.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryBreakerOpenTrap 1.3.6.1.4.1.12148.9.8.12
A battery breaker/fuse alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmDistributionBreakerOpenTrap 1.3.6.1.4.1.12148.9.8.13
A Load Distribution breaker/fuse alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorRectifierTrap 1.3.6.1.4.1.12148.9.8.14
This is a Major Rectifier alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorRectifierTrap 1.3.6.1.4.1.12148.9.8.15
This is a Minor Rectifier alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorBatterySymmetryTrap 1.3.6.1.4.1.12148.9.8.16
Battery Symmetry Delta Voltage Major alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorBatterySymmetryTrap 1.3.6.1.4.1.12148.9.8.17
Battery Symmetry Delta Voltage Minor alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryLifeEndedTrap 1.3.6.1.4.1.12148.9.8.18
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryTestmodeEnteredTrap 1.3.6.1.4.1.12148.9.8.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryBoostmodeEnteredTrap 1.3.6.1.4.1.12148.9.8.20
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController1proginputTrap 1.3.6.1.4.1.12148.9.8.21
Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController2proginputTrap 1.3.6.1.4.1.12148.9.8.22
Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController3proginputTrap 1.3.6.1.4.1.12148.9.8.23
Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController4proginputTrap 1.3.6.1.4.1.12148.9.8.24
Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController5proginputTrap 1.3.6.1.4.1.12148.9.8.25
Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController6proginputTrap 1.3.6.1.4.1.12148.9.8.26
Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController7proginputTrap 1.3.6.1.4.1.12148.9.8.27
Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmController8proginputTrap 1.3.6.1.4.1.12148.9.8.28
Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

infoHeartBeatTrap 1.3.6.1.4.1.12148.9.8.29
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnitTemp1Trap 1.3.6.1.4.1.12148.9.8.30
High or low temperature alarm 1 from any of the IO units.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnitTemp2Trap 1.3.6.1.4.1.12148.9.8.31
High or low temperature alarm 2 from any of the IO units.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnitDeltaFanSpeed1Trap 1.3.6.1.4.1.12148.9.8.32
Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnitDeltaFanSpeed2Trap 1.3.6.1.4.1.12148.9.8.33
Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit1proginputTrap 1.3.6.1.4.1.12148.9.8.34
Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit2proginputTrap 1.3.6.1.4.1.12148.9.8.35
Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit3proginputTrap 1.3.6.1.4.1.12148.9.8.36
Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit4proginputTrap 1.3.6.1.4.1.12148.9.8.37
Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit5proginputTrap 1.3.6.1.4.1.12148.9.8.38
Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit6proginputTrap 1.3.6.1.4.1.12148.9.8.39
Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit7proginputTrap 1.3.6.1.4.1.12148.9.8.40
Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit8proginputTrap 1.3.6.1.4.1.12148.9.8.41
Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit9proginputTrap 1.3.6.1.4.1.12148.9.8.42
Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit10proginputTrap 1.3.6.1.4.1.12148.9.8.43
Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit11proginputTrap 1.3.6.1.4.1.12148.9.8.44
Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit12proginputTrap 1.3.6.1.4.1.12148.9.8.45
Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit13proginputTrap 1.3.6.1.4.1.12148.9.8.46
Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmIoUnit14proginputTrap 1.3.6.1.4.1.12148.9.8.47
Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorSolarChargerTrap 1.3.6.1.4.1.12148.9.8.48
The Major Solar Charger alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorSolarChargerTrap 1.3.6.1.4.1.12148.9.8.49
The Minor Solar Charger alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorRectifierCapacityTrap 1.3.6.1.4.1.12148.9.8.50
The Major Rectifier Capacity alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorRectifierCapacityTrap 1.3.6.1.4.1.12148.9.8.51
The Minor Rectifier Capacity alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

solarChargerInstalledsolarChargers 1.3.6.1.4.1.12148.9.9.1
The number of installed solar chargers for this DC Power System.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

solarChargersActive 1.3.6.1.4.1.12148.9.9.2
Not Used!
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

solarChargerTotalCurrent 1.3.6.1.4.1.12148.9.9.3
The DC system's total delivered solar current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

solarChargerUtilization 1.3.6.1.4.1.12148.9.9.4
Utilization in % of available solar capacity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..100  

solarChargerStatusNoIndex 1.3.6.1.4.1.12148.9.9.5.1
An offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..95  

solarChargerStatusTable 1.3.6.1.4.1.12148.9.9.5.2
A table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarChargerStatusEntry

solarChargerStatusEntry 1.3.6.1.4.1.12148.9.9.5.2.1
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarChargerStatusEntry  

solarChargerStatusID 1.3.6.1.4.1.12148.9.9.5.2.1.1
The ID number of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..100  

solarChargerStatusStatus 1.3.6.1.4.1.12148.9.9.5.2.1.2
The operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)  

solarChargerOutputCurrent 1.3.6.1.4.1.12148.9.9.5.2.1.3
The output current of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

solarChargerOutputVoltage 1.3.6.1.4.1.12148.9.9.5.2.1.4
The output voltage of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

solarChargerTemp 1.3.6.1.4.1.12148.9.9.5.2.1.5
The input air temperature of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

solarChargerType 1.3.6.1.4.1.12148.9.9.5.2.1.6
The article number string of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

solarChargerSKU 1.3.6.1.4.1.12148.9.9.5.2.1.7
The solarcharger part number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..32)  

solarChargerSerialNo 1.3.6.1.4.1.12148.9.9.5.2.1.8
The serial number string of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

solarChargerRevisionLevel 1.3.6.1.4.1.12148.9.9.5.2.1.9
The HW revision number string of the solarcharger.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)