EATON-PDU-MIB

File: EATON-PDU-MIB.mib (32979 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC SNMPv2-CONF
EATON-OIDS

Imported symbols

MODULE-IDENTITY OBJECT-TYPE Integer32
DisplayString TEXTUAL-CONVENTION MODULE-COMPLIANCE
OBJECT-GROUP pduAgent

Defined Types

PositiveInteger  
TEXTUAL-CONVENTION    
  current Integer32 1..2147483647

NonNegativeInteger  
TEXTUAL-CONVENTION    
  current Integer32 0..2147483647

PduInputEntry  
SEQUENCE    
  pduInputPhaseIndex PositiveInteger
  pduInputPhaseVoltage NonNegativeInteger
  pduInputPhaseCurrent NonNegativeInteger
  pduInputPhasePercentLoad Integer32

PduOutputEntry  
SEQUENCE    
  pduOutputPhaseIndex PositiveInteger
  pduOutputPhaseVoltage NonNegativeInteger
  pduOutputPhaseCurrent NonNegativeInteger
  pduOutputPhasePercentLoad Integer32

PanelRatingsEntry  
SEQUENCE    
  panelNumber PositiveInteger
  panelRatedVoltage PositiveInteger
  panelRatedBreakerCurrent PositiveInteger
  panelNumPhases PositiveInteger
  panelNumBreakers PositiveInteger
  panelVoltageUnits DisplayString

PanelMetersEntry  
SEQUENCE    
  panelTotalKilowattHours NonNegativeInteger
  panelMonthlyKilowattHours NonNegativeInteger
  panelYtdKilowattHours NonNegativeInteger
  panelVA NonNegativeInteger
  panelPower NonNegativeInteger
  panelPowerFactor Integer32
  panelNeutralCurrent NonNegativeInteger

PanelPhaseMetersEntry  
SEQUENCE    
  panelPhaseIndex PositiveInteger
  panelPhaseVoltage NonNegativeInteger
  panelPhaseCurrent NonNegativeInteger
  panelPhasePercentLoad Integer32

BreakerRatingsEntry  
SEQUENCE    
  breakerNumber PositiveInteger
  breakerName DisplayString
  breakerRatedCurrent PositiveInteger
  breakerNumPhases PositiveInteger

BreakerMetersEntry  
SEQUENCE    
  breakerTotalKilowattHours NonNegativeInteger
  breakerMonthlyKilowattHours NonNegativeInteger
  breakerYtdKilowattHours NonNegativeInteger

BreakerPhaseMetersEntry  
SEQUENCE    
  breakerPhaseIndex PositiveInteger
  breakerPhaseVA NonNegativeInteger
  breakerPhasePower NonNegativeInteger
  breakerPhasePowerFactor Integer32
  breakerPhaseCurrent NonNegativeInteger
  breakerPhasePercentLoad Integer32

Defined Values

eatonPduMIB 1.3.6.1.4.1.534.6.6.4
The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
MODULE-IDENTITY    

eatonPduMIBObjects 1.3.6.1.4.1.534.6.6.4.1
OBJECT IDENTIFIER    

mainPdu 1.3.6.1.4.1.534.6.6.4.1.1
OBJECT IDENTIFIER    

pduPanel 1.3.6.1.4.1.534.6.6.4.1.2
OBJECT IDENTIFIER    

pduBreaker 1.3.6.1.4.1.534.6.6.4.1.3
OBJECT IDENTIFIER    

pduNameplate 1.3.6.1.4.1.534.6.6.4.1.1.1
OBJECT IDENTIFIER    

pduRatingVA 1.3.6.1.4.1.534.6.6.4.1.1.1.1
The full VA rating of this PDU (for all phases).
OBJECT-TYPE    
  PositiveInteger  

pduNominalOutputVoltage 1.3.6.1.4.1.534.6.6.4.1.1.1.2
The nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits.
OBJECT-TYPE    
  PositiveInteger  

pduNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.1.3
The number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases.
OBJECT-TYPE    
  PositiveInteger  

