EES-POWER-MIB

File: EES-POWER-MIB.mib (12955 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
Integer32 Counter32 enterprises
TEXTUAL-CONVENTION DisplayString DateAndTime

Defined Types

Status  
This integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of 'abnormal' status (4) warning - A3 (5) minor - MA (6) major - CA, highest level of 'abnormal' status Administrative values: (7) unmanaged (8) restricted (9) testing (10) disabled
TEXTUAL-CONVENTION    
  INTEGER unknown(1), normal(2), observation(3), warning(4), minor(5), major(6), unmanaged(7), restricted(8), testing(9), disabled(10)  

StatusChange  
Indicates 'activated' (1) or 'deactivated' (2) alarm events.
TEXTUAL-CONVENTION    
  INTEGER activated(1), deactivated(2)  

AlarmTrapEntry  
SEQUENCE    
  alarmTrapNo Counter32
  alarmTime DateAndTime
  alarmStatusChange StatusChange
  alarmSeverity Status
  alarmDescription DisplayString
  alarmType Integer32

Defined Values

ees 1.3.6.1.4.1.6302
OBJECT IDENTIFIER    

global 1.3.6.1.4.1.6302.2
OBJECT IDENTIFIER    

powerMIB 1.3.6.1.4.1.6302.2.1
Emerson Energy Systems (EES) Power MIB, revision B.
MODULE-IDENTITY    

ident 1.3.6.1.4.1.6302.2.1.1
OBJECT IDENTIFIER    

identManufacturer 1.3.6.1.4.1.6302.2.1.1.1
The name of the equipment manufacturer.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

identModel 1.3.6.1.4.1.6302.2.1.1.2
The manufacturers model designation of the power system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

identControllerFirmwareVersion 1.3.6.1.4.1.6302.2.1.1.3
The firmware (software) version of the controller.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

identName 1.3.6.1.4.1.6302.2.1.1.4
The name of the power plant. This object should be set by the administrator.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

system 1.3.6.1.4.1.6302.2.1.2
OBJECT IDENTIFIER    

systemStatus 1.3.6.1.4.1.6302.2.1.2.1
Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of 'abnormal' status (4) warning - A3 (5) minor - MA (6) major - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabled
Status: current Access: read-only
OBJECT-TYPE    
  Status  

systemVoltage 1.3.6.1.4.1.6302.2.1.2.2
System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

systemCurrent 1.3.6.1.4.1.6302.2.1.2.3
System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

systemUsedCapacity 1.3.6.1.4.1.6302.2.1.2.4
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psBattery 1.3.6.1.4.1.6302.2.1.2.5
OBJECT IDENTIFIER    

psBatteryVoltage 1.3.6.1.4.1.6302.2.1.2.5.1
Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psBatteryCurrent 1.3.6.1.4.1.6302.2.1.2.5.2
Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psInput 1.3.6.1.4.1.6302.2.1.2.6
OBJECT IDENTIFIER    

psInputLineAVoltage 1.3.6.1.4.1.6302.2.1.2.6.1
The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psInputLineBVoltage 1.3.6.1.4.1.6302.2.1.2.6.2
The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psInputLineCVoltage 1.3.6.1.4.1.6302.2.1.2.6.3
The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psTemperature 1.3.6.1.4.1.6302.2.1.2.7
OBJECT IDENTIFIER    

psTemperature1 1.3.6.1.4.1.6302.2.1.2.7.1
The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psTemperature2 1.3.6.1.4.1.6302.2.1.2.7.2
The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psStatusCommunication 1.3.6.1.4.1.6302.2.1.2.8
The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), normal(2), interrupt(3)  

psStatusBatteryMode 1.3.6.1.4.1.6302.2.1.2.9
The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), floatcharging(2), shorttest(3), bcfortest(4), manualtesting(5), plantesting(6), acfailtesting(7), acfail(8), manualbc(9), autobc(10), cyclicbc(11), masterbc(12), masterbt(13)  

psSMNumber 1.3.6.1.4.1.6302.2.1.2.10
OBJECT IDENTIFIER    

psSMACNumber 1.3.6.1.4.1.6302.2.1.2.10.1
The number of SM AC module.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psSMBATNumber 1.3.6.1.4.1.6302.2.1.2.10.2
The number of SM BAT module.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

psSMIONumber 1.3.6.1.4.1.6302.2.1.2.10.3
The number of SM IO module.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

alarmLastTrapNo 1.3.6.1.4.1.6302.2.1.3
The sequence number of last submitted alarm trap, also last row in alarmTrapTable.
Status: current Access: read-only
OBJECT-TYPE    
  Counter32  

alarmTrapTable 1.3.6.1.4.1.6302.2.1.4
Table holding information about the submitted alarm traps.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AlarmTrapEntry

alarmTrapEntry 1.3.6.1.4.1.6302.2.1.4.1
An entry (conceptual row) in the alarmTrapTable.
Status: current Access: not-accessible
OBJECT-TYPE    
  AlarmTrapEntry  

alarmTrapNo 1.3.6.1.4.1.6302.2.1.4.1.1
The unique sequence number of this alarm trap.
Status: current Access: read-only
OBJECT-TYPE    
  Counter32  

alarmTime 1.3.6.1.4.1.6302.2.1.4.1.2
Date and time when event occured (local time), including timezone if supported by controller.
Status: current Access: read-only
OBJECT-TYPE    
  DateAndTime  

alarmStatusChange 1.3.6.1.4.1.6302.2.1.4.1.3
The type of alarm change. One of (1) activated (2) deactivated
Status: current Access: read-only
OBJECT-TYPE    
  StatusChange  

alarmSeverity 1.3.6.1.4.1.6302.2.1.4.1.4
The severity of the alarm. One of (3) observation - OA, lowest level of alarm severity (4) warning - A3 (5) minor - MA (6) major - CA, highest level of alarm severity
Status: current Access: read-only
OBJECT-TYPE    
  Status  

alarmDescription 1.3.6.1.4.1.6302.2.1.4.1.5
Free-text description of alarm.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

alarmType 1.3.6.1.4.1.6302.2.1.4.1.6
Alarm type, i.e. an integer specifying the type of alarm.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

powerEvents 1.3.6.1.4.1.6302.2.1.5
OBJECT IDENTIFIER    

alarmTrap 1.3.6.1.4.1.6302.2.1.5.1
An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmTrapNo - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
Status: current Access: read-only
NOTIFICATION-TYPE