DeltaUPS-MIB

File: DeltaUPS-MIB.mib (46507 bytes)

Imported modules

RFC1155-SMI RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

enterprises IpAddress DisplayString
OBJECT-TYPE TRAP-TYPE

Defined Values

delta 1.3.6.1.4.1.2254
OBJECT IDENTIFIER    

ups 1.3.6.1.4.1.2254.2
OBJECT IDENTIFIER    

upsv4 1.3.6.1.4.1.2254.2.4
OBJECT IDENTIFIER    

dupsIdent 1.3.6.1.4.1.2254.2.4.1
OBJECT IDENTIFIER    

dupsControl 1.3.6.1.4.1.2254.2.4.2
OBJECT IDENTIFIER    

dupsConfig 1.3.6.1.4.1.2254.2.4.3
OBJECT IDENTIFIER    

dupsInput 1.3.6.1.4.1.2254.2.4.4
OBJECT IDENTIFIER    

dupsOutput 1.3.6.1.4.1.2254.2.4.5
OBJECT IDENTIFIER    

dupsBypass 1.3.6.1.4.1.2254.2.4.6
OBJECT IDENTIFIER    

dupsBattery 1.3.6.1.4.1.2254.2.4.7
OBJECT IDENTIFIER    

dupsTest 1.3.6.1.4.1.2254.2.4.8
OBJECT IDENTIFIER    

dupsAlarm 1.3.6.1.4.1.2254.2.4.9
OBJECT IDENTIFIER    

dupsEnvironment 1.3.6.1.4.1.2254.2.4.10
OBJECT IDENTIFIER    

dupsTraps 1.3.6.1.4.1.2254.2.4.20
OBJECT IDENTIFIER    

dupsIdentManufacturer 1.3.6.1.4.1.2254.2.4.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..20)  

dupsIdentModel 1.3.6.1.4.1.2254.2.4.1.2
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

dupsIdentUPSSoftwareVersion 1.3.6.1.4.1.2254.2.4.1.3
The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

dupsIdentAgentSoftwareVersion 1.3.6.1.4.1.2254.2.4.1.4
The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

dupsIdentName 1.3.6.1.4.1.2254.2.4.1.5
A string identifying the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

dupsAttachedDevices 1.3.6.1.4.1.2254.2.4.1.6
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

dupsRatingOutputVA 1.3.6.1.4.1.2254.2.4.1.7
The magnitude of the nominal output VA rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsRatingOutputVoltage 1.3.6.1.4.1.2254.2.4.1.8
The magnitude of the nominal output voltage rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsRatingOutputFrequency 1.3.6.1.4.1.2254.2.4.1.9
The magnitude of the nominal output frequency rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsRatingInputVoltage 1.3.6.1.4.1.2254.2.4.1.10
The magnitude of the nominal input voltage rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsRatingInputFrequency 1.3.6.1.4.1.2254.2.4.1.11
The magnitude of the nominal input frequency rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsRatingBatteryVoltage 1.3.6.1.4.1.2254.2.4.1.12
The magnitude of the nominal battery voltage rating.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsLowTransferVoltUpBound 1.3.6.1.4.1.2254.2.4.1.13
The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsLowTransferVoltLowBound 1.3.6.1.4.1.2254.2.4.1.14
The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsHighTransferVoltUpBound 1.3.6.1.4.1.2254.2.4.1.15
The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsHighTransferVoltLowBound 1.3.6.1.4.1.2254.2.4.1.16
The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsLowBattTime 1.3.6.1.4.1.2254.2.4.1.17
Minutes, time from low battery to low battery shutdown.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutletRelays 1.3.6.1.4.1.2254.2.4.1.18
Number of outlet relay. If it is 0, the function is not available for the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsType 1.3.6.1.4.1.2254.2.4.1.19
Indicate the UPS type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER on-line(1), off-line(2), line-interactive(3), phase3(4), splite-phase(5)  

dupsShutdownType 1.3.6.1.4.1.2254.2.4.2.1
This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER output(1), system(2)  

dupsAutoReboot 1.3.6.1.4.1.2254.2.4.2.2
In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the unit should restart or not next time when the power restores
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

dupsShutdownAction 1.3.6.1.4.1.2254.2.4.2.3
If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsRestartAction 1.3.6.1.4.1.2254.2.4.2.4
UPS will restart after the indicated number of minutes. -1, aborted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsSetOutletRelay 1.3.6.1.4.1.2254.2.4.2.5
Indicate which outlet relay, from 1,2,3... .
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsRelayOffDelay 1.3.6.1.4.1.2254.2.4.2.6
Turn the relay off after the seconds. The relay was indicated by SetOutletRelay.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsRelayOnDelay 1.3.6.1.4.1.2254.2.4.2.7
Turn the relay on after the seconds. The relay was indicated by SetOutletRelay.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsConfigBuzzerAlarm 1.3.6.1.4.1.2254.2.4.3.1
UPS will keep silence but will alarm again when next power event is occurred
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alarm(1), silence(2)  