pduNumPanels 1.3.6.1.4.1.534.6.6.4.1.1.1.4
The number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables.
OBJECT-TYPE    
  PositiveInteger  

pduInput 1.3.6.1.4.1.534.6.6.4.1.1.2
OBJECT IDENTIFIER    

pduFrequency 1.3.6.1.4.1.534.6.6.4.1.1.2.1
The present frequency reading for the full PDU.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputVA 1.3.6.1.4.1.534.6.6.4.1.1.2.2
The present VA input demand of the full PDU system.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputPower 1.3.6.1.4.1.534.6.6.4.1.1.2.3
The present input power demand of the full PDU system.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputPowerFactor 1.3.6.1.4.1.534.6.6.4.1.1.2.4
The input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
OBJECT-TYPE    
  Integer32 -100..100  

pduGroundCurrent 1.3.6.1.4.1.534.6.6.4.1.1.2.5
The present current in the PDU's ground phase. Ideally, this value stays at 0.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.1.2.6
Indicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
OBJECT-TYPE    
  DisplayString Size(0..31)  

pduInputNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.2.7
The number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable.
OBJECT-TYPE    
  PositiveInteger  

pduInputTable 1.3.6.1.4.1.534.6.6.4.1.1.2.8
A list of input table entries. The number of entries is given by the value of pduInputNumPhases.
OBJECT-TYPE    
  SEQUENCE OF  
    PduInputEntry

pduInputEntry 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1
An entry containing information applicable to a particular input phase.
OBJECT-TYPE    
  PduInputEntry  

pduInputPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1
The input line identifier.
OBJECT-TYPE    
  PositiveInteger  

pduInputPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2
The present input voltage for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3
The present input current for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

pduInputPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current.
OBJECT-TYPE    
  Integer32 0..200  

pduOutput 1.3.6.1.4.1.534.6.6.4.1.1.3
OBJECT IDENTIFIER    

pduOutputKilowattHours 1.3.6.1.4.1.534.6.6.4.1.1.3.1
The accumulated kilowatt-hour value for the full PDU system since the last reset.
OBJECT-TYPE    
  NonNegativeInteger  

pduOutputVA 1.3.6.1.4.1.534.6.6.4.1.1.3.2
The present VA output of the full PDU system.
OBJECT-TYPE    
  NonNegativeInteger  

pduOutputPower 1.3.6.1.4.1.534.6.6.4.1.1.3.3
The present output power of the full PDU system.
OBJECT-TYPE    
  NonNegativeInteger  

pduOutputPowerFactor 1.3.6.1.4.1.534.6.6.4.1.1.3.4
The output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
OBJECT-TYPE    
  Integer32 -100..100  

pduNeutralCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.5
The present current in the PDU's output neutral phase. Ideally, this value stays at 0.
OBJECT-TYPE    
  NonNegativeInteger  

pduRatedOutputCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.6
The rated current value for one PDU Output phase at full load (100%).
OBJECT-TYPE    
  PositiveInteger  

pduOutputVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.1.3.7
Indicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
OBJECT-TYPE    
  DisplayString Size(0..31)  

pduOutputNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.3.8
The number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable.
OBJECT-TYPE    
  PositiveInteger  

pduOutputTable 1.3.6.1.4.1.534.6.6.4.1.1.3.9
A list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutputEntry

pduOutputEntry 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1
An entry containing information applicable to a particular output phase.
OBJECT-TYPE    
  PduOutputEntry  

pduOutputPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1
The output line identifier.
OBJECT-TYPE    
  PositiveInteger  

pduOutputPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2
The present output voltage for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

pduOutputPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3
The present output current for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

pduOutputPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.
OBJECT-TYPE    
  Integer32 0..200  

panelRatingsTable 1.3.6.1.4.1.534.6.6.4.1.2.1
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
OBJECT-TYPE    
  SEQUENCE OF  
    PanelRatingsEntry

panelRatingsEntry 1.3.6.1.4.1.534.6.6.4.1.2.1.1
An entry containing information applicable to a particular output phase.
OBJECT-TYPE    
  PanelRatingsEntry  