dupsConfigBuzzerState 1.3.6.1.4.1.2254.2.4.3.2
If it is disabled then the UPS is always muted.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

dupsConfigSensitivity 1.3.6.1.4.1.2254.2.4.3.3
The seneitivity of the UPS to utility line abnormalities or noises.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normal(0), reduced(1), low(2)  

dupsConfigLowVoltageTransferPoint 1.3.6.1.4.1.2254.2.4.3.4
The minimum input line voltage allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsConfigHighVoltageTransferPoint 1.3.6.1.4.1.2254.2.4.3.5
The maximum line voltage allowed before the UPS system transfers to battery backup.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsConfigShutdownOSDelay 1.3.6.1.4.1.2254.2.4.3.6
The operating system shutdown delay time when the input power fail. -1 will disable this option.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsConfigUPSBootDelay 1.3.6.1.4.1.2254.2.4.3.7
Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the system.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsConfigExternalBatteryPack 1.3.6.1.4.1.2254.2.4.3.8
Indicate the number of external battery pack.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsInputNumLines 1.3.6.1.4.1.2254.2.4.4.1
The number of input lines utilized in this device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputFrequency1 1.3.6.1.4.1.2254.2.4.4.2
The current input line 1 frequency to the UPS system in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputVoltage1 1.3.6.1.4.1.2254.2.4.4.3
The Input line 1 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputCurrent1 1.3.6.1.4.1.2254.2.4.4.4
The Input line 1 current to the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputFrequency2 1.3.6.1.4.1.2254.2.4.4.5
The current input line 2 frequency to the UPS system in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputVoltage2 1.3.6.1.4.1.2254.2.4.4.6
The Input line 2 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputCurrent2 1.3.6.1.4.1.2254.2.4.4.7
The Input line 2 current to the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputFrequency3 1.3.6.1.4.1.2254.2.4.4.8
The current input line 3 frequency to the UPS system in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputVoltage3 1.3.6.1.4.1.2254.2.4.4.9
The Input line 3 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsInputCurrent3 1.3.6.1.4.1.2254.2.4.4.10
The Input line 3 current to the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputSource 1.3.6.1.4.1.2254.2.4.5.1
The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), battery(1), bypass(2), reducing(3), boosting(4), manualBypass(5), other(6), none(7)  

dupsOutputFrequency 1.3.6.1.4.1.2254.2.4.5.2
The present output frequency in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputNumLines 1.3.6.1.4.1.2254.2.4.5.3
The number of output lines utilized in this device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputVoltage1 1.3.6.1.4.1.2254.2.4.5.4
The Output line 1 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputCurrent1 1.3.6.1.4.1.2254.2.4.5.5
The Output line 1 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputPower1 1.3.6.1.4.1.2254.2.4.5.6
The Output line 1 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputLoad1 1.3.6.1.4.1.2254.2.4.5.7
The current UPS output line 1 load expressed in percent of rated capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputVoltage2 1.3.6.1.4.1.2254.2.4.5.8
The Output line 2 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputCurrent2 1.3.6.1.4.1.2254.2.4.5.9
The Output line 2 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputPower2 1.3.6.1.4.1.2254.2.4.5.10
The Output line 2 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputLoad2 1.3.6.1.4.1.2254.2.4.5.11
The current UPS output line 2 load expressed in percent of rated capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputVoltage3 1.3.6.1.4.1.2254.2.4.5.12
The Output line 3 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputCurrent3 1.3.6.1.4.1.2254.2.4.5.13
The Output line 3 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputPower3 1.3.6.1.4.1.2254.2.4.5.14
The Output line 3 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsOutputLoad3 1.3.6.1.4.1.2254.2.4.5.15
The current UPS output line 3 load expressed in percent of rated capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassFrequency 1.3.6.1.4.1.2254.2.4.6.1
The present bypass frequency in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassNumLines 1.3.6.1.4.1.2254.2.4.6.2
The number of bypass lines utilized in this device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassVoltage1 1.3.6.1.4.1.2254.2.4.6.3
The bypass line 1 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassCurrent1 1.3.6.1.4.1.2254.2.4.6.4
The bypass line 1 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassPower1 1.3.6.1.4.1.2254.2.4.6.5
The bypass line 1 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassVoltage2 1.3.6.1.4.1.2254.2.4.6.6
The bypass line 2 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassCurrent2 1.3.6.1.4.1.2254.2.4.6.7
The bypass line 2 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassPower2 1.3.6.1.4.1.2254.2.4.6.8
The bypass line 2 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassVoltage3 1.3.6.1.4.1.2254.2.4.6.9
The bypass line 3 voltage of the UPS system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassCurrent3 1.3.6.1.4.1.2254.2.4.6.10
The bypass line 3 current of the UPS system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBypassPower3 1.3.6.1.4.1.2254.2.4.6.11
The bypass line 3 real power of the UPS system in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBatteryCondiction 1.3.6.1.4.1.2254.2.4.7.1
The indication of the capacity remaining in the UPS system's batteries when AC normal.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER good(0), weak(1), replace(2)  