panelNumber 1.3.6.1.4.1.534.6.6.4.1.2.1.1.1
Index for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially.
OBJECT-TYPE    
  PositiveInteger  

panelRatedVoltage 1.3.6.1.4.1.534.6.6.4.1.2.1.1.2
The nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits.
OBJECT-TYPE    
  PositiveInteger  

panelRatedBreakerCurrent 1.3.6.1.4.1.534.6.6.4.1.2.1.1.3
The rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible.
OBJECT-TYPE    
  PositiveInteger  

panelNumPhases 1.3.6.1.4.1.534.6.6.4.1.2.1.1.4
The number of lines (phases) for this panel.
OBJECT-TYPE    
  PositiveInteger  

panelNumBreakers 1.3.6.1.4.1.534.6.6.4.1.2.1.1.5
The number of breakers contained in this panel. This determines the number of rows found in the breaker tables.
OBJECT-TYPE    
  PositiveInteger  

panelVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.2.1.1.6
Indicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
OBJECT-TYPE    
  DisplayString Size(0..31)  

panelMetersTable 1.3.6.1.4.1.534.6.6.4.1.2.2
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
OBJECT-TYPE    
  SEQUENCE OF  
    PanelMetersEntry

panelMetersEntry 1.3.6.1.4.1.534.6.6.4.1.2.2.1
An entry containing meter readings applicable to a particular panel.
OBJECT-TYPE    
  PanelMetersEntry  

panelTotalKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.1
The accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

panelMonthlyKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.2
The accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

panelYtdKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.3
The accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

panelVA 1.3.6.1.4.1.534.6.6.4.1.2.2.1.4
The present VA (input) demand of this panel.
OBJECT-TYPE    
  NonNegativeInteger  

panelPower 1.3.6.1.4.1.534.6.6.4.1.2.2.1.5
The present power (input) demand of this panel.
OBJECT-TYPE    
  NonNegativeInteger  

panelPowerFactor 1.3.6.1.4.1.534.6.6.4.1.2.2.1.6
The input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
OBJECT-TYPE    
  Integer32 -100..100  

panelNeutralCurrent 1.3.6.1.4.1.534.6.6.4.1.2.2.1.7
The present neutral phase current for this panel.
OBJECT-TYPE    
  NonNegativeInteger  

panelPhaseMetersTable 1.3.6.1.4.1.534.6.6.4.1.2.3
A sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels.
OBJECT-TYPE    
  SEQUENCE OF  
    PanelPhaseMetersEntry

panelPhaseMetersEntry 1.3.6.1.4.1.534.6.6.4.1.2.3.1
An entry containing meter readings applicable to a particular phase of a particular panel.
OBJECT-TYPE    
  PanelPhaseMetersEntry  

panelPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.2.3.1.1
The line or phase identifier.
OBJECT-TYPE    
  PositiveInteger  

panelPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.2.3.1.2
The present voltage for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

panelPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.2.3.1.3
The present current for this phase.
OBJECT-TYPE    
  NonNegativeInteger  

panelPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.2.3.1.4
The percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current.
OBJECT-TYPE    
  Integer32 0..200  

breakerRatingsTable 1.3.6.1.4.1.534.6.6.4.1.3.1
A sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
OBJECT-TYPE    
  SEQUENCE OF  
    BreakerRatingsEntry

breakerRatingsEntry 1.3.6.1.4.1.534.6.6.4.1.3.1.1
An entry containing information applicable to a particular output phase.
OBJECT-TYPE    
  BreakerRatingsEntry  

breakerNumber 1.3.6.1.4.1.534.6.6.4.1.3.1.1.1
Index for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially.
OBJECT-TYPE    
  PositiveInteger  

breakerName 1.3.6.1.4.1.534.6.6.4.1.3.1.1.2
Name given by the administrator to identify this breaker.
OBJECT-TYPE    
  DisplayString Size(0..31)  