dupsBatteryStatus 1.3.6.1.4.1.2254.2.4.7.2
The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of low indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of depleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), low(1), depleted(2)  

dupsBatteryCharge 1.3.6.1.4.1.2254.2.4.7.3
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER floating(0), charging(1), resting(2), discharging(3)  

dupsSecondsOnBattery 1.3.6.1.4.1.2254.2.4.7.4
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBatteryEstimatedTime 1.3.6.1.4.1.2254.2.4.7.5
Estimated time from backup to low battery shutdown.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBatteryVoltage 1.3.6.1.4.1.2254.2.4.7.6
The magnitude of the present battery voltage in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBatteryCurrent 1.3.6.1.4.1.2254.2.4.7.7
The present battery current in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsBatteryCapacity 1.3.6.1.4.1.2254.2.4.7.8
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

dupsTemperature 1.3.6.1.4.1.2254.2.4.7.9
The ambient temperature at or near the UPS Battery casing.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsLastReplaceDate 1.3.6.1.4.1.2254.2.4.7.10
The last battery replacement date. The format is YYYYMMDD.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

dupsNextReplaceDate 1.3.6.1.4.1.2254.2.4.7.11
The next battery replacement date. The format is YYYYMMDD.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

dupsTestType 1.3.6.1.4.1.2254.2.4.8.1
Perform the UPS Test procedure.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER abort(0), generalTest(1), batteryTest(2), testFor10sec(3), testUntilBattlow(4)  

dupsTestResultsSummary 1.3.6.1.4.1.2254.2.4.8.2
The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the test completed either successfully, with a warning, or with an error, respectively.Tests which have not yet concluded are indicated by inProgress(2). The value noTestsInitiated(0) indicates that no previous test results are available.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER noTestsInitiated(0), donePass(1), inProgress(2), generalTestFail(3), batteryTestFail(4), deepBatteryTestFail(5)  

dupsTestResultsDetail 1.3.6.1.4.1.2254.2.4.8.3
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