breakerRatedCurrent 1.3.6.1.4.1.534.6.6.4.1.3.1.1.3
The rated current value of this breaker (for one phase) at full load (100%).
OBJECT-TYPE    
  PositiveInteger  

breakerNumPhases 1.3.6.1.4.1.534.6.6.4.1.3.1.1.4
The number of lines (phases) for this breaker.
OBJECT-TYPE    
  PositiveInteger  

breakerMetersTable 1.3.6.1.4.1.534.6.6.4.1.3.2
A sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
OBJECT-TYPE    
  SEQUENCE OF  
    BreakerMetersEntry

breakerMetersEntry 1.3.6.1.4.1.534.6.6.4.1.3.2.1
An entry containing meter readings applicable to a particular breaker.
OBJECT-TYPE    
  BreakerMetersEntry  

breakerTotalKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.1
The accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

breakerMonthlyKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.2
The accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

breakerYtdKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.3
The accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures.
OBJECT-TYPE    
  NonNegativeInteger  

breakerPhaseMetersTable 1.3.6.1.4.1.534.6.6.4.1.3.3
A sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels).
OBJECT-TYPE    
  SEQUENCE OF  
    BreakerPhaseMetersEntry

breakerPhaseMetersEntry 1.3.6.1.4.1.534.6.6.4.1.3.3.1
An entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel.
OBJECT-TYPE    
  BreakerPhaseMetersEntry  

breakerPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.3.3.1.1
The line or phase identifier.
OBJECT-TYPE    
  PositiveInteger  

breakerPhaseVA 1.3.6.1.4.1.534.6.6.4.1.3.3.1.2
The present VA (input) demand of this phase on this breaker.
OBJECT-TYPE    
  NonNegativeInteger  

breakerPhasePower 1.3.6.1.4.1.534.6.6.4.1.3.3.1.3
The present power (input) demand of phase on this breaker.
OBJECT-TYPE    
  NonNegativeInteger  

breakerPhasePowerFactor 1.3.6.1.4.1.534.6.6.4.1.3.3.1.4
The input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
OBJECT-TYPE    
  Integer32 -100..100  

breakerPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.3.3.1.5
The present current for this phase of this breaker.
OBJECT-TYPE    
  NonNegativeInteger  

breakerPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.3.3.1.6
The percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent.
OBJECT-TYPE    
  Integer32 0..200  

eatonPduConformance 1.3.6.1.4.1.534.6.6.4.2
OBJECT IDENTIFIER    

pduNameplateGroup 1.3.6.1.4.1.534.6.6.4.2.1
The pduNameplate subgroup objects.
OBJECT-GROUP    

pduInputGroup 1.3.6.1.4.1.534.6.6.4.2.2
The pduInput Meters subgroup objects.
OBJECT-GROUP    

pduOutputGroup 1.3.6.1.4.1.534.6.6.4.2.3
The pduOutput Meters subgroup objects.
OBJECT-GROUP    

panelRatingsGroup 1.3.6.1.4.1.534.6.6.4.2.4
The panelRatings table objects.
OBJECT-GROUP    

panelMetersGroup 1.3.6.1.4.1.534.6.6.4.2.5
The BreakerMeters Table objects.
OBJECT-GROUP    

panelPhaseMetersGroup 1.3.6.1.4.1.534.6.6.4.2.6
The BreakerPhaseMeters Table objects.
OBJECT-GROUP    

breakerRatingsGroup 1.3.6.1.4.1.534.6.6.4.2.7
The breakerRatings table objects.
OBJECT-GROUP    

breakerMetersGroup 1.3.6.1.4.1.534.6.6.4.2.8
The breakerMeters table objects.
OBJECT-GROUP    

breakerPhaseMetersGroup 1.3.6.1.4.1.534.6.6.4.2.9
The breakerPhaseMeters table objects.
OBJECT-GROUP    

pdu3phaseCompliance 1.3.6.1.4.1.534.6.6.4.2.10
The compliance statement for a normal 3-phase PDU, which implements the full set of objects.
MODULE-COMPLIANCE