dupsAlarmDisconnect 1.3.6.1.4.1.2254.2.4.9.1
Does the UPS disconnect?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmPowerFail 1.3.6.1.4.1.2254.2.4.9.2
Does the input power fail?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmBatteryLow 1.3.6.1.4.1.2254.2.4.9.3
Are the UPS batteries low?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmLoadWarning 1.3.6.1.4.1.2254.2.4.9.4
Does the UPS load percent over the load warning value?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmLoadSeverity 1.3.6.1.4.1.2254.2.4.9.5
Does the UPS load percent over the load severity value?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmLoadOnBypass 1.3.6.1.4.1.2254.2.4.9.6
Does the UPS load on bypass?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmUPSFault 1.3.6.1.4.1.2254.2.4.9.7
Does the UPS general fail?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmBatteryGroundFault 1.3.6.1.4.1.2254.2.4.9.8
Does the UPS battery ground fault?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmTestInProgress 1.3.6.1.4.1.2254.2.4.9.9
Does the UPS test in progress?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmBatteryTestFail 1.3.6.1.4.1.2254.2.4.9.10
Does the UPS test fail?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmFuseFailure 1.3.6.1.4.1.2254.2.4.9.11
Does the UPS fuse failure?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOutputOverload 1.3.6.1.4.1.2254.2.4.9.12
Does the UPS output overload?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOutputOverCurrent 1.3.6.1.4.1.2254.2.4.9.13
Does the UPS output overcurrent?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmInverterAbnormal 1.3.6.1.4.1.2254.2.4.9.14
Does the UPS inverter abnormal?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmRectifierAbnormal 1.3.6.1.4.1.2254.2.4.9.15
Does the UPS rectifier abnormal?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmReserveAbnormal 1.3.6.1.4.1.2254.2.4.9.16
Does the UPS reserve abnormal?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmLoadOnReserve 1.3.6.1.4.1.2254.2.4.9.17
Does the UPS load on reserve?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOverTemperature 1.3.6.1.4.1.2254.2.4.9.18
Does the UPS over heat?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOutputBad 1.3.6.1.4.1.2254.2.4.9.19
Is the UPS output abnormal?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmBypassBad 1.3.6.1.4.1.2254.2.4.9.20
Is the UPS bypass bad?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmUPSOff 1.3.6.1.4.1.2254.2.4.9.21
Is the UPS in standby mode?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmChargerFail 1.3.6.1.4.1.2254.2.4.9.22
Does the UPS charger fail?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmFanFail 1.3.6.1.4.1.2254.2.4.9.23
Does the UPS fan fail?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEconomicMode 1.3.6.1.4.1.2254.2.4.9.24
Indicates whether the UPS is in the economic mode.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOutputOff 1.3.6.1.4.1.2254.2.4.9.25
Indicates whether the UPS output is turned off or not.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmSmartShutdown 1.3.6.1.4.1.2254.2.4.9.26
Indicates whether the Smart Shutdown is in progress.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEmergencyPowerOff 1.3.6.1.4.1.2254.2.4.9.27
UPS emergency power off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmUPSShutdown 1.3.6.1.4.1.2254.2.4.9.28
UPS shutdown.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsEnvTemperature 1.3.6.1.4.1.2254.2.4.10.1
The ambient environmental temperature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsEnvHumidity 1.3.6.1.4.1.2254.2.4.10.2
The environmental humidity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dupsEnvSetTemperatureLimit 1.3.6.1.4.1.2254.2.4.10.3
Alarm dupsAlarmOverTemperature on when the environmental temperature over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsEnvSetHumidityLimit 1.3.6.1.4.1.2254.2.4.10.4
Alarm dupsAlarmOverHumidity on when the environmental humidity over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dupsEnvSetEnvRelay1 1.3.6.1.4.1.2254.2.4.10.5
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dupsEnvSetEnvRelay2 1.3.6.1.4.1.2254.2.4.10.6
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dupsEnvSetEnvRelay3 1.3.6.1.4.1.2254.2.4.10.7
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dupsEnvSetEnvRelay4 1.3.6.1.4.1.2254.2.4.10.8
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dupsAlarmOverEnvTemperature 1.3.6.1.4.1.2254.2.4.10.9
Does the environment over temperature?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmOverEnvHumidity 1.3.6.1.4.1.2254.2.4.10.10
Does the environment over humidity?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEnvRelay1 1.3.6.1.4.1.2254.2.4.10.11
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEnvRelay2 1.3.6.1.4.1.2254.2.4.10.12
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEnvRelay3 1.3.6.1.4.1.2254.2.4.10.13
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsAlarmEnvRelay4 1.3.6.1.4.1.2254.2.4.10.14
Tok_String
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dupsCommunicationLost 1
SEVER: Communication with the UPS failed.
TRAP-TYPE    

dupsCommunicationEstablished 2
INFORMATION: Communication with the UPS reestablished.
TRAP-TYPE    

dupsPowerFail 3
WARNING: Power failed! The UPS is operating on battery power.
TRAP-TYPE    

dupsPowerRestored 4
INFORMATION: Power restored! The utility power restored.
TRAP-TYPE    

dupsLowBattery 5
SEVER: The UPS batteries are low and will soon be exhausted.
TRAP-TYPE    

dupsReturnFromLowBattery 6
INFORMATION: The UPS has returned from a low battery condition.
TRAP-TYPE    

dupsLoadWarning 7
INFORMATION: Loading percent of the UPS over the Load Warning value.
TRAP-TYPE    

dupsNoLongerLoadWarning 8
INFORMATION: Returnd from Load Warning condition.
TRAP-TYPE    

dupsLoadSeverity 9
Warning: Loading percent of the UPS over the Load Severity value.
TRAP-TYPE    

dupsNoLongerLoadSeverity 10
INFORMATION: Returned from Load Severity condition.
TRAP-TYPE    

dupsLoadOnBypass 11
SEVER: The UPS loads on bypass.
TRAP-TYPE    

dupsNoLongerLoadOnBypass 12
INFORMATION: The UPS is not on bypass mode.
TRAP-TYPE    

dupsUPSFault 13
SEVER: A general fault caused in the UPS.
TRAP-TYPE    

dupsReturnFromUPSFault 14
INFORMATION: The UPS is returned from general fault.
TRAP-TYPE    

dupsBatteryGroundFault 15
SEVER: The UPS battery ground fault.
TRAP-TYPE    

dupsNoLongerBatteryFault 16
INFORMATION: The UPS recovered from battery ground fault.
TRAP-TYPE    

dupsTestInProgress 17
INFORMATION: The UPS test in progress.
TRAP-TYPE    

dupsBatteryTestFail 18
SEVER: The UPS test fail.
TRAP-TYPE    

dupsFuseFailure 19
SEVER: The UPS fuse failed.
TRAP-TYPE    

dupsFuseRecovered 20
INFORMATION: The UPS fuse recovered.
TRAP-TYPE    

dupsOutputOverload 21
SEVER: The UPS overload!.
TRAP-TYPE    

dupsNoLongerOverload 22
INFORMATION: Recovered from UPS overload.
TRAP-TYPE    

dupsOutputOverCurrent 23
SEVER: The UPS output overcurrent.
TRAP-TYPE    

dupsNoLongerOutputOverCurrent 24
INFORMATION: Recovered from UPS overcurrent.
TRAP-TYPE    

dupsInverterAbnormal 25
SEVER: The UPS inverter abnormal.
TRAP-TYPE    

dupsInverterRecovered 26
INFORMATION: Recovered from UPS inverter abnormal.
TRAP-TYPE    

dupsRectifierAbnormal 27
SEVER: The UPS rectifier abnormal.
TRAP-TYPE    

dupsRectifierRecovered 28
INFORMATION: The UPS recovered from rectifier abnormal.
TRAP-TYPE    

dupsReserveAbnormal 29
SEVER: The UPS rectifier abnormal.
TRAP-TYPE    

dupsReserveRecovered 30
INFORMATION: The UPS rectifier abnormal.
TRAP-TYPE    

dupsLoadOnReserve 31
SEVER: The UPS load on reserve.
TRAP-TYPE    

dupsNoLongerLoadOnReserve 32
INFORMATION: The UPS no longer load on reserve.
TRAP-TYPE    

dupsEnvOverTemperature 33
WARNING: The environment overtemperature.
TRAP-TYPE    

dupsNoLongerEnvOverTemperature 34
INFORMATION: The environment recovered from overtemperature.
TRAP-TYPE    

dupsEnvOverHumidity 35
WARNING: The environment overhumidity.
TRAP-TYPE    

dupsNoLongerEnvOverHumidity 36
INFORMATION: The environment recovered from overhumidity.
TRAP-TYPE    

dupsEnvRelay1Alarm 37
INFORMATION: The environment relay1 is not in normal state.
TRAP-TYPE    

dupsEnvRelay1Normal 38
INFORMATION: The environment relay1 is in normal state.
TRAP-TYPE    

dupsEnvRelay2Alarm 39
INFORMATION: The environment relay2 is not in normal state.
TRAP-TYPE    

dupsEnvRelay2Normal 40
INFORMATION: The environment relay2 is in normal state.
TRAP-TYPE    

dupsEnvRelay3Alarm 41
INFORMATION: The environment relay3 is not in normal state.
TRAP-TYPE    

dupsEnvRelay3Normal 42
INFORMATION: The environment relay3 is in normal state.
TRAP-TYPE    

dupsEnvRelay4Alarm 43
INFORMATION: The environment relay4 is not in normal state.
TRAP-TYPE    

dupsEnvRelay4Normal 44
INFORMATION: The environment relay4 is in normal state.
TRAP-TYPE    

dupsSmartShutdown 45
SEVER: Smart Shutdown is initiated.
TRAP-TYPE    

dupsCancelShutdown 46
INFORMATION: Cancel UPS Shutdown.
TRAP-TYPE    

dupsTestCompleted 47
INFORMATION: This trap is sent upon completion of a UPS diagnostic test.
TRAP-TYPE    

dupsEPOON 48
INFORMATION: This trap is sent when emergency power off is on.
TRAP-TYPE    

dupsEPOOFF 49
INFORMATION: This trap is sent when UPS recover from emergency power off.
TRAP-TYPE    

dupsOverTemperature 50
SEVER: This trap is sent when the UPS is over heat.
TRAP-TYPE    

dupsNormalTemperature 51
INFORMATION: This trap is sent when UPS recover from over heat.
TRAP-TYPE    

dupsBattReplace 52
WARNING: The battery needs to be replaced.
TRAP-TYPE    

dupsReturnFromBattReplace 53
INFORMATION: The UPS recovered from battery replacement.
TRAP-TYPE